S&P PCLP50, PCLP80, PCLP100 Instructions For Use Manual

WARNING
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.
CAUTION
CLEANING & MAINTENANCE
OPERATION
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dust brush attachment. The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noi­ses, replace the motor with the exact service motor. The impeller should also be replaced.
Use an on/off switch to operate this fan. See “Connect Wiring” for details.
PLAN THE INSTALLATION
1. Do not use in a cooking area.
2. Two ways to connect ductwork to a factory-shipped unit.
1
VENTILATION FAN
MODEL: PCLP50 PCLP80 PCLP100
a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer. b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switching on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel. c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards. d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting.Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA),and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities. e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. f). Ducted fans must always be vented to the outdoors. g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit (ceiling installation only). h). This unit must be grounded. i). Not for Use in Kitchens. j). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or ceilings or into attics,crawl spaces, or garages. k). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control Device. l). The fan must not be installed in a ceiling thermally insulated to a value greater R40.
ROOF CAP* (with built-in
damper)
ROUND
DUCT*
WALL CAP* (with built-in damper)
* Purchase
separately
POWER CABLE*
INSULATION*
(Place around and
over Fan Housing.)
Seal gaps
around
Housing.
FAN
HOUSING
ROUND
ELBOW(S) *
Seal duct joints with
tape.
Keep duct runs short
a. Mount with mounting holes and hanger bar() Slide one hanger bar into the channel on the housing and adjust as needed to fit between framing. Hold housing in place so that the housing contacts the bottom of the joist, Screw housing to joist through the hole A and hole B. Screw the hanger bar onto the other side of joist through the hole (refer to the right diagram). Screw hanger bar to housing with screw A.
ASSEMBLY INSTRUCTIONS
Distance A
JOIST
1. Before installation, you need to know:
Hole A
Hole B
Hole A
Hole B
Distance A
13 3/4 in to 15 15/16 in (350mm-405mm)
19 11/16 in to 21 7/8 in (500mm-555mm)
13 3/8 in to 19 11/16 in (340mm-500mm)
Hanger Bar
Channel
Channel A (Fig. 3)
Channel A (Fig. 3)
Channel B (Fig. 4)
Hanger bar (short)
Hanger bar (long)
Hanger bar (long)
The choice of Hanger Bar
Channel A
Channel B
ST4.2*13mm
Screw A
Screw B
Hanger bar (short)
Hanger bar (long)
ST4.2*25mm
7 1/2 in (190mm)
13 3/8 in (340mm)
Note: Hanger bar (short) only can slide into channel A.
Channel B
Hanger bar (long)
c. Mount with hanger bars only Slide hanger bars onto housing and adjust as needed to fit between framing. Extend the hanger bars to the width of the framing. Position the ventilator with the housing tabs wrapped around the bottom edge of the framing, holding the ventilator in place. Secure hanger bars to framing using one screw on each end of hanger bar (refer to the right diagram). Screw hanger bar to housing with screw A.
Distance A
14 in to 23 1/2 in (356mm-597mm)
19 11/16 in to 23 1/2 in (500mm-597mm)
Hanger Bar A
Hanger bar (short)
Hanger bar A
Hanger bar (long)
The choice of Hanger Bar A
Screw A
Screw B
Screw B
d. Mount to I-joist Slide one hanger bar (long) into channel B on the housing and adjust as needed to fit between framing. Hold housing in place so that the housing contacts the bottom of the joist. Screw housing to joist through the hole A and hole B. Screw the hanger bar onto the other side of joist through the hole (refer to the right diagram). Screw hanger bar to housing with screw A.
Fig. 4
Fig. 2
2
Screw B
Screw A
Channel A
Fig. 3
Fig. 6Fig. 5
Fig. 7
Fig. 8
Fig. 1
Screw B
Screw B
Screw B
Screw B
Distance A
13 3/4 in to 15 15/16 in (350mm-405mm)
19 11/16 in to 21 7/8 in (500mm-555mm)
Hanger Bar A
Hanger Bar A
Hanger bar (short)
Hanger bar (long)
The choice of Hanger Bar
b. Disconnect plug connector from receptacle and remove adaptor from housing before starting installation. Slide one hanger bar into the channel A on the housing and adjust as needed to fit between framing.Insert the housing into joists make sure that adaptor claws are properly inserted into housing slots. Secure the housing to adaptor by using screw . Screw housing to joist through the hole A and hole B
Screw B
Screw B
Screw B
Screw
Screw hanger bar to housing with screw A.
Tap
Mount with mounting holes and hanger bar()
Loading...
+ 2 hidden pages