S&P SWF-100, SWF-100X, SWF-150, SWF-150X, SWF-200 Installation Instructions Manual

SIDEWALL (SWF)
CENTRIFUGAL SIDEWALL FANS VENTILADORES CENRIFUGOS DE MONTAJE EN PAREDES VENTILATEUR DE PAROI CENTRIFUGE EN LIGNE
Models SWF-100, 100X, 150, 150X, 200
U
R
C U
L
S
INSTALLATION AND WIRING INSTRUCTIONS
INSTRUCCIONES DE MONTAJE
INSTRUCTIONS DE MONTAGE ET DE CÂBLAGE
READ AND SAVE THESE INSTRUCTIONS
LEER Y GUARDAR ESTAS INSTRUCCIONES
LIRE ET CONSERVER CES INSTRUCTIONS
Dimensional Data
A
D
B
2 mm
C
C1
C2
Model A B C C1 C2 D
SWF-100
SWF-100x
SWF-150
SWF-150x
SWF-200
13 ¼
13 ¼
15 ½
15 ½
15 ½
337
337
394
394
394
13 ¼
13 ¼
13 ¼
16 1/16
16 1/16
337
337
337
408
408
9
9
10 3/16
10
11 7/16
228
228
256
254
290
3
3
3
3 3/16
3 3/8
76
76
76
81
87
2 7/16
2 7/16
2 7/16
2 7/16
2 7/16
62
62
62
62
62
4
100
4
100
6
150
6
150
8
200
WARNING
Soler and Palau designs the highest quality products available in the industry and meets stringent manufacturing requirements. These units are not designed however to be utilized as the primary devices used in a life support ventilation systems where failure could result in loss or injury, the user should provide adequate backup ventilation, supplementary natural ventilation, failure alarm sys­tem, or acknowledge willingness to accept the risk of such loss or injury
ADVERTENCIA
Soler y Palau diseña productos de la más alta calidad en la industria, los cuales han sido fabricados siguiendo las más rigurosas normas de producción. Sin embargo, estas unidades no son diseñadas para ser utilizadas como dispositivos primarios que se emplean en un sistema de ventilación vital donde una falla podría tener como resultado perdidas o lesiones. El usuario debe también adoptar un sistema de ventilación de reserva; ventilación natural de suplemento o un sistema de alarma de fallas, o reconocer que está dispuesto a asimilar el riesgo de tales pérdidas o lesiones
AVERTISSEMENT
Soler and Palau conçoit les produits de la plus haute qualité disponibles dans l’industrie et rencon­tre les exigences de fabrication rigoureuses. Toutefois, ces unités ne sont pas conçues pour être utilisées comme dispositifs principaux dans les systèmes de ventilation critiques pour préserver la vie et dont la défaillance pourrait entraîner une perte ou un préjudice ; l’usager doit assurer une ventilation de secours adéquate, une ventilation naturelle supplémentaire, un système d’alarme de
protection contre les pannes, ou signier sa disposition d’accepter le risque de telle perte ou de tel
préjudice.
3
ENGLISH Fan Installation
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY, OBSERVE THE FOLLOWING: (a) Use this unit only in the manner intended by the manufacturer. If you have any questions contact the manufacturer. (b) Before servicing or cleaning the unit, switch the power off at the service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked; securely fasten a prominent warning device such as a tag to the service panel.
(c) Installation work and electrical wiring must be done by qualied person(s) in accordance with
all applicable codes & standards including related construction. (d) When cutting or drilling into wall or roof, do not damage electrical wiring and other hidden utilities. (e) CAUTION: For General Ventilating Use Only. Do Not Use To Exhaust Hazardous Or Explosive Materials And Vapors.
(f) DO NOT USE with heated air in excess 140˚F (60˚C).
Select Fan Location
When selecting a location to install the SWF fan that has been chosen, take into consideration the application of the product, the locations of fresh air intakes, and sound generated by the SWF unit.
The fan should be located a minimum of 6 feet horizontally and 8 feet vertically from any fresh air intakes for HVAC systems, heat recovery systems, etc. to prevent exhaust air streams from being re-introduced into the occupied space. Doors or windows that are frequently opened during pleas­ant seasons may also be considered fresh air intakes so keep this in mind when selecting the location of the SWF.
Mark and Introduce Required Holes
Once the location on the exterior wall where the fan is to be mounted has been selected, mark all screw and hole locations utilizing the included template. Cut the holes through the wall for the duct connection and for the electrical conduit. Measure the thickness of the wall and the length of the duct connection that is supplied on the SWF fan. Cut a length of duct so that once connected to the fan, will extend 2” through the wall.
If mounting the fan on a masonry wall, drill four holes and insert wall anchors. If mounting to wooden structure, you will utilize wood screws to secure the SWF to the wall.
If the fan is to be mounted on a wall surface which is not ush such as lapped siding, a mounting plate to provide for a ush t needs to be made.
Mount the Fan
Insert electrical supply through the wall. Attach the duct extension to the SWF making sure that the connection is secure. Apply a generous amount of exterior silicone caulk to backplate of the fan to ensure an airtight/waterproof connection between the fan and the wall surface. If a mounting frame is used in conjunction with lapped siding, be certain to apply a generous amount of caulk between the frame and the wall as well as the fan backplate and the frame. Mount the fan to the wall.
4
Note: Be certain to make an airtight seal around all interior wall penetrations before attaching duct work.
Electrical Connection
All SWF series fans operate from a standard 120V 60Hz A.C electrical supply. All wiring must be carried out in accordance with National Electrical Code, and all applicable state and local buildings codes.
WIRING INSTRUCTIONS
WARNING! Make sure that power supply is disconnected and locked to prevent accidental activation.
1. Remove the screws securing the terminal box cover plate located on the fan motor mounting bracket. All fan motor and capacitor connections are pre-wired to the electrical terminal strip. A 3/8” romex type cable restraint connector will be needed to secure the wiring through the knockout provided on the side of the terminal box.
2. Bring incoming electrical service through the romex connector and the fan electrical service opening. Using a small regular screwdriver, tighten the neutral (white) wire of the incoming 115V power supply under the open terminal strip port opposing the motor Blue wire. Tighten the line (black) wire of the incoming supply under the open terminal opposing the motor Black wire. Now, secure the source ground to the open terminal strip opposing the Green/Yellow Wire.
3. Secure the romex connector. Secure the incoming supply with the romex connector. Replace the fan terminal box cover.
4. Apply a generous bead of silicone caulk around the electrical provision hole in the backplate of the fan to provide for a secure seal.
MAINTENANCE INSTRUCTIONS
1. Since fan bearings are sealed and provided with an internal lubricating material, no additional lubrication is necessary.
2. It is recommended that the cover is screen is checked on a regular basis to check for any ob­structions and the cover is removed and the motor and wheel are inspected and cleaned as nec­essary.
No other maintenance is necessary.
5
Loading...
+ 11 hidden pages