Smith Cast Iron Boilers 28A User Manual

5 (1)
MEA#273-89-E
SERIES 28A
GAS OR OIL BOILER
INSTALLATION & OPERATING
INSTRUCTIONS
28A-IOM-7
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF: 15 PSI STEAM OR 80 PSI WATER.
TO INSTALLER
READ THESE INSTRUCTIONS CAREFULLY. THEY WILL
SAVE YOU VALUABLE TIME WHEN ASSEMBLING THE BOILER.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
INSTALLER, THESE INSTRUCTIONS T O BE AFFIXED ADJACENT TO THE BOILER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
FOR JACKET ASSEMBLY AND BURNER SET UP SEE SEPARATE INSTRUCTIONS.
WESTCAST, INC. 260 NORTH ELM STREET WESTFIELD, MA 01085 TEL. (413) 562-9631 FAX (413) 562-3799
In Canada: 5211 Creekbank Road, Mississauga, Ont. L4W 1R3 (905) 625-2991 Fax (905) 625-6610
Page 2
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
CONTENTS
Before You Start .................................................page 2
Boiler Ratings & Capacities................................page 2
Boiler Location ...................................................page 2
Combustion Air & Ventilation..............................page 3
Chimney & Vent Pipe Connections ....................page 4
Common V ent Systems......................................page 6
Boiler Assembly ................................................ page 7
General Piping Requirements ..........................page 14
Water Boiler Piping ..........................................page 15
Steam Boiler Piping..........................................page 18
Burner Installation ............................................page 21
Electrical Wiring ...............................................page 22
Boiler Operation .............................................. page 22
Boiler Checking & Adjustment..........................page 23
Boiler Maintenance ..........................................page 23
Repair Parts .....................................................page 25
Health Warnings.......................................... back cover
BEFORE YOU START
This manual covers the assemb ly, installation, operation and maintenance of a Series 28A low pressure steam or hot water boiler.
The 28A Series boilers are supplied completely knocked down for field assembly, knocked down but with an assembled block or as complete factory assembled packaged boilers. All boiler components should be inspected for damage upon receipt. Any damage should be immediately reported to the trucker or wholesaler. All boiler components should be stored in a clean dry area. To obtain the safe, dependable, efficient operation and long life for which this boiler was designed, these instructions must be read, understood and followed.
The Series 28A boilers have been design certified by CSA. Each unit has been constructed and hydro­statically tested for a maximum working pressure of 15 psi for steam, 80 psi for water, in accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code for cast iron boilers.
All aspects of the boiler installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision or to the Installation of Oil Burning Equipment, ANSI/NFPA
31. Where required by the authority having jurisdiction, the
installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CAN/CGA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
In the Commonwealth of Massachusetts the installation of a gas burner must be performed by a licensed plumber or gas fitter.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the ser vice organization for future reference.
Direct all questions to your Smith Cast Iron Boiler distributor or contact the Smith Customer Service Department. Always include the model and serial numbers from the rating plate of the boiler in question.
BOILER RATINGS & CAPACITIES
Before undertaking the installation of the 28A Series boiler check the boiler rating plate to ensure that the boiler has been sized properly for the job. The “Net I=B=R Ratings” specify the equivalent amount of direct cast iron radiation that the boiler can supply under normal conditions. Also ensure that the boiler has been set up for the type of fuel available at the installation site.
BOILER LOCATION
1. Locate the boiler in an area that provides good access to the unit. A minimum distance of 6 in,
0.15m
must be maintained between the boiler
and combustible construction. Servicing may
require the removal of jacket panels so service clearances should be maintained. Allow a minimum clearance of 3 ft, construction and the left side, front and smoke hood. A minimum clearance of 2 ft, maintained between adjacent construction and the right side and back of the boiler. Accessibility clearances should take precedence over minimum clearances to combustible construction, Figure 1.
2. An optimum site will be level, central to the piping system, close to a chimney and have adequate fresh air for combustion.
3. The boiler should be installed on a level, flat, concrete floor or pad that is structurally sound and will support the weight of the boiler. If a concrete pad is used it must be at least 2" thick. Never install the boiler on a concrete floor or pad that contains wires, cables, water pipes or hoses. This boiler is designed for non-combustible floors!
0.9 m
between adjacent
0.6 m
should be
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
Figure 1- Service Clearances to Adjacent Construction
Page 3
WARNING: Never install a 28A boiler on top of combustible flooring without consulting the local building authorities for proper installation guidelines! A minimum clearance of 6 in,
0.15 m
and combustible construction. F ailure to comply with this warning may result in a fire causing extensive property damage, severe personal injury or death!
4. DO NOT install this boiler in a location that would
5. DO NOT place this boiler in a location that would
WARNING: Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
must be maintained between the boiler
subject any of the electrical components to direct contact with water or excessive moisture during operation or servicing.
restrict the introduction of combustion air into the boiler.
COMBUSTION AIR & VENTILATION
WARNING: This boiler must be supplied with combustion and ventilation air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and all applicable local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Failure to provide adequate combustion air for this boiler can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler requires a continuous supply of air for combustion. An adequate supply of air must be available to replace the air used by the combustion process. NEVER store objects on or around the boiler.
CAUTION: Never use an exhaust fan in the boiler room. The boiler room must never be under a negative pressure or improper burner operation will occur!
NOTE: Forced make-up air supplied to the boiler room must be approved by the local authorities. A minimum of 30 ft3/GAL, 20 ft3/100 MBH (Therm), be provided.
0.22 m3/L
0.024 m3/kW
for oil or
for gas must
Page 4
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
All Air From Inside The Building
If the boiler is to be located in a confined space mini­mum clearances of 24 in, between the boiler and any adjacent construction. When installed in a confined space, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have sufficient volume to meet the criteria for an unconfined space. The total air requirements of all fuel burning equipment or any type of exhaust fan must be considered when making this determination.
Each opening must have a minimum free area of 1 in2/ 1000 Btu/hr, 140 in2/GPH, total input rating of ALL fuel burning equipment in the confined area. Each opening must be no less than 100
in2,
64,516 mm
within 12 in, from, the top of the enclosure.
The bottom opening must be within 12 in, but not less than 3 in, enclosure.
All Air From Outside The Building
When installed in a confined space Two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in, from, the top of the enclosure. The bottom opening must be within 12 in, 305 mm of, but not less than 3 in,
76 mm
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/ 4000 Btu/hr, 35 in2/GPH, rating of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr, 70 in2/GPH,
kW
the enclosure. When ducts are used, they must have the same cross-sectional area as the free area of the opening to which they connect. When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in, is not known the louver or grill should be sized per Table 1.
from, the bottom of the enclosure.
of the total input rating of all of the equipment in
6.4mm
2
in size. The upper opening must be
305 mm
305 mm
. If the free area through a louver or grill
610 mm
2200 mm2/kW
of, but not less than 3 in,
must be maintained
based on the
305 mm
76 mm
of, but not less than 3 in,
from, the bottom of the
550 mm2/kW
of the total input
1100 mm2/
76 mm
of,
76 mm
Table 1- Make-up Air Louver Sizing
Required Cross Sectional Area (in2)
Metal Wooden
Input 1/4" Wire Louvers Louvers
(MBH) Screen 75% Free Area 25% Free Area
1000 250 333 1000 1200 300 400 1200 1400 350 467 1400 1600 400 533 1600 1800 450 600 1800 2000 500 667 2000 2200 550 733 2200 2400 600 800 2400 2600 650 867 2600 2800 700 934 2800 3000 750 1000 3000 3200 800 1066 3200 3400 850 1134 3400 3600 900 1200 3600 3800 950 1267 3800 4000 1000 1334 4000 4200 1050 1400 4200 4400 1100 1467 4400 4600 1150 1533 4600 4800 1200 1600 4800
CHIMNEY & VENT PIPE CONNECTIONS
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54-latest revision, the ASHRAE Equipment Handbook on Venting or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Improper venting of this boiler can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
CAUTION: The products of combustion from a 28A must be safely vented to the outdoors while ensuring that the flue gasses do not cool prematurely. It’s critical that the chimney system be properly designed to handle the flue gases. An oversized or uninsulated chimney can cause the moisture in the flue gases to condense resulting in damage to the chimney system unless it’s specifically designed for condensate. If this is the case a suitable condensate drain must be used to protect the boiler from condensate.
NOTE: Our warranty does not cover corrosion damage to the boiler or its vent system caused by flue gas condensate!
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
Page 5
Chimney Inspection & Sizing
If this boiler will be connected to a masonry chimney, a thorough inspection of the chimney must be performed. Ensure that the chimney is clean, properly constructed, lined and properly sized, see Figure 2. Table 2 lists the equivalent breeching and flue sizes required for the 28A boilers.
Table 2 - Equivalent Breeching & Chimney Size
Boiler Model Breeching Size Chimney Size
in 28A-4 10 28A-5 10 28A-6 10 28A-7 12 28A-8 12 28A-9 14 28A-10 14 28A-11 14 28A-12 14 28A-13 14 28A-14 16 28A-15 16 28A-16 16 28A-17 18 28A-18 18
mm 254 254 254 305 305 356 356 356 356 356 406 406 406 406 457
in
10 10 10 12 12 14 14 14 14 14 16 16 16 18 18
mm 254 254 254 305 305 356 356 356 356 356 406 406 406 406 457
Note: These sizes are based on a 20 foot chimney height.
The 28A is designed for pressurized operation with a back pressure of 0.10 in, smoke hood slide damper. If the vent configuration results in a back pressure greater than this, the burner capacity may have to be verified. Contact the Smith Technical Service Department to verify the burner capacity.
The chimney must be able to provide 0.10" WC at the boiler outlet. If the chimney is 50 ft. or taller it may produce excessive draft (approx. - 0.25" WC) and a barometric draft regulator may be needed.
When more than one appliance is connected to the same chimney flue the flue must be large enough to safely vent the combined output of all the appliances.
WARNING: If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney flue, never connect a Category I appliance to this flue. Doing so can result in the accumulation of carbon monoxide which can cause severe personal injury or death!
2.54 mm
W.C. before the
Figure 2 - Vertical Venting
Page 6
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
VENT CONNECTIONS
WARNING: Never modify or alter any part of the boilers smoke hood. This includes the removal or alteration of any baffles. Never install a vent pipe of a diameter different than that of the boiler smoke hood outlet. Failure to comply with this warning can result in severe personal injury or death.
Locate the boiler as close to the chimney as possible. Use the shortest, straightest vent connector possible for the installation. If horizontal runs exceed 5 ft, must be supported at 3 ft, hangers. Use a single wall stainless or single wall galvanized steel vent pipe the same diameter as the flue collar to connect the boiler to a masonry chimney. When using an approved metal chimney system use the appropriate vent connector. The vent connector should be sloped up toward the chimney at a minimum rate of 1/4 in/ft, must terminate flush with the inside of the chimney flue. Fasten each single wall vent connection with at least 3 corrosion resistant sheet metal screws.
The vent materials used in positive pressure vent systems must be certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. The following manufactures have systems that meet these requirements:
Heat-Fab, Inc. 38 Hayward Street Greenfield, MA 01301, (800) 772-0739.
Z-Flex U.S., Inc. 20 Commerce Park North, Bedford, NH 03110-6911, (800) 654-5600.
Protech Systems Inc. 26 Gansevoort Street, Albany, NY 12202 (518) 463-7284
2 cm/m
. On masonry chimneys the connector
0.9 m
intervals with overhead
1.5 m
they
WARNING: Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fire causing extensive property damage, severe personal injury or death!
COMMON VENT SYSTEMS
If an existing boiler is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d'une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d'évacuation commun et qui fonctionne alors que d'autres appareils toujours raccordés au système d'évacuation ne fonctionnent pas: système d'évacuation
a) Seal any unused openings in the common venting
system. Sceller toutes les ouvertures non utilisées du
système d'évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d'évacuation pour déterminer la grosser et l'inclinaison horizontale qui conviennent et s'assurer que le système est exempt d'obstruction, d'étranglement de fruite, de corrosion et autres défaillances qui pourraient présenter des risques.
WARNING: Breeching under positive pressure must be certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Type B1 vent SHALL NOT be used. Failure to comply with this warning can result in severe personal injury or death.
Always provide a minimum clearance of 6 inches between single wall metal vent pipe and all combustible materials.
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
Page 7
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan for a boiler installation. Close fireplace dampers.
Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre l'espace où les appareils toujours raccordés du système d'évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d'évacuation commun et tous les ventilateurs d'extraction comme les hottes de cuisinère et les ventilateurs des salles de bain. S'assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d'été. Fermer les registres des cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Mettre l'appareil inspecté en marche. Suivre les instructions d'allumage. Régler le thermostat de façon que l'appareil fonctionne de façon continue.
e) Test f or spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min ensuite, déterminer si le coupetirage déborde à l'ouverture de décharge. Utiliser la flamme d'une allunette ou d'une chandelle ou la fumée d'une cigarette, d'un cigare ou d'une pipe.
f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
g) Any improper operation of the venting system
should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix F in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and or CSA B149 Installation Codes.
Tout mauvais fonctionnement du systéme d'évacution commun devrait étré corrigé de façor que l'installation soit conforme au National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'installation CAN/CGA-B149. Si la grosseur d'une section du système d' évacuation doit étré modifiée, le système devrait étré modifié pour respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) des codes d'installation CSA-B149.
BOILER ASSEMBLY
Locate the boiler installation site based on the guide­lines set forth in the BOILER LOCATION section.
WARNING: Never install a 28A boiler on top of combustible flooring without consulting the local building authorities for proper installation guidelines! Failure to comply with this warning can result in a fire causing extensive property damage, severe personal injury or death!
Packaged Boilers/Factory Assembled Sections
A careful inspection of all assemblies should be made to detect possible shipping damage. Packaged boilers and factory assembled blocks of sections are hydrostatically tested at the factory to insure pressure tightness. A hydrostatic retest should be performed before any piping connections are made to detect leaks caused by shipping.
NOTE: All assembled boiler sections shall pass the hydrostatic tests prescribed in Section IV of the ASME Boiler and Pressure Vessel Code.
CAUTION: Do not connect any boiler controls during the pressure test or they will be damaged!
Une fois qu'il a été d éterminé, selon la métode indiquée cidessus, que chaque appareil raccordé au système d'évacuation est mis à l'air libre de façor adéquate. Remettre les por tes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
Page 8
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
Completed boilers must be tested as follows: Steam Boilers – the assembled boiler sections shall be
subjected to a hydrostatic test pressure of not less than 45 psig,
Water Boilers – the assembled boiler sections shall be subjected to a hydrostatic test pressure of not less than 1 1/2 times the maximum allowable working pressure.
The hydrostatic pressure shall not exceed the required test pressure by more than 10 psig, test.
WARNING: Never leak test the boiler using compressed air! Failure to comply with this warning may result in property damage, severe personal injury or death!
1. Plug all openings in the boiler and fill it with water.
2. Bleed any air off through one of the top tappings
3. Maintain the test pressure while carefully checking
NOTE: The shipping lugs, lifting lugs and metal banding should be removed before installing the jacket on factory assembled sections.
CAUTION: Remove the left jacket panels on fully packaged boilers and ensure that the cleanout covers are secure and gas tight. Loose covers could damage the boiler.
315 kPa
then increase the pressure as outlined above.
for leaks. If a leak is found it must be eliminated, see Table 4 and supporting text. Once the assembled boiler sections pass the hydrostatic test drain them and remove the plugs from any tappings that will be used in service.
.
70 kPa
during the
2. Carefully place the back section in position on the angles as shown in Figure 4.
WARNING: The section MUST be fully supported to prevent it from falling! Failure to comply with this warning may result property damage, severe personal injury or death!
Figure 4 - Section Placement
3. Clean the hydronic port connector sealing surfaces and the rope grooves with a wire brush to remove any rust or debris.
4. Apply two coats of the spray adhesive supplied with the boiler to the rope groove. Allow time for the first coat to dry before applying the second coat. When the second coat is tacky press the rope into the rope groove. Trim the rope off leaving 1/8 in., extending beyond the surface of the cast iron section, Figure 5.
Figure 5 - Rope Installation
3.2 mm
Assembly of Knocked-Down Boilers
Drilled and tapped steel angles are furnished to provide a level footing, ease of section assembly and a point of jacket attachment.
1. Set the angles as shown in Figure 3. They must be parallel and level. Grout under the angles to provide a continuous bearing surface.
Figure 3 - Steel Angle Placement
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS
Page 9
5. Insert the large port connector with its steel inner ring into the upper port.
6. Insert the two round por t connectors into the lower ports.
NOTE: Apply the spray adhesive supplied with the boiler to the port recess to hold the port connector in place if necessary.
7. Select the correct intermediate section and carefully move it into place against the back section, Figure
4.
CAUTION: Any steam uptake and heater sections must be located as shown in Table 3. Failure to comply with this caution may result in poor boiler performance and prevent the jacket from fitting! Only one intermediate section with an external leg boss has been included. It should be located toward the front of the boiler for optional low water cutoff use. See Table 3.
NOTE: A putty knife or similar tool can be used to hold the port connectors in place while the intermediate section is positioned. It must be removed before the sections make contact or the port connector will be damaged resulting in a leak!
8. Insert the four draw rods through the casting bosses. Thread nuts onto one end of the rods. Place washers on the other end of the rods before threading nuts onto them. Sn ug the nuts finger tight. Use a spirit level to ensure that the first two sections are plumb and properly aligned, Figure 6. Check the rope to insure that it’s properly positioned. Once the sections are plumb and the rope and port connectors are properly positioned follow the torque sequence shown in Table 4.
Figure 6 - Section Alignment
Table 4 - Section Torque Sequence
Step Rod Position Torque
ft lbs
1 Upper Right 25 2 Lower Left 25 3 Lower Right 25 4 Upper Left 10 5 Upper Right 50 6 Lower Left 50 7 Lower Right 50 8 Upper Right 75 9 Lower Left 75 10 Lower Right 75 11 Upper Left 30 12 Upper Right 125 13 Lower Left 125 14 Lower Right 125 15 Upper Right 125 16 Upper Left 40
Nm
34 34 34 14 68 68
68 102 102 102
42 169 169 169 169
54
NOTE: With these initial torques the sections may not be metal to metal, which is acceptable. If any of the ports leak during the hydrostatic test the torque can be increased to 200 ft lbs,
271 Nm
on the upper right rod. The tor que on the lower left and right rods can be increased to 150 ft lbs,
203 Nm
. Once the sections are metal to metal additional torque will not improve the seal.
Table 3 - Section Locations
Boiler Section Location Numbered From Front To Back Model 123456789101112131415161718 28A-4 F T H B F Front Section 28A-5 F H T H B T Intermediate Section w/ 5" Tapping & Boss 28A-6 F T H T H B H Intermediate Section w/ Heater Opening 28A-7 F T H P T H B P Intermediate Section, Plain 28A-8 F T H P H T H B B Back Section 28A-9 F T H P H P T H B
28A-10 F H T H P H P T H B 28A-11 F H T H P T P T H B 28A-12 F H T H P T H P H T H B 28A-13 F H T H P H T P P H T H B 28A-14 F H T H P H T H P H P T H B 28A-15 F H T H P H P T H P H P T H B 28A-16 F H T H P H P H T H P H P T H B 28A-17 F H T H P H P H T H P H P H T H B 28A-18 F H T H P H P H P T H P H P H T H B
Loading...
+ 19 hidden pages