SOR TA Nuclear Qualified Temperature Switch User Manual

Nuclear Qualified
thermal system.
y
Temperature Switches
General Instructions
The SOR® temperature switch utilizes a SAMA Class II thermal system.
NOTE: This type of system requires that the entire length of the sensing bulb be exposed to the temperature being measured.
II
Recommended Measurement Procedure
In considering the validity of a measurement, remember that temperature-sensing devices respond only to the temperature that they experience. It may be considerably different from the temperature one is attempting to measure if the sensor is of improper size or configuration, or if the sensor is not adequately coupled thermally to the media whose temperature is being measured. The calibration procedures given below will assure accurate and repeatable measurement of the set points of SOR temperature switches. If the switch is normally mounted in a thermowell, consideration should be given to the effect this may have on the accuracy of the switch. It is recommended that a heat transfer paste or oil be used to thermally couple the sensing bulb to the thermowell, both in service and during testing.
ond a
e
per
ately
re is
n below
of the
itch is
should
cy of
r paste
lb to the
NOTE: If you suspect that a product is defective, contact the factory or the SOR Representative in your area for a return authorization number (RMA). This product should only be installed by trained and competent personnel.
Table of Contents
without notice.
For latest revision, go to
www.sorinc.com
Form 655 (04.13) ©SOR Inc.
Recommended Measurement Procedure ...1
N6 Housing ......................................3
TA Housing .......................................4
RT Housing ......................................5
Installation .......................................6
Site Storage .....................................6
Electrical Connection ...........................6
Calibration .......................................7
1/8
Recommended temperature measurement procedure for switches used to sense temperatures of liquids and steam with set points below 200°F:
Use a liquid bath (ethylene glycol, water, oil, etc.) with sufficient circulation to provide a uniform bath temperature and efficient transfer of heat from the liquid to the sensing bulb.
Fully submerge the sensing bulb into the bath. Direct-mount sensing bulbs should be
submerged up to the bottom of the process connection threads.
Locate the tip of the temperature measuring standard (thermocouple, RTD, etc.) at the
mid point of, and adjacent to the sensing bulb.
Locate the sensing bulb and temperature measuring standard so that they do not touch
the sides or bottom of the bath or the heating and cooling coils.
When the bath temperature is within 3°F of the set points, it is recommended that the
temperature of the bath be changed at a rate of 0.1°F per 5 seconds or slower.
The minimum and maximum bath temperatures that the switch sees during testing
should be duplicated each time the switch is tested. It is recommended that the tem­perature of the bath be changed from the normal operating temperature to the critical set point and back to the reset. Do not overshoot the critical set point if the switch is going to be cycled more than once during the test.
Recommended temperature measurement procedures for switches used to sense tem­peratures of liquids and steam with set points above 200°F:
Recommended procedures for set points above 200°F are identical to those for set points below 200°F with the exception of the bath used to test the switches. We recommend either a circulated oil bath or a fluidized sand bath. The bath should be tested for uniformity of temperature from top to bottom and side to side. If necessary, steps may be taken to improve the uniformity of temperature, such as altering the air flow through a sand bath or improving circulation or stirring.
Recommended temperature measurement procedures for switches used to sense air or gas temperature:
Switches used to measure the temperature of air or gas should be tested in such a way that it simulates the actual service conditions as closely as possible. Chances of measurement error are much greater in air because of its poor thermal conductivity. Rate of change of temperature, velocity of air flow, location of sensing bulb, and location of standard must be duplicated as closely as possible for successive calibration checks to assure repeat­able results. If the switch is being used as a room thermostat, the entire switch should be placed in a test oven for calibration and testing. If only the sensing bulb is exposed to the air or gas being measured, then only the sensing bulb should be inserted into the oven or test apparatus for calibration and testing. In this case the switch housing should be kept at room temperature.
2/8
Form 655 (04.13) ©SOR Inc.
N6 Housing
Direct Mount
Remote Mount
Cover
Screws
1/8” NPT(F)
Vent
Connection
Body
Process
Connection
Sensing Bulb
3/4” NPT(F)
Conduit Connection
Mounting Holes
Cover Screws
Sensing
Bulb
1/8” NPT(F)
Vent
Connection
Process
Connection
Gland
Nut
Capillary
Conduit Connection
3/4” NPT(F)
Mounting Holes
Retainer
Mounting Hardware Fasteners per SOR Test Report 9058-102 consist of two 1/4-20, Grade 5 screws (not supplied). Torque screws to 70 to 85 in-lbs.
Maintenance Replace cover gasket (SOR P/N 8923-180) whenever cover is removed or minimum of once every 5 years, whichever comes first. Remove the four cover screws. Remove the old gasket. Place new gasket between housing and cover. Line up holes in cover, gasket and housing. Insert the 4 screws and torque each to 7 to 10 in-lbs.
Form 655 (04.13) ©SOR Inc.
3/8
Loading...
+ 5 hidden pages