SOR 1780 User Manual

1780 Wireless
Level Switch
General Instructions
The SOR® 1780 Level Switch is a horizontally mounted, float-operated level switch. The 1780 is suitable for plant and OEM applications to detect presence or absence of liquid at a discrete level.
When the liquid rises, the float extension arm moves a magnet that repels an internal magnet de-actuating the wireless unit. When the liquid level falls, the float extension arm moves in the opposite direction, actuating the wireless unit. The 1780 is recommended for use in clean liquids only.
NOTE: If you suspect that a product is defective, contact the factory or the SOR Representative in your area for a return authorization number (RMA). This product should only be installed by trained and competent personnel.
Mounting
Verify that obstructions are not present in the application that would prevent free float
movement throughout the entire range of motion.
Assure that the mounting provides a horizontal alignment of the switch.
Counterbalance area must be free from metallic particles that may attract to magnetic components in the 1780 model.
Use a 2” open end wrench on the two flats next to the process connection. Tighten the unit onto the process connection by rotating clockwise.
To ensure proper operation, the unit must be mounted with either wrench flat horizontal ±1°. (See
Mount the wireless unit using the two supplied M6X10 screws. Tighten using a 5mm
hex wrench.
Setup and calibrate the wireless unit according to the separtely supplied instructions.
Test the units action by varying the liquid level in the tank.
).
The unit can be mounted with either wrench flat horizontal ±180°
Design and specifications are subject to change without notice.
Form 1564 (09.14) ©SOR Inc.
For latest revision, go to sorinc.com
Registered Quality System to ISO 9001
1/4
Wireless Con guration
The following configuration guide is provided as a reference tool only. For the most complete and up-to-date information regarding configuration, calibration and set up please refer to the general instructions provided by the manufacturer and included in the original packaging.
Configuration consists of two parts: Configuration via a HART calibration device and configuration via the integrated display
Hart Handheld Guided Setup
Open hart on field communicator Press “right arrow” after finding the device (2) Configure press “right arrow” (1) Guided Setup press “right arrow” (1) Device Setup press “right arrow” Enter tag # press enter Enter long tag # press enter Enter Date press enter Enter optional description press enter Enter optional message press enter
Enter optional polling address press enter Set High Trip Point to 80% Set Low Trip Point to 20% Set Dead band to 5% Select no to configure power source Configuration is finished
High and Low indication can be switched on the integrated display.
Output -> “Left Button” If “In Service” -> “Left Button – Toggle Mode”, Else “right Button – Next” Calibrate -> “Left Button“ Calibrate -> “Left Button – Feedback” Select first point – High or Low When sensor is in correct position select “left button to mark” then hit next When sensor is in opposite position select “left button to mark” then hit next Then apply
Again, these steps are provided for reference only and are not guaranteed to reflect periodic software changes. If you have further questions please visit the manufacturer’s website for the most up to date general instructions.
2/4
Form 1564 (09.14) ©SOR Inc.
Dimensions
131.4
5.17
207.3
8.16
36.3
1.43
72.7
2.86
50.8
2.00
50.8
2.00 WRENCH FLATS
64.5 REF
2.54
128.9 REF
5.08
89.3 REF
3.52
NAMEPLATE
2" NPTM
PROCESS
CONNECTION
FLOAT
Linear = mm/inches
Drawing 0390759
Maintenance
 Clean the float and counterweight mechanism periodically to assure continued free
movement.
Make no adjustments to the float or counterweight mechanism. They are factory calibrated for optimum performance.
Troubleshooting
Symptom Probable Cause
The control will not function when installed but operates when removed from process connection.
Liquid is in the vessel at the actuation level but the unit does not respond.
a. Float travel is inadequate. Check for internal vessel obstructions. See Mounting Requirements.
a. The float pivot pin is bound up or dirty. Clean the float pivot pin. b. The specific gravity of the liquid is not sufficient to lift the float. c.
The float is leaky or collapsed. Contact the factory.
Form 1564 (09.14) ©SOR Inc.
3/4
Printed in USA sorinc.com
14685 West 105th Street, Lenexa, KS 66215  913-888-2630  800-676-6794 USA  Fax 913-888-0767
4/4
Registered Quality System to ISO 9001
Form 1564 (09.14) ©SOR Inc.
Loading...