SOR Adjustable Dead Band Weatherproof Pressure Switch User Manual

Adjustable Dead Band
Pressure Switches
General Instructions
These instructions provide information for installation, process
®
and electrical connections and field calibration of SOR Dead Band Pressure Switches.
Adjustable
Media pressure on the area of the pistons counteracts the force of the
he
range springs (adjustable by the adjusting nuts), which moves the piston shafts only a few thousandths of an inch to operate the lever assembly which actuates and deactuates the electrical switching element.
NOTE: If you suspect that a product is defective, contact the factory or the SOR Representative in your area for a return authorization number (RMA). This product should only be installed by trained and competent personnel.
Installation
Adjustable Dead Band Pressure Switches may be secured to bulkheads, panels or pipe stanchions with suitable bolts. When mounting the pressure switch to an irregular or uneven flat surface, install rubber washers on the mounting bolts between the housing and the mounting surface.
Line mounting by either the process connection or the electrical conduit connection is not recommended.
Failure to place washers between the housing and the mounting surface may result in torsional forces on the housing that could cause false trips or render the pressure switch inoperative.
Failure to mount the housing on a  at mounting surface may result in torsional forces on the housing that could cause false trips or render the pressure switch inoperative.
Design and specifications are subject to change without notice.
Form 466 (05.13) ©SOR Inc.
For latest revision, go to www.sorinc.com
Registered Quality System to ISO 9001
1/4
Safety Integrity Level (SIL) Installation Requirements
The SOR pressure switches have been evaluated as Type-A safety related hardware. To meet the necessary installation requirements for the SIL system, the following information must be utilized:
Proof Test Interval shall be one year. Units may only be installed for use in Low Demand Mode. Products have a HFT (Hardware Fault Tolerance) of 0, and were evaluated in a
1oo1 (one out of one) configuration.
Form 1538 (03.12) ©2012 SOR Inc.
Process Connection
Securely connect the process line to the pressure port using two wrenches: one to hold the hexagonal flats on the pressure port, the other to tighten the process pipe or tube fitting.
Ensure that the process connection is tightened and positioned so that any binding and torsional forces imposed on the pressure switch are minimal. Do not loosen the pressure port from the body because leakage could result or the pressure switch could be rendered inoperative.
Electrical Connection
Ensure that wiring conforms to all applicable local and national electrical codes and install unit(s) according to relevant national and local safety codes.
V1 – Weathertight
Common Normally Open Normally Closed
C1 NO1 NC1
V3 – Explosion proof
capsule has 18” - 18 AWG wire leads color coded and marked.
Common Normally Open Normally Closed
C1 - Blue NO1 - Black NC1 - Red C2 - Yellow NO2 - Brown NC2 - Orange
GR - Ground (earth) green wire connected to each hermetically sealed switching element capsule.
SPDT: Screw terminal block with marked insulation.
DPDT (2-SPDT): Hermetically sealed switching element
Calibration
Remove the housing cover.
Connect a suitable variable pressure source with a calibrated reference gauge to the pressure port. Connect an ohmmeter or test lamp across the switching element contact terminals to monitor contact continuity. Use a 3/4” open-end wrench to turn the adjusting nuts.
Slowly increase pressure to the pressure port. The continuity tester will indicate that the contacts have changed state when increasing set point is reached. Note pressure at increasing set point. If increasing set point is too low, turn the left adjusting nut clockwise to raise the increasing set point. If increasing set point is too high, turn the left adjusting nut counterclockwise to lower the increasing set point.
2/4
Form 466 (05.13) ©SOR Inc.
Slowly decrease pressure to the pressure port. The continuity tester will indicate that contacts have changed state when decreasing set point is reached. Note pressure at decreasing set point.If the decreasing set point is too low, turn the right adjusting nut clockwise to raise the decreasing set point. If the decreasing set point is too high, turn the right adjusting nut counterclockwise to lower the decreasing set point. The left adjusting nut must always be lower than the right adjusting nut when calibration is complete.
Repeat Steps 3 and 4 until desired set points are obtained. If the pressure switch fails to respond to pressure change during calibration, increasing/decreasing set points may be too close together. See Form 281 for minimum/maximum dead band capabilities. Replace the housing cover.
Overtravel has been preset at the factory. The 3/16” overtravel adjustment screw on the lever assembly has been precisely positioned for optimum performance. Any inadvertent movement could render the device inoperative and void the warranty.
Increasing Set
Point Adjustment
To raise the increasing set
point, turn the left adjust-
ing nut clockwise. To lower
the increasing set point,
turn the left adjusting nut
counterclockwise.
The left adjusting nut must always be lower than the right adjusting nut when calibration is complete.
Principle of Operation
Actuation
Decreasing Set Point Adjustment
To raise the decreasing set point, turn the right adjusting nut clockwise. To lower the decreasing set point, turn the right adjusting nut counter­clockwise.
Deactuation
No pressure applied. Electrical switching element is deactuated.
Pressure greater than decreasing set point but less than increasing set point: Electrical switching element remains deactuated.
Piston movement exaggerated for clarity in drawings above.
Form 466 (05.13) ©SOR Inc.
Pressure equal to or greater than increasing set point: Electrical switching element is actuated.
Pressure less than increasing set point but greater than decreasing set point: Electrical switching element remains actuated.
Pressure equal to or less than decreasing set point: Electrical switching element is deactuated.
3/4
Dimensions
V1 Housing
6.4
*Add
Linear = mm/inches
Drawing 0090236
for non-aluminum ports.
0.25
V3 Housing
6.4
*Add
Linear = mm/inches
Drawing 0090325
for non-aluminum ports.
0.25
Dimensions are for reference only. Contact the factory
for certified drawings for a particular model number.
Printed in USA www.sorinc.com
14685 West 105th Street, Lenexa, KS 66215  913-888-2630  800-676-6794 USA  Fax 913-888-0767
4/4
Registered Quality System to ISO 9001
Form 466 (05.13) ©SOR Inc.
Loading...