2.1Nominal Voltage .............................................................................................................................................4
2.3.1Disconnection due to Undervoltage ...............................................................................................................4
2.3.210-Minute Average Value...............................................................................................................................5
2.3.3Disconnection due to Overvoltage .................................................................................................................5
2.6.2Reconnection Time ...........................................................................................................................................7
2.6.4Time to Alarm ...................................................................................................................................................7
2.6.5Voltage and Frequency Connection Limits .....................................................................................................7
3.1Active Frequency Shift.....................................................................................................................................7
3.3Rate of Change of Frequency.........................................................................................................................8
4Settings of Grid Management Services: Fault Ride-Through (FRT) ..........................................9
5Settings of Grid Management Services...................................................................................... 12
5.2.1Start Signal ....................................................................................................................................................... 15
5.2.3Time Delay Until Disconnection....................................................................................................................... 15
5.2.4Reactive Power Ramp Rates ............................................................................................................................ 15
5.2.5Active Power Ramp Rates................................................................................................................................ 16
5.2.6Setting the Maximum Active Power ................................................................................................................ 16
5.2.7Setting the Reactive Power .............................................................................................................................. 16
5.2.8Setting the Power Factor (PF) .......................................................................................................................... 16
5.2.9Setting the Apparent Power............................................................................................................................. 16
• STP60-10 (SunnyTripower60) from software version 1.80
• STP 60-JP-10 (SunnyTripower 60) from software version 1.80
• SHP 75-10 (SunnyHighpowerPeak1) from software version 1.90
• SHP 75-JP-10 (SunnyHighpowerPEAK1) from software version 2.0
This document is intended to help the user get a better understanding of the functionality of the inverter. The
descriptions refer to the parameter IDs which can also be found in the "Settings report".
The value ranges indicated in the following sections do not necessarily refer to the permissible ranges in accordance
with the applied standards, but are to reflect the performance of the inverter. All adjustable parameters have the same
indicated ranges and increments. Since not all parameters are used by all standards, the parameters that are not used
will be deactivated in the file "Inverter settings".
2Grid Protection Settings
The following parameters for grid connection settings are saved in the inverter and only used here. The settings are
divided into groups. The groups reflect the various grid management services.
All requirements for grid protection settings are set at the inverter connection point.
2.1Nominal Voltage
This parameter refers to the nominal grid voltage of a country. In most countries, only one official grid voltage is valid.
For countries with several official grid voltages, additional grid codes are provided so that the user is able to set the
grid voltage requested by the grid operator.
Parameter nameSetting range
UNOM220Vac to 277Vac (L-N)
2.2Nominal Frequency
The nominal frequency can either be 50Hz or 60Hz, and for the most part only one of the two is used. For countries
where both frequency values are used, additional grid codes are provided so that the user is able to set the nominal
frequency requested by the grid operator.
Parameter nameSetting range
FNOM50Hz or 60Hz
2.3Voltage-Dependant Disconnection
2.3.1Disconnection due to Undervoltage
The undervoltage disconnection capability has two parameters in a set, the first parameter is the magnitude, which is
given in voltage, the second is the trip time, which is given in seconds. Undervoltage disconnection works in the way
that in case of grid failure below the value stated in UMIN, the inverter stays connected to the grid for the time period
stated in T_UMIN. After this time has elapsed, the inverter must disconnect from the utility grid. Depending on the
applied standard, these two values can either be a maximum, minimum or mean value. Refer to the relevant standard
to see which of the three key values is used in your file.
The ten-minute average value is defined in the standard EN50160 as maximum threshold for a continuous high
voltage in the grid. If this value is exceeded, the inverter is disconnected from the utility grid.
Parameter nameSetting rangeStep size
U10M_AVGUNOM to 350Vac (L-N)0.1 Vac (L-N)
T_U10M_AVG0.05s to 90.0s0.01s
2.3.3Disconnection due to Overvoltage
The overvoltage disconnection function has two related values: the first value indicates the voltage level in volt, the
second value indicates the tripping time in seconds. Overvoltage disconnection works in the way that if the grid
voltage exceeds the value stated in UMAX, the inverter stays connected to the grid for the time period stated in
T_UMAX. After this time has elapsed, the inverter must disconnect from the utility grid. Depending on the applied
standard, these two values can either be a maximum, minimum or mean value. Refer to the relevant standard to see
which of the three key values is used in your file.
Parameter nameSetting rangeStep size
UMAXUNOM to 350Vac (L-N)0.1 Vac (L-N)
T_UMAX0.05s to 90.0s0.01s
2.4Manual Restart
With the function Manual Restart, you can configure whether the inverter is to revert to feed-in operation automatically
after the fault has occurred, or whether feed-in operation should remain interrupted until it is manually reactivated.
2.4.1Activating Manual Restart
The parameter RST_MOD activates the manual restart. A value of 1 causes that the user must start the inverter after a
grid fault. A value of 0 causes that the inverter reverts to feed-in operation automatically after the grid fault has been
rectified.
Parameter nameSetting option
RST_MODon (1), off (0)
2.4.2Events Causing Grid Faults
The following events cause the inverter to interrupt feed-in operation and that the feed-in operation must be activated
through manual restart.
• Overvoltage
• Undervoltage
• Active islanding detection
• Passive islanding detection
• Overfrequency
• Underfrequency
If one of the parameters is set to value 1 and a corresponding grid fault occurs, a specific event is generated and the
inverter interrupts the feed-in operation until it is restarted manually.
The underfrequency disconnection function has two related values: the first value indicates the frequency level in Hertz,
the second value indicates the tripping time in seconds. Underfrequency disconnection works in the way that if the grid
frequency drops below the value stated in FMIN, the inverter stays connected to the grid for the time period stated in
T_FMIN. After this time has elapsed, the inverter must disconnect from the utility grid. Depending on the applied
standard, these two values can either be a maximum, minimum or mean value. Refer to the relevant standard to see
which of the three key values is used in your file.
Parameter nameSetting rangeStep size
FMIN45Hz to FNOM0.01 Hz
T_FMIN0.05s to 90.0s0.01s
2.5.2Disconnection due to Overfrequency
The overfrequency disconnection function has two related values: the first value indicates the frequency level in Hertz,
the second value indicates the tripping time in seconds. Overfrequency disconnection works in the way that if the
power frequency exceeds the value stated in FMAX, the inverter stays connected to the grid for the time period stated
in T_FMAX. After this time has elapsed, the inverter must disconnect from the utility grid. Depending on the applied
standard, these two values can either be a maximum, minimum or mean value. Refer to the relevant standard to see
which of the three key values is used in your file.
Parameter nameSetting rangeStep size
FMAXFNOM to 66Hz0.01 Hz
T_FMIN0.05s to 90.0s0.01s
2.6Connection, Reconnection and Disconnection
2.6.1Connection Time
The connection time is the time period of grid monitoring between start of the inverter and start of grid feed-in.
If a fault on the grid makes the inverter disconnect and the grid then afterwards stabilizes within the allowed voltage
and frequency ranges, then the inverter is allowed to reconnect to the grid with this time delay. The reconnection time
is usually shorter than the connection time, but it can also be the same time or longer than the connection time.
Parameter nameSetting rangeStep size
T_RECON0s to 1800s0.01s
2.6.3Short Interruption Time
The short interruption time is the permissible time period after which the inverter must start the complete reconnection
procedure. If the grid fault is remedied in a shorter time period, the inverter can reconnect to the utility grid after the
reconnection time T_RECON.
Parameter nameSetting rangeStep size
T_SHT_INT0s to 1800s0.01s
2.6.4Time to Alarm
Time to alarm is the period which the inverter must wait before generating an alarm event. This is to prevent the inverter
from generating alarm events all the time.
Parameter nameSetting rangeStep size
T_ALARM0s to 1800s0.01s
2.6.5Voltage and Frequency Connection Limits
The minimum and maximum connection limits for voltage and frequency define the value range in which the inverter
can connect to the utility grid.
Parameter nameSetting rangeStep size
UMIN_CONUMIN1 to UNOM0.1V
UMAX_CONUNOM to UMAX10.1V
FMIN_CONFMIN1 to FNOM0.01 Hz
FMAX_CONFNOM to FMAX10.01 Hz
2.6.6Ramp-In
The ramp-in factor describes the ramp for the power up of the inverter. More details can be found in the settings for
grid management services under parameter Connection/reconnection ramp rate.
3Grid Failure
3.1Active Frequency Shift
The active frequency shift works in the way that if the grid becomes unstable for any reason, this function then helps to
push the grid even more of balance so that the inverter disconnects due to RoCoF or one of the regular disconnection
parameters.
The phase failure detection is used to determine the failure of one or more line conductors of the utility grid. In case of
a grid failure, the grid relays open.
Parameter nameSetting options
OPEN_PH_DETECTon (1)
off (0)
The ramp-in factor describes the ramp for the power up of the inverter. More details can be found in the settings for
grid management services under parameter Connection/reconnection ramp rate.
3.3Rate of Change of Frequency
The parameter RoCoF or Rate of Change of Frequency measures the change in frequency. If the change in
frequency exceeds the stated maximum limit for a longer period of time, the inverter disconnects from the utility grid.
The frequency can change very rapidly if one or several line conductors fail.
4 Settings of Grid Management Services: Fault Ride-Through (FRT)
4Settings of Grid Management Services: Fault Ride-Through (FRT)
The inverter is equipped with the Fault Ride-Through function for both undervoltage (LVRT) and overvoltage (HVRT/
OVRT) situations. Although the FRT function belongs to grid management services, it is stored in the inverter. The FRT
function is set to cope with voltage dips down to 0% UNOM without time limit. This is confirmed in the FRT
performance test which was manually stopped after 60 seconds (see figure 1).
Figure 1: The FRT function of the inverter has been tested at 60 kW and three-phase voltage dips down to 80% UNOM, 50% UNOM, 20%
UNOM, 5% UNOM. The performance test was manually stopped after 60 seconds.
The parameter FRT_MODE is used to set the FRT operating mode for current feed-in. There are six selectable
operating modes.
4 Settings of Grid Management Services: Fault Ride-Through (FRT)
SMA Solar Technology AG
For reactive power feed-in, the positive and negative sequence components are considered separately. The half-cycle
root-mean-square values of the positive and negative sequence components of the grid voltage during the grid fault
are compared with the average root-mean-square values before the fault. The relevant time frame for the average
voltage before the grid fault can be set via the parameter FRT_T_U_AVG (default 10 minutes). Figure 2 shows the
functionality of the parameter FRT_T_U_AVG.
Figure 2: FRT voltage average as a function of time (IEC61850-90-7)
The voltage differences (DeltaU_pos and DeltaU_neg) are passed through one of the following Iq(V) characteristic
curves. The choice of the characteristic curve depends on parameter FRT_IQ_MODE (default: 0).
Figure 3: FRT_IQ_MODE = 0: as per BDEW (IEC 62850-90-7)
Figure 4: FRT_IQ_MODE = 1: as per SDLWind (IEC 62850-90-7)
4 Settings of Grid Management Services: Fault Ride-Through (FRT)
In both operating modes, there is a common set of parameters which have to be set for the FRT functionality to work
properly:
1. The deadband is defined by two thresholds: the lower threshold FRT_ULOW and the upper threshold FRT_UUP.
2. For the positive sequence component, the gradient K for the slope of voltage dips is defined by
FRT_DIDU_POS_LVRT and for the slope of voltage increase by FRT_DIDU_POS_HVRT.
3. For the negative sequence component, the gradient K for the slope of voltage dips is defined by
FRT_DIDU_NEG_HVRT and for the slope of voltage increase by FRT_DIDU_NEG_HVRT.
The additional reactive current is added to the pre-fault reactive current value.
The positive sequence components have priority over the negative sequence components. Thus, first the negative
sequence component is limited if the current limitation is reached. In case that Id has higher priority than Iq, the reactive
currents will be limited in such way as the total current does not exceed the limit.
After fault clearance, reactive current feed-in stays active for a certain transition period. This period can be set with the
grid code parameter FRT_T_TRANS.
Active current is fed in under the following conditions:
1. Active current feed-in is activated in accordance with the selection made in FRT_MODE (operating modes 3, 4,
and 5).
2. The current reactive power value allows additional active current without the total current being greater than the
nominal current.
3. There is enough primary input power.
Restriction: active power feed-in during fault is upwards limited to the pre-fault active power, even if higher primary
input power is (or becomes) available during the fault.
After the fault, the active power returns to its initial level with first order dynamic. The recovery time can be set via the
parameter FRT_T_P_RECOV.
If required, it is possible to set up a so-called blocking zone during the grid fault: if the voltage falls below a
configurable limit FRT_U_BLK, power generation is ceased after a configurable time FRT_T_BLK. Over the blocking
zone FRT_U_BLK there is the hysteresis band determined by FRT_U_BLK_HYS. Once voltage exceeds this hysteresis
band again, power generation is continued.
FRT_MODE0: Frt_OffThe FRT function is deactivated.
1: Frt_ZeroCurrentNo current feed-in
2: Frt_ReactiveOnlyReactive current is fed in, but no ac-
tive current.
3: Frt_ActiveOnlyActive current is fed in, but no reac-
tive current.
4: Frt_Full_IqPriorityThe reactive current is fed in. If PV
power is available, the total current is
supplied with active current until current limitation is reached.
5: Frt_Full_IdPriorityThe maximum possible active current
is fed in. Starting from the grid code
characteristic curve, the total current
is supplied with reactive current until
the current limitation is reached.
SMA Solar Technology AG
FRT_DIDU_POS_LVRT1 to 100.1
FRT_DIDU_POS_HVRT1 to 100.1
FRT_DIDU_NEG_LVRT1 to 100.1
FRT_DIDU_NEG_HVRT1 to 100.1
FRT_IQ_MODE0 or 1-
FRT_T_BLK0s to 10s0.01s
FRT_T_TRANS0s to 10s0.01s
FRT_T_U_AVG0s to 1800s1s
FRT_U_BLK0% to 100%1%
FRT_U_BLK_HYS0% to 100%1%
5Settings of Grid Management Services
The following parameters for grid management services are loaded to the SMAInverterManager(IM) and only used
here. The settings are divided into groups. The groups reflect the various grid management services (control modes).
The value ranges indicated in the following sections do not necessarily describe the permissible ranges in accordance
with the grid code, but are to reflect the performance of the inverter. Since not all parameters are used by all
standards, the parameters that are not used will be deactivated in the file "Grid Code".
Regarding the signs for reactive power and power factor (PF), plus means overexcited reactive power (grid voltage is
increased) and minus means underexcited reactive power (grid voltage is reduced).
All requirements for grid management services are given for the point of common coupling (PCC).
Figure 5: Overview of a system with inverters, SMAInverterManager, local load, power meter and definition of Point of Common Coupling
(PCC).
5.1Default Settings
5.1.1Selecting the Control Modes for Reactive Power Provision
Reactive power references can either be given as a direct reference for reactive power (Q) or as an indirect reference
via the power factor (PF). The references are based on the following control modes (setting options), can be set with
the number 1 to 9 in the parameter ModeSelect.
Parameter nameSetting optionExplanation
ModeSelect1Q(U) - Reactive Power as a Function of Grid Voltage
2Q(P) - Reactive Power as a Function of Active Power
3Q(S) - Reactive power as a function of apparent power
4Control mode is in implementation phase
5Q(ext) - Reactive power as a function of an external setpoint (default)
6PF(U) - Power Factor as a Function of Grid Voltage
7PF(P) - Power Factor as a Function of Active Power
8Control mode is in implementation phase
9PF(ext) - Power factor as a function of an external setpoint
The system with an inverter provides reactive power also in night mode. Therefore, the inverters are not switched off
after sunset. Information: If no primary energy source is available, only the control modes 1 to 5 can be used for
reactive power provision.
In the inverter, no switch-on circuit is installed. Thus, the inverter cannot start-up / reconnect to the grid after a voltage
dip when no DC-voltage is present. The voltage of the DC busbar is directly connected to the PV arrays at night. Thus,
current can flow in the arrays. This can only be prevented via one of the following measures: using string diodes in the
DC String-Combiner or using a controllable switch in the DC String-Combiner.
Parameter nameSetting optionExplanation
NightMode0Deactivated (Default)
1Activated
5.1.3Active Power Limitation for Reactive Power Feed-In
Some grid codes require that the PV system can also be operated during feed-in of nominal reactive power at nominal
active power. Example: A PV system is required to have a controllable power factor (PF) between ±0.9 and 1.0
without affecting the generation of active power. Thus, the nominal active power is no longer 100% but rather 90% so
that the parameter P_LIM_IF_Q should be set to 90%.
Parameter nameSetting option
P_LIM_IF_Q80% to 100% (default: 100%)
5.1.4Nominal Apparent Power at Point of Common Coupling (PCC)
All grid management services in the inverter are based on the nominal apparent power at the point of common
coupling. Example: At an active power limitation to 50%, the active power at the point of common coupling is limited
to 50% by Sgrid_nom. The default value is "blank" meaning that the PV system uses the sum of apparent power from
the commissioned inverters. In some cases the installed power of the PV system is higher than agreed upon with the
distribution grid operator. Thus, the Sgrid_nom parameter should be set according to the contract clauses. In cases
where the PV system is installed to supply local loads (this requires an external power meter) and no active power is
allowed to be fed into the grid, the Sgrid_nom parameter should be left "blank" and the parameter P_ref should be
set to 0%.
Parameter nameSetting option
Sgrid_nomblank, 0kVA to 4000kVA (default: blank)
5.1.5Voltage Differences Between the Point of Common Coupling (PCC) and the
PV System
This parameter serves to compensate for possible voltage differences on the cables between the inverters and the PCC
and is called up in the case where voltage-based control modes are used, i.e. Q(U), PF(U) and P(U). Thus, only a
single characteristic curve is required for different PV systems and only the parameter UNOMOffset (line to line
voltage) needs to be set for each PV system.
Parameter nameSetting option
UNOMOffset0, generally between ±10 V for low-voltage grids and
This parameter refers to the nominal grid voltage at the point of common coupling. The parameter is used to scale the
grid voltage for the control modes where the grid voltage is the independent variable, i.e. for Q(U), PF(U) and P(U). If
no external energy meter is used, this parameter should have the same value as UNOM in the protection part of the
grid code file. This also applies if an external energy meter is switched on the low-voltage (LV) side of the transformer.
If an external power meter is connected to the medium-voltage (MV) side of the transformer, the corresponding
nominal values for the grid voltage must be set, e.g. 33 kV.
Parameter nameSetting option
UNOM_LL200V to 480V (default: 398V) for low-voltage grids
and 3300V to 33000V for medium-voltage grids
5.2Direct Control
5.2.1Start Signal
The PV system can be disconnected immediately from the grid or it can be set that it connects to the grid once the grid
parameters (voltage level and frequency) are within the permissible range for connection (see Section2 "Grid
Protection Settings", page4).
Parameter nameSetting optionExplanation
ReleaseToStart0Immediate disconnection
1Connection when grid parameter is in the permissible range (default)
5.2.2Connection/Reconnection Ramp Rate
The active power is ramped according to this setting whenever the inverter is connected / reconnected to the grid, i.e.
when starting up in the morning, when starting up after the parameter ReleaseToStart is set to 1 and after
disconnection due to overvoltage or undervoltage, overfrequency or underfrequency etc.
Parameter nameSetting rangeStep size
RmpIncTmm_ONLINE0.6%/min to 1200%/min (default:
10%/min)
0.1%
5.2.3Time Delay Until Disconnection
Controlled disconnection over the defined time period, this means the power will be ramped down in a controlled
manner over the delay period.
Parameter nameSetting rangeStep size
T_DELAY_SHUTDOWN0s to 600s (default: 2s)0.2s
5.2.4Reactive Power Ramp Rates
The reactive power is ramped according to this setting whenever the setpoint for reactive power is changed (both for
external setpoints and for other control modes, e.g. Q(U) or PF(P)). Note that two parameters are available: one for
decreasing and one for increasing setpoints.
The active power is ramped according to these setting whenever the external setpoint for active power is changed.
Note that two parameters are available: one for decreasing and one for increasing setpoints.
Parameter nameSetting rangeStep size
RmpDecTmm_EXT-0.6%/min to -1200%/min (default)0.1%
RmpIncTmm_EXT0.6%/min to 1200%/min (default)0.1%
5.2.6Setting the Maximum Active Power
The active power is limited according to this parameter.
Parameter nameSetting rangeStep size
P_ref0% to 100% (default)0.1%
5.2.7Setting the Reactive Power
This parameter indicates the reactive power setpoint (only available if control mode 5 has been selected in the
parameter ModeSelect).
Parameter nameSetting rangeStep size
Q_ref0% to ±100% (default: 0%)0.1%
5.2.8Setting the Power Factor (PF)
This parameter indicates the setpoint for the power factor (PF) (only available if control mode 9 has been selected in
the parameter ModeSelect).
Parameter nameSetting rangeStep size
PF_ref0.8 to 1.0 for overexcitation
-0.8 to -1.0 for underexcitation (default)
0.01
5.2.9Setting the Apparent Power
Some grid codes require that the PV system always generates a certain amount of apparent power, i.e. the system
operates within a unit circle in the PQ diagram. If the parameter S_ref is set to 60%, the PV system does not generate
reactive power until the active power is above 60%. However, if the active power is lower than 60%, the PV system
starts to generate reactive power to keep the apparent power at 60%. If the sign is positive, the PV system will
exchange overexcited reactive power. If the sign is negative, the system will exchange underexcited reactive power.
This type of control mode should not be used when a local load is connected, since it could cause the PV system to
lower the production of active power (only available if control mode 3 has been selected in the parameter
The general approach for the control modes is based on the structure in the technical report of the standard
IEC61850-90-7 (see the figure below).
Up to five parameters are used to program the local modes depicted above. The parameter RmpTmsPT1 is the rise
time from 0% to 95% (equal to 3τ) for the low-pass filter applied on the independent variable (e.g. grid voltage). The
reference table is made of two characteristic curves each containing up to ten break-points. One characteristic curve is
used when the independent variable is increasing and the other when decreasing. In this way, hysteresis can be
included in the reference table. Finally, the parameters RmpIncTmm and RmpDecTmm are the ramp rates for
increasing and decreasing output values (dependent variable) from the reference table.
Independent ramp rates are only available for control modes for active power, whereas for reactive power the ramp
rates are always given by the parameters RmpDecTmm_Q and RmpIncTmm_Q. If the input value (independent
variable) of the reference table exceeds the values defining the characteristic curves, the output value (dependent
variable) of the reference table is given as the first or last value in the characteristic curve respectively.
5.3.1Q(U) - Reactive Power as a Function of Grid Voltage
This control mode uses the grid voltage to generate a reference value for the reactive power so that the grid voltage
can be controlled at the point of common coupling. The control mode contains two additional parameters for
activation. The mode is activated when the active power is above the set threshold and deactivated again when the
active power is below the set threshold. The threshold for activation must be larger than or equal to the threshold for
deactivation. If this control mode shall always be available, set lock_in_UQ = lock_out_UQ = 0% (only available if
control mode 1 has been selected in the parameter ModeSelect).
Parameter nameSetting rangeStep size
RmpTmsPT1_UQ0.6s to 3600s0.01s
lock_in_UQ0% to 100% of active power0.1%
lock_out_UQ0% to 100% of active power (must be smaller than lock_in_UQ)0.1%
Q_of_UU: Grid voltage (independent values) from 80% to 120% of nominal
voltage
Q: Reactive power (dependent values) from -100% to 100% of nominal power
-
-
5.3.2Q(P) - Reactive Power as a Function of Active Power
This control mode uses the active power to generate a reference value for the reactive power so that the grid voltage
can be controlled at the point of common coupling. The independent variable (grid power) can be negative if an
external energy meter is installed and the PV system must compensate for a local load (only available if control mode
2 has been selected in the parameter ModeSelect).
Q_of_PP: Active power (independent values) from -100% to 100% of nomi-
nal power
Q: Reactive power (dependent values) from -100% to 100% of nominal power
-
-
5.3.3Q(S) - Reactive Power as a Function of Apparent Power
See above, Section "Maximum apparent power" (only available if control mode 3 has been selected in the parameter
ModeSelect).
5.3.4Q(ext) - Reactive Power as a Function of an External Setpoint
See above, Section "Maximum reactive power" (only available if control mode 5 has been selected in the parameter
ModeSelect).
5.3.5PF(P) - Power Factor as a Function of Active Power
This control mode uses the nominal active power to generate a reference value for the power factor (PF) so that the
grid voltage can be controlled at the point of common coupling. The control mode contains two additional parameters
for activation. The control mode is activated when the grid voltage is above the lock-in threshold and deactivated when
the grid voltage is below the lock-out threshold. The threshold for activation must be larger than or equal to the
threshold for deactivation. If this control mode shall always be available, set lock_in_PPF = lock_out_PPF = 90%
(only available if control mode 6 has been selected in the parameter ModeSelect).
Parameter nameSetting rangeStep size
RmpTmsPT1_PPF0.6s to 3600s0.01s
lock_in_PPF80% to 120% of grid voltage0.1%
lock_out_PPF80% to 120% of grid voltage (must be smaller than lock_in_PPF)0.1%
PF_of_PP: Grid active power (independent values) from -100% to 100% of
nominal apparent power
PF: Power factor (dependent values) from ±0.8 to 1.0-
-
5.3.6PF(U) - Power Factor as a Function of Grid Voltage
This control mode uses the grid voltage to generate a reference value for the power factor (PF) so that the grid voltage
can be controlled at the point of common coupling (only available if control mode 7 has been selected in the
parameter ModeSelect).
Parameter nameSetting rangeStep size
RmpTmsPT1_UPF0.6s to 3600s0.01s
PF_of_UU: Grid voltage (independent values) from 80% to 120% of nominal
voltage
-
PF: Power factor (dependent values) from ±0.8 to 1.0-
5.3.7PF(ext) - Power Factor as a Function of an External Setpoint
See above, Section "Maximum power factor" (only available if control mode 9 has been selected in the parameter
ModeSelect).
5.3.8P(V) – Active Power as a Function of Grid Voltage
This control mode uses the grid voltage to generate a threshold for the active power so that the grid voltage can be
controlled at the point of common coupling. The P(V) characteristic curve must be coordinated with the Q(U) or PF(U)
control modes.
Parameter nameSetting rangeStep size
RmpTmsPT1_UP0.6s to 3600s0.01s
RmpDecTmm_UP-0.6%/min to -1200%/min (default)0.1%
RmpIncTmm_UP0.6%/min to 1200%/min (default)0.1%
P_of_UU: Grid voltage (independent values) from 80% to 120% of nominal
voltage
P: Active power (dependent values) from -100% to 100% of nominal
power
-
-
5.3.9P(f) - Active Power as a Function of Frequency
This is the common type of primary frequency control applied, e.g. as per the BDEW (German Association of Energy
and Water Industries) technical guidelines, with some extensions, see the figure below. By using the parameter
tdelay_on, it is possible to add a delay between the point in time where the frequency reaches its threshold (e.g.
50.2Hz) and the point in time where the active power starts to decrease. The purpose of this time delay is to reach a
lower sensitivity in terms of transient frequency changes and higher reliability when detecting grid failures. The amount
of generated active power is still sampled and hold at the instant where the frequency exceeds the threshold. Some
grid codes, e.g. CEI0-16, requires that the generation of active power is kept low in a certain duration after the
frequency has returned back to its normal range. This can be set via the parameter tdelay_off. Once the frequency is
back to its normal range, the active power is ramped up again with a certain ramp rate. This is done via the parameter
RmpIncTmm_FPReg. Some grid codes, e.g. CEI0-16, require that the ramp rate is variable. This can be
programmed with the parameter variable.
Hysteresis can be added in the P(f) curve, e.g. as per BDEW, by programming two P(f) characteristic curves with the
same values. Information: Active power will not start to increase again before the output value from the reference table
is equal to 100%.
Parameter nameSetting rangeStep size
tdelay_on0s to 2s (default: 0)0.01s
tdelay_off0s to 600s (default: 0)0.01s
RmpIncTmm_FPReg0.6%/min to 1200%/min0.1%
Variable (e.g. as per
CEI0-16)
FP_of_fFP: Power frequency (independent values) from 45 Hz to 65 Hz-
0 for constant rate limitation and 1 for variable rate limitation-
f: Active power (dependent values) from 0% to 100% of the nominal
power
Typical programming of the FP_of_f characteristic curve when hysteresis is not required, e.g. as
per VDEAR-N4105. Thus, the two characteristic curves in the reference table contain equal co-ordinates (x, y).
B
Example of programming the FP_of_f characteristic curve when hysteresis is required, e.g. as per
BDEW. Thus, the two characteristic curves contain different co-ordinates (x, y).
COutput power of the PV system after the frequency transient has ended (at time = 0) when constant
rate limit and no delay is applied, e.g. as per BDEW.
DOutput power of the PV system after the frequency transient has ended (at time = 0) when variable
rate limit and delay is applied, e.g. as per CEI0-16.