SMC Networks SMCSD10-Z User Manual

Copyright ©2013 SMC Networks Page 1
All Rights Reserved
I/M SMCSD10-Z rev. 1.0 6/18/13
1 Product Introduction
The SMCSD10-Z meets FPA 72 field-sensitivity testing requirements without the need for external meters. Built-in drift compensation allows the SMCSD10-Z to adjust sensitivity automatically as it becomes dirty over time. The drift-compensation feature dramatically increases the time between cleanings, as well as reducing the chance of a nuisance alarm.
2 Parts List
Your SMCSD10-Z package includes:
(1) SMCSD10-Z Smoke Detector (2) CR123A lithium batteries (1) Mounting plate (1) Mounting screws and anchors (1) This User Guide
3 Tools Required
Flat-Tipped Screw Driver
4 Finding a Suitable Location
Review this section to ensure you get the most out of the SMCSD10-Z. This information is in accordance with NFPA 72 depending on country of installation.
Pre-installation Considerations
Install the SMCSD10-Z in accordance with the National Fire Protection Association’s (NFPA) Standard 72, Chapters 2 and 8. Depending on the application, you may need to reference other chapters of NFPA 72 or NFPA 101.
Choosing an Installation Location
When choosing an installation location, consider:
Use of structure and type of construction Contents you want to protect and their
burning characteristics
Human occupancy Total area to be monitored Ceiling height and surface condition Air movement and vent locations Obstructions Deflections
Recommended Locations
After considering these factors, choose a location:
Where the temperature range is between 40°
and 100° F (4.4° and 37.8° C).
Where the humidity is between 0 and 90%
non-condensing.
Away from ventilation sources that can
prevent smoke from reaching the smoke detector.
At least 5 feet (1.5 m) from bathrooms.
When placing the SMCSD10-Z on a ceiling, mount it in the center of the room or hallway at least 4 inches (10cm) away from any walls or partitions.
SMCSD10-Z S m o ke Detector Gui d e
Congratulations on purchasing your SMCSD10-Z Smoke Detector with Heat Detection Sensor.
The SMCSD10-Z Smoke Detector provides triple protection against fire. It combines a photoelectric smoke detector with an integrated heat detector that senses both fixed temperature and temperature rate-of-rise within a room.
SMCSD10-Z Smoke Detector Guide
Copyright ©2013 SMC Networks Page 2
All Rights Reserved
I/M SMCSD10-Z rev. 1.0 6/18/13
When mounting the SMCSD10-Z on a wall, place it so the top is 4 to 12 inches (10 to 31cm) below the ceiling.
In rooms with sloped, peaked, or gabled ceilings, place the SMCSD10-Z 3 feet (.9 m) down or away from the highest point of the ceiling.
If mounting to suspended ceiling tile, secure the tile with the appropriate fastener to prevent tile removal.
Smoke detectors are not to be used with alarm guards unless the combination has been evaluated and found suitable for that purpose.
Note: A smoke detector does not provide
warnings for fires resulting from explosions, smoking in bed or other furniture; ignition of flammable liquids, vapors and gasses; and children playing with matches or lighters.
Locations to Avoid
Areas where normal ambient temperature
exceeds 100° F (37.8° C).
Dirty, dusty, insect infested areas.
In or near areas with combustion particles
(kitchens, garages, furnaces, hot-water heaters, gas space heaters).
On the ceiling in rooms next to kitchens,
where there is no transom between the kitchen and such rooms.
Damp or humid areas, or near bathrooms
with showers.
Near fresh-air inlets or returns or very drafty
areas.
Near heating/air conditioning vents, fans,
and fresh air intakes, which can drive smoke away from the smoke alarm.
In dead-air spaces at the top of peaked
ceilings or in corners where walls and ceiling meet. Dead air can prevent smoke from reaching a smoke detector.
Within 10 feet (3 m) of fluorescent light
fixtures.
Not suitable for outdoor use.
WARNING! LIMITATIONS OF SMOKE DECTECTORS
The SMCSD10-Z Smoke Detector does not contain a built-in audio alarm. It is not intended for stand-alone use; it MUST be used with an approved Touchscreen.
Wireless smoke detectors are very reliable, but may not work under all conditions. No fire alarm product provides total protection of life or
property. Smoke detectors are not a substitute for life insurance.
Smoke detectors require a source of power to work.
This smoke detector does not operate and the alarm will not sound if batteries are dead or not installed properly.
This SMCSD10-Z relies on the Touchscreen Alarm to sound an audible alarm in case of fire. The alarm may not be heard. A sound sleeper or someone who has taken drugs or alcohol may not awaken if Touchscreen is installed outside a bedroom. Closed or partially closed doors and distance can block sound. This product is not designed for the hearing impaired.
Smoke detectors may not always activate and provide warning early enough. Smoke detectors only activate when enough smoke reaches the
product’s smoke chamber. If a fire starts in a
chimney, wall, roof, on the other side of closed doors, or on a different level of the property, enough smoke may not reach the product for it to alarm.
Smoke detectors are a significant help in reducing loss, injury and even death. However, no matter how good a detection device is, nothing works perfectly under every circumstance and we must warn you that you cannot expect a smoke detector to ensure that you will never suffer any damage or injury.
SMCSD10-Z Smoke Detector Guide
Copyright ©2013 SMC Networks Page 3
All Rights Reserved
I/M SMCSD10-Z rev. 1.0 6/18/13
Current studies show smoke detectors may not awaken all sleeping individuals. It is the responsibility of individuals in the household that are capable of assisting others to provide aid to those who may not be awakened by the alarm, or to those who may be incapable of safely evacuating the area unassisted.
5 Installing / Replacing Battery
The SMCSD10-Z comes with two 3V Lithium CR123A batteries preinstalled. When you need to replace them use the following procedure. Use batteries specified in this document specifications or as listed on the battery compartment cover. Use of a different battery can have a detrimental effect on the detector operation. Constant exposures to high or low humidity can reduce battery life.
A. Remove the SMCSD10-Z from the mounting
base (see section 7 of this guide). Slide the battery compartment cover away from the SMCSD10-Z to unsnap it and lift it off.
B. If you are replacing batteries, remove and
dispose of the batteries appropriately. Wait
30 seconds after removal before continuing to the next instruction.
C. Observing proper polarity as indicated in the
battery compartment, insert two new 3V lithium batteries into the SMCSD10-Z battery compartment and replace the battery compartment cover.
Note: Use two new batteries when replacing old
batteries. Do not replace with batteries that were used previously.
D. Reattach the SMCSD10-Z to the mounting
base and test the system.
E. The SMCSD10-Z ships with a dust cover for
protection on construction sites with dusty environments. If your product is new, remove the red plastic dust cover from the SMCSD10­Z.
6 Pairing with Touchscreen
Each SMCSD10-Z is programmed with a unique ID when manufactured. The unique ID is enrolled into the Touchscreen at the time of installation,
allowing the SMCSD10-Z to communicate with that specific Touchscreen.
A. At the Home screen, touch the Settings
widget.
B. When the Keypad screen appears, touch the
numbers to enter your keypad code.
C. At the Settings menu, use the keypad to
enter the Installer Code (this code is the same for all Touchscreen installed by your company).
D. At the Technician keyboard pad, enter your
Technician ID and touch Done.
E. At the Technician Settings menu, select
Sensors & Zones > Add a Sensor/Zone. The Locating Sensors screen appears.
F. Click Next. The system scans the premise for
wireless sensors that can be added, which must meet the following requirements:
- Not currently paired with another
Touchscreen.
- Is active. New sensors must be activated as
follows: Turn the back cover counter­clockwise to remove. Open the battery compartment. Removing the battery activation tab to power on the unit.
- Defaulted if previously paired. To default
the sensor, see section 9 of this guide.
G. Follow the system prompts to complete the
add process. Trip the sensor by pressing and holding down the Test Button on the front cover of the detector for 10 seconds.
SMCSD10-Z Smoke Detector Guide
Copyright ©2013 SMC Networks Page 4
All Rights Reserved
I/M SMCSD10-Z rev. 1.0 6/18/13
H. When all the sensors are found and paired,
tap Done. Any located sensors that were not paired are released by the Touchscreen and can be added later. The Wireless Sensors Located screen shows the number of wireless sensors found and paired.
I. Tap Next. The Configure Wireless Sensors
screen shows icons of the sensors that were found and paired.
J. Tap Next. The Add Sensor/Zone Modify
screen appears.
K. To modify a field on the Touchscreen, tap
the field. Use the onscreen keyboard to enter changes. Tap Next to save changes.
L. When all sensors are configured properly, tap
Return to Menu in the Configure Wireless Sensors screen.
M. If all sensors have not been configured, the
Modify screen appears for each sensor to let
you review its details. Change the details as needed or tap Next to cycle through all the sensors. The sensors are marked as configured.
7 Mounting the Sensor
The following procedure describes how to mount the SMCSD10-Z. Add the SMCSD10-Z to the Touchscreen before physically mounting it in the desired location.
A. Test communications between the
Touchscreen and the SMCSD10-Z as follows before permanently mounting the SMCSD10­Z:
- Hold the SMCSD10-Z where you plan to
install it.
- Press the SMCSD10-Z Test button for 10-to-
15 seconds. The SMCSD10-Z sends a signal to the Touchscreen.
- At the Touchscreen, verify the signal was
received. A message will appear in the upper right corner of the Touchscreen for 5 seconds. If no signal is received relocate the SMCSD10-Z and retest.
B. Using two supplied screws and anchors,
mount the base.
C. Attach the SMCSD10-Z to the mounting base
as follows:
- Line up the raised alignment tab on the lip
of the SMCSD10-Z with the arrow on the mounting base.
- Insert the SMCSD10-Z into the base and
turn clockwise about 15 degrees until it snaps into place.
Note: The SMCSD10-Z cannot be attached to the
mounting base if no batteries are installed.
D. Test communications between the
Touchscreen and SMCSD10-Z again:
- Press the Test button on the detector for
10-to-15 seconds. The SMCSD10-Z sends a signal to the Touchscreen.
- Verify that the signal at the Touchscreen
was received.
E. Test the SMCSD10-Z (see “Testing the
SMCSD10-Z” on page 5).