Sofar solar Sunny Horse Series, 10k-20ktl User Manual

PV Grid-Connected Inverter
Shenzhen SOFARSOLAR Co.,Ltd.
Product Model: Sunny Horse Series(10K-20KTL) Document Version 2.0(2016.03.29)
User manual
Product Nome: PV Grid-Connected Inverter Company Name: Shenzhen SOFARSOLAR Co., Ltd. ADD: 3A, Huake Building, East Tech. Park, Qiaoxiang Road, Nanshan District, Shenzhen, China Http://www.sofarsolar.com
Notice
This manual contains important safety instructions that must be followed during installation and maintenance of the equipment.
Save these instructions!
This manual must be considered as an integral part of the equipment, and must be available at all times to everyone who interacts with the equipment. The manual must always accompany the equipment, even when it is transferred to another user or field.
Copyright Declaration
The copyright of this manual belongs to Shenzhen SOFARSOLAR Co., Ltd. Any corporation or individual should not plagiarize, partially copy or fully copy it (including software, etc.), and no reproduction or distribution of it in any form or by any means. All rights reserved. SOLARSOFAR reserves the right of final interpretation. This manual is subject to change ac cor din g to us er ’s o r c usto mer ’s fe edb ack . P lea se ch ec k o ur we bsi te at http://www.sofarsolar.com for latest version.
Shenzhen SOFARSOLAR Co ., Ltd.
ADD: 3A,Huake Building,East Tech.Park,Qiaoxiang Road,Nanshan District,Shezhen,China
P.C. 518000:
Http://www.sofarsolar.com
E-mail: service@sofarsolar.com
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
I
Preface
Please read the product manual carefully before installation, operation or maintenance. This manual contains important safety instructions and installation instructions that must be followed during installation and maintenance of the equipment.
This manual is for qualified person (support person, service person are qualified mentioned in this manual).
Outline
Scope
Target Group
Symbols Used
This manual provides safety operation information and uses the symbol in order to ensure personal and property security and use the inverter efficiently when operating the inverter. You must understand these emphasize information to avoid the personal injury and property loss. Please read the following symbols which used in this manual carefully.
This product manual describes the assembly, installation, commissioning, and maintenance of the following inverters.
Sunny Horse Series 10000-Sx Sunny Horse Series 15000-Sx Sunny Horse Series 17000-Sx Sunny Horse Series 20000-Sx(x=2,4,5)
Keep this manual where it will be accessible at all times.
Danger indicates a hazardous situation which, if not avoided, willresult in death or serious injury.
Warning indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Caution indicates a hazardous situation, if not avoided, could result in minor or moderate injury.
Attention indicates there are potential risks. If fail to prevent, may lead to equipment cannot run normally or property damage.
Note provides tips that are valuable for the optimal operation of the product.
Danger
Warning
Caution
Attention
Note
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
II
Sunny Ho rse Series( 10K~20 KTL) User manual
Sunny Ho rse Series( 10K~20 KTL) User manual
Preface
1
Basic safety information
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
III
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
IV
User manual User manual
Table of contentsTable of contents
Table of contents
1
1
1.1
1.2 S ymbol s and sig ns
Saf ety ins truct ions
3
Preface
II
5
5
2
Product characteristics
2.1
2.2 F uncti on desc ripti on
2.3 P rotec tion mo dules
2.4 E ffici ency an d derat ing cur ve
Pro duct id entif icati on
11
13
14
3
Inst allat ion
3.1
3.2 C hecki ng Befo re Inst allat ion
3.3 Too ls
3.4 D eterm ining t he Inst allat ion Pos ition
3.5 M oving t he Sunn y Horse S eries
3.6 I nstal ling th e Sunny H orse Se ries
Ins talla tion Pr ocess
15
16
16
18
20
21
22
4
Electrical Connections
4.1
4.2 C onnec ting PG ND Cabl es
4.3 C onnec ting AC Ou tput Po wer Cabl es
4.4 C onnec ting Co mmuni catio ns Cabl es
4.5 C onnec ting DC I nput Po wer Cab les
4.6 S afety c heck
Ele ctric al conn ectio n
24
25
25
27
31
37
43
5
Commissioning of inverter
5.1
5.2 S tart in verte r
Saf ety ins pecti on befo re comm issio ning
44
44
44
45
45
6
Operation interface
6.1
6.2 S tanda rd Inte rface
6.3 M ain Int erfac e
Ope ratio n and Dis play Pa nel
46
48
55
55
7
Trouble shooting and maintenance
7.1
7.2 M ainte nance
Troub le shoo ting
59
8
Decommissioning
8.1
8.2 P ackag e
8.3 S torag e
8.4 D ispos al
Dec ommis sioni ng step s
60
60
60
60
60
9
Technical data
9.1
9.2 O utput p arame ter (AC )
9.3 E ffici ency, Sa fety an d Protec tion
9.4 G enera l Data
Inp ut para meter ( DC)
61
61
62
62
63
10
Quality Assurance
64
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Basic safety information
1
Outlines of this chapter
safety instruction
It mainly introduce the safety instruction when install and operate the equipment.
1.1 Safety instructions
If you have any question or problem when you read the following information, please contact Shenzhen SOFARSOLAR Co ., Ltd .
Note
Symbols and signs
It mainly introduce the safety symbols on the inverter.
Read and understand the instruction of this manual ,and be familiar with relevant safety symbols in the paragraph, then start to install and debug the equipment.According to the national and state requirements, before connect the grid ,you must get power department permission, and perform the operation only by qualified electrical engineer.Before installing and maintaining the equipment, you should cut off the high voltage application of PV array. You can also open the switch of Solar Array Combiner to cut off the high voltage. Otherwise, serious injury may be caused.
Qualified persons
The customer must make sure the operator has the necessary skill and training to do his/her job. Staff in charge of using and maintaining the equipment must be skilled, aware and mature for the described tasks and must have the reliability to correctly interpret what is described in the manual. For safety reason only a qualified electrician, who has received training and / or has demonstrated skills and knowledge in construction and in operation of this unit, can install this inverter. Shenzhen SOFARSOLAR Co., Ltd does not take any responsibility for the property destruction and personal injury because of any incorrect use.
Assembly situation requirements
Please install and start inverter according to the following sections. Put the inverter in appropriate bearing capacity objects(such as wall and components and so on), to ensure that inverter vertical placed. Choose suitable place for installing electrical equipment. And assure enough fire exit space, convenience for maintenance. Maintain proper ventilation, and ensure that have the enough air cooling cycle.
Transport requirements
If you find packing problems that may cause the damage of the inverter, or find any visible damage, please immediately notice the responsible transportation company. You can ask solar equipment installation contractor or Shenzhen SOFARSOLAR Co.Ltd for help if necessary. Transport of the equipment, especially by road, must be carried out with by suitable ways and means for protecting the components (in particular, the electronic components) from violent shocks, humidity, vibration, etc.
Electric connection
Please comply with all the current electrical regulations about accident prevention in dealing with the current inverter.
Before the electrical connection, make sure to use opaque material to cover the PV modules or to disconnect PV array DC switch. Exposure to the sun, PV array will produce a dangerous voltage!
Danger
Warning
Attention
All installation accomplished only by professional electrical engineer!
Only get permission by the local power department and complete all electrical connection by professional electrical engineer then connect inverter into grid!
must be trained; Completely read the manual operation and understand relevant matters.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
1
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
2
User manual User manual
Basic safety informationBasic safety information
The equipment is composed of two cases. It’s forbidden to remove the tamper evident label, and open the upper case. Otherwise Sofarsolar will not provide service and maintenance.!
Note
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Danger
Attention
Touching the power grid or the terminal of equipment may lead to die of electric shock or fire!
Don’t touch the terminal or conductor which connect to the power circuit; Pay attention to anything about grid connection and security document.
Safety symbols
Signs on the inverter
There are some symbols which are related to security on the inverter. Please read and understand the content of the symbols, and then start the installation.
I
P65
Operation
Maintenance and repair
EMC / noise level of inverter
Danger
Attention
Disconnected with the PV components array and electricity grid before any repair work;
After turn off AC breaker and DC switch for 5 minutes later, the maintenance or repair of the inverter can be carried out!
Some internal components will be very hot when inverter is working. Please wear protective gloves!
Inverter should work again after removing any faults. If you need any repair work, please contact with the local authorized service center;
Can’t open the internal components of inverter without authorized. Shenzhen SOFARSOLAR Co., Ltd. does not take any responsibility for the losses from that.
Electromagnetic compatibility (EMC) refers to that one electrical equipment functions in a given electromagnetic environme nt without any trouble or error, and impose no unacceptable effect upon the environment. Therefore, EMC represents the quality characters of electrical equipment.
The inherent noise-immune character: immunity to internal electrical noise. External noise immunity: immunity to electromagnetic noise in external system. Noise emission level: influence of electromagnetic emission upon environment.
Danger
Electromagnetic radiation from inverter may be harmful to health!
Please do not continue to stay away from the inverter in less than 20 cm when inverter is working.
1.2 Symbols and signs
Danger
Electromagnetic radiation from inverter may be harmful to health!
Please do not continue to stay away from the inverter in less than 20 cm when inverter is working.
Caution
PV array should be connected to the ground in accordance with requirements of local power department!
Ensure input DC voltage < Max.DC voltage .Over voltage may cause permanent damage to inverter or other losses, which will not be included in warranty!
To protect system and the personnel security, we suggest that PV array of border and inverter should be reliable grounding .
Caution of burn injuries due to hot enclosure parts!
During working only can touch the display and key parts of inverter.
Attention
Warning
The re is resid ual volt age in the inv erter ! B efore op en the equi pment , ope rator s hould w ait for f ive min utes to e nsure t he capa citan ce disc harge com plete ly.
Be ca reful o f high vo ltage .
Be ca reful o f high te mpera ture.
Con formi ty with E urope an.
Poi nt of con necti on for gr oundi ng.
Thi s indic ates th e allow ed temp eratu re rang e.
Thi s i ndica tes the degr ee o f p rotec tion of the equ ipmen t ac cordi ng to IEC s tanda rd 70-1 ( EN 6052 9 June 19 97).
Pos itive p ole and n egati ve pole o f the inp ut volt age (DC ).
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
3
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
4
User manual User manual
Basic safety informationBasic safety information
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Transformer
L1
L2
L3
PE
IT
Product characteristics
2
2.1 Product identification
This equipment is a multi-string inverter designed to: transform a direct electric current (DC) coming from a photovoltaic generator (PV) into an alternating electric current (AC) Suitable for being fed into the national grid.
The inverter can be used only with photovoltaic modules that do not require one of the poles to be grounded.
The operating current during normal operation must not exceed the limits specified in the technical specifications.
Only the photovoltaic generator can be connected to the input of the inverter (do not connect batteries or other sources of power supply)
Sunny Horse Series inverters are compatible with TN-STN-CTN-C-STTIT grid configurationsFor the TT type of electricity gridthe voltage between neutral and earth should be less than 30V.
Comp on ent s of t he in ve rte r:
708.8mm
492.0mm
Intended grid types:
Outlines of this chapter
Product identification
It introduces the field of use, and how to indentify different types of Sunny Horse Series.
Function description
It introduces how the inverter works and the function modules inside.
Protection modules
It introduce the protection modules in the inverter.
Field of use
Figure2-1 PV Grid-tied System
Figure2-2 Overview of the grid configurations
Figure2-3 Two parts of the inverter
1 power converter part 2 wiring box
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
5
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
6
User manual User manual
Product characteristicsProduct characteristics
Sunny Horse Series
Transformer
L1
L2
L3 N PE
PE
Transformer
L1
L2
L3 PEN
PE
Transformer
L1
L2
L3 N PE
PE
Transformer
L1
L2
L3 N
PE
TN- S TN- C TN- C-S TT
1
2
Sunny Horse Series Sunny Horse Series Sunny Horse Series
Sunny Horse Series
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
The specific models of multi-string inverter that this manual is about are divided into four groups according to the maximum output power (10 kW,15kW ,17kW and 20 kW).
For inverters of equal output power, the variant between the various models is the layout of the wiring box 2. The wiring box2 has three configuration(sx = 2,4,5) .
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
7
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
8
User manual User manual
Product characteristicsProduct characteristics
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
S2
Figure2-6Wiring Box components (3)
1. DC input terminal 2. Communication card 3. AC output terminal 4. DC switch 5. DC positive poles connecters
6. DC Negative poles connecters 7. RS485 cable gland 8. AC cable gland 9. Earth terminal 10. Anti-condensation valve
11. WIFI cable gland
S5
Figure2-9 Wiring Box components (6)
1. DC SPD 2. Communication card 3. AC SPD 4. AC output terminal
5. DC switch 6. DC positive poles connecters 7. DC Negative poles connecters 8. RS485 cable gland.
9. AC cable gland 10. Earth terminal 11. Anti-condensation valve 12. WIFI cable gland
S4
Figure2-8 Wiring Box components (5)
1. DC SPD 2. Communication card 3. AC output terminal 4. DC switch
5. DC positive poles connecters 6. DC Negative poles connecters 7. RS485 cable gland
8. AC cable gland 9. Earth terminal 10. Anti-condensation valve 11. WIFI cable gland
5
7
7
8
10
9
11
44
1
2
3
6
5
8
8
9
11
10
12
1
2
4
3
7
6
3
2
1
5
44
7
7
8
10
9
11
44
6
The choice of model of inverter must be made by a qualified technician who knows about the installation conditions, the devices that will be installed outside the inverter and possible integration with an existing system.
Inverter type identification:
SOFAR - 20000 TL Sx
Wiring box configuration
Overall dimensions: L×W×H=708.8mm×492.0mm×245.7mm
Isolation: transformerless
Rated output power
Inverter name
Figure2-10 Front view and left view dimensions
1 Cabinet 2. Human Interface board.
245.7mm
708.8mm
492.0mm
1
2
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
9
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
10
User manual User manual
Product characteristicsProduct characteristics
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Identification labels of the equipment
The labels must NOT be hidden with objects and extraneous parts (rags, boxes, equipment, etc.); they must be cleaned regularly and kept visible at all times.
1. Heat sink 2. Bracket
Figure2-11 Back view and Bracket dimensions
336.0
135.0
135.0
14.0
80.0
135.0
135.0
10.0
Φ
10
492.0mm 44.2mm
1
2
2.2 Function description
DC power generated by PV array is filtered through Input Board before entering into Power Board. Input Board also offer functions such as insulation impedance detection and input DC voltage / current detection. DC power is converted to AC power by Power Board. AC power is filtered through Output Board then AC power is fed into the grid. Output Board also offer functions such as grid voltage / output current detection, GFCI and output isolation relay. Control Board provides the auxiliary power, controls the operation state of inverter and shows the operation status by Display Board. Display Board displays fault code when inverter is in abnormal operation conditions. At the same time, Control Board can trigger the relay so as to protect the internal components.
Operating Principle
Operating Principle
The DC switch disconnects internal circuits from the DC input to facilitate maintenance;
DC SPD (category III, category II is added to S4 & S5) provides the discharge loop for the overvoltage power on the DC side to protect the Sunny Horse Series internal circuits from DC overvoltage;
The input and output electromagnetic interference (EMI) filters filter out the EMI inside the Sunny Horse Series to ensure that the Sunny Horse Series meets electromagnetic compatibility requirements;
The Input Board detects the insulation impedance of the PV array and ensures the maximum output power of the PV system by measuring the voltages & currents of PV array and tracking the maximum power point (MPPT);
The DC-AC conversion circuit converts DC power into AC power and then the AC power is fed into the electric grid. The AC output power quality meets the requirements of the electric grid;
The output isolation relay isolates the inverter from the electric grid when the grid or the inverter is faulty.
The LC filter filters out the high-frequency components from the AC output of Sunny Horse Series to ensure that the AC output meets electric grid requirements;
AC SPD (category III, category II is added to S5) provides the discharge loop for the overvoltage power on the AC side to protect the Sunny Horse Series internal circuits from AC overvoltage;
The Communication Board enables the inverter to communicate via RS485, WIFI(optional), user can access all the operating data via the web browser(PC) and APP(ios & android).
SOFAR 2000 0TL-S x Serie s
Figure2-12 Electrical block diagram
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
11
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
12
User manual
Product characteristics
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
MASTER DSP SLAVE DSP
DC SPDII
EARTH
DC SPDII
EARTH
S4/S5
DC SPD
S2/S4/S5
DC SWITCH
OVP
DC SPDIII
OVP
DC SPDIII
MPPT1
DC/DC
INPUT EMI FILTER
MPPT
DC/DC
OUTPUT EMI FILTER
AC SPDIII
EARTH
AC SPDII
S5
AC SPD
L1
L2
L3
N
PE PE
L1
L2
L3
N
AC Output terminal station
PE
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N1
RLY
EARTH
INVERTER
DC/AC
IN
2
IN
1
+
-
+
-
+
-
+
+
-
-
+
-
+
-
PV CONNECTOR
DC Input terminal station
IN
1(+)IN1(-)IN1(-)IN2(+)
IN
1(+)IN1(-)IN1(-)IN2(+)
SD Card
RS
485
WIFI/GPRS
(OPT)
RS
485
MARK
MARK
MARK
Upper part of the case
Lower part of the case
OPTIONAL
Machine types S2S4/S5
REMOTE CONTROL
ALARM
+T/R
-T/R
GND
GND+RN.C
N.O
C
2-12 电路框图
IN1A(+)
IN1B(+)
IN1A(-)
IN1B(-)
IN2A(+)
IN2B(+)
IN2A(-)
IN2B(-)
IN1A(+)
IN1B(+)
IN1A(-)
IN1B(-)
IN2A(+)
IN2B(+)
IN2A(-)
IN2B(-)
A. Configurable relay
B.1 Remote switching on/off
Function module
The inverter has a configurable switching relay that can be used in various operating conditions set in the dedicated menu. A typical application example is the closing of the contact when an alarm occurs.
B. Energy management unit
2.3 Protection modules
This control can be used to switch the inverter on/off through an external (remote) control.
B.2 Feeding reactive power into the grid
The inverter is able to produce reactive power and can therefore feed it into the grid through the setting of the phase shift factor. Feed-in management can be controlled directly by the grid company through a dedicated RS485 serial interface.
B.3 Limiting the active power fed into the grid
The inverter, if enabled can limit the amount of active power fed into the grid by the inverter to the desired value (expressed as a percentage).
B.4 Self power reduction when grid over frequency
When the grid frequency is over limited value, inverter will reduce output power which do good to the grid stability.
B.5 Power reduction due to environmental conditions, input output voltage
The power reduction value and the inverter temperature at which it occurs depend on the ambient temperature and on many operating para-meters. Example: input voltage, grid voltage and power available from the photovoltaic field. The inverter can therefore reduce the power during certain periods of the day and according to the value of these parameters.
The inverter or a grid of inverters may be monitored remotely through an advanced communications system based on an RS485 serial interface, or remotely via the WIFI.
C. Data transmission
SD card is used for updating the firmware.
D. Software update
The inverter monitors the status of the surge arresters (both AC and DC) and generates a warning in the event of a fault (visible on the display).
E. Monitoring surge arresters (S4,S5 versions only)
A. Anti-islanding
In the event of a local grid outage by the electricity company, or when the equipment is switched off for maintenance operations, the inverter must be physically disconnected safely, to ensure protection of people working on the grid, all in accordance with the relevant national standards and laws. To prevent possible islanding, the inverter is equipped with an automatic protective disconnection system called “Anti-Islanding”.
B. RCMU
Sofar inverters are equipped with a redundancy on the reading of the ground leakage current sensitive to all components of both direct and alternating current. Measurement of the ground leakage current is carried out at the same time and independently by 2 different processors: it is sufficient for one of the two to detect an anomaly to trip the protection, with consequent separation from the grid and stopping of the conversion process.
Documen t Versi on 2.0(2016. 03.29) Documen t Versi on 2.0(2016. 03.29)
User manual
Product characteristics
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
13
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
14
User manual User manual
Product characteristicsProduct characteristics
C. Grid monitoring
Continuous monitoring of the grid voltage to ensure the voltage and frequency values stay within operating limits.
D. Inverter internal device protection
The inverter has all kinds of internal protection to protect the device inside when grid or input DC side have abnormal situation.
E. Ground fault protection
This inverter must be used with panels connected with “floating” connections, that is, with positive and negative terminals without ground connections. An advanced ground fault protection circuit continuously monitors the ground connection and disconnects the inverter when a ground fault is detected. The ground fault condition is indicated by a red LED on the front panel.
2.4 Efficiency and derating curve
Efficiency curve
Input voltage derating curve
Vpv=450V
Vpv=600V
Vpv=800V
5% 10% 20% 30% 40% 50% 60% 75% 80% 90% 100%
% of Rated Output Power
86
88
90
92
94
96
98
100
Efficiency[%]
250 350 440 500 600 700 850 900 950
0
3000
6000
9000
12000
15000
18000
21000
Output Power vs Input Voltage
Output Power(W)
Vin(V)
Output voltage derating curve
Output Power vs Grid Voltage
15000
16000
16500
17000
17500
18000
18500
20500
15500
19000
19500
20000
180 190 200 210 220 230 240
Vgrid(V)
250 270 280260
Output Power(W)
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Installation
3
3.1 Installation Process
Outlines of this chapter
This topic describes how to install the Sunny Horse Series.
Installation notes
Caution
Danger
Attention
Do not install the Sunny Horse Series on flammable building materials. Do not store the Sunny Horse Series in areas with flammable or explosive
materials.
Do not install the Sunny Horse Series in places prone to body contact because the Sunny Horse Series shelf and heat sinks become hot during the Sunny Horse Series operation.
Take the Sunny Horse Series weight into consideration when transporting and moving the Sunny Horse Series.
Install the Sunny Horse Series in an appropriate position and surface. Assign at least two persons to install the Sunny Horse Series.
This topic describes the process for installing the Sunny Horse Series.
3.2 Checking Before Installation
Before unpacking, check that the packing materials are intact. After unpacking, check that the deliverables are complete and intact.
3.3 Tools
Prepare tools required for installation and electrical connections.
3.4 Determining the Installation Position
Determine an appropriate position for installing the Sunny Horse Series.
3.5 Moving the Sunny SeriesHorse
This topic describes how to move the Sunny Horse Series to the installation position horizontally.
3.6 Installing the Sunny SeriesHorse
Before installing the Sunny Horse Series, secure the shipped rear panel to the wall. Then secure the Sunny Horse Series to the rear panel by using hexagon screws.
After unpacking the Sunny Horse Series, check whether deliverables are intact and complete. If any damage is found or any component is missed, contact the dealer.
3.1 Installation Process
Figure3-1 Installation flowchart
Start
Check before installation
Prepare installation tools
Determine the installation position
Moving the Sunny Horse Series
Installation the rear panel
Installation the Sunny Horse Series
End
3.2 Checking Before Installation
Checking Outer Packing Materials
Checking Deliverables
Packing materials and components may be damaged during transportation. Therefore, check the outer packing materials before installing the Sunny Horse Series. Checking the surface of packing materials for damage, such as holes and cracks. If any damage is found, do not unpack the Sunny Horse Series and contact the dealer as soon as possible. You are advised to remove the packing materials within 24 hours before installing the Sunny Horse Series.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
15
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
16
User manual User manual
Installation Installation
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
No.
1
Pictures
2
3
4
5
6
7
8
9
10
11
1PCS
1PCS
4PCS
Sunny Horse Series
Rear panel
DC+ input terminal
DC- input terminal
Metal terminals secured to DC+ input power cables
M6 Hexagon screws
M8*80 Expansion bolts used to secure the rear panel to the wall
Manual
The warranty card
Certificate
Table3-1 shows the components and mechanical parts that should be delivered
Quantity Description
4PCS
4PCS
4PCS
1PCS
6PCS
1PCS
1PCS
1PCS
Metal terminals secured to DC- input power cables
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
17
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
18
User manual User manual
Installation Installation
Prepare tools required for installation and electrical connections.
3.3 Tools
Table3-1 Shows the components and mechanical parts that should be delivered
Tool Function
Hammer drill
Adjustable wrench
Flat-head screwdriver
Socket wrench
Rubber mallet
Removal tool
Diagonal pliers
Wire stripper
With a drill bit of Φ8.0
Model
Used to drill holes on the wall
Used to tighten expansion bolts
Used to tighten or loosen screws when installing AC power cables.
Used to tighten ground bolts
Used to hammer expansion bolts into holes
Used to remove DC connectors from the Sunny Horse Series
Used to remove AC connectors from the Sunny Horse Series.
Note: The torque screwdriver and flat-head screwdriver are alternative.
Used to cut and tighten cable ties
Used to peel cable jackets
With an open end of larger than or greater than 32 mm
M4
M5
N/A
N/A
N/A
N/A
R 45 crimping tool
J
Used to prepare RJ45 connectors for Communications cables
N/A
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Measuring tape
Tool Model Function
0-180º
Cable cutter
Hexagon socket
Crimping tools
Vacuum cleaner
Multimeter
Marker
Level
ESD gloves
Safety goggles
Anti-dust respirator
Used to measure distances
Used to mark signs
Use d to ens ure that the rear pan el i s pro perly i nstal led
Operators wear ESD gloves when installing equipment.
Pun ch oper ator we aring
Pun ch oper ator we aring
Used to cut power cables
M6 use to uninstall and install the front top cover and down cover. M4 use to install the rear panel on the Sunny Horse Series.
Used to crimp power cables
Use d to cl ean up d usts aft er d rilli ng hol es
Used to check grounding
N/A
M4,M6
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
R 45
J
2PC S
80
cm
50 cm 50 cm
50
cm
OK OK NO OK
OK OK NO
NO
NO
Minimum installation distance for single Sunny Horse Series
Determine an appropriate position for installing the Sunny Horse Series. Comply with the following requirements when determining the installation position:
3.4 Determining the Installation Position
Figure 3-2 Installation position requirements
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
19
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
20
User manual User manual
Installation Installation
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
max 15º
OK NO
NO NO
Many Sunny Horse Series installation
300mm
100mm
1000mm
200mm
This topic describes how to move the Sunny Horse Series to the installation position horizontally
Step 1 Opening the packing, insert hands into the slots on both sides of the Sunny
Series and hold the handles, as shown in Figure 3-3 and Figure 3-4. Two persons are required to move the Sunny Horse Series.
Horse
Figure 3-3 Moving the Sunny Horse Series (1)
3.5 Moving the Sunny Horse Series
Procedure
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
21
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
22
User manual User manual
Installation Installation
Figure3-4 Moving the Sunny Horse Series (2)
Step 2 Lift the Sunny Horse Series from the packing case and move it to the installation
position.
End
Step 1 To determine the position for drilling holes, level hole positions, and then mark the
hole position by using a marker, use the hammer dril to dril hole on the wall. Keeping the hammer perpendicular to the wall, do not shake when drilling, so as not to damage the walls. If the aperture errors, need to reposition.
Attention
To prevent device damag and personal injury, keep balance when moving the Sunny Horse Series because the Sunny Horse Series is heavy.
Do not put the Sunny Horse Series with its wiring terminals contacting the floor because the power ports and signal ports are not designed to support the weight of the Sunny Horse Series. Place the Sunny Horse Series horizontally.
When placing the Sunny Horse Series on the floor, put foam or paper under the Sunny Horse Series to protect its shell.
3.6 Installing the Sunny Horse Series
Step 2 The expansion screw is vertically inserted into the hole, pay attention to expanding screw insertion depth (not too shallow).
Step 3 Putting the rear panel on the wall, the rear panel is fixed by the nuts.
Step 1 Step 2 Step 3
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
End
Step 4 Putting the Sunny Horse Series hook on the rear panel.
Step 5 Using an M6 screw back and inverter bottom fastening, to ensure safety.
Step 6 Putting the rear panel and inverter to lock together, In order to ensure the safety (the
user can select lock according to the actual situation).
Step 4 Step 5 Step 6
NOTE:
Before performing electrical connections, ensure that the DC switch is OFF.Since the stored electrical charge remains in a capacitor long after the DC switch is turned OFF. So it’s necessary to wait for at least 5 minutes for the capacitor to be electrically discharged.
This topic describes the Sunny Horse Series electrical connections. Read this part carefully before connecting cables.
4.1 Electrical connection
This topic describes the electrical connection process.
4.2 Connecting PGND Cables
Connect the Sunny Horse Series to the grounding electrode using protection ground (PGND) cables for grounding purposes.
4.3 Connecting AC Output Power Cables
Connect the Sunny Horse Series to the AC power distribution frame (PDF) or electrical grid using AC output power cables after obtaining approval from local electrical grid operator.
4.4 Connecting Communication Cables
This topic describes the functions of WIFI and RS485 ports and the method of connecting WIFI and RS485 communication cables.
4.6 Safety check
Before start the inverter, comply with the safety precautions and check ACDC connections.
4.5 Connecting DC Input Power Cables
Connect the Sunny Horse Series to PV arrays using DC input power cables.
4
Electrical Connections
Outlines of this chapter
PV modules generate electric energy before exposed to sunlight and can create an electrical shock hazard. Therefore, before connecting DC input power cable, cover PV modules using opaque cloth.
Sunny Horse Series has 2 MPP trackers, all PV modules connected to the same MPPT should have similar rated electrical characteristics (including Isc, Voc, Im, Vm, Pm and temperature coefficients), have the same number of series connected PV modules and be all in the same orientation (azimuth and tilt angle).
Installation and maintenance of inverter, must be operated by professional electrical engineer.
Attention
Danger
Note
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
23
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
24
User manual User manual
Installation
Electrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
1 2
3
4.1 Electrical connection
Start
4.2 Connecting PGND Cables
Connect the Sunny Horse Series to the grounding electrode using protection ground (PGND) cables for grounding purposes.
Note:
Good grounding for the Sunny Horse Series can help resist the impact of the surge voltage and improve the EMI performance. First connect the PGND cable before connecting the AC power cable, DC power cable, and communication cable.
For the system with one Sunny Horse Series, connect the PGND cable to the ground. For the system with multiple Sunny Horse Series, connect the PGND cables of all Sunny Horse Series to the grounding electrode using equipotential bonding.
If the installation location is near the ground, first connect the PGND cable to the ground before installing the Sunny Horse Series on the wall.
Figure4-1 Shows the flowchart for connecting cables to the Sunny Horse Series
Connect PGND Cables
Connect AC Output power Cables
End
Connect DC Input power Cables
Connect Communication Cables
The inverter is transformerless, Requires The positive pole and the negativepole of the PV array are not grounded, Otherwise it will cause inverter failure, In the PV power generation system, all non current carrying metal parts(such as: Bracket, Junction box shell, inverter shell) should be connected to earth.
Attention
Figure4-2 Ground terminal composition
1 M5 welded stud 2 OT Terminal 3 M5 Antiskid nut. . .
Sunny Horse Series Grounding Stud
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
25
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
26
User manual User manual
Electrical ConnectionsElectrical Connections
Prerequisites:
The PGND cables are prepared (8 AWG outdoor power cables are recommended for grounding purposes).
Procedure:
Step 1 Remove the insulation layer with an appropriate length using a wire stripper, as shown
in Figure 4-3.
L2=L1+(2 -3 )m m
L1
NoteL2 is 2 to 3mm longer than L1
Step 2 Insert the exposed core wires into the OT terminal and crimp them by using a crimping tool, as shown in Figure 4-4.
L3< 2mm
L4< 1.5mm
Note 1: L3 is the length between the insulation layer of the ground cable and the crimped part.L4 is the distance between the crimped part and core wires protruding from the crimped part. Note 2: The cavity formed after crimping the conductor crimp strip shall wrap the core wires completely. The core wires shall contact the terminal closely.
Step 3 Install the crimped OT terminal, flat washer, and spring washer on the M5 welded stud, and tighten the nut to a torque of 5 N.m using a socket wrench.
To enhance the anti-corrosion performance of the ground terminals, apply silica gel on them after connecting the ground cable.
End
Note:
Figure4-4 Preparing a ground cable (2)
Figure4-3 Preparing a ground cable (1)
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Context
All the AC output cables used for the inverters are outdoor five-core cables. To facilitate the installation, use flexible cables . Table 4-1 lists the recommended specifications for the cables and the breakers.
Type
Sofar 10000TL
-Sx Series
Sofar 15000TL
-Sx Series
Sofar 17000TL
-Sx Series
Sofar 20000TL
-Sx Series
4mm ²
4mm ²
6mm ²
6mm ²
20A 32A 40A 40A
4.3 Connecting AC Output Power Cables
Connect the Sunny Horse Series to the AC power distribution frame (PDF) or electrical grid using AC output power cables.
Sofar 10000TL
-Sx Series
Sofar 15000TL
-Sx Series
51
The cross-section of the AC line conductor must be sized in order to prevent unwanted disconnections of the inverter from the grid due to high impedance of the line that connects the inverter to the power supply point; In fact, if the impedance is too high, it causes an increase in the AC voltage that, on reaching the limit set by the country of installation, causes the inverter to switch off Table4-2.
Multi core copper wire mm²≥6
Multi core copper wire
Caution
It is not allowed for several inverters to use the same circuit breaker.
It is not allowed to connect loads between inverter and circuit breaker.
Table4-1
Cable(Copper)
Breaker
Note: For the sake of safety, please make sure to use correctly sized cables, otherwise the current makes the cable overheat or overload, even cause a fire.
Table4-2
The cable cross-sectional area(mm²)
The maximum length(m)
68
85
137
35
47
59
95
6
8
10
16
4
34 23
Sofar 17000TL
-Sx Series
Sofar 20000TL
-Sx Series
27
36
45
73
//
In Italy, any solar system bigger than 6kW should be connected to grid via a external SPI.
31
42
52
84
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
27
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
28
User manual User manual
Electrical ConnectionsElectrical Connections
55(
P
E
)
12
55(
PE
)
12
Procedure
Sunny Horse Series is a three-phase output inverter, strictly comply with local grid-connection requirements and safety standards.
Step 1 Open the cover.
Figure4-5 Open the cover schematic diagram
Step 2 Remove the insulation layer of an appropriate length according to figure 4-6, then insert the AC output cable though the PG waterproof cable gland.
Figure4-6 AC Output Cable schematic diagram
End
Step 3 Connecting the AC output power cable: The AC output cable(R,S,T,N and PE) is
connected to the terminal block, as shown in figure 4-7.
Figure4-7 Cable connection schematic diagram
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Connecting Communications Port
Sunny Horse Series shown in the following figure:
has two communication interface, RS485 interface, WIFI interface,as
1. RS485 interface 2. WIFI interface
By the RS485 communication line, connecting Sunny Horse Series to communication equipment (such as data acquisition, PC terminal).
You are recommended to use 24 AWG outdoor shielded network cables with the internal resistance less than or equal to 1.5 ohms/10 m and external diameter of 4.5 mm to 7.5 mm as RS485 communications cables.
A waterproof RJ45 connector has six parts: plug, screw nut, seals, housing, sealing plug and cable screw nut , as shown as follow.
1 2
3 4 5 6
When routing communications cables, ensure that communications cables are separated from power cables and away from interference sources to prevent communication interruptions.
Figure 4-8WIFI/RS485 location map
Connecting RS485 Communications Cables
Figure 4 9 Waterproof RJ45 connector composition-
1. Plug 2. Screw nut 3. Seals 4. Housing 5. Sealing Plug 6. Cable Screw nut
4.4 Connecting Communications Cables
1
2
Step 4 Crystal plug with RJ45 crimping tool. Step 5 Insert the plug into the RS485 port on the Sunny Horse Series. Step 6 Insert sealing plug into housing, and tighten the screw nut.
Step 1 Remove the insulation layer of an appropriate length from the shielded network cable
using a wire stripper. Step 2 Open Sunny Horse Series lower cover and insert the shielded network cable into the cable screw nut, seals, screw nut. Step 3 Connect the stripped network cable to corresponding pins on the plug, as shown as
follow.
1
8
1
8
TOP
FRONT
ColorNo.
White and orange
1
2
3
4
5
6
7
8
R S485 B
R S485 A
R S485 A
R S485 B
R S485 B
R S485 A
NC
NC
Procedure
Follow-up Procedure
To remove an RJ45 connector from Sunny Horse Series, remove the cable screw nut, press the clip on the RJ45 connector, and then pull out the shielded RJ45 connector.
End
Function
Orange
White and green
Blue
White and blue
Green
White and brown
Brown
Figure 4 10 RS485 Connecting Communications Cables(1)-
Figure 4 11 RS485 Connecting Communications Cables(2)-
Figure 4 12RS485 Connecting Communications Cables(3)-
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
31
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
32
User manual User manual
Electrical ConnectionsElectrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
By the WIFI communication line, connecting Sunny Horse Series to communication equipment (such as data acquisition, PC terminal).
Procedure Step 1 Buckle the antenna to the WIFI module.
Step 3 Screw out the sealing nut corresponding, to let the antenna expose a portion, and
tighten the screw nut.
Connecting WIFI Communications Cables
Figure 4 13 WIFI Connecting Communications Cables(1)-
Step 2 Open Sunny Horse Series lower cover and insert the WIFI module to the location as show as follow.
Figure 4 14WIFI Connecting Communications Cables(2)-
Figure 4 15 WIFI Connecting Communications Cables(3)-
Communications Port Description
Note: Pull the WIFI antenna out a little bit to enhance the signal.
WIFI
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
33
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
34
User manual User manual
Electrical ConnectionsElectrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Set the match resistor by the SWT2, the corresponding list as follows (0 OFF, 1 ON).
0
1
Reserve
SWT2_1 SWT2_2
State
Reserve
No connect
Connect
S
This topic describes the functions of the RS485 and WIFI ports.
R 485
By RS485 interface, transfer the inverter power output information, alarm information, operation state to the PC terminal or local data acquisition device , then uploaded to the server (such as S-WE01S).
USB
RS-485
1. USB-RS485 2. S-WE01S
If only one Sunny Horse Series is used, use a communication cable with waterproof RJ45 connectors, and choose either of the two RS485 ports and need to set the RS485 address according to chapter 6.3 “Set address” part and SWT2(Match Resistance as shown in Figure
Figure 4 16 A single Sunny Horse Series connecting Communications-
RS485/422
电适配器接口
RS485/422
USB/485 接口
Figure 4 17Multi Sunny Horse Series connecting Communications-
WIF I
By the WIFI interface, transfer the inverter power output information, alarm information, operation state to the PC terminal or local data acquisition device , then uploaded to the server (such as S-WE01S).
According to the manufacturers to provide SN number can register remote monitoring of Sunny Horse Series through http://www.solarmanpv.com/portal/LoginPage.aspx.
Figure 4 18 Connect multiple Wifi to wireless router-
If multiple Sunny Horse Series are used, connect all Sunny Horse Series in daisy chain mode over the RS485 communication cable. First,set the RS485 address according to chapter 6.3 “Set address” part and SWT2(Match Resistance).
According to the manufacturers to provide SN number can register remote monitoring of Sunny Horse Series through http://www.solarmanpv.com/portal/LoginPage.aspx.
RS485/422
RS485/422
USB/485 Interface
Ada pter In terfa ce
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
35
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
36
User manual User manual
Electrical ConnectionsElectrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
The length of the RS485 communication cable should be less than 1000 m. The length of the Wifi communication cable should be less than 100 m. If multiple Sunny Horse Series are connected to the monitoring device over an RS485/RS232 converter, a
maximum of 31 inverter can be connected in a daisy chain. If multiple Sunny Horse Series are connected to a S-WE01S, a maximum of 31 Sunny Horse Series can be
connected in three daisy chains.
The Sunny Horse Series has a multifunctional relay , its output can be configured. The connecting terminal in a communication board, as shown in Figure4-8. Connecting CNT10 view as shown as follow.
It can be connected to the normally open mode (i.e. connecting NO contact and COM contact),can also be configured as a normally closed mode (i.e. connecting NC contact and COM contact).
The Relay has 4 different control function, the details please see the LCD display interface settings on the set relay function description.
CNT10
NC COM
NO
Nonormally open contact COMcommon contact Ncnormally closed contact
Note
Connecting Relay Cables
Step 1 To prepare the appropriate cable. The front of a wire stripping to will be in accordance with the following picture size, and then through the PG waterproof joint.
2
0
(
P
E
)
8
2
0
8
Step 2 Insert sealing plug into housing, and tighten the screw nut.
Procedure
Figure 4 19 Relay Connection (1)-
Figure Wire strip Figure Through wire
End
4.5 Connecting DC Input Power Cables
Connect the Sunny Horse Series to PV arrays over DC input power cables.
Input mode selectionSunny Horse Series has 2 MPPT, The two MPPT can run independently, but also can be operated in parallel, According to the system design, the user can choose the mode of MPPT operation.
Figure 4 20 Relay Connection (2)-
Step 3 The cable stripped to the corresponding stem node hole.
Figure 4 21 Connection (3)- Relay
CNT10
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
37
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
38
User manual User manual
Electrical ConnectionsElectrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Type
MPPT voltage range
1000 Vdc
Sofar10000TL-Sx Sofar15000TL-Sx Sofar17000TL-Sx Sofar20000TL-Sx
350~850 Vdc 370~850 Vdc 420~850 Vdc 430~850 Vdc
DC inductance should choose PV cable, from the junction box to the inverter, line voltage drop is about 1~2%, The inverter is installed in the PV bracket, which saves the cable and reduce the DC loss.
According to the inverter type, choose the inverter accessories (cables, fuse holder, fuse, breaker etc.), Sofar inverter with PV array should be excellent performance, reliable quality. The open circuit voltage of PV must be less than Maximum DC input voltage of Sofar inverter, The output voltage of the solar array must be consistent with the MPPT voltage range.
Note
Table4-5 MPPT voltage range
Max. input voltage
Note
Che ck pola rity of P V array, to e nsure t he corre ct wiri ng of PV ar ray;
Ple ase don' t put the po sitiv e or nega tive of th e PV array c onnec t t o ear th.
If the two MPPT panels is independent, the input mode should be set as "independent mode". The setting method is introduced at chapter 6.3.
Independent mode (default):
If the two MPPT panels is paralleled together by combiner, the input mode should be set as "parallel mode".
The setting method is introduced at chapter 6.3.
Parallel mode :
Note
Caution
Danger
PV m odule s gen erate elec tric energ y whe n exp osed t o sun light and can crea te an el ectri cal sh ock ha zard. T heref ore, wh en conn ectin g DC in put pow er cable , cover P V modul es by usi ng opaq ue clot h.
Bef ore perf ormin g elect rical conne ction s, ensu re that v oltag es of the D C cab les s hould be w ithin the safe volta ge ra nge, that is, l ower than 60 V DC, a nd the DC S WITCH i s OFF. Othe rwise , the hig h volta ge may re sult in fa tal dan ger.
PV mod ules co nnect ed in ser ies in ea ch PV arra y are of th e same sp ecifi catio ns.
The op en-ci rcuit v oltag e of each P V array i s alway s lower t han or eq ual to 96 0 V DC.
The sh ort-c ircui t curre nt of eac h PV inpu t is alwa ys lowe r than or e qual to 1 2 A DC .
The o utput power of eac h PV arr ay is a lways less t han or e qual t o the m aximu m inpu t powe r of the Su nny Hor se Seri es.
The p ositi ve and negati ve ter minal s of PV a rrays conne ct to th e posi tive a nd neg ative DC inp ut term inals r espec tivel y.
Ensure that the following conditions are met. Otherwise, fire accident may occur.
If the Sun ny H orse Ser ies conne cts to the powe r gr id d irect ly, e nsure tha t the PV arr ays are n ot grou nded.
If th e DC volt age is a n on-ze ro valu e betwe en the p ositi ve term inal of P V arr ays and the ground , th e PV arr ays are subje ct t o in sulat ion fault s. Rec tify th e fault b efore co nnect ing cab les.
Dur ing PV a rray and Sun ny Horse Ser ies inst allat ion, the pos itive or neg ative ter minal s of PV arra ys m ay b e gr ounde d if pow er c ables are not prop erly insta lled or r outed . In this cas e, an DC short cir cuit may occ ur and dam age the S unny Ho rse Ser ies.
If the PV arra ys n eed to be ground ed, inst all a t hree-p hase fou r-wire iso latio n tra nsfor mer o n the out put s ide a nd d isabl e the ISO dete ction fun ction by re ferri ng t o 6.2 .10 S ettin g Iso latio n Par amete rs. I f an iso latio n tr ansfo rmer is not inst alled , t he S unny Hor se S eries ma y be dam aged.
Context
Cross-Sectional Area (mm)
4.0~6.0
Recommended ValueRange
4.0
External Cable Diameter(mm)
4.5~7.8
DC input connectors are classified into positive and negative connectors, as shown in Figure 4-24 and Figure 4-25.
1. Housing 2. Cable gland 3. Positive connector
1. Housing 2. Cable gland 3. Negative connector
Table 4-6 Recommended DC input cable specifications
Figure 4-23 Positive connector composition
Figure 4-24 Negative connector composition
Positive and negative metal terminals are packed with positive and negative connectors respectively. Separate the positive from negative metal terminals after unpacking the Sunny Horse Series to avoid confusing the polarities.
Note
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
39
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
40
User manual User manual
Electrical ConnectionsElectrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Procedure
Step 1 Remove cable glands from the positive and negative connectors.
Figure 4-25 Connecting DC input power cables
1. Positive power cable 2. Negative power cable
L2 is 2 to 3 mm longer than L1.
Note
Step 2 Remove the insulation layer with an appropriate length from the positive and negative
power cables by using a wire stripper as show in Figure 4-26.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
41
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
42
User manual User manual
Electrical ConnectionsElectrical Connections
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Step 3 Insert the positive and negative power cables into corresponding cable glands.
Step 5 Insert crimped power cables into corresponding housings until you hear a "click" sound.
The power cables snap into place.
End
Figure 4-26 Connecting DC input power cables
Step 4 Insert the stripped positive and negative power cables into the positive and negative metal terminals respectively and crimp them using a clamping tool. Ensure that the cables arecrimped until they cannot be pulled out by force less than 400 N, as shown in Figure 4-27.
1. Positive power cable 2. Negative power cable
Step 6 Reinstall cable glands on positive and negative connectors and rotate them against the insulation covers.
Step 7 Insert the positive and negative connectors into corresponding DC input terminals of the Sunny Horse Series until you hear a "click" sound, as shown in Figure 4-28.
Figure 4-27 Connecting DC input power cables
1. Bayonet
Follow-up Procedure
To remove the positive and negative connectors from the Sunny Horse Series, insert a removal wrench into the bayonet and press the wrench with an appropriate strength, as shown in Figure 4-29.
4.6 Safety check
Before the inverter operation, need to be examined for the photovoltaic array, Check Open circuit voltage of the each PV array whether accord with the requirements.
Photovoltaic array
Ensure Open circuit voltage of the each PV array accord with the requirements; Ensure that the positive and negative polarity is correct.
Sunny Ho rse Seri es
DC conne ct
Use the multimeter to check the DC side voltage and current;
Check the DC cableNote the positive and negative poles cannot be reversed, Consistent with the positive and negative pole of photovoltaic array, measured each input Open circuit voltage
Compare the voltage, if the difference is greater than 3%, PV array line may be a fault
Sunny Ho rse Seri es
AC conne ct
Ensure the AC breaker of the inverter is off
Check the inverter phase with grid is connected properly, Check the voltage of each phase is within a predetermined range, if possible, Measure the THD, If the distortion is serious, the inverter may not work.
Figure 4-28 Removing a DC input connector
Caution
Before removing the positive and negative connectors, ensure that the DC SWITCH is OFF.
Installing cover and Locking screw.
Figure4-29 NOT allowed: connect loads between inverter and circuit breaker
Breaker
Inverter
Load
Commissioning of inverter
5
5.2 Start inverter
Step 1 Turn on DC switch.
5.1 Safety inspection before commissioning
Attention
Ensure that DC and AC voltages are within the range permitted by the inverter.
Step 2 Turn on AC switch.
When the solar arrays generate adequate power, the inverter will startup automatically. Display showing “normal” indicates correct operation.
If the inverter indicates any other fault, please refer to part 7——error messages for help.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
43
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
44
User manual User manual
Electrical Connections
Commissioning of inverter
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
ON: GFCI fault OFF: GFCI normal
Operation interface
6
·Back : to back up or enter into main interface at standard interface states
·Up : to move up or increase value
·Down : to move down or decrease value
·Enter : to confirm selection
·States Light(GREEN)
Flashing: Waiting or checking state ON: Normal operation OFF: Fault or permanent state
GFCI Warning
OK
Down
Buttons and Indicator lights
Outlines of this chapter
Introduce the dispalyoperationbuttons and LED light of Sofar 30~40KTL.
6.1 Operation and Display Panel
Inverter States Light
Warning Light
Up
Back
Key-button:
Indicator Lights:
·Warning Light (RED)
Flashing: Fans fault ON: The inverter is faulty OFF: Normal operation
·GFCI Warning Light (RED)
Con necti on to the AC gri d:
Che ck whet her the c ircui t bre aker con necte d to th e AC grid i s in the OF F state, che ck whet her the t ype of th e AC grid i s correc t (TN-C , TN-S OR T T). And c heck th e wirin g conne ction s of PE, N, L 1®, L2( S), L3( T) are cor rect.
Con necti on of DC in put:
Che ck whet her the D C switch of th e inverter i s in the OF F state, the D C volta ge of e ach PV st rin g conne cted to the sa me MPPT s hall be t he same . The m aximu m DC volta ge (cor rected a ccord ing to th e lowest o perating t empera ture) sha ll be les s than 96 0V.
Ple ase che ck the po larit y of each P V strin g. If o ne the PV s tring s is conn ect ed inc orrec tly, thi s can dam age SOFAR s olar in verter.Ple ase make s ure tha t all P V strin gs are firml y con necte d to th e DC inpu ts of sol ar inver ter.
Ple ase test the l eakage cur rent of e ach P V strin g to groun d using a m egger. The i nsula tion re sis tance o f eac h PV stri ng to grou nd shal l be high er than 3 00kΩ , or th is can da mage SO FAR so lar inve rter
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
45
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
46
User manual User manual
Operation interface Operation interfaceSunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
6.2 Standard Interface
LCD standard interface is used to display inverter statesinformation and parameter setting etc.
LCD displays the updates of inverter energy powerinput informationwarning information etc
A1 - Indicates modbus communication address. A2 - RS485 communicating
A3 - Light ON for RS485 communicating
A4 - WIFI communicating
A5 - Light flashes to warn over frequency and power derating. Light ON to warn remote
A6 - Indicates today’s energy A7 - Indicates the total energy
A10 - M PPT SCA N funct ion is ac tivate d (not ava ilabl e)
A9 - In dicate s real ti me outp ut powe r A8 - Li ght ON war ning fo r invert er high t empera ture
A11 - Light ON when input voltage over 350V
A12 - Indicates real time input voltage and current channel A13 - Indicates the input voltage and current of phase 1&2 and displays in turns in
every three seconds A14 - Light ON when the state is normal
in every three seconds A15 - Indicates R/T/S phase voltage and displays in turns in every three seconds
A16 - Indicates R/T/S phase current or frequency and displays in turns
When power-on, LCD interface displays INITIALIZING, refer below picture.
when control board successfully connected with communication board, the LCD display the
current state of the inverterdisplay as shown in the figure below.
Initializing…
Wait 1 0s
Waiting StatesCountdown 10S
Check
Checking
Normal
Fault
Permanent
Normal Power Generation
Regular error state
Unrecoverable error state
A17 Indicates the energy from 3:00am-21:00pm in the day-
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
47
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
48
User manual User manual
Operation interface Operation interfaceSunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
DSP communicate fail
Inverter states includes: waitchecknormal、fault and permanent
WaitInverter is waiting to Check State at the end of reconnection time. In this state, the
PV voltage is more than 250V, grid voltage value is between the max and min limits and so on; If not, Inverter will go to Fault State or Permanent State.
Check: Inverter is checking isolation resistor, relays, and other safety requirements. It also does self-test to ensure inverter software and hardware are functional. Inverter will go to Fault State or Permanent State if any error or fault occurs.
NormalInverter enter to Normal Stateit is feeding power to the grid; inverter will go to Fault State or Permanent state if any error or fault occurs.
FaultFault State: Inverter has encountered recoverable error. It should recover if the errors disappear. If Fault State continues; please check the inverter according error code.
PermanentInverter has encountered unrecoverable error, we need maintainer debug this kind of error according to error code.
When the control board and communication board connection fails, the LCD display interface as shown in the figure below.
6.3 Main Interface
Press “Back” button under standard interface to enter into main interface, including:
Normal
1. Enter Setting
2. EventList
3. SystemInfo
4. System Time
5. Software Update
Key Back”
(A) “Enter Setting” Interface as below:
1. Set Time
Users press “Back” button to enter “1.Enter Setting” interface, Press “OK button to enter main setting interface. Enter “1. Set Time” by pressing“Up” button or “Down” button, then press”OK“button and start to set up time.
Time set from year, month, day, minutes, and seconds in turns, “Up” button or “Down”button to choose different value to set each date. Set each value is need to press “OK” button to confirm setting. “success” is displayed if the setting time is correct, “fail” means failure settings.
1.Enter Setting
1. Set time
2. Clear Produce
3. Clear Events
4. Set Country Code
5. Remote Control
6. Relay Command
7. Enable Set Country
9. Set Mod-bus Address
8. Set Total Energy
10. Set Inputmode
11. Set Language
12. Set StartPara
13. Set SafetyVolt
14. Set SafetyFreq
15. Set Insulation
16. Relay Test
17. Set Reactive
18. Set PowerDerat
19. Setti ng P(f)
20. Setti ng Q(v)
21. Contr ol 81.S 1
2. Clear Produce
3. Clear Events
Users press “Back” button to enter “1.Enter Setting” interface, Press OK button to enter main setting interface. Then Enter “2.Clear Produce” by pressing “Up” button or “Down” button, press “OK” button and start to clear produce. “success” is displayed after settings.
“ ”
Users press “Back” button to enter “1.Enter Setting ” interface, Press OK button to enter main setting interface.Enter “3. Clear Events” by pressing ”Up” button or “Down” button. Press “OK ”button and start to clear events. “success” is displayed after settings.
“ ”
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
49
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
50
User manual User manual
Operation interface Operation interfaceSunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
4. Set Country Code
Users press “Back” button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “4.Set Country Code” by pressing “Up” button Or “Down” button, press “OK” button and enter “Input Password” Setting interface. If it's shown "set disable" on the screen, then you can NOT choose the operating country, you should enable country setting through "7. Enable Set Country" interface. If it's shown "set Country code?" on the screen, then press Confirm button to start country setting. "Success" will be shown on the screen after a successful country setting.
Table 6-1 country code setting
Germany VDE
AR-N4105
Denmark
Italy CEI0-21
Australia
Spain RD1699
Turkey
Greece Continent
00
01
02
03
04
05
06
Netherland
07
Belgium
UK-G59
08
09
China
France
Poland
Germany BDEW
10
11
12
13
Germany VDE
0126
14
Italy CEI0-16
15
UK-G83
Greece island
EU EN50438
IEC EN61727
16
17
18
19
Korea
20
21
Sweden
Europe General
Customer VDE
0126
22
23
Cod e
Cou ntry
Cod e
Cou ntry
Cod e
Cou ntry
5.Remote Control
6.Relay Command
Users press “Back” button to enter “1.Enter Setting” interface, Press OK button to enter main setting interface.Enter “5. Remote Control” by pressing “Up” button or “Down” button. Press “OK” button and enter Remote Control Switch On &Off interface. Choose “1.Enable”or “2.Disable” by pressing “Up” button or “Down” button, press “OK” button, then communication board start to transmit control signals to control board. “success” is displayed after setting success ; otherwise it will show “fail”.
“ ”
Users press “Back” button to enter “1.Enter Setting” interface, Press ”OK“ button to enter main setting interface.
Enter “6. Relay Command” by pressing “Up” button or ”Down“button, press “OK ” button and enter “Relay Command setting “interface. Choose corresponded setting items by pressing “Up” button or “Down” button, then press “OK” button. “success” or “fail” is displayed after setting.
6.Relay Command
1. Production
2. Alarm
3. Config Alarm
4. Relay Disable
Relay Command Definition:
the relay switches whenever a connection to (and therefore a disconnection from) the grid occurs.
If the relay contractor is in normally open (close) mode, the contact will stay open (or closed) until the inverter is connected to the grid; once the inverter con-nects to the grid and starts to export power, the relay switches state and therefore closes (or opens).
When the inverter disconnects from the grid, the relay contact returns to its position of rest, namely open (or closed).
Production
Alarm
Config Alarm
The relay switches whenever there is an alarm on the inverter (Error). No switching occurs when there is a Warning.
If the relay contractor is in normally open(close)mode, the contact will stay open (or closed) until the inverter reports an error; once the inverter reports an error, the relay switches state and therefore closes (or opens).The contact remains switched from its rest condition until normal opera-tion is restored.
the relay switches whenever there is an alarm (Error) or a Warning, which have been previously selected by the user through the PC. the contact will stay open (or closed) until the inverter reports an error or a warning out of those selected from the menu; once the inverter displays an error or a warning out of those selected, the relay switches state and therefore closes (or opens) the contact. The relay remains switched from its rest condition until the alarm or warning has disappeared.
Relay Disable
Control function is forbidden
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
52
User manual User manual
Operation interface Operation interfaceSunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
7. Enable Set Country
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “7.Enable Set Country” by pressing “Up” button Or “Down” button, press “OK” button and enter “Input Password” Setting interface. Press “Back” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error!” Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “Success” will be displayed if setting successfully.
8. Set Total Energy
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “8. Set Total Energy” by pressing “Up” button or “Down” button , then press “OK” button and enter “Input Password” Setting interface. Press “OK” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to confirm the value and to next value setting. “Error! Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords then set total energy. “Success” or “fail” is displayed after setting.
9. Set mod-bus address
Users press “Back” button to enter “1.Enter setting” interface, Press ”OK“ button to enter main setting interface. Enter “9. Set mod-bus address” by pressing “Up” button or ”Down“ button. Press “OK” button and enter setting interface. Choose corresponded setting items by pressing “Up” button or “Down” button, then press “OK” button. “Success” or “fail” is displayed after setting.
10. Set input mode
Input mode selection: Sunny Horse Series inverter has 2 MPPT channels, the 2 MPPT can operate independently, also can operate in parallel. If the PV strings are connected in parallel outside the inverter, you should choose the "in parallel mode", otherwise use the default setting. Press “Back” button to enter “1.Enter setting” interface, press ”OK“ button to enter main setting interface. Enter “10. Set inputmode” by pressing “Up” or ”Down“ buttons. Press “OK” button to enter setting interface. Choose “In parallel Mode?” or “Independent Mode?” by pressing “Up” or “Down” buttons, then press “OK” button. “Success” or “fail” is displayed after setting.
11. Set Language
Users press “Back” button to enter “1.Enter setting” interface, Press ”OK“ button to enter main setting interface. Enter “11. Set Language” by pressing “Up” button or ”Down“ button. Press “OK” button and enter setting interface. Choose corresponded setting items by pressing “Up” button or “Down” button, then press “OK” button. “Success” or “fail” is displayed after setting.
12. Set StartPara
User can change the start parameter by the LCD. First the User need to copy the. TXT file which is used to change the start parameter to the SD card .
Attention: when inverter working for power generation over 24h, country setting is forbidden, it can only be set after LCD setting. Key in passwords for country setting through LCD (default:
0001), country setting can be set in 24h after keying in the correct passwords, over 24h, set through LCD again.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
51
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “12. Set StartPara” by pressing “Up” button Or “Down” button, press “OK” button and enter “Input Password” Setting interface. Press “Back” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error!” Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “Success” will be displayed if setting successfully.
13. Set SafetyVolt
14. Set SafetyFreq
User can change the Voltage protection point by the LCD. First the User need to copy the. TXT file which is used to change the Voltage protection point to the SD card .
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “13. Set SafetyVolt” by pressing “Up” button Or “Down” button, press “OK” button and enter “Input Password” Setting interface. Press “Back” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error!” Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “Success” will be displayed if setting successfully.
User can change the Frequency protection point by the LCD. First the User need to copy the. TXT file which is used to change the Frequency protection point to the SD card .
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “14. Set SafetyFreq” by pressing “Up” button Or “Down” button, press “OK” button and enter “Input Password” Setting interface. Press “Back” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error!” Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “Success” will be displayed if setting successfully.
15.Set Insulation
User can change the Insulation protection point by the LCD. First the User need to copy the. TXT file which is used to change the Insulation protection point to the SD card .
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “15. Set Insulation” by pressing “Up” button Or “Down” button, press “OK” button and enter “Input Password” Setting interface. Press “Back” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error!” Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “Success” will be displayed if setting successfully.
Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main setting interface. Enter “16. Relay Test” by pressing “Up” button Or “Down” button, then press “OK” button and start test relay. “Success” will be displayed if setting successfully.
16. Relay Test
20. Setting Q(v)
Users press Back button to enter “1.Enter setting ” interface, Press OK button to enter main setting interface. Enter “20. Setting Q(v) by pressing “Up” button Or “Down” button, then press “OK” button . Then press Confirm button to start to set Q(v)."Success" will be shown on the screen after a successful Q(v) setting.
Users press Back button to enter “1.Enter setting ” interface, Press OK button to enter main setting interface. Enter “21.Control 81.S1 by pressing “Up” button Or “Down” button, then press “OK” button. Then press Confirm button to start Control 81.S1.
21. Control 81.S1
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
53
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
54
User manual User manual
Operation interface Operation interfaceSunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
(C) “SystemInfo” Interface as below:
Users press Back button to enter “1.Enter Setting” interface, Press OK button to enter main setting interface.Enter “17.Set Reactive” by pressing “Up” button or“Down”button, press “OK” button and enter “Input Password” Setting interface.
Press “Back” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error! Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “success” will be displayed if setting successfully,
“ ”
17. Set Reactive
Users press Back button to enter “1.Enter Setting” interface, Press OK button to enter main setting interface.Enter “18.Set PowerDerat” by pressing “Up” button or“Down”button, press “OK” button and enter “Input Password” Setting interface.
Press “OK” button to set passwords (default: 0001), increase or decrease value though pressing “Up” button or “Down” button, press “OK” button to next value setting. “Error! Try again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct passwords. “success” will be displayed if setting successfully,
“ ”
18. Set PowerDerat
19. Setting P(f)
Users press Back button to enter “1.Enter setting ” interface, Press OK button to enter main setting interface. Enter “19. Setting P(f)” by pressing “Up” button Or “Down” button, then press “OK” button and enter “Setting P(f)”interface. Then press Confirm button to start to Set P(f). "Success" will be shown on the screen after a successful P(f) setting.
(B) “Event List” Interface as below:
Event List is used to display the real-time event records, including the total number of events and each specific ID No. and happening time. User can enter Event List interface through main interface to check details of real-time event records, Event will be listed by the happening time, and recent events will be listed in the front. Please refer to below picture:
Users press “Back” button and “Down” button in standard interface, then enter into 2.Event List” interface.
Press “OK” button to get the total event numbers, show as below:
Press ”OK“ button again; user can check each event ID number and happening time, see below:
Events TotalNum:02
2.EventList
Events AllNum:02
91
ID
EventID NO.
Key ”“OK
Key ”“OK
2013-10-31 16:42
Happening time
Key ”“OK
3.SystemInfo
1.Inverter Type
2.Serial Number
3.SoftVersion
4.HardVersion
5.Country
6.Input Mode
7.Relay Command
8.Power Factor
9.P (f)
10. Q(v)
Relay Command
then press Up button or Down button enter into “6. Input Mode”,then press OK button the Input Mode will be displayed.
“ ” “ ”
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “7. Relay Command”,then press “OK” button the Relay Command will be displayed.
“ ”
Power Factor
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “8. Power Factor”,then press “OK” button the Power Factor will be displayed.
“ ”
User manual User manual
Operation interface Operation interfaceSunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
55
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
56
Inverter Type
Serial Number
SoftVersion
HardVersion
Users press Back button and Up button or Down button enter “3. SystemInfo” interface, Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “1. Inverter Type”,then press “OK” button the Inverter Type will be displayed.
“ ”
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, Press ”OK“ button to enter enter into system information checking interface,then press“Up” button or “Down” button enter into “2. Serial Number”,then press “OK” button ,the serial number will be displayed.
“ ”
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “3. SoftVersion”,then press “OK” button the SoftVersion will be displayed.
“ ”
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “4. HardVersion”,then press “OK” button the HardVersion will be displayed.
“ ”
Country
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “5. Country”,then press “OK” button the Country will be displayed.
“ ”
Input Mode
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,
“ ”
P(f)
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “9.P(f)”,then press “OK” button the P(f ) will be displayed.
“ ”
Q(v)
Users press Back button and Up button or Down button to enter “3. SystemInfo” interface, then Press “OK” button to enter enter into system information checking interface,then press “Up” button or “Down” button enter into “10.Q(v)”,then press “OK” button the Q(v) will be displayed.
“ ”
(D) System Time
Press the “Back” button and “Up” button or “Down” key in the standard user interface to enter into “4.System Time”,then press “OK ” button to display the current system time.
(E) Software Update
Press the “Back” button and “Up” button or “Down” button in the standard user interface to enter into “5. Software Update”,then press “OK” button to enter into the”input password” interface,now press the “OK” button to input the password(initial passwords is 0001),Press the“Up” and “Down” button to change the value,then press “OK” button to confirm the current value of input and enter the next set of value .when set overif the password is wrongthe LCD will display “Error! Try again”,at this time ,you should re-enter your password.If the password is correctthen begin the update process.
online update program steps are as follows:
Step 1 First, open sofar 10~20KTL lower cover.
Step 2 After open the lower cover, Press SD card , Then the SD card will automatically pop up.
Step 3 The SD card reader must be ready by the users, so that SD card so easy to establish the
connection with the computer.
Step 4 SOFAR SOLAR will send the Software code to the user who needs to update. After user receive the file, please decompressing file and cover the original file in SD card.
Step 5 Insert the SD card into the SD card slot, there will be a faint clicking sound typically, indicating that has stuck.
Step 6 then enter into the online upgrade to the main menu “5. Software Update” in the LCD display program. The method to enter the menu can refer to operation interface of LCD.
Step 7 Input the password, if password is correct, and then begin the update process, the original password is 0001.
Step 8 System update main DSPslave DSP FUSE and ARM in turns. If main DSP update success ,the LCD will display “Update DSP1 OK”, otherwise display “Update DSP1 Fail”; If slave DSP update success ,the LCD will display “Update DSP2 OK”, otherwise display “Update DSP2 Fail”; If FUSE update success ,the LCD will display “Update FUSE OK”, otherwise display “Update FUSE Fail”
Step 9 If Fail , please turn off the DC breaker, wait for the LCD screen extinguish, then turn on the DC breaker again,then Continue to update from step 6.
Step 10 After the update is completed, turn off the DC breaker, wait for the LCD screen extinguish, then install the lower coverand turn on the DC breaker and AC breaker again, the inverter will enters the running state.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
57
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
58
User manual User manual
Trouble shooting and maintenance Trouble shooting and maintenance
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
7.1 Trouble shooting
This section contains information and procedures for solving possible problems with the Sunny Horse Series inverter.
In case of problem with inverter, check the following tips.
Check the warning fault messages or Fault codes on the inverter information panel. Record it before doing anything further.
EventList information
solution
EventList Name
EventList NO.
GridOVP
ID01
GridUVP
ID02
GridOFP
ID03
GridUFP
ID04
Trouble shooting and maintenance
7
Outlines of this chapter
This topic describes how to perform daily maintenance and troubleshooting to ensure long­term proper operation of the Sunny Horse Series inverter.
If inverter does not display any Fault, please check the following lists.
- Is the inverter located in a clean, dry, adequately ventilated place?
- Is the DC switch turned ON?
- Are the cables adequately sized and short enough?
- Are the input and output connections and wiring in good condition?
- Are the configuration settings correct for the particular installation?
- Are the display panel and the communications cable properly connected and undamaged?
Follow the steps below to view recorded problems:
Press “ESC ” to enter the main menu in the normal interface. In the interface screen select “Event List”, then press “OK” to enter events.
Table 7-1 Eventlist
If the alarm occurs occasionally, the possible cause is that the electric grid is abnormal occasionally. SOFAR inverter automatically returns to normal operating status when the electric grid’s back to normal. If the alarm occurs frequently, check whether the grid voltage/frequency is within the acceptable range. If no, contact SOFAR technical support. If yes, check the AC circuit breaker and AC wiring of the SOFAR inverter. If the grid voltage/frequency is within the acceptable range and AC wiring is correct, while the alarm occurs repeatedly, contact SOFAR technical support to change the grid over-voltage, under-voltage, over­frequency, under-frequency protection points after obtaining approval from the local electrical grid operator.
EventList description
The power grid voltage is too high
The power grid voltage is too low
The power grid frequency is too high
The power grid frequency is too low
HwAcOCP
AcRmsOCP
HwADFaultIGrid
PVUVP
Vlvrtlow
Reserved
PvOVP
IpvUnbalance
PvConfigSetWrong
GFCIFault
HwBoostOCP
Check whether too few PV modules are series connected in a PV string, thus the voltage(Vmp) of the PV string is lower than the minimum operating voltage of SOFAR inverter. If yes, adjust the number of series connected PV modules to increase the voltage of the PV string to fit the input voltage range of SOFAR inverter. SOFAR inverter automatically returns to normal o perating st atus after correct adjustments.
Check the AC wiring connection to the electric grid, if it’s correct, please contact SOFAR technical support.
Reserved
Check whether too many PV modules are series connected in a PV string, thus the voltage(Voc) of the PV string is higher than the maximum input voltage of SOFAR inverter. If yes, adjust the number of series connected PV modules to decrease the voltage of the PV string to fit the input voltage range of SOFAR inverter. SOFAR inverter automatically returns to normal operating status after correct adjustments.
Check the input mode(parallel mode/ independent mode) setting of SOFAR inverter according to Section 6 of this user manual.
If the fault occurs occasionally, the possible cause is that the external circuits are abnormal occasionally. SOFAR inverter automatically returns to normal operating status after the fault is rectified. If the fault occurs frequently and lasts a long time, check whether the insulation resistance between the PV array and earth(ground) is too low, then check the insulation conditions of PV cables.
HwADFaultDCI
ID24
ID23
ID22
ID21
ID20
ID15
ID16
ID17
ID05
ID06
ID09
ID10
I
D11
I
D12
ID13
ID14
ID07 -
ID08
ID18
HwAD Fault VGrid
ID19
GFCIDeviceFault
Check whether the input current is higher than the maximum input current of SOFAR inverters, then check the input wiring, if both are correct, please contact SOFAR technical support.
MChip_Fault
HwAuxPowerFault
BusVoltZeroFault
IacRmsUnbalance
ID15-ID24 are internal faults of SOFAR inverter, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
Reserved Res erved
The input voltage is too low
Low voltage across
Reserved
The input voltage is too high
In p ut c ur re n t is n o t balanced
Incorrect input mode
GFCI Fault
Phase sequence errors
Ihe input current is too hi gh , an d ha s h ap pe n hardware protection
The grid current is too hi gh , an d ha s h ap pe n hardware protection
The grid current is too high
The grid current sampling error
The DCI sampling error
The grid voltage sampling error
The GFCI sampling error
The master chip fault
The auxiliary voltage error
The bus voltage sampling error
The Output current is not balanced
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
59
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
60
User manual User manual
Trouble shooting and maintenance Trouble shooting and maintenance
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
ID66
ID65
UnrecoverHwAcOCP
UnrecoverBusOVP
ID65-ID70 are internal faults of SOFAR inverter, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
The grid current is too h ig h , an d h a s c a u se unr ecov erab le hard ware fault
The bus volta ge i s to o h ig h , an d h a s c a u se unrecoverable fault
ID83
Reserved
ID73ID72 -
Res erved
ID67
UnrecoverIacRmsUnbalance
ID70
ID69
ID68
UnrecoverIpvUnbalance
UnrecoverVbusUnbalance
UnrecoverOCPInstant
ID74-ID77 are internal faults of SOFAR inverter, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
OverTempDerating
ID81
Reserved
ID78 - ID80
UnrecoverRelayFail
ID77
UnrecoverREADEEPROM
ID76
UnrecoverWRITEEEPROM
ID75
UnrecoverIPVInstant
ID74
Res erved
ID82
OverFreqDerating
RemoteDerating
RemoteOff
ID84
ID89ID85 -
Reserved Res erved
Ensure the installation position and installation method meet the requirements of Section 3.4 of this user manual. Check whether the ambient temperature of the installation position exceeds the upper limit. If yes, improve ventilation to decrease the temperature. Check whether the ID90~ID92 fault (fan fault) exist, if yes, please replace the corresponding fan.
SOFAR inverter automatically reduce the output power when the frequency of electrical grid is too high.
SOFAR inverter records ID83 in case of remote power derating operation. Check the wiring of remote input and output control signal port on the communication board according to Section 4.4 of this user manual.
SOFAR inverter records ID84 in case of remote shutdown operation. Check the wiring of remote input and output control signal port on the communication board according to Section 4.4 of this user manual.
Th e g r id cu r re n t i s unbalan ce,and has cause unrecoverable fault
Th e i np ut c ur re nt i s unbalan ce,and has cause unrecoverable fault
T he bu s v o l ta g e I s unbalan ce,and has cause unrecoverable fault
The grid current is too h ig h , an d h a s c a u se unrecoverable fault
Res erved
The input current is too hi gh , an d ha s h ap pe n unrecoverable fault
T h e E E P R O M i s unrecoverable
T h e E E P R O M i s unrecoverable
R e l a y h a s h a p p e n permanent fault
Res erved
the inverte r has dera ted because of the temperature is too high
the inverte r has dera ted be c au se of th e g ri d frequency too hig
The inverter has derated by the Remote control
The inverter has shut down because by the Remote control
Res erved
ID71
UnrecoverPvConfigSetWrong
Check the input mode(parallel mode/ independent mode) setting of SOFAR inverter according to Section 6 of this user manual.
Incorrect input mode
BusUVP
ID25
BusOVP
I
D26
VbusUnbalance
ID27
DciOCP
I
D28
ConsistentFault_VGrid
ID49
OverTempFault_Env
ID59
OverTempFault_Boost
I
D58
ConsistentFault_FGrid
ID50
ConsistentFault_DCI
ID51
ConsistentFault_GFCI
ID52
SpiCommLose
ID53
PvIsoFault
ID56
OverTempFault_Inv
ID57
SciCommLose
ID54
RelayTestFail
ID55
ID26-ID27 are internal faults of SOFAR inverter, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
Check the input mode(parallel mode/ independent mode) setting of SOFAR inverter according to Section 4.5 of this user manual. If the input mode is correct, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
Reserved
ID31 - ID 48
ID49-ID55 are internal faults of SOFAR inverter, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
Rese rved
Reserved
ID64ID6 0-
Res erved
If the PV array configuration is correct (no ID5 fault), the possible cause is that the solar irradiance is too low. SOFAR inverter automatically returns to normal operating status after the solar irradiance returns to normal level.
Check the insulation resistance between the PV array and earth(ground), if a short circuit occurs, rectify the fault.
Ensure the installation position and installation method meet the requirements of Section 3.4 of this user manual. Check whether the ambient temperature of the installation position exceeds the upper limit. If yes, improve ventilation to decrease the temperature. Check whether the ID90~ID92 fault (fan fault) exist, if yes, please replace the corresponding fan.
The bus voltage Is too low
The bus voltage Is too high
The bus volta ge i s no t balanced
The Dci is too high
Rese rved
The grid voltage sampling value between the master DSP and slave DSP is not consistent
T he gr i d f r eq u en c y sampling value between the master DSP and slave DSP is not consistent
The DCI sampling value between the master DSP and s lav e D SP is no t consistent
The GFCI sampling value between the master DSP and s lav e D SP is no t consistent
The sp i c ommun icati on between the master DSP and slave DSP is fault
The Sci co mmunic ation between the control board communication board is fault
The relays fault
The insulation resistance is too low
The inverter temp is too high
The Boost temp is too high
The environment temp is too high
Reserved
I
D29
I
D30
SwOCPInstant
The grid current is too high Internal faults of SOFAR inverter, turn OFF the “DC
switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
SwBOCPInstant
Ihe input current is too high Check whether the input current is higher than the
maximum input current of SOFAR inverters, then check the input wiring, if both are correct, please contact SOFAR technical support.
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
62
User manual User manual
Trouble shooting and maintenance Decommissioning
8.1 Decommissioning steps
8.2 Package
8.3 Storage
8.4 Disposal
Switch off the AC grid
Switch Off the DC switch
Wait for 5 minutes
Release the DC connectors
Release the AC terminals using screw drivers.
If possible, please pack the inverter in the original packaging. If original packing it is not available, use an equivalent carton suitable for loads more than 50 kg, has handle and can be closed fully.
Store the inverter in a dry place where ambient temperature is between -25 and - +70 °C.
At the end of its life, dispose inverters and packing materials at locations that can handle and or recycle electric equipment safely.
Decommissioning
8
Outlines of this chapter
This topic describes how to remove, pack, and dispose the Sunny Horse Series inverter.
Remove inverter from the mounting carefully to avoid injury. Please note that the Sunny Horse Series inverters weight over 45 kgs.
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
ID99 - ID1 00
Reserved Res erved
Communication board EEPROM fault
ID95
RTC clock chip anomaly
ID96
ID98
SD fault
ID97
Invalid Country
ID95~ID96 are internal faults of SOFAR inverter, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If no, please contact SOFAR technical support.
Check the country setting according to Section 4.4 of this user manual.
Please replace the SD card.
7.2 Maintena nce
Inverters generally do not need any daily or routine maintenance. Cooling fan should not be blocked by dust or any other items.
Inverter cleaning
Please use hand blower, soft dry cloth or brush to clean inverters. Water, corrosive chemical substances or intense cleaning agent should not be used for cleaning the cooling fan or inverter. Switch off AC and DC power supply to inverter before undertaking any cleaning activity.
Cooling fin cleaning
For the long-term proper operation of SOFAR inverters, ensure there is enough space around the heat sink for ventilation, check the heat sink for blockage (dust, snow, etc.) and clean them if they exist. Please clean the heat sink with an air blower, a dry & soft cloth or a soft bristle brush. Do NOT clean the heat sink with water, corrosive chemicals, detergent, etc.
Lightning protection alarm
ID93
Check the light ning protection modu le, i f it’s undamaged, please contact SOFAR technical support.
There has Lightning happen
Software version is not consistent
ID94
Conta ct SOFAR techn ical suppo rt t o u pgrade software.
The Software between the con tro l boa rd an d the communication board is not consistent
The Communication board EEPROM is fault
RTC clock chip is fault
The Country is InValid
The SD card is fault
Check whether the external fan with red heat-shrink tubing is not working, if so, replace the fan, if the alarm still exits after the replacement, please contact SOFAR technical support.
Fan1 alarm
ID91
Fan2 alarm
I
D92
The fan1 is fault
The fan2 is fault
ID90
Fan3 alarm
Check whether the internal fan is not working, if so, replace the fan, if the alarm still exits after the replacement, please contact SOFAR technical support.
The fan3 is fault
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
61
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
63
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
64
User manual User manual
Sunny Ho rse Series( 10K~20 KTL) Sunny Ho rse Series( 10K~20 KTL)
Technical data Technical data
9.2 Output parameter (AC)
Parameter
Sofar 10000TL
-Sx Series
Sofar 15000TL
-Sx Series
Sofar 17000TL
-Sx Series
Sofar 20000TL
-Sx Series
Input (DC)
Rated power Max. AC power
Active power adjustable range
0100%
Grid voltage range
Grid frequency range
15A
3/N/PE, 230/400( +/-20%)
THDI
Power factor
<3%(full load at nominal voltage)
1 ( adjustable +/-0.8)
Overvoltage category of output
Max. output current
10000VA
10000VA
15000VA 17000VA
15000VA 17000VA
20000VA
20000VA
22A
29A
44~55Hz 66Hz(adjustable, must meet local grid requirements)/54~
9.3 Efficiency, Safety and Protection
Parameter
Sofar 10000TL
-Sx Series
Sofar 15000TL
-Sx Series
Sofar 17000TL
-Sx Series
Sofar 20000TL
-Sx Series
Performance
Max efficiency
Weighted eff. (EU/CEC)
Self-consumption at night
<1W
MPPT efficiency
DC reverse polarity protection
>99.5%
DC switch
Feed in start power
98.2%
97.6%/97.8%
Yes
Yes
97.9%/98% 97.9%/98% 98%/98.1%
45W
Input/output SPD(II)
Safety protection
Certification
Anti islanding, RCMU, Ground fault monitoring
CE, CGC, AS4777,AS3100,VDE0126(more available on request)
Communication
Power management unit
According to certification and request
III ( S2, S4 version), II ( S5 version)
Input SPD(II): ( S4, S5 version)/
Output SPD(II): (S5 version)
R 485, Wifi(option), Multi-function relay
S
9.1 Input parameter (DC)
Parameter
Sofar 10000TL
-Sx Series
Sofar 15000TL
-Sx Series
Sofar 17000TL
-Sx Series
Sofar 20000TL
-Sx Series
Input (DC)
Max. input voltage
Start-up input voltage
Number of independent MPPT
Number of DC inputs
1000V
350V (+/-1v)
2 (A/B)
2 for each MPPT
Input range with Full power operation with 2 MPPT parallel
350V-850V 370V-850V 420V-850V 430V-850V
Max DC power for single MPPT Operating input volt range
Max. input MPPT current
Input short circuit current for each MPPT
Overvoltage category of input
6750(450V-850V) 10500(500V-850V) 10500(500-850V) 12000(500-850V)
250V-960V
15A/15A15A/15A 21A/21A 21A/21A 24A/24A
20A
27A 27A
30A
III ( S2 version), II ( S4, S5 version)
Technical data
9
Outlines of this chapter
This topic lists the technical specifications for all Sunny Horse Series inverters.
25A
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
65
User manual
Technical data
Shenzhen SOFARSOLAR Co., Ltd offers 5 years product warranty for Sunny Horse Series inverters from date of installation. However the warranty period can’t exceed 66 months from the date of delivery of the inverter. During the warranty period, Shenzhen SOFARSOLAR Co., Ltd guarantees normal operation of the inverter.
If during the warranty period, the inverter develops fault, please contact your installation contractor or supplier. In case of faults falling within manufacturers’ responsibility, Shenzhen SOFARSOLAR Co., Ltd will provide service and maintenance free of any charge.
Disclaimer:
Quality Assurance
10
Use of Sunny Horse Series inverters for any other purpose than intended;
Faulty system design or installation;
Improper operation;
Use wrong protection settings on the inverter;
Carry out unauthorized modification on the inverter.
Damage because of external factors or the majeure force (such as lightning, over-voltage, bad weather, fire, earthquake, tsunami etc);
Parameter
Sofar 10000TL
-Sx Series
Sofar 15000TL
-Sx Series
Sofar 17000TL
-Sx Series
Sofar 20000TL
-Sx Series
General data
Ambient temperature range
Transformerless
Allowable relative humidity range
9.4 General Data
Topology
Degree of protection
0…95% no condensing
Max. operating altitude
2000m
45kg
45kg 48kg48kg
Nature
Weight
Cooling
Dimension( )L×W×H
Warranty
708.8mm×492.0mm×245.7mm
5 yea rs
I 65
P
-25 ºC... +60ºC
All right s reserved She nzhen SOFARSOLA R Co ., Ltd.
C
Documen t Versi on 2.0(2016. 03.29)
66
User manual
Sunny Ho rse Series( 10K~20 KTL)
Technical data
Loading...