Smith Cast Iron Boilers GB200 User Manual

GB200-IM-5
42-9184
GB200 SERIES
INSTALLATION, OPERATION
& MAINTENANCE MANUAL
WITH REPLACEMENT
PARTS LIST
GAS-FIRED STEAM
85,000 TO 165,000 BTUH INPUT
INTERMITTENT PILOT/VENT DAMPER
& STANDING PILOT/VENT DAMPER
SECTION 1: INTRODUCTION
Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Venting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . .3
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Shipment of Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
SECTION 2: BOILER INSTALLATION
Step 1: Locating/Setting Boiler . . . . . . . . . . . . . . . . . . . . .4
Step 2: Installing Steam Piping . . . . . . . . . . . . . . . . . . . .5
Step 3: Installing Hydronic Components . . . . . . . . . . . . .5
Step 4: Venting Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Step 5: Installing/Testing Gas Piping . . . . . . . . . . . . . . . . .7
Step 6: Wiring Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SECTION 3: START-UP & OPERATION
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . .11
Prior To Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Start-Up & Adjustments . . . . . . . . . . . . . . . . . . . . . . . . .11
SECTION 4: MAINTENANCE
Before Each Heating Season . . . . . . . . . . . . . . . . . . . . .14
Steam Boiler Cleaning Instructions . . . . . . . . . . . . . . . . .15
How To Change Orifices . . . . . . . . . . . . . . . . . . . . . . . . .15
Heating System Problems & Causes . . . . . . . . . . . . . . .15
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . .16-17
WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
TABLE OF CONTENTS
WESTCAST, INC. 260 NORTH ELM STREET WESTFIELD, MA 01085 TEL. (413) 562-9631 FAX (413) 562-3799 www.smithboiler.com
2
SECTION 1: INTRODUCTION
The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product:
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or prop­erty damage.
NOTE: Used to notify of special instructions on installa­tion, operation or maintenance which are important to equipment but not related to personal injury hazards.
CODE COMPLIANCE
Boiler installations must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code ANSI Z223.1­latest edition. Where required by the authority having jurisdic­tion, the installation must also conform to the American Soci­ety of Mechanical Engineers Code for "Controls and Safety Devices for Automatically Fired Boilers", ANSI/ASME CSD-1.
All electrical wiring must be in accordance with National Electric Code ANSI/NFPA No.70-latest edition and any addi­tional state or local code requirements. If an external source is utilized, the boiler, when installed, must be electrically grounded in accordance with requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA No.70-latest edition. UL listed power limited circuit cable is almost univer­sally approved for safety controls on heating equipment, either internally or externally, without protection of conduits or raceway.
VENTING REQUIREMENTS
When connecting to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
When two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue plus 50% of the areas of the additional flue or vent connectors.
When existing boiler is removed from common venting sys­tem, common venting system is likely to be too large for proper venting of appliances remaining connected to it. At time of removal of existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining connected to the common venting sys­tem are not in operation:
1. Seal all unused openings in common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ances remaining connected to the common venting sys­tem are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at draft hood relief opening after 5 min­utes of main burner operation. Use the flame of a match or candle, or smoke from cigarette, cigar or pipe.
6. After it has been determined that each appliance remain­ing connected to common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burn­ing appliance to previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting sys­tem, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1-latest edition.
WARNING: Indicates a potentially hazardous situa­tion which, if not avoided, could result in death, seri­ous injury or substantial property damage.
DANGER: Indicates an imminently hazardous situa­tion which, if not avoided, will result in death, serious injury or substantial property damage.
CHIMNEY REQUIREMENTS
DANGER: A chimney which does not meet modern safety standards will result in a fire or deadly carbon monoxide poisoning of the building residents.
Chimney condition is of paramount importance for a safe and efficient boiler installation. All new and replacement installa­tions must include a chimney inspection by a qualified indi­vidual or agency. Chimney construction materials must be compatible with the fuel being used.
Particular attention should be paid on all oil-to-gas conver­sions. Soot may have accumulated in chimney and/or degraded chimney liner. Most utilities require complete chim­ney cleaning. Others may require installation of new liner, spill switches or other chimney upgrades. Check with local utility for required safety precautions.
COMBUSTION AIR REQUIREMENTS
Provisions for combustion air must be in accordance with the National Fuel Gas Code ANSI Z223.1 - latest edition, as well as all applicable local codes. If the boiler is installed in an unconfined space, adequate air will be available via normal infiltration. However, if building construction is unusually tight or the boiler is installed in a confined space (a space whose volume is less than 50 cubic feet per 1000 Btu/hr of gas input for all fuel burning equipment), adequate air for combustion must be provided by two openings: one located about 6” below the ceiling, the other about 6” above the floor. When communicating directly with the outside or through a vertical duct, each opening must have a minimum free area of one square inch per 4000 Btu/hr of gas input. Horizontal ducts to the outside must have a minimum free area of one square inch per 2000 Btu/hr of gas input. When ventilation is provid­ed by openings in doors, etc. to adjoining spaces having ade­quate infiltration, each opening must have a minimum free area of one square inch per 1000 Btu/hr of gas input.
3
NOTE: Boiler employs atmospheric combustion. Com­bustion air must not be contaminated with halogenated hydrocarbon vapors, aerosol propellants or freon. Other­wise, boiler heat exchanger will be subject to corrosion, reducing boiler life.
WATER TREATMENT
Water treatment is recommended in areas where water quali­ty is a problem. A local water treatment company should be consulted to determine the requirements for your particular system and locality.
NOTE: Boiler is not for use in systems where water is replenished. Minerals in the water can build up on the heat transfer surfaces and cause overheating and subse­quent failure of the heat exchanger.
NOTE: Boiler utilizes synthetic rubber seals. Water treat­ment chemicals and system cleaning chemicals must be compatible with this and all other construction materials.
SHIPMENT OF BOILER
Each boiler is shipped in a single carton.
Optional Vent Damper
When ordered, the vent damper is shipped in an individual carton packaged with the boiler. Mounting of the damper and flue outlet extension are required.
WARNING: Adequate fresh air must be provided for combustion. Improper boiler operation and inade­quate venting of deadly flue gases may otherwise result.
4
FIGURE 2.1: MODEL GB200 BOILER DIMENSIONS
WARNING: Never install boiler on carpeting as heat damage and/or fire may result.
STEP 1: LOCATING/SETTING BOILER
Boiler may be installed in an alcove (see dimensions in Fig­ure 2.1). Locate boiler so connecting flue pipe between draft hood and chimney is as short as possible.
Observe the following minimum clearances to combustibles: 18" on sides...alcove at front...28" at top...18" at rear...6" from flue pipe in any direction. Maintain a minimum 1” clearance between hot water piping and combustible materials. Local code requirements may specify greater clearances and must be adhered to.
Remove boiler from carton and set it in position. Install on non-combustible floor only, unless local codes permit use and fabrication of a fireproof base (see Figure 2.2).
Remove all packing material from boiler. Check that burners, draft diverter and controls are in proper position.
Boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (low water cut-off repacement, condensate trap replacement, control replacement).
NOTE: Do not loosen tie rods on boiler absorption unit. They are intended to accommodate thermal expansion. Loss of boiler's structural integrity and water leaks/dam­age may result.
SECTION 2: BOILER INSTALLATION
PRESS. GAUGE
LOW WATER CUT-OFF
41"
2 1/2"
21"
14 3/4"
2" RETURN FRONT
MINIMUM CLEARANCES TO COMBUSTIBLES Top: 28" Rear: 18" Left & Right: 18" Front: ALCOVE
WATER
LINE
A
23 1/4"
18 1/4"
3/4" PLUGGED TAPPING
26 7/8"
2" RETURN REAR
18 1/8"
B
SPILL SWITCH
9 7/8"
16 1/2"
18 1/8"
21 7/8"
20"
BOILER MODEL
GB200-S-3 GB200-S-4L GB200-S-4H GB200-S-5
PRESSURE CONTROL
3"
2" STEAM SUPPLY
WATER LEVEL INDICATOR
1/2" PLUGGED TAPPING
23 1/4"
3 3/8"
2 3/8"
15 3/8" 18 7/8" 18 7/8" 22 3/8"
PRESS. RELIEF VALVE
GAS VALVE
6 3/4"
DIMENSIONS
A
B
5" 6" 6" 7"
ROLLOUT SWITCH
-LEFT SIDE VIEW- -FRONT VIEW- -RIGHT SIDE VIEW­PROBE LOCATION
FOR ELECTRIC
LWCO.
NOTE: OPTIONAL FLOAT LOW WATER CUT-OFF SHOWN.
23 7/8"
14 3/4"
2 1/2"
5
STEP 2: INSTALLING STEAM PIPING
Typical piping connections are shown in Figure 2.3. All exter­nal piping must be supported by hangers, not by the boiler or its accessories.
Supply outlet must run full size from the boiler to a header at least 24" above top of boiler. Condensate return piping should be connected to boiler through a "Hartford Loop." Install gate valves in supply and return. Proper steam piping practices must be followed at all times. Maintain proper clearances between piping and combustible material.
The supply and return lines should be equipped with drain cocks to drain sediment and sludge from lowest points of boiler.
STEP 3: INSTALLING HYDRONIC COMPONENTS
A low-water cutoff must be installed to protect the unit from dry fire.
Screw extension nipple into 3/4" tapping on top of the absorption unit and install relief valve into top of nipple with the spindle in the vertical position (i.e., with the valve dis­charge in the horizontal).
Most localities require the discharge piping to terminate with­in 6" of the floor. Check local code requirements if in doubt. Discharge piping must be of same size or larger than the relief valve outlet and should be run as short and straight as possible. Elbows in the discharge piping should be placed as close to the valve as possible. If valve discharge is to be drained away, the discharge piping must not be hard-piped to the drain piping (i.e., an open funnel or similar arrangement must be used).
CAUTION: Piping must be installed from the relief valve discharge so there will be no danger of scalding person­nel.
FIGURE 2.2: RECOMMENDED FIREPROOF BASE
FIGURE 2.3: TYPICAL STEAM BOILER PIPING
WARNING: Never install any type of valve between the boiler and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
6" OVERHANG OF BLOCKS AND SHEETMETAL ALL AROUND
6"
22 GAUGE SHEETMETAL
4" HOLLOW CLAY
TILE (TWO COURSES)
OPENINGS THRU BLOCKS
IN TOP COURSE TO
BE AT 90° ANGLE
TO OPENINGS THRU
BOTTOM COURSE
FLOOR
STEAM
SUPPLY
GATE VALVE
MUST BE CLOSE NIPPLE
HARTFORD LOOP
GATE VALVE
RETURN
DRAIN COCKS
RETURN TAPPING 2" NPT
COLD WATER FILL
SUPPLY TAPPING 3" NPT
12" MIN.
WATER LINE
C/L OF HARTFORD
LOOP TO BE 2"
BELOW WATER
23 1/4"
LINE
6
STEP 4: VENTING BOILER
A factory-mounted spill switch is provided on all GB200 boil­ers (see Figures 2.4 & 2.4A).
The flue or vent connectors must be installed flush with the inside chimney liner surface and sealed in place with furnace cement. Horizontal positions of the single wall and type B venting systems shall be supported by use of strap hangers or their equivalent. Vent supports should be placed a maxi­mum of 15 feet apart and as required to prevent sagging. The vent connectors shall be pitched 1/4" per foot upwards towards the chimney or vent termination.
Installing Vent Damper
The vent damper must be mounted directly on top of the draft diverter. The vent outlet extension must be installed between the damper and the outlet to allow the damper plate to open and close.
Locate the motor on the front side and position the cable so that it does not touch the metal surface of the draft diverter (see Figure 2.4). If necessary, turn angle connector on vent damper upward until cable clears; tighten locknut to secure. The direction of the flow arrow imprinted on the vent damper must point upward. The damper position indicator, which is located on the side of the vent damper opposite the motor, must be visible.
CAUTION: A minimum of 6" between vent damper and combustible materials must be maintained. The vent damper must be accessible for servicing and checking position indicator.
If applicable, remove hair pin shipping clip which holds damper blade in closed position and observe that damper blade rotates slowly to open position. Do not force it closed as it may damage the gear train and void the warranty. The blade should move freely and without obstruction.
Secure the vent damper housing to the draft diverter outlet with sheet metal screws or pop rivets. Refer to Figure 2.5 for fastener locations. Install flue pipe over top of vent damper and secure to damper housing with sheet metal screws or pop rivets.
Attach vent damper cable to cable clamp on boiler left panel and join the Molex connector (see Figures 2.4 & 2.4A).
DANGER: Draft diverter, vent outlet and vent damper as supplied must not be altered in any way, as proper boiler operation would be jeopardized. Flame rollout, fire or carbon monoxide poisoning will result.
DANGER: Only the boiler may be served by the vent damper. Do not attempt to use it to vent an addition­al appliance. This will cause fire or carbon monoxide poisoning.
FIGURE 2.4A: VENT DAMPER INSTALLATION
FOR STANDING PILOT
FIGURE 2.4: VENT DAMPER INSTALLATION
FOR INTERMITTENT PILOT
VENT DAMPER
PRESSURE
SPILL SWITCH
CABLE BRACKET
DK. BLUE
CONTROL
THERMOSTAT CONNECTION
TRANSFORMER
THERMOSTAT CONNECTION
PILOT CONTROL
VENT DAMPER
PRESSURE
SPILL SWITCH
CABLE BRACKET
DK. BLUE
CONTROL
THERMOSTAT CONNECTION
TRANSFORMER
GAS VALVE
THERMOSTAT CONNECTION
Loading...
+ 14 hidden pages