Copyright ©2010 SMC Networks 1
e
gaP
All Rights Reserved
I/M SMCSM01-Z rev. 1.0
8/19/10
1 Unpacking
Your SMCSM01-Z package includes the following items:
One SMCSM01-Z Smoke Sensor
One dust cover
Two CR123A batteries
Mounting bracket
This user manual
If any items are missing or damaged, contact your place of
purchase. Keep the carton, including the original packing
material, in case you need to
store or return the product.
2 Specifications
The SMCSM01-Z specifications are:
Voltage: 3VDC
Battery type1 3V Lithium, Duracell
®
123, Sanyo
®
, and
Panasonic® CR123A
Sensitivity 2.25 % ± 1.35 %
Drift compensation adjustment 0.5%/ft. max
Operating temperature: 40° to 100° F (4.4° and 37.8° C)
Compatible control panel: RB5701-Z SMA Gateway
The SMCSM01-Z specifications heat alarm specifications are:
Rate-of-rise: 15°F/min >105°F (8.3°C/min > 40.6°C)
Fixed: 135°F ± 5°F (57.2°C ± 2.8°C)
Note: Constant exposures to high or low temperatures or
high humidity may reduce battery life.
3 NFPA Guidelines
NFPA 72, 2-1.4.2.1 Total (Complete) Coverage
NFPA 72, 2-1.4.2.2 Partial Coverage
NFPA 72, 2-1.4.2.3 Selective Coverage
NFPA 72, 2-1.4.2.4 Supplementary (Non required)
Coverage
NFPA 72, 2-1.4.3
NFPA 72, 2-2 Heat-Sensing Fire Detectors
NFPA 72, 8-1.4.1.3.2 Detection in New Apartment
Buildings
NFPA 72, 8-1.4.1.4.2 Detection in Existing Apartment
4 Technical Bulletin
Pre-installation Considerations
continued on next page
SMCSM01-Z Smoke Sensor User Manual
Congratulations on purchasing your SMCSM01-Z Smoke Sensor.
The SMCSM01-Z Smoke Sensor is a low-profile wireless smoke detector designed to provide reliable smoke or fire detection. The SMCSM01-Z is ideal for
difficult-to-wire residential or commercial applications. This user manual has all the information to get your SMCSM01-Z Smoke Sensor up and running quickly.
If required, total coverage shall include all rooms, halls,
storage areas, basements, attics, lofts, spaces above
suspended ceilings, and other subdivisions and accessible
spaces; and the inside of all closets, elevator shafts, enclosed
stairways, dumbwaiter shafts, and chutes. Inaccessible areas
shall not be required to be protected by detectors. (For
exceptions, refer to NFPA 72.)
If required, partial detection systems shall be provided in all
common areas and work spaces, such as corridors, lobbies,
storage rooms, equipment rooms, and other tenantless spaces
in those environments suitable for proper detector operation
in accordance with this code.
Where codes, standards, laws, or authorities having
jurisdiction require the protection of selected areas only, the
specified areas shall be protected in accordance with this
code.
Where installed, detection that is not required by an
applicable law, code, or standard, whether total (complete),
partial, or selective coverage, shall conform to the
requirements of this code. (For exceptions, refer to NFPA 72
Chapter 2 Spacing Requirements.)
Where non required detection devices are installed for a
specific hazard, additional non required detection devices
shall not be required to be installed throughout an entire
room or building.
Heat-sensing fire detectors shall be installed in all areas
where required by the NFPA codes and standards or by the
authority having jurisdiction.
Approved, single-station smoke alarms shall be installed in
accordance with 7-6.2.10 of NFPA 101 outside every sleeping
area in the immediate vicinity of the bedrooms and on all
levels of the dwelling unit including basements. (101:
18-3.4.4.2) (For exceptions, refer to this section of NFPA 72.)
Buildings Approved, single-station smoke alarms shall be
in-stalled in accordance with 7-6.2.10 of NFPA 101 outside
every sleeping area in the immediate vicinity of the
bedrooms and on all levels of the dwelling unit including
basements. (101: 19-3.4.4.1) (For exceptions, refer to this
section of NFPA 72.)
SMCSM01-Z is a member of SMC Networks’ family of
reliable, high-quality products using the latest technology
available. Please review the information in this section to
ensure you get the most out of your new SMCSM01-Z Smoke
Sensor. The information in this guide is in accordance with
NFPA 72 and/or CAN/ULC-S524, depending on country of
installation.
Install the SMCSM01-Z in accordance with the National
Fire Protection Association’s (NFPA) Standard 72, Chapters
2 and 8. Depending on the application, you may need to
reference other chapters of NFPA 72 or NFPA 101.