Installation and Maintenance Manual
VQ100 Series Solenoid Valve
This manual should be read in conjunction with the current valve catalogue.
For future reference, please keep this manual in a safe place
Safety Instructions
These safety instructions are intended to prevent a hazardous situation and/or equipment damage.These instructions indicate the level
of potential hazard by label of “Caution”,“Warning” or “Danger”.
To ensure safety,be sure to observe ISO4414
(Note1)
, JIS B 8370
(Note2)
and other safety practices.
Note 1: ISO 4414:Pneumatic fluid power – Recommendations for the
application of equipment to transmission and control systems.
Note 2: JIS B 8370: Pneumatic system axiom.
CAUTION : Operator error could result in injury or
equipment damage.
WARNING: Operator error could result in serious
injury or loss of life.
DANGER : In extreme conditions, there is a
possible result of serious injury or loss of life.
WARNING
1. The compatibility of pneumatic equipment is the responsibility of the person who designs the pneumatic system
or decides its specifications.
Since the products specified here are used in various operating
conditions, their compatibility for the specific pneumatic system
must be based on specifications or after analysis and/or tests to
meet your specific requirements.
2. Only trained personnel should operate pneumatically
operated machinery and equipment.
Compressed air can be dangerous if an operator is unfamiliar
with it.Assembly, handling or repair of pneumatic systems should
be performed by trained and experienced operators.
3. Do not service machinery/equipment or attempt to
remove component until safety is confirmed.
1) Inspection and maintenance of machinery/equipment should
only be performed after confirmation of safe locked-out
control positions.
2) When equipment is to be removed, confirm the safety process
as mentioned above.Switch off air and electrical supplies and
exhaust all residual compressed air in the system.
3) Before machinery/equipment is re-started, ensure all safety
measures to prevent sudden movement of cylinders etc.
(Bleed air into the system gradually to create back-pressure,
i.e. incorporate a soft-start valve).
4. Contact SMC if the product is to be used in any of the
following conditions:
1) Conditions and environments beyond the given specifica-
tions, or if product is used outdoors.
2) Installations in conjunction with atomic energy, railway, air
navigation, vehicles,medical equipment, food and beverage,
recreation equipment, emergency stop circuits, press
applications, or safety equipment.
3) An application which has the possibility of having negative
effects on people, property, or animals, requiring special
safety analysis.
CAUTION
Ensure that the air supply system is filtered to 5 micron.
Main parts (Fig 1)
No. Description Material Note
1 Solenoid coil ––
2 Body Resin
3 Fixed iron core SUS
4 Movable iron core assembly SUS · Resin
5 Return spring SUS
6 Poppet NBR
7 Philips/ordinary round head screw Carbon steel AXT632-7-3 (M1.7x14)
8 Interface gasket NBR AXT782-11
9 Subplate ZDC AXT662-1-1/2 (1: M5,2: M3)
Valve specifications
Specifications 1 wattage
specifications
0.5 wattage
specifications
Item 0.7 MPa 0.7 MPa
Type 3 port direct operated poppet type (NC)
Fluid Air · inert gas
Max. operating pressure 0.7MPa (8.2 kgf/cm2) 0.7MPa (7.1 kgf/cm2)
Min. operating pressure 0MPa (0 kgf/cm2)
Effective orifice PRA 0.28mm2(Cv 0.016) 0.14mm2(Cv 0.008)
ARR 0.36mm2(Cv 0.02) 0.20mm2(Cv 0.011)
Response time Note 1 ON: 3.5ms,OFF: 2ms ON: 3.5ms, OFF: 2.5ms
Ambient and fluid temperature -10~+50°C Note 2
Lubrication Not required
Manual override Non-locking recessed type/Locking tool type Note 3
Mounting orientation Free
Protection structure IP40
Weight 12.6g (L/M type connector,without subplate)
Note 1:As per JISB8375-1981 (with indicator light and surge voltage suppressor; clean air), dispersion accuracy ±1ms.
Note 2: Use dry air to prevent dew condensation when operating at low temperature.
Note 3: Locking type is optional specification.
Solenoid specifications
Specifications 1 wattage
specifications
0.5 wattage
specifications
Item 0.7 MPa 0.7 MPa
Coil rated voltage 24VDC, 12VDC
Allowable voltage ±10% of rated voltage
Type of coil insulation Class B
Power consumption 1WDC 0.5WDC
Electrical entry
Plug-in, L/M type connector
(with indicator light and surge voltage suppressor)
Installation
CAUTION
Ensure all air and power supplies are isolated before commencing
installation.
WARNING
DO NOT INSTALL THESE VALVES IN EXPLOSIVE ATMOSPHERES.
If these valves are exposed to water or oil droplets, ensure that the
valves are protected.
If it is intended to energise a valve for an extended period please
consult SMC.
Tube connections-push-in fittings (Fig 2)
Ensure that the end of the tube 6 is cut square.
Push the tube 6 firmly into the fitting 7 until it stops.
Pull back on the tube 6 to ensure it is correctly gripped.
Tube disconnection (Fig 2)
Push down on the collet flange 2, via the release button 4, hold
down, and withdraw the tube 6.
Connection of plug connector (Fig 3)
Push the connector, in a straight line,onto the pins of the solenoid,
ensuring that the lip of the lever is securely positioned in the groove
of the solenoid cover.
Disconnection of plug connector (Fig 3)
Press the lever against the connector and pull the connector away
from the solenoid.
CAUTION
Do not exert excessive force on the wires, as this may cause contact
failure.
Wiring specifications (Fig 4)
The lead wires are connected to the valve as shown below.Connect
each to the power supply side.
Solenoid manual override (Fig 5)
WARNING
Exercise extreme CAUTION when operating solenoid manual
overrides, as connected equipment will commence operation.
Push non-locking type
Push down on the manual button 1 (Fig 5) until it stops (ON).
Hold this position whilst carrying out function checks.
Release the manual override button and the override will re-set to the
OFF position.
Locking type manual override (Fig 5)
Turn the manual override clockwise through 180°,using a small slotted screwdriver,until the mark P lines up with the No. 1.
Push down on the button until the override locks (ON) position.
WARNING
In this position the manual override is mechanically locked ON.
Un-locking (Fig 5)
Turn the manual override anti-clockwise through 180°,using a small
slotted screwdriver until the mark Plines up with the No.0.
Remove the screwdriver and the manual override will re-set to the
(OFF) position.
Latching Type (Fig 5)
Locking (Fig 5)
Turn the manual override clockwise 180°using a small slotted screwdriver until the mark P lines up with the letter A.
Push the override button down until it locks in position (ON).
WARNING
In this position the manual override is mechanically locked in the ON
position.
Un-locking
Turn the manual override anti-clockwise through 180° until the mark
P lines up with the letter B.
Remove the screwdriver, and the Manual override will re-set to the
OFF position.
Indicator light and surge suppressor (Fig 6a)
In the latching type, A (set) side and B (re-set) side energisation are
indicated by two colours,which match the colours of the manual override buttons. See below (Fig 6a)
019A/ENG
Symbol
Fig 2
Fig 4
Fig 6a
Fig 1
Fig 3
Fig 5
Latching type specification
1 Guide
2 Collet
3 Chuck
4 Release button
5 Packing
6 Tube
7 Body
8 O-ring
9 Stud
DC positive COM
DC negative COM
SOL.
Latching solenoid type
Single solenoid type
Lead wire colour
(-) Black
(+)Red
(-) White
SOL.
Single solenoid type
Lead wire colour
(+)Red
(-) Black
Non-locking recessed type
Latching type
Locking recessed type
Locking tool type (option)
1
2
3
4
1
2
3
5
6
7
8
9
Cover
Cover
Groove
Groove
Pin
Pin
Lever
Connector
Connector
Simultaneously
energised
protection
circuit
set
COM.
reset
Latching solenoid type
Lead wire colour
(+)Red
(-) Black
(+)White
Simultaneously
energised
protection
circuit
set
COM.
reset
SOL.
Indicator light
• ON
: Orange
(Set)
• (Reset) : Green
Indicator light
• ON
: Orange
(Set)
• (Reset) : Green
M type plug connector
Note: Dotted line shows latching type
L type plug connector
1 3 4 5 7 2
6
8
9
Lead wire colour
(-) Black
(+)Red
Valve specifications
(A)
2
3
(R)1(P)
3
(R)1(P)
(A)
2