Smith Cast Iron Boilers GB250 User Manual

GB250-IM-5
42-9185
GB250 SERIES
INSTALLATION, OPERATION
& MAINTENANCE MANUAL
AND REPLACEMENT PARTS LIST
Gas-Fired Steam Cast Iron Boilers
175,000 to 400,000 Btuh Input
Intermittent Pilot, Intermittent Pilot & Vent
Damper
SECTION 1: INTRODUCTION
Code Compliance. ....................................................2
Venting Requirements ..............................................3
Chimney Requirements ............................................3
Combustion Air Requirements..................................3
Water Treatment........................................................4
Shipment of Boiler ....................................................4
SECTION 2: BOILER INSTALLATION
Step 1: Locating/Setting Boiler..................................5
Step 2: Installing Steam Piping ................................6
Step 3: Installing Hydronic Components ..................7
Step 4: Venting Boiler................................................7
Step 5: Installing/Testing Gas Piping ......................10
Step 6: Wiring Boiler ..............................................11
SECTION 3: START-UP & OPERATION
Sequence Of Operation..........................................16
Prior To Start-Up ....................................................16
Start-Up & Adjustments ..........................................16
SECTION 4: MAINTENANCE
Before Each Heating Season..................................19
How To Change Orifices ........................................20
Heating System Problems & Causes......................20
Replacement Parts List ..........................................21
Warnings ................................................................25
WESTCAST, INC. 260 NORTH ELM STREET WESTFIELD, MA 01085 TEL. (413) 562-9631 FAX (413) 562-3799 www.smithboiler.com
CODE COMPLIANCE
Boiler installations must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code ANSI Z223.1-latest edition. Where required by the authority having jurisdiction, the installation must also conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
All electrical wiring must be in accordance with National Electric Code ANSI/NFPA No.70-latest edition and any additional state or local code requirements. If an external source is utilized, boiler, when installed, must be electrically grounded in accordance with
requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA No.70-latest edition. UL listed power limited circuit cable is almost universally approved for safety controls on heating equipment, either internally or externally, without protection of conduits or raceway.
For Canada, the installation must be in accordance with Standards CGA B149.1 and B149.2 Installation Codes for Gas Burning Appliances and Equipment and/or local codes. All electrical connections are to be made in accordance with Standard C.S.A. C22.1 Canadian Electrical Code, Part 1 and/or local codes.
2
DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or property damage.
The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product:
NOTE: Used to notify of special instructions on installation, operation or maintenance which are important to equipment but not related to personal injury hazards.
SECTION 1: INTRODUCTION
21 1/2"
28 1/2"
DIMENSIONS
B
18" 18"
25"
TRANSF. 115/24V
GAS VALVE
C
10 1/2" 7" 25" 10 1/2" 7" 25" 12 1/2" 8" 30"
14" 8" 30" 15 1/2" 17 1/2" 9" 37"
PRESSURE RELIEF VALVE
*E
31 1/2"
PRESS. GAUGE
LOW WATER CUT-OFF
2 1/2"
21"
20"
14 3/4"
2" RETURN FRONT
BOILER MODEL
GB250-S-5L GB250-S-5H GB250-S-6 GB250-S-7 GB250-S-8 GB250-S-9
SPILL SWITCH
9 3/8"
8 15/16"
16 1/2"
21 7/8"
-LEFT SIDE VIEW- -FRONT VIEW- -RIGHT SIDE VIEW-
A
22 1/2" 22 1/2"
26"
29 1/2"
29 1/2" 28 1/2"
36 1/2" 32"
PRESSURE CONTROL
3"
3" STEAM SUPPLY
1/2" PLUGGED TAPPING
3 3/4"
23 1/4"
FOR MODELS SUPPLIED WITH VENT
D
9"
E
37"
D
WATER
LINE
ROLLOUT SWITCH
A6 3/4"
DAMPER ADD 3 5/8" TO DIM. E
B
C
18 1/4"
3/4" PLUGGED TAPPING
26 7/8"
23 1/4"
2" RETURN REAR
18 1/8"
2 1/2"
14 3/4"
23 7/8"
PROBE LOCATION
FOR ELECTRIC
LWCO.
VENTING REQUIREMENTS
When connecting to gas vents or chimneys, vent instal­lations shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes. For Canada, the provisions of B149.1 and B149.2 shall apply.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechani­cal draft systems operating under positive pressure.
When two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue plus 50% of the areas of the additional flue or vent connectors.
When an existing boiler is removed from common venting system, common venting system is likely to be too large for proper venting of appliances remaining connected to it. At time of removal of existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining connected to the common venting system are not in operation:
1. Seal all unused openings in common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Tur n on clothes dr yers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Fo­llow the lighting instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to common venting system proper­ly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to previous conditions of use.
7. Any improper operation of the common venting sys­tem should be corrected so the installation conforms with National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1-latest edition. For Canada, the provisions of B149.1 and B149.2 shall apply.
CHIMNEY REQUIREMENTS
Chimney condition is of paramount importance for a safe and efficient boiler installation. All new and replace­ment installations must include a chimney inspection by a qualified individual or agency. Chimney construction materials must be compatible with the fuel being used.
Particular attention should be paid on all oil-to-gas con­versions. Soot may have accumulated in chimney and/or degraded chimney liner. Most utilities require complete chimney cleaning. Others may require installation of new liner, spill switches or other chimney upgrades. Check with local utility for required safety precautions.
COMBUSTION AIR REQUIREMENTS
Provisions for combustion air must be in accordance with the National Fuel Gas Code ANSI Z223.1 - latest edition, as well as all applicable local codes. If the boiler is installed in an unconfined space, adequate air will be available via normal infiltration. However, if building construction is unusually tight or the boiler is installed in a confined space (a space whose volume is less than 50 cubic feet per 1000 Btu/hr of gas input for all fuel burning equipment), adequate air for combustion must be provided by two openings: one located about 6” below the ceiling, the other about 6” above the floor. When communicating directly with the outside or through a vertical duct, each opening must have a minimum free area of one square inch per 4000 Btu/hr of gas input. Horizontal ducts to the outside must have a minimum free area of one square inch per 2000 Btu/hr of gas input. When ventilation is provided by openings in doors, etc. to adjoining spaces having adequate infiltration, each opening must have a minimum free area of one square inch per 1000 Btu/hr of gas input.
3
DANGER: A chimney which does not meet modern safety standards will result in a fire or deadly carbon monoxide poisoning of the building residents.
4
NOTE: Boiler employs atmospheric combustion. Combustion air must not be contaminated with halogenated hydrocarbon vapors, aerosol propellants or freon. Otherwise, boiler heat exchanger will be subject to corrosion, reducing boiler life.
WATER TREATMENT
Water treatment is recommended in areas where water quality is a problem. A local water treatment company should be consulted to determine the requirements for your particular system and locality.
NOTE: Boiler is not for use in systems where water is replenished. Minerals in the water can build up on the heat transfer surfaces and cause overheating and subsequent failure of the heat exchanger.
NOTE: Boiler utilizes synthetic rubber seals. Water treatment chemicals and system cleaning chemicals must be compatible with this and all other
construction materials.
SHIPMENT OF BOILER
Each boiler is shipped in a single carton. Draft hood is shipped in a separate carton on larger models.
Optional Vent Damper
When ordered, the vent damper is shipped in an individual carton packaged with the boiler. Mounting of the damper is required.
WARNING: Adequate fresh air must be provided for combustion. Improper boiler operation and inadequate venting of deadly flue gases may otherwise result.
WARNING: Installers must follow local regulations with respect to the installation of CO detectors and follow the manufacturer’s stated maintenance schedule for this boiler!
ATTENTION: Observer les règlements règional à l’egard des détecteurs de monoxyde de carbone et observer entretien de manufacturier pour cette chaudière!
SECTION 2: BOILER INSTALLATION
STEP 1: LOCATING AND SETTING THE BOILER
PROCEDURE A: Check that provisions for combustion air are in accordance with National Fuel Gas Code ANSI Z223.1-latest edition and all applicable local codes. In Canada, follow CAN/CGA B149(.1 or .2) installation codes.
PROCEDURE B: Check minimum clearances to combustibles are proper as shown. Local requirements may specify greater clearances & must be adhered to.
Boiler shall be install­ed such that the gas ignition system com­ponents are protected from water (dripping, spraying, rain, etc.) during appliance oper­ation and service.
WARNING: Never install boiler on combustible flooring without combustible flooring pan or on carpeting as heat damage and/or fire may result.
FIGURE 2.1
5
Step 1 Continued On Next Page
NOTE: Do not loosen tie rods on absorption unit. They accommodate thermal expansion. Loss of boiler structural integrity and water leaks/damage may result.
CAUTION: Locate boiler so horizontal connecting flue pipe is as short as possible. Maximize height of vertical flue connector.
6"
6"
VENT DAMPER
* TOP
18"
1
1
1 1
1
1
1
1111
1 1
12"
RECOMMEND MORE FOR ACCESS TO VENT DAMPER POSITION INDICATOR
* 52" FOR GB250-S-5L THRU GB250 S-7
58" FOR GB250-S-8 THRU GB250-S-9
12"
6
PROCEDURE C: Check component positioning.
1. Remove all packing material from boiler.
2. Install on non-combustible floor
only, unless local codes permit use and fabrication of a fireproof base (see Fig. 2.2).
3. Check that burners and controls
are in the proper position.
FIGURE 2.2
STEP 2: INSTALLING STEAM PIPING
Typical piping connections are shown in Figure 2.3. All external piping must be supported by hangers, not by the boiler or its accessories.
Supply outlet must run full size from boiler to a header at least 24" above top of boiler. Condensate return piping should be connected to boiler through a "Hartford Loop." Install gate valves in supply and return.
Proper steam piping practices must be followed at all times. Maintain proper clearances between piping and combustible material.
The supply and return lines should be equipped with drain cocks to drain sediment and sludge from lowest points of boiler.
FIGURE 2.3
4" HOLLOW CLAY TILE (TWO COURSES) OPENINGS THRU BLOCKS IN TOP COURSE TO
0
BE AT 90 ANGLE TO OPENINGS THRU BOTTOM COURSE
6" OVERHANG OF BLOCK AND SHEETMETAL ALL AROUND
6"
22 GAUGE SHEETMETAL
FLOOR
STEAM
SUPPLY
GATE VALVE
SUPPLY TAPPING 3" NPT
HARTFORD LOOP
RETURN
MUST BE CLOSE NIPPLE
GATE VALVE
DRAIN COCKS
RETURN TAPPING 2" NPT
COLD WATER FILL
24" MIN.
WATER LINE
C/L OF HARTFORD LOOP TO BE 2" BELOW WATER LINE
23-1/4"
7
STEP 3: INSTALLING HYDRONIC COMPONENTS
A low-water cutoff must be installed to protect the unit from dry-fire.
Screw extension nipple into 3/4" tapping on top of the absorption unit and install relief valve into top of nipple with the spindle in the vertical position (i.e., with the valve discharge in the horizontal)(See Figure 2.4).
Most localities require the discharge piping to terminate within 6" of the floor. Check local code requirements if in doubt. Discharge piping must be of same size or larger than the relief valve outlet and should be run as short and straight as possible. Elbows in the discharge piping should be placed as close to the valve as possible. If valve discharge is to be drained away, the discharge piping must not be hard-piped to the drain piping (i.e.,
an open funnel or similar arrangement must be used).
FIGURE 2.4
STEP 4: VENTING BOILER
Install draft hood on boiler. If the draft hood shroud has a hole near the relief opening for installing a spill switch, mount draft hood so the hole faces to the front of the boiler. Spill switches are provided on Model GB250-5L,
GB250-5H, and GB250-6 boilers.
Applicable boiler is equipped with a factory-mounted spill switch harness/mounting bracket assembly; spill switch is provided in plastic bag. See Figure 2.5. Install mounting bracket on outside surface of draft hood shroud with screws provided (HARNESS MUST BE ON OUTSIDE OF SHROUD). Install spill switch in hole in shroud (on outside surface) with screws provided. Plug wiring leads from harness/bracket assembly onto flat terminals on spill switch.
NOTE: Boiler will not operate unless wiring leads to spill switch are connected.
FIGURE 2.5
If vent damper is supplied with boiler, it must be installed between the top of the draft hood and the flue pipe. See Installing The Vent Damper instructions.
Connect draft hood to chimney or Class B vent. Flue pipe must be same diameter as the draft hood outlet.
WARNING: No Valve of any type may be installed between the boiler and the relief valve to prevent accidental explosion from overpressure.
DANGER: Drafthood, vent outlet and vent damper as supplied must not be altered in any was as proper boiler operation would be jeopardized. Flame rollout, fire or carbon monoxide poisoning will result.
CAUTION: Piping must be installed from the relief valve discharge so there will be no danger of scalding personnel.
PRESSURE RELIEF VALVE
PRESSURE RELIEF VALVE DISCHARGE PIPING
INSTALL SWITCH
IN OPENING
ON DRAFTHOOD
CONNECT
WIRE
LEADS
INSTALL
MOUNTING
BRACKET
ON DRAFTHOOD
8
The flue or vent connectors must be installed flush with the inside chimney liner surface and sealed in place with furnace cement. Horizontal portions of the single wall and type B venting systems shall be supported by use of strap hangers or their equivalent. Vent suppor ts should be placed a maximum of 15-feet apart and as required to prevent sagging. The vent connectors shall be pitched 1/4" per foot upwards towards the chimney or vent termination.
Installing Vent Damper
The vent damper must be mounted directly on top of the draft hood.
Locate the motor on the front side and position the cable so that it does not touch the metal surface of the drafthood (see Figure 2.6). If necessary, turn angle connector on vent damper upward until cable clears; tighten locknut to secure.The direction of the flow arrow imprinted on the vent damper must point upward. The damper position indicator, which is located on the side of the vent damper opposite the motor, must be visible.
Remove hairpin shipping clip which holds damper blade in closed position and observe that damper blade rotates slowly to open position. Do not force it closed as it may damage the gear train and void the warranty. The blade should move freely and without obstruction.
Secure the vent damper housing to the drafthood outlet with sheet metal screws or pop rivets. Refer to Figure
2.8 for fastener locations. Install flue pipe over top of vent damper and secure to damper housing with sheet metal screws or pop rivets.
Attach vent damper cable to cable clamp on boiler left panel and join the Molex connector (see Figure 2.6 or Figure 2.6A).
FIGURE 2.6: Vent Damper Installation for Intermittent Pilot
FIGURE 2.7
DANGER: Only the boiler may be served by the vent damper. Do not attempt to use it to vent an additional appliance. This will cause fire or carbon monoxide poisoning.
CAUTION: A minimum of 6" between vent damper and combustible materials must be maintained. The vent damper must be accessible for servicing and checking position indicator.
R
FIGURE 2.6A: Vent Damper Installation for Standing Pilot
FLOW DIRECTION ARROW POINTS UP
MAKE SURE MOTOR IS LOCATED ON FRONT SIDE
MOUNT VENT DAMPER OVER DRAFTHOOD
VENT DAMPER
DRAFTHOOD
CABLE BRACKET
PRESSURE CONTROL
THERMOSTAT CONNECTION
TRANSFORMER
PILOT CONTROL
VENT DAMPER
DRAFTHOOD
CABLE BRACKET
PRESSURE CONTROL
THERMOSTAT CONNECTION
TRANSFORME
GAS VALVE
DK. BLUE
THERMOSTAT CONNECTION
DK. BLUE
THERMOSTAT CONNECTION
9
ADDITIONAL VENTING REQUIREMENTS: When connecting to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
When two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area
of the largest flue plus 50% of the areas of the additional flue or vent connectors.
When an existing boiler is removed from a common venting system, common venting system is likely to be too large for proper venting of appliances remaining connected to it. At time of removal of existing boiler, following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining connected to common venting system are not in operation:
1. Seal all unused openings in common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Tur n on clothes dryers and any appliance not connected to the common venting system. Tur n on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to previous conditions of use.
7. Any improper operation of the common venting system should be corrected so installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1-latest edition. For Canada, the provisions of CAN/CGA B149(.1 or .2) shall apply.
ADDITIONAL CHIMNEY REQUIREMENTS: Chimney condition is of paramount importance for a safe and efficient boiler installation. All installations must include a chimney inspection by a qualified individual or agency. Chimney construction materials must be compatible with the fuel being used.
Particular attention should be paid on all oil-to-gas conversions.Soot may have accumulated in chimney and/or degraded chimney liner. Most utilities require complete chimney cleaning. Others may require installation of new liner, spill switches or other chimney upgrades. Check with local
utility for required safety precautions.
PROCEDURE C: Install flue pipe between vent damper and chimney (6" minimum clearance required between flue pipe and combustibles).
FIGURE 2.9
DANGER: A chimney which does not meet modern safety standards will result in a fire or deadly carbon monoxide poisoning of the building residents.
A
A
ATTACH LOWER
FIGURE 2.8
PORTION OF VENT DAMPER TO DRAFTHOOD OUTLET WITH 1/2" OR SHORTER SCREWS OR POP RIVETS
AA AA
USE VENT SUPPORT(S) AS REQUIRED TO PREVENT SAGGING
MAXIMUM
SINGLE WALL OR TYPE B FLUE PIPE
6 FT.
APART
PITCH 1/4" PER FOOT
SECURE FLUE PIPE TO VENT DAMPER
INSTALL
FLUSH
WITH
CHIMNEY
LINER
SEAL WITH
FURNACE
CEMENT
Loading...
+ 19 hidden pages