3.2.Changing from pump to gravity condensate discharge10
3.3.Fan only / dehumidifying (modes of operation)10
3.4.Fan speed operation11
4. Installation wiring11
5. Control panel15
6. Maintenance and fault finding15
6.1.Maintenance15
6.2.Faults16
6.3.Technical support17
7. Spares list17
7.1.Electrical17
7.2.Refrigeration/ mechanical17
8. Contact Information18
QA/IOM/46 Issue 11 - MD Dehumidifier
1.GENERAL DESCRIPTION
The dehumidifier is based around a closed refrigeration system comprising evaporator coil,
condenser coil, expansion valve and compressor. It uses heat pipes to increase the cooling
efficiency, allowing more moisture to be extracted, compared to conventional dehumidifiers. A fan is
used to draw air inthrough a filter and across the evaporatorand discharge it through the condenser.
Moisture is removed from the entering humid air at the evaporator coil and it is collected in a drain
pan mounted below the coil. The collected condensate is then removed by an integral condensate
pump.
Figures 1. to 4. Showthe general layout of the dehumidifiers externallyand internally.
Figure 1. General layout of MD units with front grille removed
Figure 2. General layout of MD units
QA/IOM/46 Issue 11 - MD Dehumidifier
Page 3
Figure 3. Front view with front panel removed
QA/IOM/46 Issue 11 - MD Dehumidifier
Figure 4. Side view with side panel removed
Page 4
1.1.General
The dehumidifiers are mounted on 2 skids at the front and 2 fixed wheels at the back. These allow
secure siting of the units and make provision for local manoeuvring. All units are designed to allow
lifting by forklift. Dimension and weights are shown below:
Model
Width (mm)
Depth (mm)
Height (mm)
Weight (mm)
MD100
690
770
920
150
MD160
690
770
1234
169
MD200
690
770
1234
173
VoltageSupply 230V. 4% 50 Hz. Single Phase.
The supply current required byeach model is detailed in Section 4.
The unit is constructedaround 4 'pentapost' type pillars. The panels are screwed into the pillars via a
series of screws and captive nuts fitted inside the pillars. Removal of the side panel allows access to
the control void where the majority of the controls are located. These controls should not be altered
from their factory settings. The upper front panel carries the inlet grille and allows access to the air
filter. This panel sits on the lower front panel supported by studs and is removed by using the keys
provided to unlock the panel,and hinging forward.
The control panel allows switchingbetween different modes, see section 5.
The evaporator with heat pipesis mounted vertically behind the front grille.
The condenser is mounted horizontallyat the top of the unit belowthe discharge grille.
To prevent the evaporator coil freezing below design range conditions, a low pressure cut-out is
included in the refrigeration system. This detects if the condensateis freezing on the evaporator and
stops the compressor. The coil is allowed to thawpassively before the compressor is restarted.
QA/IOM/46 Issue 11 - MD Dehumidifier
Page 5
1.3.Fan and ventilation system
All dehumidifiers use double inlet low-pressure centrifugal direct drive fans fitted with forward
curved impellers.
Restriction or adjustment of the air flow rate has a significant effect on the performance of the units.
Therefore, the inlet and exhaustmust never be obstructed or attempts made to duct theair to or from
the units.
The filters remove air borne dirt from the air and keep the evaporator clean and this should not be
removed, except for cleaning purposes, as indicated in section 6.1. The filters should not be
replaced by other filters withdifferentpressure drop characteristics.
To ensure that the air is drawn through the evaporator, great care has been taken to seal and
insulate all panels. To ensure proper operation the dehumidifier must never be operated with any of
the panels removed. Great careshould also be taken to avoid damageto the seals on the panels.
1.4.Safety features
Compressor on delay
To protect the compressor from hunting, a start delay has been built into the electrical start-up
circuit. It is important thatthis delay isadjusted as this may result in compressordamage.
not
Hi/low pressure cut outs
To protect the compressor from operating at temperatures too high or too low, pressure cut-outs
have been included in the refrigeration circuit. These are mounted in the control void behind the side
panel. Both pressure cut outs are automatically reset when the pressure has returned within the
design range.
The low pressure cut-out is set to prevent operation against conditions which would encourage the
freezing of the evaporator. The coil is allowed to thaw passively should any ice would have built up,
before the compressor is restarted.
High level condensate
If the level of the condensate in the pump drain pan becomes excessively high, the warning light on
the front panel lights up,Figure 10. If this occurs refer tosection 6.2.
QA/IOM/46 Issue 11 - MD Dehumidifier
Page 6
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.