SMA SB 6000TL‑US User Manual

CA
US
PV Inverter
SUNNY BOY 6000TL‑US⁄7000TL‑US⁄8000TL‑US⁄ 9000TL‑US⁄10000TL‑US⁄11000TL‑US
User Manual
SB6-11TLUS-BA-eng-BUS121211 | TBUS-SB6-11TLUS | Version 1.1
Copyright © 2012 SMA America,LLC. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form
or by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior written permission of SMA America,LLC.
Neither SMA America,LLC nor SMA Solar Technology Canada Inc. makes representations, express or implied, with respect to this documentation or any of the equipment and/or software it may describe, including (with no limitation) any implied warranties of utility, merchantability, or fitness for any particular purpose. All such warranties are expressly disclaimed. Neither SMA America,LLC nor its distributors or dealers nor SMA Solar Technology Canada Inc. nor its distributors or dealers shall be liable for any indirect, incidental, or consequential damages under any circumstances.
(The exclusion of implied warranties may not apply in all cases under some statutes, and thus the above exclusion may not apply.)
Specifications are subject to change without notice. Every attempt has been made to make this document complete, accurate and up-to-date. Readers are cautioned, however, that SMAAmerica,LLC and SMA Solar Technology Canada Inc. reserve the right to make changes without notice and shall not be responsible for any damages, including indirect, incidental or consequential damages, caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material.
All trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand is not a registered trademark.
The Bluetooth
®
word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by SMA America,LLC and SMA Solar Technology Canada Inc. is under license.
SMA America, LLC
3801 N. Havana Street
Denver, CO 80239 U.S.A.
SMA Solar Technology Canada Inc.
2425 Matheson Blvd. E
8th Floor
Mississauga, ON L4W 5K5
Canada
User Manual SB6-11TLUS-BA-eng-BUS121211 3
Important Safety Instructions SMA America, LLC
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the following products:
• Sunny Boy 6000TL‑US⁄7000TL‑US⁄8000TL‑US⁄9000TL‑US⁄10000TL‑US⁄11000TL‑US
This manual must be followed during installation and maintenance.
The product is designed and tested according to international safety requirements, but as with all electrical and electronic equipment, certain precautions must be observed when installing and/or operating the product. To reduce the risk of personal injury and to ensure the safe installation and operation of the product, you must carefully read and follow all instructions, cautions and warnings in this manual.
Warnings in this document
A warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the SMA equipment and/or other equipment connected to the SMA equipment or personal injury.
Symbol Description
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
4 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC Important Safety Instructions
Markings on this product
The following symbols are used as product markings with the following meanings.
Symbol Description
Beware of dangerous voltage
The product works with high voltages. All work on the product must only be performed as described in the documentation of the product.
Beware of hot surface
The product can become hot during operation. Do not touch the product during operation.
User Manual SB6-11TLUS-BA-eng-BUS121211 5
General Warnings SMA America, LLC
General Warnings
General Warnings All electri cal installations m ust be done in accordance with the local and NationalElectrical Code
ANSI/NFPA 70 or the Canadian Electrical Code® CSAC22.1. This document does not and is not intended to replace any local, state, provincial, federal or national laws, regulation or codes applicable to the installation and use of the product, including without limitation applicable electrical safety codes. All installations must conform with the laws, regulations, codes and standards applicable in the jurisdiction of installation. SMA assumes no responsibility for the compliance or noncompliance with such laws or codes in connection with the installation of the product.
The product contains no user-serviceable parts except for the fans on the bottom of the enclosure and the filters behind the fans as well as the handle covers on the sides of the unit. For all repair and maintenance, always return the unit to an authorized SMA Service Center.
Before installing or using the product, read all of the instructions, cautions, and warnings in this manual.
Before connecting the product to the electrical utility grid, contact the local utility company. This connection must be made only by qualified personnel.
Wiring of the product must be made by qualified personnel only.
®
6 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC Table of Contents
Table of Contents
1 Information on this Document. . . . . . . . . . . . . . . . . . . . . . . 9
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 Intended Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Sunny Boy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Type Labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.1 Type Label of the Sunny Boy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.2 Type Labels of the DC Disconnect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 DC Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4 Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.5 Arc-Fault Circuit Interrupter (AFCI) . . . . . . . . . . . . . . . . . . . . . . 19
4 Operating the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.1 LED Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 Measurement Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3 Display Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3.1 Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3.2 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.3 Resetting "Error AFCI" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6 Cleaning and Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.1 Checking the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.2 Checking the DC Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.3 Cleaning the Inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.4 Cleaning the Fan Guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.5 Cleaning the Ventilation Grids . . . . . . . . . . . . . . . . . . . . . . . . . 37
User Manual SB6-11TLUS-BA-eng-BUS121211 7
Table of Contents SMA America, LLC
7 Compliance Information . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 1 Information on this Document

1 Information on this Document

Validity
This document is valid for the following device types:
• SB 6000TLUS-12
• SB 7000TLUS-12
• SB 8000TLUS-10
• SB 8000TLUS-12
• SB 9000TLUS-10
• SB 9000TLUS-12
• SB 10000TLUS-10
• SB 10000TLUS-12
• SB 11000TLUS-12
Target Group
This document is intended for end users.
Additional Information
Additional information is available at www.SMA-America.com.
Typography
Typography Usage Example:
"light" • Display messages
• Parameters
•Terminals
•Slots
bold • Elements to be selected
• Elements to be entered
User Manual SB6-11TLUS-BA-eng-BUS121211 9
• The inverter switches to "Balanced" mode.
• Select the FanTest parameter and set to 1.
1 Information on this Document SMA America, LLC
Nomenclature
The following nomenclature is used in this document:
Complete designation Designation in this document
SMA America, LLC SMA
SMA Solar Technology Canada Inc. SMA
Sunny Boy
Inverter/Sunny Boy 6000TL-US ⁄ 7000TL-US ⁄ 8000TL-US ⁄ 9000TL-US ⁄ 10000TL-US ⁄ 11000TL-US
Abbreviations
Abbreviations Designations
AC Alternating Current
AFCI Arc-Fault Circuit Interrupter
DC Direct Current
LED Light-Emitting Diode
MPP Maximum Power Point
MPPT Maximum Power Point Tracker
PV Photovoltaics
10 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 2 Safety

2Safety

2.1 Intended Use

The Sunny Boy is a PV inverter which converts the direct current of the PV array to alternating current and feeds it into the power distribution grid.
Figure1: Principle of a PV plant with Sunny Boy
Position Description
APV array
B Sunny Boy Combiner Box
C Sunny Boy with DC Disconnect
D AC miniature circuit-breaker
E Loads
FEnergy meter
G Power distribution grid
The Sunny Boy takes current from a DC source and converts it to alternating current for the power distribution grid. This current is first supplied to the local loads (E). The surplus energy is fed into the power distribution grid (G). The amount of current required from the power distribution grid is reduced by the current supplied directly to the local loads. An energy surplus may even result in the energy meter (F) of your plant running backwards. This power may also be recorded as power credits by the electric utility company depending on the interconnection agreement.
The Sunny Boy is suitable for indoor and outdoor use. The PV modules used must be suitable for use with the Sunny Boy and must be approved by the
module manufacturer. Do not connect any energy sources other than PV modules to the Sunny Boy.
User Manual SB6-11TLUS-BA-eng-BUS121211 11
2 Safety SMA America, LLC
For safety reasons, it is forbidden to modify the product or install components that are not explicitly recommended for this product or distributed by SMA.
The enclosed documentation is an integral part of this product.
• Read and adhere to the documentation.
• Keep the documentation in a convenient place for future reference.

2.2 Safety Precautions

Danger to life due to electric shock
The components in the inverter are live. Touching live components can result in serious injury or death.
• Do not open the inverter.
• Electrical installation, repairs and conversions may only be carried out by electrically qualified persons.
• Do not touch damaged inverters.
Risk of burns due to hot enclosure parts
Parts of the enclosure can become very hot during operation. Touching hot enclosure parts can result in burns.
• Only touch the enclosure lid and display during operation.
Excessive input voltage can damage the inverter.
Incorr ect sizing of the PV plant may result in voltages bein g present which co uld destroy the inverter. The inverter display will read the error message „!PV-Overvoltage!, !DISCONNECT DC!“ or "VpvMax".
• Turn the rotary switch of the DC Disconnect to the Off position immediately.
• Contact installer.
12 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 3 Product Description

3 Product Description

3.1 Sunny Boy

The Sunny Boy is a PV inverter which converts the direct current of the PV array to alternating current and feeds it into the power distribution grid.
Figure2: Sunny Boy design
Position Description
A Ventilation grids (left and right)
BType label
CDC Disconnect
DLEDs
EDisplay
FEnclosure lid
User Manual SB6-11TLUS-BA-eng-BUS121211 13
3 Product Description SMA America, LLC
Symbols on the inverter
Symbol Description Explanation
Tap symbol Indicates display operation (see Section 4).
Green LED Indicates the operating state of the inverter
(see Section 5.1).
Red LED Indicates the status of the ground fault monitoring
(see Section 5.1).
Yellow LED Indicates a fault or a disturbance (see Section 5.3.2).
14 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 3 Product Description

3.2 Type Labels

3.2.1 Type Label of the Sunny Boy

The type label provides a unique identification of the inverter. The type label is on the right-hand side of the enclosure.
Figure3: Layout of the Sunny Boy type label
Position Description Explanation
AModel Device type
B Serial No. Inverter serial number
C Device-specific characteristics
You require the information on the type label to use the inverter safely and for customer support at the SMA Service Line. The type label must be permanently affixed to the inverter.
User Manual SB6-11TLUS-BA-eng-BUS121211 15
3 Product Description SMA America, LLC

3.2.2 Type Labels of the DC Disconnect

The type labels provide a unique identification of the DC Disconnect. The type labels are on the right-hand side of the enclosure.
Figure4: Layout of the DC Disconnect type label
Position Description Explanation
AItem No.I Device type
B Device-specific characteristics
16 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 3 Product Description
Figure5: Layout of the DC Disconnect type label
Position Description Explanation
A Serial No. DC Disconnect serial number
You require the information on the type labels to use the DC Disconnect safely and for customer support at the SMA Service Line. The type labels must be permanently affixed to the DC Disconnect.
Symbols on the type labels
Symbol Explanation
Observe the operating instructions
Read the documentation of the product before working on it. Follow all safety precautions and instructions as described in the documentation.
UL1741 is the standard applied by Underwriters Laboratories to the product to certify that it meets the requirements of the
National Electrical Code
®
, the Canadian Electrical Code® CSA C22.1, and IEEE-929-2000. IEEE 929-2000 provides recommendations regarding the proper equipment and functionality necessary to ensure compatible operation when power generation is connected to the power distribution grid.
User Manual SB6-11TLUS-BA-eng-BUS121211 17
3 Product Description SMA America, LLC

3.3 DC Disconnect

The DC Disconnect safely disconnects the PV array from the inverter.
Figure6: DC Disconnect design
Position Description
ARotary switch
BCover
The DC Disconnect forms a conductive path between the PV array and the inverter. Actuating the DC Disconnect interrupts the flow of current and the DC cabling can be safely disconnected from the inverter.
18 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 3 Product Description

3.4 Communication

The inverter can be fitted with a Piggy-Back to enable cable-based communication with special data capture devices or a PC with the relevant software (for information about supported communication products for communication via Piggy-Back, see www.SMA-America.com).

3.5 Arc-Fault Circuit Interrupter (AFCI)

In accordance with the National Electrical Code®, Article 690.11, the Sunny Boy is equipped with a system for electric arc detection and interruption.
An ele ctr ic a rc w ith a po wer of 3 00 W o r gr eat er m ust be i nte rru pted by the AFCI in the time specified by UL 1699B. A tripped AFCI may only be reset manually.
Only the following types of Sunny Boy are equipped with an automatic arc-fault circuit interrupter:
• SB 6000TLUS-12
• SB 7000TLUS-12
• SB 8000TLUS-12
• SB 9000TLUS-12
• SB 10000TLUS-12
• SB 11000TLUS-12
The 2011 edition of the National Electrical Code PV plants attached to a building must be fitted with a means of detecting and disconnecting serial electric arcs on the PV side.
If the automatic arc-fault circuit interrupter function is not required, it can be deactivated in the "Installer" mode via the communication device.
®,
Article 690.11 stipulates that newly installed
User Manual SB6-11TLUS-BA-eng-BUS121211 19
4 Operating the Display SMA America, LLC

4 Operating the Display

The display shows the current operating data of the inverter (e.g. status, power, input voltage) and errors or disturbances.
The displayed operating data is updated every five seconds. The backlight shuts off automatically after two minutes.
You can operate the display by tapping on the enclosure lid:
• To activate the backlight, tap once.
• To scroll to the next text line of a displayed message, tap once.
• To display the serial number and designation of the inverter, the firmware version, and the status of the Power Balancer (if active) in succession during operation, tap twice in succession.
20 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting

5Troubleshooting

5.1 LED Signals

The LEDs display the operating state of the inverter and indicate the messages in the display via various blink codes.
Figure7: Position of the LEDs
Position Description Status Explanation
A Green LED Glowing Operation
Indicates normal operation of the inverter.
Flashes three times per second
Flashes once per second
Start The inverter is calibrating internal systems.
Calibration takes 10 s, after which the inverter begins normal operation.
Stop The inverter has been set manually to Stop
mode.
Waiting The inverter is checking the conditions for grid
connection.
User Manual SB6-11TLUS-BA-eng-BUS121211 21
5 Troubleshooting SMA America, LLC
Position Description Status Explanation
Goes out briefly once per second
Derating At temperatures above +113°F (+45°C), the
inverter continues to operate but reduces the power so as to protect the internal components from overheating.
Corrective measures:
• Ensure that the inverter has sufficient ventilation.
• Ensure that air can emerge from the fan guards at the bottom of the inverter. If air is not emerging from the fan guards, clean the fan guards (see Section 6.4).
B Red LED Glowing Ground fault
A ground fault is present in the PV array. The inverter does not feed into the power distribution grid.
Corrective measures:
• Contact installer.
22 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting
Position Description Status Explanation
C Yellow LED Glowing Control system fault
The inverter is no longer feeding into the power distribution grid.
Corrective measures:
• Contact installer.
Blinking AFCI self-test
The inverter is performing an AFCI self-test.
Glows for 5 s, goes out for 3 s, blinks twice
Grid failure The power distribution grid has failed or the
AC miniature circuit-breaker has tripped.
Corrective measures:
• E nsure tha t ther e is no pow er dis tri butio n grid failure.
• If there is no power distribution grid failure, contact the installer.
Glows for 5 s, goes out for 3 s, blinks 4 times
DC overvoltage The inverter has detected a DC input voltage
that is too high for safe operation.
Corrective measures:
• Contact installer.
Glows for 5 s, goes out for 3 s, blinks 5 times
Disturbance The inverter has detected an internal fault that
interrupts normal operation.
Corrective measures:
• Contact installer.
User Manual SB6-11TLUS-BA-eng-BUS121211 23
5 Troubleshooting SMA America, LLC
Position Description Status Explanation
Glows for 5 s, goes out for 3 s, blinks 6 times
High leakage current The leakage current from the inverter and the
PV array is too high.
Corrective measures:
• Contact installer.
Glows for 5 s, goes out for 3 s, blinks 7 times
Change of differential current The inverter has detected a change of
differential current. The inverter is no longer feeding into the power distribution grid.
Corrective measures:
• Contact installer.
B + C Red LED +
yellow LED
Glowing Ground fault
The inverter has detected a ground fault. The inverter will not restart automatically after detecting a ground fault.
Corrective measures:
• Contact installer.
A + B + C All LEDs Glowing Initialization
The DC input current available from the PV array is not sufficient for normal operation. Data transmission is not possible during initialization.
A + B + C All LEDs Not glowing Standby
The inverter is in standby mode. The input voltage is too low for operation.
24 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting

5.2 Measurement Channels

The measured values of the inverter are shown on the display in the measurement channels. In addition, you can read out a variety of measurement channels and messages from the inverter using special communication devices (e.g. Sunny WebBox) or a PC with the relevant software (e.g. Sunny Explorer).
Measurement channel Explanation
Balancer Operating mode set via "Power Balancer" parameter
CO2 saved Amount of CO
E-total Total energy yield
Error Description of fault
Event-Cnt Number of events
Fac Power frequency
Grid Type Type of power distribution grid to which the inverter is connected
h-on Total operating hours
h-Total Total number of operating hours in feed-in operation
I-dif Residual current
Iac Line current
Inv.TmpVal Temperature measured at IGBT module
Ipv DC input current
Max Vpv Maximum DC input voltage
Mode Current operating mode
Pac Power fed into the power distribution grid
Pcb.Tmp.Val Temperature measured at printed circuit board
Power On Total system start-up counter
Riso Insulation resistance of the PV plant before connecting to the power
distribution grid
Serial Number Inverter serial number
Vac Line voltage L1 - L2
Vac L1 Line voltage L1 - N
Vac L2 Line voltage L2 - N
Vpv DC Input voltage
Vpv Setpoint MPP tracking DC target voltage
saved during the operating time
2
User Manual SB6-11TLUS-BA-eng-BUS121211 25
5 Troubleshooting SMA America, LLC

5.3 Display Messages

5.3.1 Status Messages

Message Explanation
Balanced The inverter has disconnected from the power distribution grid or is
limiting its power to a defined value over a 10-minute average. The inverter is part of a three-phase system with two further inverters and is equipped with the SMA Power Balancer to prevent the formation of unbalanced loads.
Derating Reduction of the power due to abnormal heat sink temperatures
Disturbance The inverter has detected a disturbance. The inverter is no longer
feeding into the power distribution grid.
Error The inverter has detected a fault. The error has to be remedied before
the inverter can continue feeding into the power distribution grid.
Grid monitoring When the system starts, the inverter synchronizes with the power
distribution grid.
MPP The inverter is in MPP mode.
The inverter adjusts the DC input voltage and the DC input current of the PV array to achieve the highest possible AC output power.
MPP-Search When the system starts, the inverter checks the MPP tracking range.
Offset When the system starts, the inverter calibrates the electronics.
Riso The inverter measures the PV plant insulation resistance.
Stop The inverter has been manually set to system stop.
Turbine The inverter is in turbine mode.
This operating mode was specifically designed for use with wind turbine systems.
V-Const The input voltage of the PV array is set at a given target value and the
inverter is not operating in MPP mode. This operating mode is suitable for using the inverter with fuel cel ls o r small hy dro ele ctr ic power plants.
Wait The DC input voltage is not high enough for the start.
Warning System warning requires further investigation.
26 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting

5.3.2 Error Messages

In the eve nt o f an err or, th e re lev ant mes sag es are sho wn o n th e display and the backlight is activated. Ea ch e rro r mess age is d ispla yed for 5 s eco nds . Af ter 5 s eco nds, t he d isp lay sc rol ls t hro ugh the re gul ar operation messages. The error message will be displayed in the display sequence until the fault is rectified.
Message Cause and corrective measures
!PV-Overvoltage! !DISCONNECT DC!
CAN An internal communication fault has occurred.
Check L-N-PE L and N are swapped on the AC connection or PE is not connected.
DC link The internal hardware monitoring system has detected a fault in the power
Overvoltage at DC input, Risk of inverter destruction. When this message is signaled, it is accompanied by rapid flashing of the backlight.
Corrective measures:
• Turn the rotary switch of the DC Disconnect to the Off position immediately.
• Contact installer.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
electronics. The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
User Manual SB6-11TLUS-BA-eng-BUS121211 27
5 Troubleshooting SMA America, LLC
Message Cause and corrective measures
Derating The inverter reduces the output power due to high internal temperatures.
Corrective measures:
• Ensure that the inverter has sufficient ventilation.
• Ensure that air can emerge from the fan guards. If no air is emerging from the fan guards, clean the fan guards (see Section 6.4).
dI-OCU dI-Srr
The inverter has detected a change in the differential current. A change of the differential current can be caused by a ground fault,
residual current or a malfunction. The inverter disconnects from the power distribution grid.
Corrective measures:
• Contact installer.
dI-Meas-Srr dI-Meas
The inverter has detected a deviation in the differential current measurement. If this message is repeated frequently, the inverter disconnects from the power distribution grid.
Corrective measures:
• Contact installer.
EEPROM Temporary disturbance during reading or writing of data from the
EEPROM. This data are not essential for safe operation. This message is for
information purposes and has no effect on the performance of the inverter.
EEPROM p EEPROM data are defective.
The inverter has switched off because the loss of data has disabled important inverter functions.
Corrective measures:
• Contact installer.
EeRestore One of the duplicate records in the EEPROM is defective and has been
reconstructed without loss of data. This message is for information purposes and has no effect on the performance of the inverter.
28 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting
Message Cause and corrective measures
Error AFCI The inverter has detected an electric arc in the PV system.
The inverter disconnects from the power distribution grid. As soon as the error is remedied , the inverter performs an AFCI test. If the AFCI test is unsuccessful, the inverter keeps restarting the AFCI test until it has been carried out successfully.
Corrective measures:
• Restart the inverter (see section 5.3.3"Resetting "Error AFCI"",page34).
• If the message occurs frequently, contact the installer.
Fac-Bfr Fac-Srr
The AC power frequency has exceeded the permissible range. The inverter disconnects from the power distribution grid to prevent islanding.
Corrective measures:
• Contact installer.
HW Signal The inverter has detected an internal measuring disturbance or the
hardware is defective. The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
Iac-DC_Offs-Srr The inverter has detected a system incident.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
User Manual SB6-11TLUS-BA-eng-BUS121211 29
5 Troubleshooting SMA America, LLC
Message Cause and corrective measures
IGBTs The inverter has detected a disturbance in the power electronics.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
MSD-FAC MSD-Idif
MSD-VAC
The inverter has detected an internal measurement comparison disturbance or the hardware is defective.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
Offset The grid monitoring self-test has failed.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• If the message occurs frequently, contact the installer.
PowerBalancer Three Sunny Boys are combined into one three-phase feed-in unit to
prevent unbalanced loads. The parameter "PowerBalancer" is set to "PhaseGuard" or "FaultGuard".
REL_INV_CLOSE REL_GRID_CLOSE
A grid relay does not close. The inverter checks the relays connecting it to the power distribution grid before feeding power into the grid.
If the grid relays do not function properly, the inverter cannot connect to the power distrubution grid.
Corrective measures:
• Contact installer.
30 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting
Message Cause and corrective measures
REL_INV_OPEN REL_GRID_OPEN
A grid relay does not open. The inverter checks the relays connecting it to the power distribution grid before feeding power into the grid.
If the grid relays do not function properly, the inverter cannot connect to the power distrubution grid.
Corrective measures:
• Contact installer.
Riso The electrical insulation between the PV plant and ground is defective.
The resistance between the positive and negative DC connection to ground is outside the permissible range. The inverter disconnects from the power distribution grid.
Corrective measures:
• Contact installer.
Riso-Sense Insulation measurement failed.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
ROM The internal test of the inverter control system firmware failed.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• If the message occurs frequently, contact the installer.
SD-DI-Conv The inverter has detected an insulation fault on the DC side.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
User Manual SB6-11TLUS-BA-eng-BUS121211 31
5 Troubleshooting SMA America, LLC
Message Cause and corrective measures
SD-Imax The inverter has detected an overcurrent on the AC side.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
SD-INV-Bridge The inverter has detected a fault in the power electronics.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
Shut-Down Overcurrent present at the DC input of the inverter.
The inverter switches off.
Corrective measures:
• Contact installer.
STM-Timeout The inverter has detected an internal program run disturbance.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
Vac-Bfr Vac-Srr
The AC line voltage has exceeded the permissible range. The cause may be disconnection of the power distribution grid or an AC
cable. The inverter disconnects itself from the power distribution grid to prevent islanding.
Corrective measures:
• Contact installer.
32 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 5 Troubleshooting
Message Cause and corrective measures
VacL1-Bfr VacL2-Bfr, VacL1-Srr VacL2-Srr
The DC input voltage is too high or too low on the indicated branch. The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
VdclinkMax The internal hardware monitoring system has detected an overvoltage in
the intermediate circuit of the inverter. The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Contact installer.
VpvMax The DC input voltage is above the set maximum limiting value.
The inverter disconnects from the power distribution grid. As soon as the error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter trips the permanent operation inhibition.
Corrective measures:
• Turn the rotary switch of the DC Disconnect to the Off position immediately.
• Contact installer.
Watchdog Watchdog Srr
The inverter has detected an internal program run disturbance. The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power distribution grid again. If the inverter cannot feed into the power distribution grid after several attempts, the inverter triggers the permanent operation inhibition.
Corrective measures:
• Contact installer.
User Manual SB6-11TLUS-BA-eng-BUS121211 33
5 Troubleshooting SMA America, LLC

5.3.3 Resetting "Error AFCI"

If the yellow LED is permanently glowing and the message "Error AFCI" is displayed, an electric arc has been detected in the PV system. The AFCI has been tripped and operation of the inverter is permanently inhibited.
1. Turn the rotary switch of the DC Disconnect to the Off position.
2. Wait until the display and all LEDs switch off.
3. Turn the rotary switch of the DC Disconnect to the On position.
☑ The message "Error AFCI. Knock to reset." is displayed. ✖ The message "Error AFCI. Knock to reset." is not displayed.
Possible error cause: The disturbance was not remedied.
• Contact installer.
4. If the message "Error AFCI. Knock to reset." is displayed, tap the enclosure lid within 10 s. ☑ The inverter starts up. ✖ The inverter does not start up.
Possible cause of error: You did not tap the enclosure lid within 10 s of the message appearing.
• Repeat steps 1 to 3.
34 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 6 Cleaning and Care

6 Cleaning and Care

6.1 Checking the Inverter

• Ask the installer to check for correct inverter operation at regular intervals.
• Check whether there is any externally visible damage to the inverter. If there is any externally visible damage to the inverter, contact the installer.

6.2 Checking the DC Disconnect

• Check for externally visible damage and discoloration of the DC Disconnect and the cables at regular intervals.
If there is any visible damage to the DC Disconnect, or visible discoloration or damage to the cables, contact the installer.
• Once a year, turn the rotary switch of the DC Disconnect from the On position to the Off position 10 times in succession. This cleans the contacts of the rotary switch and prolongs the electrical endurance of the DC Disconnect.
User Manual SB6-11TLUS-BA-eng-BUS121211 35
6 Cleaning and Care SMA America, LLC

6.3 Cleaning the Inverter

• If the inverter is dirty, clean the enclosure lid, the display, and the LEDs using only clean water and a cloth. Do not use any cleaning agents (e.g. solvents or abrasives).

6.4 Cleaning the Fan Guards

If the inverter displays the message "Derating", the fan guards may be dusty or dirty.
Figure8: Position of fan guards and fan
Position Description
A Fan guards with fan
• Check whether the fan guards are dusty or dirt-clogged. If the fan guards are dusty, clean them with a vacuum cleaner. If the fan guards are clogged with dirt, contact the installer.
36 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 6 Cleaning and Care

6.5 Cleaning the Ventilation Grids

The ventilation grids must be clean for optimum heat dissipation of the device. Clean the ventilation grids regularly according to the following procedure.
1. Remove the ventilation grids sideways.
2.
Damage to the inverter caused by foreign bodies.
• Do not remove the ventilation grids permanently. This prevents foreign bodies from entering the enclosure.
3. Clean the ventilation grids with a soft brush, a paintbrush or compressed air.
4. Close the recessed grips with the ventilation grids. Ensure that the assignment is correct. The correct enclosure side is marked on the interior of each ventilation grid: left side "links ⁄ left" and right side "rechts ⁄ right".
User Manual SB6-11TLUS-BA-eng-BUS121211 37
7 Compliance Information SMA America, LLC

7Compliance Information

FCC Compliance
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A & B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
The user is cautioned that changes or modifications not expressly approved by SMA America, Inc. could void the user’s authority to operate this equipment.
IC Compliance
This device complies with Industry of Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions:
• This device may not cause interference, and
• This device must accept any interference, including interferences that may cause undesired operation of the device.
38 SB6-11TLUS-BA-eng-BUS121211 User Manual
SMA America, LLC 8 Contact

8Contact

If you have technical problems concerning our products, contact the SMA Service Line. We require the following information in order to provide you with the necessary assistance:
•Inverter device type
• Inverter serial number
• Type and number of the PV modules connected
• LED signal and display message of the inverter
• Optional equipment, e.g. communication products
SMA Solar Technology America, LLC
6020 West Oaks Blvd, Ste 300 Rocklin, CA 95765 Tel. +1 916 625 0870 Tel. +1 877-MY SMA TECH Tel. +1 877 697 6283 (Toll free, available for USA, Canada and Puerto Rico) Fax +1 916 625 0871 Service@SMA-America.com www.SMA-America.com
SMA Solar Technology Canada Inc.
2425 Matheson Blvd E , 8th Floor Mississauga, ON L4W 5K5 , Canada Tel. +1 877 506 1756 (Toll free, available for Canada) Service@SMA-Canada.ca www.SMA-Canada.ca
User Manual SB6-11TLUS-BA-eng-BUS121211 39
XXX4."4PMBSDPN
4."4PMBS5FDIOPMPHZ
4.""NFSJDB--$
XXX4.""NFSJDBDPN
Loading...