Solis Solis-25K-5G, Solis-30K-5G, Solis-33K-5G, Solis-36K-5G, Solis-40K-5G User Manual

...
Solis Three Phase Inverter
Ginlong Techn ologi es Co., L td.
No. 57 Jintong Roa d, Binh ai Indu strial Park, Xian gshan , Ningb o,
Zhejiang, 3157 12, P.R.Chi na.
Fax: +86 (0)574 65 78 1606
Plea se a dhere to th e actual pr od ucts in cas e of any disc re pancies i n this user m an ual.
If you e nc ounter an y problem o n th e inverte r, please fi nd o ut the inve rter S/N
and co nt act us, we wi ll try to res po nd to your qu estion ASA P.
(25-50)K
Installation and Operation Manual
Ver1.7
Ginlong Tech nologies Co., Ltd.
Contents
1. Introduction
1.1 Product Description
1.2 Packaging
2. Safety Instructions
2.1 Safety Symbols
2.2 General Safety Instructions
2.3 Notice For Use
3. Overview
3.1 Front Panel Display
3.2 LED Status Indicator Lights
3.3 Keypad
3.4 LCD
……………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………
……………………………………………………………………………………………………………
…………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………
……………………………………………………………………………………………………………………………
……………………………………………………………………………………………………………………………………
4. Product handing and storage
4.1 Product handling
4.2 Product Storage
5. Installation
5.1 Select Location for the Inverter
5.2 Mounting the Inverter
5.3 Electrical Connections
6. Start & Stop
6.1 Start the Inverter
6.2 Stop the Inverter
7. Operation
7.1 Main Menu
7.2 Information
7.3 Settings
7.4 Advanced Info.
7.5 Advanced Settings
7.6 AFCI function
………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………
8. Maintenance
9. Troubleshooting
10. Specifications
11. Appendix
11.1 Grid standard selection guide
………………………………………………………………………………………………………………………………
……………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………
………………………………………………………………………………………………………
……………………………………………………………………………………………………
…………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………
……………………………………………………………………………………………………………………
……………………………………………………………………………………………
……………………………………………………………………………………………
…………………………………………………………………………………
………………………………………………………………………………………
………………………………………………………………………………………
2 2 3
4 4 4 5
6
6
6
6
6 7 7 8
9
9
11 13
26
26
26
27 27 27 29
30
33
44 45
45
48
58
58
1. Introduction 1. Introduction
1.1 Product Description
Soli s 5G t hr ee phase inve rt er is suitabl e fo r ut ility-sca le P V pr ojects . This m an ua l covers the th re e phase inver te r mo del listed be lo w: Soli s- 25 K-5G, Solis -3 0K-5G, Soli s- 33 K-5G, Solis -3 6K -5G, Solis- 40 K-5G, Solis -4 0K -HV-5G, Soli s- 50 K-HV-5G, Sol is -15K-LV-5G, Solis-2 0K -LV-5G , Solis-23K -LV-5G
LED lights
LCD display
4 buttons
1.2 Packaging
When you receive the inverter, please ensure that all the parts listed below are included:
Inv er ter x1
Hex scr ews x2
Back pl ate x1
RJ45 co nnect or x 1
Cross s crews x 4
DC conn ector s
(25-3 3)K x6, ( 36 -50 )K x 8
DC Switch
DC input
Figu re 1 .1 F ront view
Meter
OFF DC1 DC2 DC3 DC4 DC5 DC6 DC7 DC8
ON
Figu re 1 .2 B ottom view
Manua l
AC output
AC te rm inal co ve r x1 User ma nual x1
METER
COM1
DRM
If anything is missing, please contact your local Solis distributor.
DRM
.3..2 .
2. Safety Instructions 2. Safety Instructions
2.1 Safety Symbols
Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed as follows:
WARNI NG :
WAR NI NG symbol ind ic ates import an t sa fety instru ct io ns, which if no t corr ec tl y followed, c ou ld result in se ri ou s injury or dea th .
NOTE :
NOTE s ym bo l indicates i mp ortant safety i ns tructions , wh ic h if not correc tl y foll ow ed , could resul t in s ome damage or t he d es truction of t he i nv erter.
CAUT IO N:
CAUT IO N, R ISK OF ELECTR IC S HO CK symbol ind ic ates import an t sa fety inst ru ct ions, which i f no t correctly fol lo wed, could re su lt i n electric sh oc k.
CAUT IO N:
CAUT IO N, H OT SUR FACE symbol in di ca tes safety in st ructions, w hi ch i f not corr ec tl y followed, c ou ld result in bu rn s.
CAUT IO N:
The PV a rr ay ( Solar panel s) s upplies a DC vo lt ag e when they are e xp os ed to sunl ig ht .
CAUT IO N:
Risk o f el ec tric shock fr om e nergy stored in c ap acitors of th e In ve rter.
Do not r em ov e cover for 5 min ut es after discon ne cting all pow er s ou rces
(ser vi ce t echnician o nl y). Warr an ty m ay be voided if t he c over is remov ed
with ou t un authorize d.
CAUT IO N:
The su rf ac e temperatu re o f th e inverter ca n ex ceed 75 (167).
To avoid r is k of b urns, DO NOT touch th e su rf ace when inve rt er is operati ng .
The in ve rt er must be inst al led out of reac h of c hi ldren.
2.2 General Safety Instructions
WARNIN G:
Pleas e don’t con nect PV arr ay positi ve (+) or ne gative(-) to ground, i t could
cause s erious da mage to the inverter.
WARNI NG :
Elec tr ic al installa ti ons must be don e in a cc ordance wit h th e lo cal and natio na l elec tr ic al safety sta nd ards.
WARNING:
To reduce the r is k of fire, over-current protective de vi ce s (O CP D) are required for circuits c on ne ct ed t o the Inverter. The DC OCPD sha ll b e in st al led per local requirements. All ph ot ov ol ta ic source and output cir cu it c on du ct ors shall have disconnects that c om pl y with the NEC Art ic le 6 90 , Part II. All Solis thr ee p ha se i nverters feature an integrated DC sw it ch .
CAUT IO N:
Risk o f el ec tric shock. D o no t remove cove r. There is n o us er servicea bl e part s in si de. Refer ser vi cing to quali fi ed a nd accredit ed s er vice techni ci ans.
2.3 Notice For Use
The in ve rt er has been con st ructed acco rd in g to the applic ab le s afety and tec hn ical guid el in es. Use the inv er ter in instal la ti ons that meet t he f ol lowing spec if ications on ly :
1. Perm an en t installat io n is required .
2. The el ec tr ical instal la tion must mee t al l th e applicabl e re gu lations and s ta ndards.
3. The in ve rt er must be inst al led accordi ng t o th e instructi on s st ated in this ma nu al.
4. The in ve rt er must be inst al led accordi ng t o th e correct tec hn ic al specific at ions.
5. To start up t he i nverter, the G ri d Supply Main S wi tc h (AC) must be sw it ch ed on, before the so la r pa nel's DC isol at or shall be swi tc he d on. To sto p the inverte r, th e Gr id Supply Main S wi tc h (AC) must be sw it ch ed off b efore the sol ar p anel's DC iso la to r shall be swit ch ed o ff .
.5..4 .
3. Overview
4. Product handing and storage
3.1 Front Panel Display
Figu re 3 .1 F ront Panel Di sp lay
3.2 LED Status Indicator Lights
Light
1
2
3
PO W E R
OPE R AT ION
AL A R M
Status
ON
OFF
ON
OFF
FLASHING
ON
OFF
Descripti on
The inverte r ca n de te ct D C power.
No DC power or lo w DC p ow er.
The inverte r is o pe ra ti ng properly.
The inverte r ha s st op pe d to supply power.
The inverte r is i ni ti al izing.
Alarm or faul t co nd it io n is detected.
The inverte r is o pe ra ti ng without faul t or a la rm .
4.1 Product handling
Plea se r ev iew the instr uc tion below fo r ha nd ling the inve rt er :
1. The red cir cl es b elow denote c ut ou ts on the produ ct p ackage. Push i n th e cu touts to form h an dles for moving t he i nverter (se e Fi gu re 4.1).
3
Figure 4.1 move the inverter
2.Op en t he c arton, then t wo p eople handl e bo th s ides of inver te r th rough the are a deno te d do tted line. ( se e fi gure 4.2).
Table 3. 1 St at us Indicato r Li ghts
3.3 Keypad
Ther e ar e fo ur keys in the fr on t pa nel of the Inve rt er(from lef t to r ig ht): ESC, U P, DOWN an d EN TE R keys. The keypad is u se d fo r:
Scro ll in g through the d is played opti on s (t he UP an d DOWN keys);
Acce ss t o mo dify the adju st able settin gs ( th e ESC and ENTER k ey s) .
3.4 LCD
The tw o- li ne Liquid Cry st al Display (L CD ) is l ocated on the f ro nt p anel of the Inv er ter, whic h sh ow s the followi ng i nformatio n:
Inve rt er o peration st at us and data;
Alar m me ss ages and faul t in dications .
.6 .
Serv ic e me ssages for op er ator;
Figure 4.2 Inverter handles
NOTE :
Be car ef ul t o lift the inve rt er. The w ei ght is around 4 5k g.
.7.
4. Product handing and storage
5. Installation
4.2 Product Storage
If the i nv er ter is not to be in st al led immedia te ly, sto rage instru ct io ns and enviro nm ental cond it io ns are below:
Use th e or ig inal box to rep ac kage the inve rt er, s eal with adhe si ve tape with the desi cc an t inside the bo x.
Stor e th e in verter(s) i n a cl ean and dry pla ce , fr ee of dust and di rt .
Stor ag e te mperature m us t be between -4 0 an d 70 a nd the humidi ty s ho uld be
betw ee n 0 an d 100% non-co nd ensing.
Stac knom or ethanthree(3 )in vertershig h.
Keep b ox (e s) away from co rr osive mater ia ls t o avoid damag e to t he i nverter enc lo sure.
Insp ec t pa ckaging reg ul arly. If pa ckaging is da ma ged(wet, pe st d am age, etc), repa ck ag e the inverte r im mediately.
Stor e th e in verter(s) o n a fla t, hard surface - n ot i nclined or up si de d own.
Afte r lo ng -term stora ge , th e inverter ne ed s to be fully exa mi ne d and tested by q ua lified serv ic e or t echnical pe rs onnel befor e us in g.
Rest ar ti ng after a long p er iod of non-us e re qu ires the equi pm ent to be inspect ed and, i n so me c ases, the rem ov al of oxidati on a nd d ust that has se tt le d inside the equi pm en t will be requi re d.
5.1 Select a Location for the Inverter
To selec t a lo ca tion for the in ve rter, the foll ow in g criteria sh ou ld b e considere d:
WARNI NG : Risk of fir e
Desp it e ca reful const ru ction, elec tr ic al devices ca n ca us e fires. Do not i ns ta ll the invert er i n areas conta in in g highly flam ma bl e materials o r gase s. Do not i ns ta ll the invert er i n potential ly e xp losive atmo sp he res.
Do not i ns ta ll in small clo se d spaces wher e ai r ca nnot circula te f re ely. To avo id over he at ing, always m ak e sure the flow o f ai r ar ound the inve rt er i s not blocked .
Expo su re t o direct sunl ig ht will incre as e th e operation al t em perature of t he i nverter and may ca us e ou tput power li mi ting. Ginlo ng r ec ommends inv er te r installed t o av oid dire ct s un light or rain in g.
To avoid o ve r he ating ambie nt a ir temperat ur e mu st be conside re d wh en choosi ng the in ve rt er installa ti on location . Gi nl ong recomme nd s us ing a sun shade m in imizing dire ct s un light when th e am bient air tem pe ra ture around t he u ni t exceeds 104 °F /40°C.
Figu re 5 .1 R ecommende d In stallatio n lo ca tions
NOTE :
Noth in g sh ould be store d on o r placed agai ns t th e inverter.
.9..8 .
Vertical Backward
5. Installation5. Installation
5.2 Mounting the Inverter
Back hanging plate size:
15°
Inverted
× ×
Install on a vertical surface or structure capable of bearing the weight.
Please install the inverter vertically. If the inverter cannot be mounted vertically, it may be tilted backward to 15 degrees from vertical.
For multiple inverters are installed on site, a minimum clearance of 500mm,should be kept between each inverter and any other mounted equipment. The bottom of the inverter must be at least 500mm from the ground or floor. See figure 5.2.
Visibility of the LED status indicator lights and LCD display screen should be considered.
500mm
500mm
m
m
00
10
500mm
Figu re 5 .3 I nverter wal l mo unting
Refe r to f ig ure 5.4 and fig ur e 5.5. Inverter s ha ll be mounted v er ti cally. The st ep s to m ount the inve rt er a re listed bel ow.
1. Refer t o Fi gu re 5.4, the hol es f or expansio n bo lt b ased on the hol e di am eter of brack et (M10 *7 0) , u sing the perc us sion drilli ng w it h the 10mm dril l ne ed t o stay vertic al ly on the wa ll . And t he drill hole m us t be vertical ly o n th e wall. And all dr il l ho les' depth is 6 0m m.
2. Make su re t he b racket is hor iz ontal. And the m ou nt ing holes (in F ig ur e 5.4) are mark ed corr ec tl y. Dr il l the holes int o wa ll a t your marks.
3. Use the s ui ta ble expansi on s crews to fix th e br ac ket on the wall .
Bra ck et
Suita ble fix in g scr ew s
500mm
Figu re 5 .2 I nverter Mou nt ing clearan ce
Figu re 5 .4 I nverter wal l mo unting
.11..10 .
WARNI NG :
The in ve rt er must be moun te d verticall y.
5. Installation5. Installation
5.3 Electrical Connections
Inve rt er d esigns quic k- connect ter mi na l, so top cover n ee dn 't open durin g el ectrical conn ec ti on. Th e sign meanin g lo cated the botto m of i nverter, as sh ow n be low in table 5. 1. All el ec tr ical connec ti ons are suit fo r th e lo cal or nation al s ta ndard.
4. Lif t th e in verter and ha ng i t on the bracke t, a nd t hen slide dow n to m ak e sure they matc h pe rf ectly.
Figu re 5 .5 I nstall the in ve rter
5. If th e in st allation po si tion is high, t he i nv erter canno t be d ir ectly mount ed o n the moun ti ng p late, and the h oi sting rope is h oi st ed through th e tw o li fting holes .
The ro pe n ee ds to meet the lo ad -bearing re qu ir ements of thi s pr od uct.
DC 1 ~ DC 8
ON
OFF
COM1
METER
DRM
The el ec tr ical connec ti on of the inver te r mu st follow the s te ps l isted below :
1. Swit ch t he G rid Supply Ma in S witch (AC) OFF.
2. Swit ch t he D C Isolator OF F.
3. Con ne ct t he inverter t o th e grid.
4. Assem bl e PV i nput connec to r to the Inverter.
DC inp ut t er minal
Swit ch o n th e DC switch
Swit ch o ff t he D C sw itch
COM po rt f or m onitoring
COM po rt f or M eter
COM po rt f or D RM
Table 5. 1 El ec trical conn ec tion symbol s
5.3.1 Grounding
To effective ly p ro tect the inve rt er, t wo groundin g me thods must be p er fo rmed. Conn ec t th e AC grounding c ab le (Please re fe r to s ection 5.3. 3) Conn ec t th e external gr ou nding termi na l.
To conne ct t he g rounding te rm inal on the hea t si nk , please foll ow t he s teps below:
1. Pre pa re t he groundin g ca ble: recomm en d to u se the ≥ 16mm² outdoor
copp er -c ore cable.
2. Pre pa re O T te rm inals: M6.
Impo rt an t:
For mu lt ip le inverter s in p arallel , all i nv er ters should b e co nn ected to the same g ro un d point to elim in ate the possi bi li ty of a voltage p ot en tial existi ng betw ee n in verter grou nd s.
Figu re 5 .6
.1 2. .13.
5. Installation5. Installation
3. Str ip t he g round cable i ns ulation to a su it ab le length(s ee F ig ure 5.12).
B
A
Figu re 5 .1 2 Suitable le ngth
Impo rt an t:
B (ins ul at ion strippi ng l ength) is 2mm ~3 mm l onger than A (O T cable term in al c rimping are a) 2 mm~3mm.
4. Ins er t th e stripped wi re i nto the OT terminal cri mp ing area and us e th e hy draulic clam p to c ri mp the termin al t o th e wire (see Fig ur e 5.13).
C
5. Rem ov e th e screw from th e he at sink ground po in t.
6. Con ne ct t he groundin g ca ble to the grou nd in g point on the he at s in k,and tight en t he grou nd in g screw, Torque is 3-4Nm (s ee figure 5.14) .
Gro undin g screw
Figu re 5 .1 4 Fixed cabl e
Impo rt an t:
For im pr ov ing anti-co rr osion perfo rm an ce, afte r gr ou nd cable inst al led, apply si li co ne or paint is pr ef er red to protec t.
D
Figu re 5 .1 3 Strip wir e
Impo rt an t:
Afte r cr im ping the term in al to the wire, ins pe ct the connec ti on t o ensure the term in al i s solidly cri mp ed to the wire.
.1 4. .15.
5.3.2 Connect PV side of inverter
Befo re c on necting inv er ter, please ma ke s ur e the PV array op en c ir cuit volt ag e is w ithin the lim it o f the inverte r.
Befo re c on nection, pl ea se make sure th e po la rity of the out pu t vo ltage of PV arr ay m at ches theDC+an dDC -symbols.
5. Installation5. Installation
5. Mea su re P V voltage of DC i np ut with multi me te r, verify DC inp ut c ab le polar
(see f ig ur e 5.21), and en su re each string of P V vo ltage in rang e of i nv erter opera ti on.
Conn ec t DC c onnector wi th i nverter until h ea ring a slight c li ck ing sound ind ic ates
conn ec ti on succeed. ( se e fi gure 5.22 )
Figu re 5 .1 5 DC+ Connect or Figu re 5 .1 6 DC- Connect or
Plea se u se a ppropriat e DC c able for PV sys te m.
Cabl e t yp e
Ind us try ge ne ric P V ca bl e
model :P V1-F
Rang e
4.0~6 .0
12~10 AWG
Cros s se ct ionmm²
Reco mm en ded value
4.012AWG
The st ep s to a ssemble the D C co nnectors ar e li st ed as follows :
1. Str ip o ff t he D C wi re for about 7m m, d is assemble th e co nnector cap n ut . (s ee Figure 5.1 7)
2. Ins er t th e wire into the c on nector cap nut an d co ntact pin. (s ee F ig ure 5.18)
3. Cri mp t he c ontact pin to t he w ire using a pro pe r wi re crimper. (s ee F ig ure 5.19)
4. Ins er t me tal connect or i nto top of connec to r, and tighten n ut w it h torque 3-4 Nm
(see f ig ur e 5.20).
Figure 5.17 D is as se mb le the Connecto r Ca p nu t
Figure 5.18 I ns er t th e Wi re into the Connector C ap n ut a nd c on tact pin
Crim pi ng p lier
Figure 5.19 C ri mp t he c on tact pin to the wir e Figure 5.20 C on ne ct or w ith Cap nut Screw ed o n
OFF DC1 DC2 DC3 DC4 DC5 DC6 DC7 DC8
+
ON
METER
COM1
DRM
-
Figure 5.21 M ul ti me te r measurement
Caut io n:
If DC in pu ts a re accident ly r eversely co nn ec ted or invert er i s fa ulty or not work in g pr operly, it is NOT allowed to t ur n of f th e DC s witch as it wil l da ma ge the in ve rt er and even lea ds t o a fire disast er. The co rr ec t actions are : *Use a c li p- on ammeter t o me asure the DC st ri ng c urrent. *If it i s ab ov e 0.5A, pleas e wa it for the solar ir ra diance redu ce s un til the curr en t de creases to be lo w 0.5A. *Onl y af te r the current i s be low 0.5A, you are a ll owed to turn off the DC swit ch es a nd disconne ct t he PV strings . Plea se n ot e that any dama ge s due to wrong op er at ions are not co ve re d in the de vi ce w arranty.
Figure 5.22 C on ne ct t he D C
Connector s to t he I nv er ter
.1 6. .17.
5.3.3 Connect grid side of inverter
For th e AC co nn ection, 10- 35 mm² cable is req ui re d to be used.
Plea se m ak e sure the resi st ance of cable i s lo we r than 1.5ohm .
Cabl e sp ec ification
Tra ve rse cross sectional a re a (m m )²
Cable outer d ia me te r (mm)
NOTE :
For re li ab le connecti on , recommend c us to mer select co rr es ponding Eur o type c on ne ctors based o n wi ring specif ic at ion to connec t th e te rminal.
The st ep s to a ssemble the A C grid termin al s are listed as f ol lo ws:
1. Str ip t he e nd of AC cable ins ul ating jacke t ab ou t 80mm then str ip t he e nd of each wire .
(as sh ow n in f igure 5.23)
Range
Recom mende d
Range
Recom mende d
Figu re 5 .2 3 Strip AC cable
Copp er -c ored cable
10~35
25
22~32
27
80MM
S2
N
PE
L
S1
5. Installation5. Installation
4. Rem ov e th e 4 screws on the i nv erter junctio n bo x and remove th e ju nc tion box cove r .
5. Ins er t th e cable throu gh t he nut, sheath, a nd AC t erminal cov er. C on nect the cabl e to the AC te rm in al block in tur n, u sing a socket w re nc h.Tight en t he screws on th e te rm inal block. The to rq ue i s 3~4Nm (as sho wn i n Figure 5.24 ).
Figu re 5 .2 4 wiring
5.3.4 Inverter monitoring connection
The in ve rt er can be monit or ed via Wi-Fi or GPR S. Al l Solis commu ni ca tion device s ar e opti on al ( Figure 5.25 ). F or connecti on i ns tructions , pl ea se refer to the S ol is Monitori ng Devi ce i ns tallation m an uals.
Smar t ph on e monitorin g
GPRS m on it oring
NOTE :
S2 (in su la tion stripp in g length) sho ul d be a s long as S1 (AC te rm in al cable comp re ssion area) .
2. Str ip t he i nsulation o f th e wire past the cab le c rimping are a of t he O T te rm inal, then u se a h yd raulic crim p to ol to crimp the ter mi nal. The crimped po rt io n of the termin al must b e in su lated with he at s hrinkable t ub e or i nsulating t ap e.
3. Lea ve t he AC b reaker disc on nected to ens ur e it d oes not close u ne xp ectedly.
Wi-F i mo ni toring
Wi-F i mo ni toring
Figu re 5 .2 5 Wireless co mm unication f un ct ion
Rout er
Wi-F i bo x
Interne t
Web server
PC mon it or ing
.19.. 18 .
Monitoring system for multiple inverters
Mult ip le i nverters ca n be m onitored by R S- 48 5 daisy chain c on fi guration. ( Se e figure 5.26 ).
Inver te r 1 Inver te r 2 I nv erter n
RS4 85 IN | O UT
RS4 85 IN | O UT
RS4 85 IN | O UT
Wi- Fi box
RS4 85ter mi nal
GP RS bo x
RS4 85ter mi nal
Rou ter
Eth ernet
Int ernet
Int ernet
5. Installation5. Installation
Terminal bloc k co nnection
a. Use a w ir e st ripper to pee l off th e in su lation laye r of t he communic at io n cables to a cert ai n le ngth as shown i n Fi gure 5.28. b. Scr ew o ff t he c ov ers of "COM2" a nd " CO M3" on the inve rt er as shown in Fi gu re 5 .29.
30m m
8mm
RS4 85-23 2conv erter
RS4 85
RS2 32
PC
RS2 32
Figu re . Mult ip le i nverter mon it oring syste m 5 26
5.3.4.1 RS485 Connection
Inst al l th e RS485 commu ni cation cabl es t hr ough the term in al b lock as shown i n Fi gure 5.27. Reco mm en ded cable cro ss s ectional ar ea i s 0. 2 - 1.5mm², the cab le o ut er diameter i s 5mm -1 0m m, t he cable leng th s hall not exce ed 3 m.
1 2 3 4
Figu re 5 .2 7 RS485 Terminal Defi ni tion
NO.
1
2
3
4
Port d ef in ition
RS48 5A 1 IN
RS48 5B 1 IN
RS48 5A 2 OU T
RS48 5B 2 OU T
Desc ri pt ion
RS48 5A 1, RS485 different ia l si gnal+
RS48 5B 1, RS485 different ia l si gnal-
RS48 5A 2, RS485 different ia l si gnal+
RS48 5B 2, RS485 different ia l si gnal-
Table 5. 2 Po rt d efinition
Figu re 5 .2 8
Figu re 5 .2 9
c. Ins er t th e communica ti on cables int o th e "C OM2" and "COM 3" p or ts. d. Fas te n th e cables onto t he p luggable te rm in als provide d in t he a ccessory pa ck age. e. Mat ch t he p luggable te rm inals to the te rm in al block in the i nv er ter and press t o fa sten it.
Afte r ca bl e installat io n, please rem em be r to fasten the s cr ew s of the AC termin al c over in case o f wa te r damage.
5.3.5 Max. over current protection device (OCPD)
To prote ct t he i nverter's AC g ri d connectio n co nd uctors, Sol is r ec ommends ins ta lling brea ke rs t hat will prot ec t against ove rc ur rent. The followi ng t ab le defines OC PD rati ng s fo r the Solis 25- 50 kW Thr ee p hase invert er s.
Inve rt er
Soli s- 25 K-5G
Soli s- 30 K-5G
Soli s- 33 K-5G
Soli s- 36 K-5G
Soli s- 40 K-5G
Soli s- 40 K-HV-5G
Soli s- 50 K-HV-5G
Soli s- 15 K-LV-5 G
Soli s- 20 K-LV-5 G
Soli s- 23 K-LV-5 G
Rate d volt ag e( V)
220/ 38 0, 230/400
220/ 38 0, 230/400
220/ 38 0, 230/400
220/ 38 0, 230/400
220/ 38 0, 230/400
480
480
220
220
220
Table 5. 3 Ra ti ng of grid OCPD
Rate d ou tp ut curr en t (A mps)
38.0 /3 6. 1
45.6 /4 3. 3
50.1 /4 7. 6
54.7 /5 2. 0
60.8 /5 7. 7
48.1
60.1
39.4
52.5
60.4
Curr en t fo r protectio n devi ce ( A)
50
63
63
80
80
63
80
63
80
80
.2 0.
.21.
5. Installation 5. Installation
DC8
COM1
METER
DRM
DC8
COM1
METER
DRM
DC8
COM1
METER
DRM
5.3.6 Meter Connection(optional)
The in ve rt er can work wit h a th ree phase sma rt m et er to achieve E xp or t Power Manag em ent func ti on a nd/or 24hou r co nsumption m on it oring funct io n.
NOTE
To achieve Expo rt P ow er M an agement funct io n, t he s ma rt meter can be ins ta ll ed o n either grid s id e or l oa d si de . To achieve 24ho ur c on su mp ti on monitori ng f un ct io n, the smart mete r ca n on ly b e installed o n gr id s id e.
Pre-made Cable in Meter Package
2-Pin Connector
INV L1 INV L2 INV L3 INV N INV PE
Grid L1 Grid L2 Grid L3
Grid N Grid PE
Two typ es o f me ters are supp or ted: Dire ct I ns ert Typ e Meter - Max inp ut c ur rent 80A(DT SD 1352-Dire ct I ns ert Typ e). Exte rn al C T Type Mete r - 15 0A/5A CTs are supp li ed (DTSD1352 -E xternal CT Type). Cust om er c an place the or de r for a suitabl e me te r from Solis Sa le s Re ps. Belo w ar e th e connectio n di agrams of different m et ers connect in g to d iffe rent locati on s. Deta il ed s ettings ple as e refer to Sect io n 7. 5.12
Pre-made Cable in Meter Package
L1 L1' L2 L2' L3 L3' N
A B
21 22 17
1819 20
2-Pin Connector
INV L1
INV L2 INV L3 INV N INV PE
L1 L2
L3
Load
NPE
Grid L1
Grid L2 Grid L3 Grid N Grid PE
Figu re 5 .3 0 Direct Inse rt Type M et er - “ Meter in Grid ”
A B
1819 20
21 2217
L1 L1' L2 L2' L3 L3' N
L1 L2
Load
Figu re 5 .3 1 Direct Inse rt Type M et er - “ Meter in Load ”
Pre-made Cable in Meter Package
A B
21 22 17
UaUb Uc N Ia* Ia Ib* Ib Ic* Ic
2-Pin Connector
INV L1 INV L2 INV L3 INV N INV PE
L3
L1 L2
N PE
Load
L3
NPE
1819 20
CT Arrow
Grid L1 Grid L2 Grid L3
Grid N Grid PE
Grid
Figu re 5 .3 2 External CT Type Meter - “Me te r in G rid”
.23.. 22 .
5. Installation 5. Installation
DC8
COM1
METER
DRM
5.3.7 Logic interface connection
Lo gi c interface i s re quired by som e lo ca l regulatio ns t hat can be oper at ed b y a simple swit ch
Pre-made Cable in Meter Package
2-Pin Connector
INV L1 INV L2 INV L3 INV N INV PE
Grid L1 Grid L2 Grid L3 Grid N Grid PE
or con ta ct or(Not avai la ble in South Afr ic a) . When t he s wi tch is closed t he i nverter can o pe ra ted normall y. When t he s wi tch is opened , the in ve rt er will reduc e it ’s o ut pu t power to zero w it hin 5s. Pin5 a nd P in 6 of RJ4 5 te rm inal is used fo r th e logic inter fa ce c onnection .
Plea se f ol low below ste ps t o assemble RJ 45 c on nector.
1. Inse rt t he n etwork cabl e in to the commun ic at ion connect io n te rminal of R J 45.
A B
1819 20
21 22 17
UaUb Uc N Ia* Ia Ib* Ib Ic* Ic
Figu re 5 .3 3 External CT Type Meter - “Me te r in L oad”
Grid
CT Arrow
L1 L2
L3
Load
NPE
Figu re 5 .3 4 R J45 c om mu nication co nn ection term in al s
2. Use th e ne tw ork wire stri pp er to strip the ins ul ation layer o f th e co mmunicati on c able. Acco rd in g to the standa rd l ine sequenc e of f ig ure 5.35 conn ec t th e wire to the plu g of RJ45, a nd t hen use a netwo rk c ab le crimping t oo l to make it tigh t.
Rj4 5 plug
1-- 8
Rj4 5term inal
1 2 3 4 56 7 8
1 2 3 4 5 6 7 8
Swi tch_ in put 1 Sw itc h_ in put 2
DRM (logi c inter face)
Corresp on de nc e between t he c ab les and the sti tc he s of plug, Pi n5 a nd P in 6 of RJ45 ter mi na l is u sed for the l og ic interfa ce , ot he r Pins are re se rv ed .
Pin 1: Reserved ; Pi n 2: R es er ve d Pin 3: Reserved; Pi n 4: R es er ve d Pin 5: Switch_i np ut 1; P in 6 : Sw it ch_input2
Pin 7: Reserved ; Pi n 8: R es er ve d
Figu re 5 .3 5 Strip the ins ul ation layer a nd c on nect to R J 45 p lug
3. Conn ec t R J45 to D RM (l ) . ogic i nt er face
Afte r wi re c onnection , pl ease refer ch ap te r 7.5.9.1 to en ab le t he logic inte rf ace functio n.
.25.. 24 .
6. Start & Stop
6.1 Start the Inverter
To start up the Inverter, it is important that the following steps are strictly followed:
1. Swit ch t he g rid supply ma in S witch (AC) ON fir st .
2. Swit ch t he D C switch ON. If t he v ol tage of PV arra ys a re higher tha n st ar t up voltage, the in ve rt er will initi al ize. The r ed LED power wi ll l ight.
3. When b ot h th e DC and the AC side s su pply to the inv er te r, it will be read y to g en erate powe r. In it ially, the inverte r wi ll c heck both its i nt ernal param et er s and the param et ers of the AC g ri d, t o ensure that t he y ar e within the ac ce ptable limi ts . At th e same time, the gr ee n LE D will flash an d th e LCD display s th e in formation o f IN IT IALIZING.
4. After 3 0- 30 0 seconds (de pe nding on loca l re qu irement), t he i nverter will st ar t to gene ra te p ower. The green LED wi ll b e on continua ll y an d the LCD displ ay s GENE RATING.
WARNI NG :
Do not t ou ch t he surface wh en t he inverter i s op er ating. It may b e hot an d ca us e burns.
6.2 Stop the Inverter
7. Operation
In nor ma l op eration, LC D sc reen altern at iv ely shows inv er te r power and ope ra tion status (see F ig ur e 7.1). The screen ca n be s cr olled manua ll y by pressing t he U P/ DOWN keys. Pres si ng t he ENTER key gi ve s access to Main Me nu .
Sta rt
5 sec
Press ing the
ENTER k ey gives a ccess t o the m ai n menu.
Press ing the
ESC k ey
calls b ack the
previ ous men u.
Power 11 000 0W 01-01 -2019 1 2: 04
UP/DO WN or
auto- scrol l
(10 sec )
Sta tu s: Gene ra tin g 01-01 -2019 1 2: 04
Advan ced set ti ngs
Figu re 7 .1 O peration Ov er view
Advan ced Inf o.
Main Me nu
Infor matio n
UP/DO WN
Setti ngs
UP/DO WN
UP/DO WN
To stop th e In ve rter, the foll ow ing steps mus t be s tr ictly follo we d:
1. Turn off the ac s wi tc h.
2. Put th e DC S WI TCH on the inve rt er i n the positio n of " OFF".
7.1 Main Menu
Ther e ar e fo ur submenus i n th e Main Menu (se e Fi gu re 7.1):
1. Info rm at ion
2. Sett in gs
3. Advan ce d In fo.
4. Advan ce d Se ttings
7.2 Information
The So li s th ree Phase 5G In ve rter main men u pr ov ides access t o op er ational data a nd i nf ormation. The inf or ma tion is displ ay ed by selecti ng " In formation " fr om the menu a nd t he n by scrollin g up o r down.
.2 6. .27.
7. Operation7. Operation
Disp la y
V_DC0 1: 0000 .0 V i_DC0 1: 0000 .0 A
V_A: 00 0.0V I_ A: 00 0. 0A
V_C: 00 0.0V I_ C: 000 .0A
Sta tu s: Gene ra tin g Power : 0000W
Rea_P ower: 0 00 0Var App_P ower: 0 00 0VA
Gri d Fr equen cy F_G ri d 00.00 Hz
Total Ene rgy 00000 00 kwh
Thi s Mo nth: 00 00 kwh Last Mo nth: 00 00 kwh
Today: 00 .0kwh Yest erd ay : 00. 0k wh
Dura ti on
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
Desc ri pt ion
V_DC 01 : Sh ows input DC vo lt age.
I_DC 01 : Sh ows input DC cu rr ent.
V_A: S ho ws t he grid's vol ta ge value.
I_A: S ho ws t he grid's cur re nt value.
V_C: S ho ws t he grid's vol ta ge value.
I_C: S ho ws t he grid's cur re nt value.
Stat us : Sh ows instant s ta tu s of the Invert er.
Powe r: S ho ws instant ou tp ut power valu e.
Rea_Power : Sh ow s th e re active power of t he i nv er te r.
App_Power : Sh ow s th e ap parent power of t he i nv er te r.
F_Gr id : Sh ows the grid' s fr eq uency val ue .
Total ge ne ra ted energy va lu e.
This M on th : Tota l en ergy genera te d th is month.
Last M on th : Tota l en ergy genera te d la st month.
Today: Total ene rg y ge nerated tod ay.
Yest er day: Total energy gen er ated yester da y.
7.2.1 Lock screen
Pres si ng t he ESC key retu rn s to the Main Menu. P re ssing the ENT ER k ey l ocks (Fig ur e 7. 2(a)) or unlo ck s (Figure 7.2 ( b) ) th e screen.
(b)(a)
Figu re 7 .2 L ocks and Unlo ck s the Screen of L CD
7.3 Settings
The fo ll ow ing submenu s ar e displayed w he n th e Settings me nu i s se lected:
1. Set Tim e
2. Set Add re ss
7.3.1 Set Time
This f un ct ion allows ti me a nd date setti ng . Wh en this funct io n is s elected, th e LC D will disp la y a sc reen as shown i n Fi gure 7.3.
NEXT =< EN T> OK=<ESC>
01-0 1- 20 19 16:37
Figu re 7 .3 S et Time
Pres s th e UP /DOWN keys to s et t im e and data. Pre ss t he ENTER key to m ov e fr om one digi t to t he n ext (from lef t to r ig ht). Press th e ES C key to save the s et ti ngs and retur n to the pr ev io us menu.
Inv er ter SN 00000 00000 00 00
10 sec
Disp la y se ries number o f th e inverter.
7.3.2 Set Address
This f un ct ion is used to se t th e address whe n mu ti i nverters ar e co nn ected to thre e mo nitor.
Wor k Mo de: N UL L DRM NO. :08
I_P V0 1: +05. 0A I_P V0 2: +04. 9A
.. .
I_P V0 8: +05. 2A
10 sec
Work Mode: S ho ws c urrent work in g mo de.
DRM NO .: S ho ws DRM Number.
I_PV 01 : S ho ws input 01 cur re nt value.
10 sec
I_PV 02 : S ho ws input 02 cur re nt value.
...
I_PV 08 : S ho ws input 08 cur re nt value.
Table 7. 1 In fo rmation lis t
The ad dr es s number can be a ss igned from “0 1” to “ 99”(see Fig ur e 7. 4). Th e default add re ss numb er o f So lis Th ree Phase Inv er te r is “01”.
YES= <E NT > NO=<ESC>
Set Add re ss : 01
Figu re 7 .4 S et Address
Pres s th e UP /DOWN keys to s et t he a ddress. Pre ss t he ENTER key to s av e th e settings. Pres s th e ES C key to cancel t he c ha nge and ret ur n to t he previous m en u.
.2 8. .29.
7.4 Advanced Info - Technicians Only
7. Operation7. Operation
NOTE :
To acces s to t hi s area is for ful ly q ualified an d ac cr edited tech ni ci ans only. Ente r me nu “ Advanced In fo .” and “Advan ce d se ttings” (ne ed p as sword).
Sele ct “ Ad vanced Info .” f ro m the Main Menu . The sc re en will requi re t he p assword as be lo w:
YES= <E NT > NO=<ESC>
Pass wo rd :0000
Figu re 7 .5 E nter passwo rd
The de fa ul t password is “ 00 10". Plea se p re ss “down” to mo ve t he cursor, pre ss “ up ” to select the n um be r. Afte r en te r the correct p as sw ord the Main Me nu w ill display a s cr ee n and be able to ac ce ss to the f ol lo wing inform at ion.
1. Alar m Me ss age 2. Runnin g me ss age 3.Versio n 4. D aily Energy 5 . Mo nt hly Energy
6. Yearly Ene rg y 7. D aily Record s 8. Co mm unication D at a 9. Warni ng M es sage
The sc re en c an be scrolle d ma nually by pre ss in g the UP/DOWN k ey s. P ressing the E NT ER key gi ve s ac cess to a subme nu . Press the ESC key t o re turn to the Mai n Me nu .
7.4.1 Alarm Message
The di sp la y shows the late st a la rm messages ( se e Figure 7.6) . Sc re ens can be scro ll ed 100 manu al ly b y pressing th e UP / DOWN keys. Pres s th e ESC key to retu rn t o th e previous me nu .
Alm0 00 : OV- G-V
T: 00- 00 00 :00 D : 00 00
Figu re 7 .6 Al arm Message
Soft wa re Ve rsion: D200 01
Mode l: 0 8
Figu re 7 .7 M odel Version a nd S oftware Vers io n
7.4.4 Daily Energy
The fu nc ti on is for check in g the energy ge ne ra tion for sele ct ed d ay.
YES =<E N T > N O=< ESC>
Sele ct : 20 19-01-01
Figu re 7 .8 S elect date fo r da ily energy
Pres s D OWN ke y to m ove the curso r to d ay, m on th a nd year, press UP k ey t o change the di gi t. Pres s En te r after the dat e is f ix ed.
2019 -0 1- 01: 051.3kW h 2019 -0 1- 01: 061.5kW h
Figu re 7 .9 D aily energy
Pres s U P/D O W N key to mo ve o ne d ate from anot he r.
7.4.5 Monthly Energy
The fu nc ti on is for check in g the energy ge ne ra tion for sele ct ed m onth.
YES =<E N T > N O=< ESC>
Sele ct : 20 19-01
Figu re 7 .1 0 Select mont h fo r monthly ene rg y
7.4.2 Running Message
This f un ct ion is for main ta ince person t o ge t ru nning messa ge s uc h as internal t em perature, Stan da rd N o.1,2,etc . Scre en s ca n be scrolled m an ually by pres si ng t he UP/DOWN ke ys .
7.4.3 Version
The sc re en s hows the mode l ve rsion of the in ve rt er. And the scree n wi ll s how the
soft wa re v er by pressin g th e UP and D OW N at the same tim e. (see Figure 7 .7 ).
Pres s D OWN ke y to m ove the curso r to d ay a nd month, pre ss UP k ey to change th e di git. Pres s En te r after the dat e is f ix ed.
2019 -0 1: 0 510kWh 2019 -0 1: 0 610kWh
Figu re 7 .11 M on th e nergy
Pres s U P/D O W N key to mo ve o ne d ate from anot he r.
.31.. 30 .
7. Operation7. Operation
7.4.6 Yearly Energy
The fu nc ti on is for check in g the energy ge ne ra tion for sele ct ed y ear.
YES =<E N T > N O=< ESC>
Sele ct : 20 19
Figu re 7 .1 2 Select year f or y early energ y
Pres s D OWN ke y to m ove the curso r to d ay a nd year, press UP k ey t o change the di gi t. Pres s En te r after the dat e is f ix ed.
2018 : 00 17 513kWh 2017 : 01 65 879kWh
Figu re 7 .1 3 Yearly energy
Pres s U P/D O W N key to mo ve o ne d ate from anot he r.
7.4.7 Daily Records
The sc re en s hows histor y of c hanging set ti ng s. Only for mai nt an ce personel .
7.4.8 Communication Data
The sc re en s hows the inte rn al data of the In ve rt er (see Figur e 7. 14 ), which is for s er vice tech ni ci ans only.
7.5 Advanced Settings - Technicians Only
NOTE :
To acces s to t hi s area is for ful ly q ualified an d ac cr edited tech ni ci ans only. Plea se f ol low 7.4 to ente r pa ssword to acc es s th is menu.
Sele ct Ad va nced Settin gs f rom the Main Me nu t o ac cess the foll ow in g options:
1. Sele ct S ta ndard 2. Grid ON /O FF 3 . 24H Switch 4. Cl ea r En ergy
5. Res et P as sword 6. Powe r Co nt rol 7. Calibr at e Energy 8. Speci al S ettings
9. STD . Mo de S ettings 10. R es to re Settings 11 . HM I Update 12. Inte rn al EPM Set
13. Ex te rn al EPM set14. R es tart HMI 15. Debu g Pa rameter 16. D SP Upd at e
17. Co mp en sation Set 18 .I /V C urve
7.5.1 Selecting Standard
This f un ct ion is used to se le ct the grid's ref er ence standa rd ( se e Figure 7.16 ).
YES= <E NT > NO=<ESC>
Stan da rd :G59/3
Figu re 7 .1 6
Pres s th e UP /DOWN keys to s el ec t the standar d (G 59/3, UL-48 0V, VDE0126, AS4 77 7-15, AS47 77 -0 2, CQC380A, E NE L, UL-380V, MEX -CFE, C10/11 and “Us er -D ef” functio n) . Pres s th e EN TER key to conf ir m th e setting. Pres s th e ES C key to cancel c ha nges and retu rn s to p revious men u.
01-0 5: 0 1 25 E 4 9D AA 06-1 0: C 2 B5 E 4 9D 55
Figu re 7 .1 4 Communica ti on Data
7.4.9 Warning Message
The di sp la y shows the late st w ar n messages (s ee F igure 7.15) . Sc re ens can be scro ll ed 100 manu al ly b y pressing th e UP / DOWN keys. Pres s th e ESC key to retu rn t o th e previous me nu .
Msg0 00 : T: 00- 00 00:00 D : 00 00
Figu re 7 .1 5 Warnin g Me ssage
NOTE :
This f un ct ion is for tech ni cians use onl y.
Sele ct in g the “User-D ef ” menu will acc es s to t he followin g su bm enu (see Figu re 7 .17),
OV-G- V1 : 40 0V
OV-G- V1 -T: 1. 0S
Figu re 7 .1 7
NOTE :
The " Us er -D ef" functio n ca n be only used by t he s er vice engine er a nd must b e al lo wed by the loca l en ergy suppli er.
.33.. 32 .
Belo w is t he s etting rang e fo r “User-Def ”. U si ng this funct io n, t he limits can b e ch anged manu al ly.
OV-G -V1: 236---335V OV-G-F1: 50.2-53Hz (6 0. 2-63Hz)
OV-G -V1-T: 0.1---9s OV-G-F 1- T: 0. 1- --9s
OV-G -V2: 248---341V OV-G-F2: 51-53Hz(6 1- 63 Hz)
OV-G -V2-T: 0.1---1s OV-G-F 2- T: 0. 1- --9s
UN- G-V1: 173---236V UN-G- F1 : 47- 49 .5Hz(57-5 9. 5H z)
UN- G-V1-T: 0.1 ---9s UN -G -F 1-T: 0. 1- -- 9s
UN- G-V2: 132---219V UN-G- F2 : 47- 49 Hz(57-59H z)
UN- G-V2-T: 0.1 ---1s UN -G -F 2-T: 0. 1- -- 9s
St ar tup-T:10---600 S
Pres s th e UP /DOWN keys to s cr ol l through ite ms . Press the ENT ER k ey t o edit the high li ghted item . Pr es s the UP/DOWN k ey s ag ain to change t he s etting. Pre ss t he E NTER key to sav e th e sett in g. P ress the ESC ke y to c an cel changes a nd r eturns to the p re vi ous menu.
NOTE
For diffe re nt c ountries, the g ri d st an da rd needs to be set as d if ferent accord in g to l oc al requireme nt s. I f th er e is any doubt, ple as e co ns ul t Solis service t ec hn ic ia ns for details.
Re st ore-T:10---600 S
7. Operation7. Operation
7.5.3 24H Switch
This f un ct ion control s th e 24H hours con su mp tion functi on e na ble or disabl e.
Enab le Disa bl e
Figu re 7 .1 9 Set 24H ON/OF F
NOTE :
When t hi s is e nabled, the i nv erter LCD wil l st il l be alive at nig ht w it h the po we r LE D light on. If th e gr id is in malfun ct io n at night, the s ys te m can’t reco ve r ev en after the gr id i s back to norma l bu t th e consumpti on d at a will stil l be r ec orded in the me te r. Until the sun ri se , the system wi ll s ta rt to work agai n wh il e the meter dat a ca n be uploaded t o th e So lis monitor in g system to cal ib ra te the load con su mption data .
7.5.4 Clear Energy
Clea r En er gy can reset th e hi story yield o f in ve rter
Thes e tw o fu nctions are a pp licable by ma in te nance perso nn el only, wr ong oper at io n will preven t th e inverter fr om w or king proper ly.
7.5.2 Grid ON/OFF
This f un ct ion is used to st ar t up o r stop the powe r ge neration of S ol is I nverter.
Grid O N
Grid O FF
Figu re 7 .1 8 Set Grid ON/O FF
Scre en s ca n be scrolled m an ually by pres si ng t he UP/DOWN ke ys . Pr ess the ENTER k ey to sav e th e se tting. Pres s th e ES C key to return t o th e previous me nu .
7.5.5 Reset Password
This f un ct ion is used to se t th e ne w passwor d fo r me nu “Advance d in fo .” and “Advan ce d info rm at ion” (see Fig ur e 7.20).
YES= <E NT > NO=<ESC>
Pass wo rd : 0000
Figu re 7 .2 0 Set new passw or d
Ente r th e ri ght passwor d be fore set new pa ss wo rd. Press the D OW N ke y to move the cur so r, Pres s th e UP k ey t o re vise the valu e. P re ss the ENTER ke y to e xecute the se tt in g. Pres s th e ES C key to return t o th e pr evious menu .
.35.. 34 .
7. Operation7. Operation
7.5.6 Power control
Acti ve a nd r eactive pow er c an be set throu gh p ow er setting bu tt on . Ther e ar e 5 it em for this sub m en u:
1. Set o ut pu t power 2. Set Re ac ti ve Power 3. Out _P Wit h Re st ore
4. Rea _P Wit h Re st ore 5. Select P F Curve
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
7.5.7 Calibrate Energy
Main te na nce or replac em ent could cle ar o r ca use a different val ue o f to tal energy. Use this func ti on c ould allow us er t o revise the va lu e of t otal energy t o th e sa me value as bef or e. If the mo ni to ring websit e is u sed the data wi ll b e sy nchronous w it h th is setting au to matically.
YES= <E NT > NO=<ESC>
Ener gy :0 000000kWh
Figu re 7 .2 1 Calibrate e ne rgy
Pres s th e DO WN key to move th e cu rs or, Press the UP key to re vi se the value. Pre ss t he ENTE R ke y to e xecute the se tt in g. Press the ES C ke y to return to th e pr ev ious menu.
7.5.8 Special Settings
7.5.9.1 Enable logic interface settings
When s el ec t G 98 o r G99 standar d to u se t he logic inte rf ac e function, p le ase follow be lo w
sett in gs t o enable the DR M. D RM default sett in g is “OFF” , if DRM s et “ ON ”, but the logi c
inte rf ac e un-connec te d to the switch o r th e sw itch is open, t he i nv erter HMI wil l di splay “Limi t
by DRM ” an d th e inverter ou tp ut power will b e li mi ted to zero.
1. Sel ec t In itial Setti ng s
2. Sel ec t DR M and set it ON
7.5.10 Restore Settings
Ther e ar e 5 it ems in initia l se tting subme nu .
Rest or e se tting could s et a ll item in 7.5. 8 sp ec ial setting t o de fa ult. Thesc re ens howsasbelow :
Are yo u su re ?
YES= <E NT > NO=<ESC>
Figu re 7 .2 2 Restore Set ti ngs
Pres sth eEn terkeytosavet hes ettingafterse tt inggridoff.
Pres sth eES Ckeytoreturnt hep reviousmea n.
7.5.11 HMI Update
This f un ct ion is used for u pd ating the LCD p ro gr am.
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
7.5.9 STD Mode settings
Ther e ar e 6 se tting under S TD . Mo de settings .
1. Working Mod e Se t 2. Power Rate L im it 3 . Freq Derate S et
4. 10m in s Volta ge S et 5.Power Pr io ri ty 6.Initia l Se tt ings
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
.37.. 36 .
7.5.12 Internal EPM Set
This section includes two functions related to the smart meter.
Please refer to section 5.3.6 for detailed connection diagrams.
Function 1: Internal Export Power Management Function
Inverters can work with a smart meter to dynamically limit the export power of
the system. Zero injection can be achieved.
Smart meter can be installed either on the grid side OR the load side.
Function 2: 24 Hour Consumption Monitoring Function
Only applicable if Solis monitoring system is used.
Inverters can work with a smart meter to monitor the load consumption data for
the whole day and the data will be displayed on the Solis monitoring system.
Smart meter can only be installed on the grid side.
Please refer to below instructions for different user scenarios.
Scenario 1. Only Function 1 is required
Step 1: Refer to Section 5.3.6 to connect the smart meter on the grid side or load side.
Step 2: Select the Section 7.5.12.1 Mode Select as Option 2(Meter in Load) or
Option 3 (Meter in Grid) accordingly.
Step 3: Configure the Section 7.5.12.2 to set the allowed backflow power.
Step 4: Configure the Section 7.5.12.3 to enable the failsafe function (If necessary).
Step 5: Configure the Section 7.5.12.4 to modify the work mode (If necessary).
Scenario 2. Both Function 1 and 2 are required
Using a Smart Meter:
Step 1: Refer to Section 5.3.6 to connect the smart meter on the grid side.
Step 2: Select the Section 7.5.12.1 Mode Select as Option 3(Meter in Grid).
Step 3: Select the Section 7.5.3 24H Switch as "Enable".
Step 4: Configure the Section 7.5.12.2 to set the allowed backflow power.
Step 5: Configure the Section 7.5.12.3 to enable the failsafe function (If necessary).
Step 6: Configure the Solis monitoring system (Please refer to the manual of monitoring
device).
If customer does not want to enable the export power control function, please change
the "backflow power" to the max output power of the inverter in Step 4 OR simply
select the mode as "consumption monitor" in Step 2 and skip Step 4-5.
7. Operation7. Operation
Sele ct E PM S ettings fro m th e Ma in Menu to acce ss t he followin g op ti ons:
1. Mod e Se le ct 2.Backflo w Po we r 3.Fail safe ON /O FF 4 .Backflow Work Mod e
7.5.12.1 Mode Select
Ther e ar e 4 se ttings in thi s me nu as below:
1. OFF 2 . Me te r in Load 3. Mete r in G ri d 4.Consump ti on M onitor OFF: F un ct ions are disa bl ed Mete r in L oa d: Solis Smar t Me te r is connecte d in t he load branc h ci rc uit. Mete r in G ri d: Solis Smar t Me te r is connecte d in t he grid conne ct io n point (The ba ck flow
powe r is d ef ault as 0W). Cons um pt ion Monitor : So li s Smart Meter i s co nnected in th e gr id c onnection p oi nt ( The back fl ow p ower settin g is n ot applicab le ).
7.5.12.2 Backflow Power
The se tt in g is used to defi ne t he allowed ex po rt p ower into the g ri d. The se tt in g range is betw ee n 00000W to 299 00 W.
->Se t Ba ck flow Power
Figu re 7 . Se t the powe r 23 back fl ow
YES=<ENT> NO= <E SC >
Power:-0000 0W
Figu re 7 .2 4
Pres s th e UP /DOWN keys to s et d at a.Press the E NT ER key to set bac kf lo w power. Then p re ss D OWN keys to mov e th e cu rsor, press UP to chan ge t he number. Pres s th e ES C key to save the s et ti ngs and retur n to t he previous m en u.
7.5.12.3 Fail safe ON/OFF
This s et ti ng is used to giv e ou t an alarm (stop in ve rter genera ti on a s well) when th e Me ter conn ec ti on is lost duri ng o peration. It can p re ve nt potentia l ba ckflow powe r in to t he grid when th e sy st em loses cont ro l.
YES= <E NT > NO=<ESC>
Fail S af e Se t:ON
Figu re 7 .2 5 Set the Fail Sa fe O N/ OFF
.39.. 38 .
7. Operation7. Operation
It is on ly m an datory to tur n on t hi s function wh en t he inverter i s in st alled in UK due t o th e G100 regu la ti on. For other r eg ions,cust om er s can enable or d is ab le the functi on a s they desire .
NOTE :
When t he failsa fe functi on i s ON and CT/M eter is dis connect ed someho w, the in verter wi ll stop gen er ation a nd g ive "Fail safe" ala rm on the LCD . When t he failsa fe functi on i s OFF and CT/ Meter is di sconnec ted someh ow, the in verter wi ll keep the o ut put pow er a s the last mo ment when t he CT/M eter is sti ll c onnec te d. After a res tart, the i nverter w ill outpu t at f ull powe r without l imit.
7.5.12.4 Backflow Work Mode
This s ub me nu is used for se t ba ckflow work m od e: 0 1, 02. “01” is th e de fa ult mode.
->Ba ck fl ow Wor k Mode
Figu re 7 .2 6 Set the Backf lo w work mode
YES=<ENT> NO= <E SC >
Mode:01
Figu re 7 .2 7
Mode “ 01 ”, As s hown in the fig ur e 7.28, the ave ra ge l imiting mod e, t he o utput power o f ea ch phas e is t he a verage of the t hr ee-phase lo ad p ow er, and it is more t ha n th e phase of the lowe st p ow er in three pha se s.
Inverter
Mode “ 02 ”, As s hown in the fig ur e 7.29 the per ph as e li miting mode , th e in verter only
gene ra te t he power that e qu als to one of thr ee -p hase load pow er t ha t is the lowest load p ow er o f a certain pha se .
Inverter
Mete r
Figu re 7 .2 9
7.5.13 External EPM Set
This s et ti ng should onl y be t urned on when S ol is e xternal EPM d ev ic e is used.
Two opt io ns a re availabl e5G-EPM and Ot he rs -EPM.
->5G -E PM Othe rs -E PM
Figu re 7 .3 0
5G-E PM F ai lsafe Optio n sh ould be turne d ON w he n 5G series EPM d ev ic e is used Othe rs -E PM Failsafe O pt io n should be tur ne d ON when 2G seri es E PM d evice is used Only o ne o pt ion can be acti va ted each time .
Figu re 7 .2 8
Mete r
7.5.14 Restart HMI
Thefu nc ti onisusedforre st arttheHMI.
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
.41.. 40 .
7. Operation7. Operation
7.5.15 Debug Parameter
This f un ct ion is used for m an ufacturer mai nt enance pers on ne l only.
7.5.16 DSP Update
The fu nc ti on is used for up da te the DSP.
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
7.5.17 Compensation Set
This f un ct ion is applic ab le by mainten an ce p ersonnel on ly, wro ng o pe ration will p re ve nt the invert er f rom reachin g ma xi mum power.
7.5.18 I/V Curve
This f un ct ion is used to sc an t he I/V characte ri stic curves o f ea ch P V strings.
Set I/ V Cu rv e I/V Cu rv e Sc an
7.5.18.2 I/V Curve Scan
Pres s “E NT ” to start the I/ V cu rv e scan.
Scan ni ng ...01
Figu re 7 .3 3 I/V Curve Sca n (1 )
Afte r it i s co mpleted, th e sc re en will displ ay “ Scan OK” and th en e nt er the follow in g section.
Sele ct S tr ing No.: 01
Figu re 7 .3 4 I/V Curve Sca n (2 )
9.56 A
9.44 A
Figu re 7 .3 4 I/V Curve Sca n (3 )
Figu re 7 .3 1 I/V Curve
7.5.18.1 Set I/V Curve
This s et ti ng can set the sc an ning voltag e st ar t point and the v ol ta ge interval .
850V 010V
Figu re 7 .3 2 Set I/V Curve
Star t_ V: Th e start volta ge o f th e I/V scan. (Ad ju stable from 3 00 V-1 000V) Inte rv al _V: The scanni ng v oltage inte rv al .(Adjusta bl e fr om 1-100V) In tot al , 60 d ata points ca n be s canned.
.43.. 42 .
7. Operation
7.6 AFCI function
Soli s in ve rters have th e bu ilt-in AFCI fu nc ti on which can de te ct t he arc fault on t he D C circuit and sh ut d ow n the inverte r to p revent a fire d is as ter.
7.6.1 Enable the AFCI function
The AFC I fu nc tion can be ena bl ed in the follo wi ng . Path : Adv an ced Setting - > Pa ssword: 0010 -> Sp ecial Setti ng s -> AF CI Set ->
AFCI ON /O FF - > ON
AFCI O N/ OF F AFCI L ev el
Figu re 7 .3 5 Set AFCI
ON OFF
8. Maintenance
Soli s Thre e Ph as e Inverter do es n ot r equire any re gu lar mainten an ce . However, clea ni ng t he dust on heat -s ink will help t he i nv erter to diss ip at e the heat and in cr ease its life time . The du st c an b e removed wit h a so ft b rush.
CAUT IO N:
Do not t ou ch t he inverter 's s urface when i t is o pe rating. Som e pa rt s of the inve rt er m ay be hot and cau se b urns. Turn off the inver te r (refer to Sec ti on
6.2) a nd w ai t for a cool-do wn p eriod befor e an y ma intenance o r cl eaning oper at io n.
The LC D an d th e LED status in di cator light s ca n be c leaned with a d am p cl oth if they are t oo dirt y to b e re ad.
War ni ng:
The "A FC I Le vel" is reser ve d for Solis techn ic ians ONLY. Do not c ha ng e the sens it iv ity otherwi se i t will lead to fr eq ue nt false alar ms o r ma lfunction s. Soli s is n ot r esponsibl e fo r any further d am ag es caused by un au th orized modi fi ca tions.
NOTE :
The se tt in g correspon ds t o the current sta tu s as well which c an b e us ed to insp ec t th e ON/OFF stat e of t he AF CI function .
7.6.2 Arc Fault
Duri ng the norm al operat io n, if an DC a rc i s detecte d, the inve rter will s hut down
and gi ve out the fo llowing a la rm:
ARC-FA ULT
Rest ar t Pr ess ESC 3s
Figu re 7 .3 6 Arc Fault
Inst aller nee ds to thoro ug hly inspe ct the DC cir cuit to ens ure all the c ables are
corr ectly fas te ned.
Once t he DC circu it issue ha s be en fixed or i t is confir med to be OK, p ress “ESC ” fo r
3s and w ait for the i nverter t o re start.
NOTE :
Neve r us e an y solvents, a br asives or cor ro si ve material s to c le an the invert er.
9. Troubleshooting
The in ve rt er is designe d in a ccordance w it h th e most import an t in ternation al g rid-tied stan da rd s and safety an d el ectromagn et ic c ompatibil it y re quirement s. B efore deliv er in g to the cu st om er, the invert er h as been subje ct ed t o several tes ts t o en sure its opti ma l operation and re li ab ility.
In cas e of f ai lure, the LCD s cr een will disp la y an a larm messag e. I n th is case, the in ve rter may st op f ee ding into the g ri d. The f ai lure descri pt ions and thei r co rr esponding a la rm mess ag es a re listed in Table 9.1:
.45.. 44 .
9. Troubleshooting
9. Troubleshooting
Alarm Messa ge
No power
LC D show initializing all the time
OV-G-V01/ 02 /0 3/ 04
UN -G-V01 /0 2
OV-G-F01/ 02
UN -G-F01 /0 2
G- IMP
NO - GR ID
OV-D C01/02/0 3/ 04
OV-B U S
UN - BU S01/ 02
GR I D-I N TF01/02
OV-G-I
IG B T- OV-I Over I G BT curre nt
DC - IN TF OV-D C A- I
IG F O L- F
IG - AD
OV-T E M
IN I -F AULT
DS P -B -F AU LT
12Power-FA ULT
PV ISO-P R O 01/02
Failure des cr ip ti on
Inverter no p ow er on L C D
Can not start -u p
Over grid vol ta ge
Under grid vo lt ag e
Over grid fre qu en cy
Under grid fr eq ue nc y
High grid imp ed an ce
No grid volta ge
Over D C voltage
Over D C bus voltag e
Under DC bus volta ge
Grid interf er en ce
Over grid cur re nt
DC input ove rc ur re nt
Grid curren t tr ac ki ng f ail
Grid curren t sa mp li ng f ail
Over Temp er at ur e
Initializ at io n sy st em fault
Comm. failu re b et we en m ain and slave DS P
12V power sup pl y fa ul t
PV isolatio n pr ot ec ti on
Solution
1. Check P V input co nn ec ti on s.
2. Check D C input vo lt ag e. (single pha se > 12 0V, th re e ph as e >3 50V)
3. Check if PV +/- is r ev er se d.
1. Check if the c on ne ct or o n main board or powe r bo ar d ar e fi xed.
2. Check if the DS P connecto r to power board a re f ix ed .
1. Resistan t of A C ca bl e is t oo h ig h. Change bigg er s iz e gr id c able.
2. Adjust the pr ot ec ti on l imit if it’s allowed by el ec tr ic al c ompany.
1. Use user def in e fu nc ti on to adjust the protectio n li mi t if i t’s allow ed b y electrica l co mp an y.
1. Check conn ec ti on s an d grid switch.
2. Check the gr id v ol ta ge i nside inverte r terminal.
1. Reduce the m od ul e nu mb er in series.
1. Check inve rt er i nd uc tor connectio n.
2. Check driv er c on ne ct ion.
1. Restart in ve rt er.
2. Change pow er b oa rd .
1. Restart in ve rt er.
2. Identify and remove the string to the fault MPPT .
3. Change pow er b oa rd .
1.Restart i nv er te r or c ontact instal le r.
1. Check inve rt er s ur ro unding ventil at io n.
2. Check if the re ’s sunshine dir ec t on inverter in h ot w ea th er.
1. Restart in ve rt er o r co ntact install er.
1. Remove all DC inp ut , re co nn ec t and restart inv er te r on e by o ne.
2. Identify w hi ch s tr in g cause the fault a nd check the iso la ti on o f th e string.
Alarm Messa ge
ILeak-PRO 01/02/03/ 04
RelayChk- FAI L
DCinj-FAULT High DC injec ti on c ur re nt
Reve-DC
Screen OFF with DC appli ed
Failure des cr ip ti on
Leakage cur re nt p ro te ction
Relay check f ai l
One of the DC str in g is reversely c on ne ct ed
Inverter in te rn al ly d amaged
Solution
1. Check AC and DC connectio n.
2. Check inve rt er i ns id e cable connect io n.
1. Restart in ve rt er o r co ntact install er.
1. Plea se c he ck the in ve rters ’ PV stri ng p olari ty, if ther e ar e st rings r ev ersel y co nn ected w ai t fo r the nig ht w he n the sol ar i rradi an ce i s low and t he PV stri ng c ur rent do wn b elow 0. 5A . Tur n off t he two DC sw it ch s and fix t he p olari ty i ss ue.
1.Do not turn o ff t he DC switches as i t wi ll damage the in ve rt er.
2.Please wa it f or t he s ol ar irradiance r ed uc es and confirm t he s tr in g cu rrent is less tha n
0.5A with a clip -o n am me te r and then turn off t he D C sw it ch es.
3.Please no te t ha t an y da mages due to wron g operation s ar e no t co ve red in the device warranty.
Table 9. 1 Fa ul t message and d es cription
NOTE :
If the i nverter d is plays a ny a larm mess age as list ed in Table 9.1, pl ea se turn o ff t he i nverter ( refer to Se ction 6.2 t o stop your i nv erter ) an d wait for 15 minu tes befor e restart in g it (refer t o Section 6 .1 to start y our inver te r). If the fail ure persi sts, plea se c ontact yo ur local di stribut or or the ser vice cent er. Plea se keep rea dy with you t he f ollow in g informa tion befo re contac ting us.
1. Seri al n um ber of Solis Three Ph as e In verter;
2. The distri bu to r/dealer of S ol is T hr ee P hase Invert er ( if availabl e) ;
3. Inst al la tion date.
4. The descri pt io n of problem (i .e . th e alarm messa ge d isplayed on t he L CD a nd the status of the L ED s ta tus indicat or l ig hts. Other re ad ings obtain ed f ro m the Informa ti on submenu (ref er t o Se ction 6.2) wi ll a ls o be helpful. );
5. The PV arra y co nf iguration ( e. g. n umber of pane ls , capacity of p an el s, number of st ri ngs , etc. );
6. Your co nt ac t details.
.47.. 46 .
10. Specifications
10. Specifications
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con necti on s
Warran ty
Solis -25K- 5G
1100
600
180
200.. .1000
3*26
3*40
3/6
25000
27500
27500
3/N/PE, 220 /3 80 , 23 0/ 400
38.0/ 36.1
41.8
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con nection s
Warran ty
Solis -30K- 5G
1100
600
180
200.. .1000
3*26
3*40
3/6
30000
33000
33000
3/N/PE, 220 /3 80 , 23 0/ 400
45.6/ 43.3
50.2
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
.49.. 48 .
10. Specifications10. Specifications
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con necti on s
Warran ty
Solis -33K- 5G
1100
600
180
200.. .1000
3*26
3*40
3/6
33000
36300
36300
3/N/PE, 220 /3 80 , 23 0/ 400
50.1/ 47.6
55.1
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con nection s
Warran ty
Solis -36K- 5G
1100
600
180
200.. .1000
4*26
4*40
4/8
36000
39600
39600
3/N/PE, 220 /3 80 , 23 0/ 400
54.7/ 52.0
60.2
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
.51.. 50 .
10. Specifications10. Specifications
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con necti on s
Warran ty
Solis -40K- 5G
1100
600
180
200.. .1000
4*26
4*40
4/8
40000
44000
44000
3/N/PE, 220 /3 80 , 23 0/ 400
60.8/ 57.7
66.9
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con nection s
Warran ty
Solis -40K- HV-5G
1100
600
180
200.. .1000
4*26
4*40
4/8
40000
44000
44000
3/PE, 480
48.1
53.0
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
.5 2. .53.
10. Specifications
10. Specifications
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con necti on s
Warran ty
Solis -50K- HV-5G
1100
600
180
200.. .1000
4*26
4*40
4/8
50000
55000
55000
3/PE, 480
60.1
66.2
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
VD E-A R-N 4105 , VDE V 0124, V D E V 0126 -1-1,
UT E C 15 -712- 1, N R S 097-1 -2 , G9 8, G 99 ,
EN 505 49-1/ -2, RD 169 9, U N E 20600 6,
UN E 2060 07 -1, IE C617 27,D EWA
IE C 6 2109- 1/-2, IE C62116 & EN 6 1000- 6- 2/-4
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con nection s
Warran ty
Solis -15K- LV-5G
1100
600
180
200.. .1000
3*26
3*40
3/6
15000
16500
16500
3/PE, 220
39.4
43.3
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
IE C 6172 7, I E C 62 116, C 10 /11,
VD E 4105 , IEE E 1547
IE C 6 2109- 1/-2 , I EC 610 00-3- 11/1 2,
IE C62116 & EN 610 00-6- 1/-2/-3 /-4, U L 174 1
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
.5 4.
.55.
10. Specifications
10. Specifications
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con necti on s
Warran ty
Solis -20K- LV-5G
1100
600
180
200.. .1000
3*26
3*40
3/6
20000
22000
22000
3/PE, 220
52.5
57.7
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
IE C 6172 7, I E C 62 116, C 10 /11,
VD E 4105 , IEE E 1547
IE C 6 2109- 1/-2 , I EC 610 00-3- 11/1 2,
IE C62116 & EN 610 00-6- 1/-2/-3 /-4, U L 174 1
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
Model
Max. DC inpu t volta ge (Volt s)
Rated D C vol ta ge (Vo lts)
Start -up vol tage (Vo lts)
MPPT volta ge rang e (Volts )
Max. in put cur rent (A mps)
Max sho rt ci rc uit inp ut cu rr ent (Am ps)
MPPT numbe r/Max i nput st rings n umber
Rated o utput p ower (Wa tts)
Max. ou tput po wer (Wat ts)
Max. ap paren t outpu t power ( VA)
Rated g rid vol tage (Volts )
Rated g rid out put cur rent (A mps)
Max. ou tput cu rrent ( Amps)
Power F actor ( at ra te d out pu t pow er )
THDi (a t rat ed outp ut powe r)
Rated g rid fre quenc y (Hert z)
Max.e ffi ciency
EU effici ency
Dimen sions ( W*H*D )
Wei ght
Topol ogy
Self co nsump tion (n ight)
Opera ting am bient t emper ature ran ge
Relat ive hum idity
Ingre ss prot ectio n
Cooli ng conc ept
Max.o perat ion alt itude
Grid co nnect ion sta ndard
Safty /EMC st andar d
DC co nn ectio n
AC co nn ectio n
Displ ay
Commu nicat ion con nection s
Warran ty
Solis -23K- LV-5G
1100
600
180
200.. .1000
3*26
3*40
3/6
23000
25000
25000
3/PE, 220
60.4
65.0
0.8le ading ~0.8l ag ging
<3%
50/60
98.8%
98.3%
647*6 29*25 2mm
45kg
Transf ormerle ss
1W
-25℃.. . +60
0~100 %
IP65
Natur al conv ectio n
4000m
IE C 6172 7, I E C 62 116, C 10 /11,
VD E 4105 , IEE E 1547
IE C 6 2109- 1/-2 , I EC 610 00-3- 11/1 2,
IE C62116 & EN 610 00-6- 1/-2/-3 /-4, U L 174 1
MC4 con necto r
OT Ter min al
LC D, 2×2 0 Z
RS 48 5, O pt ional : Wi fi, GP R S
5 yea rs (ext an d to 20 y ears)
.5 6.
.57.
11. Appendix 11. Appendix
11.1 Grid standard selection guide
NO. Cod e in LCD C ou nt ry/Region Co mm ents
NOTE :
Plea se c he ck if the grid co de s etting comp ly w it h local requi re me nt.
Fo r di ff er ent countri es a nd r egions, cor re sponding gr id c od e needs to be sel ec ted in the inve rt er LCD to meet the re qu irements of l oc al n etwork prov id er. Th is i nstructio n in dicates how t o ch an ge the grid cod e an d what code sho ul d be s elected in differen t pl ac es.
Th is f ollowing li st i llustrate s th e gr id standard o pt io ns in the inver te r which are sub je ct t o chan ge . It is f or y our referen ce o nl y. If cust om er h as any doubts o r un certainty, please cons ul t Sol is s ervice depa rt me nt for confir ma tion.
To set t he c orrect grid c od e, please ent er t he f ollowing pa th : Ad va nced Settings -> P asswo rd :0010 -> Select Standar d
De ta iled protec ti on limits can b e vi ew ed when choos in g the code. Pl ea se select " Save& Send" t o en force the cod e.
NO.
1
2
EN505 49 PO
3
EN505 49 NL
Co de i n L C D
VDE 4015
Co un try/R egion
Ge rm any
Po la nd
Ne th erland
Co mm ents
Fo r Ger ma n L ow Vol ta ge Gr id .
Fo r Pol is h L ow Vol ta ge Gr id
Fo r Dut ch Lo w Volt ag e Gri d
13
14
15
16
17
18
19
20
21
22
G9 8 N I
G9 9 N I
Us er -define
Ge n5 0
Ge n 60
DK1
DK2
5043 8IE
RD169 9
EN505 49
No rt h I re land
No rt h I re land
-
-
-
Ea st De nm ark
West D enmar k
Ir el and
Sp ai n
-
Fo r Nor th Ir el an d L ow Vol ta ge Gr id < 16A
Fo r Nor th Ir el an d L ow Vol ta ge Gr id > 16A
Cu st omized Protect io n Lim it s
Ge ne rator C onnecte d, Freq ue ncy-D erating, 50 Hz
Ge ne rator C onnecte d, Freq ue ncy-D erating, 60 Hz
Fo r Eas t Dan is h lo w voltage gri d
Fo r West Danish lo w vo lt age grid
Fo r Iri sh l ow voltage gr id
Fo r Spa ni sh low voltag e gr id
Ge ne ral E N 50 549 R eq uirement.
Po ss ible to be used i n Cyp ru s, Fi nl and,
Cz ec h R ep ublic, Slovenia, Jam ai ca
EN504 38 L
4
5
EIF S - S W
6
7
8
9
10
11
12
.5 8. .59.
Fr an ce
C1 0/ 11
NRS 097
CEI 0-21
EN505 49 L
(E N 50549-1)
G9 8
G9 9
-
Sw ed en Fo r Swe di sh Lo w Vo lt ag e G ri d
Fr an ce
Be lg ium
So ut h Af ri ca
It al y
-
UK
UK
Ge ne ral E N 50 43 8 R eq uirement.
Po ss ible to be used i n Aust ri a, Cy pr us, F in land,
Cz ec h R ep ublic, Sloveni a, e tc .
Fo r Fre nc h L ow Vol ta ge Gr id
Fo r Bel gi an Lo w Vo lt ag e G ri d
Fo r Sou th Afr ic an Lo w Volt ag e G ri d
Fo r Ita li an Lo w Vo lt ag e G ri d
Ge ne ral E N 50 54 9-1 requi re me nt which meet s
loca l re qu irements of m os t E ur op ean countri es
Fo r U K L ow Vol tage Grid <16A
Fo r U K L ow Vol tage Grid >16A
Loading...