GLS60 Series, GLS60-M Series Installation & Operating Instructions
To comply with the published safety standards, the following must be observed when using
this power supply:
1. Maximum ambient temperature for the power supply must not exceed 50°C.
2. When installing the power supply in the end-use equipment, special attention is
required to ensure safety compliance with the following safety standards: UL60950-1,
EN60950-1, IEC60950-1, and CSA22.2 No. 60950-1-03 for GLS62, GLS63, GLS64,
and GLS65; UL60601-1, EN60601-1, IEC60601-1, and CSA22.2 No. 60601-1-M90
for GLS63-M, GLS64-M, and GLS65-M. The safety requirements include creepage
distances, clearances, and distance through insulation between primary wiring and
earth or secondary (SELV) wiring.
3. The power supply’s rated input voltage is automatically selected for GLS62, GLS63,
GLS64, and GLS65. Please refer to the specication sheet for the input voltage range.
GLS63-M, GLS64-M, and GLS65-M are approved and certied for the rated voltage
range of 100 V ac to 250 V ac and/or 140 V dc to 300 V dc.
4. The maximum output power of the supply must not exceed the rating indicated in the
specication sheet.
5. The earth ground wire must be connected only to the point marked with the earth
ground symbol (on the unit).
6. The disconnection from the line must be in the end system.
7. Hazardous voltages exist in the primary circuits. Disconnect the power supply before
servicing.
8. When operating with a dc input voltage range, the unit input must be protected by a dc
rated fuse in the end-use installation system.
9. The internal fuse should only be replaced with a 3.15 A, 250 V ac, type SP0001.1009
manufactured by Schurter AG, type 2163.15 manufactured by Littelfuse, or type S501
manufactured by Cooper.
10. This power supply is not suitable for direct contact to the patient.
11. This equipment is considered Class I according to protection against electrick shock.
12. This power supply is
marked following the provisions of the Low Voltage Directive,
2006/95/EC.
13. For technical assistance, contact SolaHD Technical Support at (800) 377- 4384 or
send an e-mail to tech@solahd.com. Please visit our Web site at www.solahd.com for
additional product information and specication sheets.
Mechanical Outline
SK1
GND
R16
C32
C33
W6
R31
IC4
R32
C21
IC1
D1
1
T1
FB1
W4
3
D15
C27
J8
D16A
W2
SK201
V Adj. Pot
W3
1
SK2
6
Connector PIN Designation
Input Connector PIN GLS62 GLS63 (-M) GLS64 (-M) GLS65 (-M)
SK1
Output Connector PIN GLS62 GLS63 (-M) GLS64 (-M) GLS65 (-M)
SK2
SK201
NOte: Mounting holes M1 and M2 should be grounded for EMI purposes. Mounting hole M1 is a safety ground connection.
1 Neutral
3 Line
1
+5 V +12 V +15 V +24 V2
3
4
Common5
6
1 +Sense
2 -Sense
Output Ratings
Model
GLS62 +5 12.0
GLS63 (-M) +12 5.0 6.7
GLS64 (-M) +15 4.0 5.3
GLS65 (-M) +24 2.5 3.3
Output
Voltage (V)
Convection Cooling 30 CFM Forced Air Cooling
Max. Output
Current (A)
Max. Output
Power (W)
60
Max. Output
Current (A)
16.0
Max. Output
Power (W)
80
Visit our Web site at www.solahd.com or contact Technical Support at (800) 377- 4384 with any questions P/N: A272-198 Rev 0 5/12/09 Ref: 03361001333/03366200541

GLS60 Series, GLS60-M Series Installation & Operating Instructions
.22 [5.6]
2.55 [64.8]
3.00 [76.2]
.22 [5.6]
Mechanical Dimensions
Bottom View
4.55 [115.6]
5.00 [127.0]
Side View
6.69 [170.0]
1.57 [40.0]
Typical Ventilation Setup
Top View
AIR FLOW
FAN
7.28 [185.0] 4.33 [110.0]
Side View
T1
UNIT
1.08 [27.5] MAX
.06 [1.6]
All dimensions are in inches [mm]
Mounting hole diameter (4X): 0.15″ [3.81 mm]
.12 [3.0] MAX
Visit our Web site at www.solahd.com or contact Technical Support at (800) 377- 4384 with any questions.
GLS62, GLS63, GLS64, and GLS65 are commercial designations of model numbers LPS62, LPS63, LPS64, and LPS65 respectively.
GLS63-M, GLS64-M, and GLS65-M are commercial designations of model numbers LPS63-M, LPS64-M, and LPS65-M respectively.
4.33 [110.0]
FAN
AIR FLOW
UNIT
Fan: MINEBEA 3110NL-04W-B30
Fan Input: 12 V dc
NOTE: Dimensions and fan used are for reference only
While every precaution has been taken to ensure accuracy and completeness in this manual, EGS Electrical Group, LLC.
assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
©2009 EGS Electrical Group, LLC. All rights reserved. Specications subject to change without notice.

GLS60 Series Specifications
Electrical Specifications
Input
Input ra nge 85-264 Vac (wide range); 120-300 Vdc
Frequency 47-440 Hz
Inrush current <18 A peak @ 115 Vac, <36 A peak @ 230 Vac, cold start @ 25°C
Input current 1.5 A max. (RMS) @ 115 Vac
Efficiency 70% typical at full load
EMI filter
Safety ground
leakage current
Output
Maximum power 60 W convection; 80 W with 30 CFM forced air
Adjustment range -5, 10% min.
Hold-up time 20 ms @ 60 W load, 115 Vac nominal line
Overload protection
Overvoltage protection 5 V output; 5.7 to 6.7 Vdc; Other outputs 10% to 25% above nominal output
FCC Class B conducted; CISPR 22 Class B conducted;
EN55022 Class B conducted; VDE 0878 PT3 Class B conducted
<0.5 mA @ 50/60 Hz, 264 Vac input
Short circuit protection on all outputs.
Case overload protected @ 110-145% above peak rating
Remote sense Compensates for 0.5 V lead drop minimum, will operate without remote sense connected. Reverse connection protected
Environmental Specifications
Operating temperature
Storage temperature -40°C to 85°C
Temperature coefficient ±0.04% per °C
Electromagnetic
susceptibility
Humidity Operating; non-condensing 5% to 95% RH
Vibration Three orthogonal axes, sweep at 1 oct/min, 5 min. dwell at four major resonances 0.75G peak 5 Hz to 500 Hz, operational
MTBF demonstrated >550,000 hours at full load and 25°C ambient conditions
Mating Connectors
AC Input Molex 09-50-8031 (USA) Not required for (-T) option
09-91-0300 (UK); PINS: 08-58-0111
DC Outputs Molex 09-50-8061 (USA) Not required for (-T) option
09-91-0600 (UK); PINS: 08-58-0113
Remote Sense
Molex 22-01-2025
PINS: 08-52-0113
Connector Kit #70-841-006, includes all of the above
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±0.02” (±0.5mm).
3. Mounting holes M1 and M2 should be grounded for EMI purposes.
4. Mounting hole M1 is safety ground connection.
5. Specifications are for convection rating at factory settings at 115 Vac input, 25°C unless otherwise stated.
6. Warranty: 2 year
7. Weight: 0.75 lb/0.34 kg
0° to 50°C ambient. Derate each output 2.5% per degree from 50° to 70°C, -20°C startup
Designed to meet IEC 801, -2, -3, -4, -5, -6, Level 3
Power Derating Curve
80W
30 CFM Forced Air Cooling
60W
Output
Power
(Watts)
40W
20W
0W