Smart temp SMT-110 User Manual

Page 1
Smart Temp Model SMT-110 Digital Thermostat
A. Installation, Mounting:
CAUTION:
2. The installer must be a trained HVAC service technician.
1. Installation Location
The thermostat should be mounted on an inner wall 1.5m above the floor in a position where it is readily affected by changes of general room temperature with freely circulating air. Prevent direct exposure to sunlight. Do not place this unit at a location where air circulation is low or where there is great temperature changes (e.g. near door). Do not place the thermostat near any heat generating sources (hot air vents, TV or lights).
2. Wiring
TheSMT-110 has 6 terminals at the back of the thermostat which are labeled
as “C”, “Y” and “G”, “RC”, “R” and “O/W B”.
Different wirings are for different Mode types.
“C” Terminal is optional for 24Vac Powered
Mode type 1 (HO) : Two wire Heat only
Mode type 2 (HF) : Three wire Heat only
Mode type 3 (CL) : Three wire Cool only
Mode type 4 (HP) : Four wire Single Stage Heat Pump:
Mode type 5 : Single Transformer Heat/Cool System
Mode type 5 : Two Transformer Heat/Cool System
3. Mounting:
1. Ensure that the surface is level.
2. Place the cables at the hole near the terminal block.
3. Insert 2 pcs of wall anchors into the holes of the wall.
4. Fasten the thermostat with 2 pcs of long screws through the 2 mounting holes.
B. Start/Reset:
1. When the system is reset, all the LCD segments is ON and the
measured temperature will be displayed after a while.
2. Low Battery Check will be done at startup.
will be shown
battery is low
3. Output will be turned off at startup
C. Normal Display Mode:
1. Temperature detection starts and LCD displays the room temperature.
2. In Heat or Auto Mode, defrost function is activated with displayed when temperature is below 5
°C/ 40F. Heater is on
regardless of the setting temperatures
3. Below 0
°C/ 32°F, SMT-110 will display LO.
4. Above 40
°C/ 99°F, SMT-110 will display HI.
5. Press <Up>/ <Down> to adjust Heat/ Cool setting temperature
6. Press <Mode> to select Heat/ Cool/ Auto/ Off Mode
7. Press <Fan> to select Fan On/ Auto
D. Temperature Setting Display Mode:
To adjust Heat/ Cool setting
1. Press <Up> or <Down> keys to adjust Heat/ Cool setting temperature in Normal Display Mode.
2. Heat/ Cool setting temperature flashes.
3. In Heat Mode, only Heat setting temperature can be adjusted.
4. In Cool Mode, only Cool setting temperature can be adjusted.
5. In Auto Mode, Heat and Cool setting temperature can be adjusted
6. In Off Mode, no setting temperature can be adjusted.
7. Press <Mode> key to exchange the Heat and Cool setting temperature in Auto Mode.
8. The operation will resume to Normal Display Mode if no key is pressed for 10 sec.
E. Internal Mode Setting Display:
To adjust the internal setting of SMT-110:
Mode Type Selection
1. Press and hold <Mode> and <Up> keys for 2 sec.
2. LCD changes to the display of Mode type selection.
<Up> key
<Down> key
<Mode> key <Fan> key
Optional
Page 2
3. The letters represent Mode type.
4. Press <Up>/ <Down> to adjust Mode type.
5. Press <ENT> to select Mode type and return to Normal Display Mode.
Function Setting Selection
1. Press and hold <Fan> and <Down> keys for 2 sec.
2. LCD changes to the display of Function setting selection.
3. The left letters represent Function type; the right letters represent Setting.
4. Press <Up>/ <Down> to adjust Function type/ Setting.
5. Press <NEXT> to select Function type/ Setting.
6. Press <ENT> to return to Normal Display Mode. Description of the Mode types:
1. Heat only Heat Only Mode can be used for normal-open or normal -close valves. Fan cannot be selected.
2. Heat with fan Heat Only Mode with Fan Selection.
3. Cool Cool Only Mode with Fan Selection.
4. Heat Pump Heat/ Cool/ Auto Mode can be selected with changeover valve (reversing Valve). (**While in Auto Mode, there is a Heat/Cool switching delay of 4 minutes for switching a heating system to cooling system or vice versa. During the period, neither Heater / Cooler nor Fan will turn on.)
5. Electric / gas heat with cool
Heat/ Cool/ Auto Mode can be selected. ( Default Setting)
Table of the Internal Setting: Mode type Function type Setting
HO
Heat only
HS Span of Heater
1C / 2F 2C/ 4F
dU Temperature Display Unit
C F
HF Heat with fan
HS Span of Heater
1C/ 2F 2C/ 4F
dU Temperature Display Unit
C F
FC Fan Control Method
O
Gas Heater– equipment controls fan
E
Electric furnace – thermostat controls fan
CL Cool
dU Temperature Display Unit
C F
CS Span of Cool
1C/ 2F 2C/ 4F
Cd
Compressor Minimum-Off Delay
1 1 minute compressor off delay 2 2 minute compressor off delay 3 3 minute compressor off delay 4 4 minute compressor off delay 5 5 minute compressor off delay
HP Heat pump
HS Span of Heater
1C/ 2F 2C/ 4F
CO Changeover Valve
C
O/B terminal energized in cooling (default)
H O/B terminal energized in heating
dU Temperature Display Unit
C F
CS Span of Cool
1C/ 2F 2C/ 4F
Cd
Compressor/ Heater Minimum-Off Delay
1 1 minute compressor off delay 2 2 minute compressor off delay 3 3 minute compressor off delay 4 4 minute compressor off delay 5 5 minute compressor off delay
SL Mode Adjustment
1 Heat, Cool, Off Selectable 2 Auto, Off Selectable 3 Heat, Cool, Off, Auto Selec table
HC
Electrical /gas heat with cool (Default setting)
HS Span of Heater
1C/ 2F (Default setting) 2C/ 4F
dU Temperature Display Unit
C (Default setting) F
CS Span of Cool
1C/ 2F (Default setting) 2C/ 4F
Cd
Compressor Minimum-Off Delay
1 1 minute compressor off delay 2 2 minute compressor off delay 3 3 minute compressor off delay
4
4 minute compressor off delay (Default setting)
5 5 minute compressor off delay
SL Mode Adjustment
1 Heat, Cool, Off Selectable 2 Auto, Off, Selectable
3
Heat, Cool, Off, Auto Selectable (Default setting)
FC Fan Control Method
O
Gas furnace – equipment controls fan
E
Electric furnace – thermostat controls fan (Default setting)
F. Replaceable Batteries Instruction
Batteries shall be installed with proper polarity and correct battery type.
Do not use old and new batteries simultaneously. Batteries shall be removed if consumed or if product is
to be left unused for a long time. Use 1.5V/ cell ALKALINE batteries 2 pieces.
G. Specification:
1. Temperature Measurement: 0C~40C/ 32F~99F
2. Accuracy: ±0.5C/ 1°F
3. Temperature Controllable Range: Heat/ cool Mode: Heat/Cool Setting: 5C~35C/ 40F~95F Auto Mode: Heat Setting: 5C~30C/ 40F~85F Cool Setting: 10C~35C/ 50F~95F
4. Resolution: 0.5C/1°F
5. Power Supply: 24V~ +/-10% or 2 x AAA alkaline
batteries
6. Rating: 24V~ 50/ 60Hz 1A max
7. Terminals: 2mm
2
cable
8. Operating Temperature: 0~50°C/ 32~122 °F
9. Storage Temperature:
-5~50°C/ 23~122 °F
10. Sensing Element: NTC thermistor
Due to continual product improvement these specifications are subject to change without notice.
Warranty – One Year Return to Base.
Smart Temp Australia Pty Ltd Unit 20, 1488 Ferntree Gully Road Knoxfield Vic 3180
Tel (03) 9763 0094
www.thermostat.com.au
130508
<Up> key
<Down> key
<ENT> key
Mode Type
<Up> key
<Down> key
<ENT> key
Function type
<NEXT> key
Setting
Loading...