Slant-Fin XL-2000 User Manual

Page 1
XXLL--22000000
OIL-FIRED WATER BOILERS/NO. 2 OIL
INSTALLATION AND OPERATING INSTRUCTIONS
SAFETY WARNING: KEEP BOILER AREA CLEAR AND FREE FROM COM­BUSTIBLE MATERIALS, GASOLINE AND OTHER FLAM­MABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO ABOVE SAFETY WARNING, MAY RESULT IN PERSONAL INJURY OR DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Air Supply and Venting . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
Controls and Accessories . . . . . . . . . . . . . . . . . . . . . . . . .5
Piping for Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Vent Piping and Draft Regulator . . . . . . . . . . . . . . . . . . . .5
Operating Instructions:
Precautions Before Starting . . . . . . . . . . . . . . . . . . . . . . .7
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Cleaning and Filling New Water Boiler . . . . . . . . . . . . . . .8
Care and Maintenance:
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Burner Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
IIMMPPOORRTTAANNTT:
form to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the Installation of Oil Burning Equipment, ANSI/NFPA 31, latest edition, and to the National Electrical Code ANSI/NFPA 70, latest edition. The installation must also conform to the additional require­ments in this Slant/Fin Instruction Manual. Where there is any difference, the more stringent requirement shall govern.
In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1, latest edition.
:
The installation of this equipment must con-
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJACENT TO THE BOILER
FOR REFERENCE.
IMPORTANT: This boiler must be installed, serviced and repaired by a trained, experienced, service technician, licensed for the installation and servicing of oil burning hot water heating system equipment or otherwise qualified by the author
ities having jurisdiction over the installation.
Printed in U.S.A.305 Publication No. XL-40 Part No. 48-0090 Revision C
Page 2
2
3
/4" RELIEF
VALVE TAPPING
1
1/2 SUPPLY
T
APPING
1
/2" AIR VENT
O
R EXPANSION TANK
T
APPING
T
OP VIEW
1/4 NPT PRESSURE & TEMPERATURE TAPPING
F
RONT VIEW
3/4 REAR DRAIN
1 1/2 ALTERNATE REAR RETURN
1 1/2 RETURN TAPPING
1/2 NPT CONTROL TAPPING
Figure 2.
XL-2000
Figure 1.
TABLE 1: Ratings and Dimensions
BOILER MODEL
NO.
I=B=R
BURNER
CAPACITY
OIL INPUT † §
GPH BTUH
D
.O.E.
HEATING
CAPACITY
MBH *
W
ATER
I=B=R
WATER
NET
RATING
MBH *
NOM.
X HEIGHT‡
(in x in x ft)
I=B=R
CHIMNEY SIZE
I.D
RECT
. ROUND
X HEIGHT
(in x ft)
XL-20 0.65 91,000 78 68 8 x8x15 6 x 15 83.56 8 XL-30H 0.85 119,000 104 90 8 x8x15 6 x 15 86.00 12 XL-30 1.00 140,000 121 105 8 x8x15 6 x 15 85.04 12
1.15 161,000 138 120 8 x8x15 6 x 15 84.12 12 XL-40H 1.25 175,000 152 132 8 x8x15 7 x 15 86.00 15 XL-40 1.35 189,000 162 141 8 x8x15 7 x 15 85.05 15
1.55 217,000 186 162 8 x8x15 7 x 15 84.38 15 XL-50 1.80 252,000 217 189 8 x8x15 8 x 15 85.00 19
2.00 280,000 239 206 8 x8x15 8 x 15 84.19 19
Standard working pressure 30 psi. All boilers hydrostatically tested — A.S.M.E. * For forced hot water heating systems where the boiler and all piping are
located within the area to be heated, the boiler may be selected on the basis of D.O.E. capacity output. The net I=B=R output ratings shown are based on an allowance for piping and pickup of 1.15 (water) or 1.33 (steam). D.O.E. capacity output is divided b Technical Service department should be consulted before selecting a boiler for unusual piping and pickup requirements such as intermittent system oper­ation, extensive piping, etc.
† Ratings apply to the use of light oil at 140,000 Btu per gallon and apply only
when burner models listed on pages 11 and 12 of this manual are used, and
y the allowance to obtain net rating. The Slant/Fin
are properly adjusted to produce 13% CO2.
Nominal clay tile liner dimensions.
§ Water boiler models XL-30 and larger have two firing rates. The boiler is fac­tory shipped at the lower firing rate. To obtain the higher firing rate, refer to the XL-2000 boiler installation instructions for the appropriate field adjust­ments
Oblong flue collar. Fits 6” dia. vent connectors.
#
All dimensions subject to nor
NOTE: All boilers under 300,000 Btuh (87.9 kw) input are tested and rated for capacity under the U.S. Depar tment of Energy (D.O.E.) Test Procedures for Boilers.
DIMENSIONS (inches) #
BOILER
LENGTH
AFUE %
. “H” models have only one firing rate.
“A”
11
FRONT TO
FLUE
“B”
/
16
3
/
16
3
/
16
3
/
16
11
/
16
11
/
16
11
/
16
3
/
16
3
/
16
9
4
/
5
6
/
5
6
/
5
6
/
1
8
/
1
8
/
1
8
/
13
9
13
9
mal manufacturing tolerance.
FLUE
DIA.
“C”
1
16
61
16
6 1
16
61
16
71
16
7 1
16
71
16
/
81
16
/
81
16
CIRCULA
SUPPLY
FLANGE
NPT
1
1
1 1
1
1 1
1 1
/
/
/ /
/
/ /
/ /
TOR
4
4
4 4
4
4 4
2 2
“D”
APPROX.
OVERALL
LENGTH
“E”
3
25
/
8
7
28
/
8
7
28
/
8
7
28
/
8
3
32
/
8
3
32
/
8
3
32
/
8
7
35
/
8
7
35
/
8
Page 3
XL-2000
3
T
HE INSTALLATION INSTRUCTIONS IN THIS MANUAL ARE ABBREVIATED. SEE THE FRONT COVER OF THIS MANUAL FOR REFERENCES TO CODES AND STAN­DARDS.
BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be near the chimney so that the Flue Pipe Connector or B
reeching to the chimney is short and direct.
A. The foundation must be capable of supporting the weight
of the boiler when filled with water:
Boiler Approximate Total Weight of Boiler
Size Assembly*, filled with water
XL-20 317 XL-30 405 XL-40 493 XL-50 581
* Includes burner, circulator and controls
B. The XL-2000 Boiler has full wet base sections which sur-
round fire-box for maximum heat absorption of burning fuel, and low floor temperature.
C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific require­ments.
MINIMUM CLEARANCE
Provide accessibility clearance of 24" from surfaces requiring servicing (top and front) and 18" on any side requiring pas­sage. The boiler shall be installed with the following MINIMUM clearances from combustible materials: A. CHIMNEY CONNECTOR-18" B. BACK AND SIDES- 6" EXCEPT as limited by 18" clear-
ance from chimney connector NOTE: Except in closets and alcoves, clearances above in (A) and (B) may be reduced by providing forms of protection as specified in NFPA 31, latest edition.
C
HIMNEY REQUIREMENTS (see NFPA 31, latest edition)
A. The chimney must be constructed in accordance with all
l
ocal applicable codes and the National Board of Fire Underwriters. See boiler models and rating table shown on page 2 for chimney sizes.
B
. Check chimney condition.
Existing chimneys and stacks may have deteriorated; with­out repairs their use would be hazardous. Before connect­i
ng to an old chimney or stack:
1. Clean it.
2. Inspect it thoroughly.
3. Remove obstructions.
4. Replace worn sections of metal stacks. 5
. Seal bad masonry joints.
6. Repair damaged lining.
C. Where more than one appliance vents into a common
chimney, the area of the common breeching should at least equal the area of the largest appliance flue plus 50% of the additional flue areas.
D. Breeching area must not be reduced at connection into
chimney. Breeching must be inserted into, but not beyond, inside of chimney liner.
E. Chimney height shall extend at least 3 feet above where it
passes through the roof of the building, and at least 2 feet above any ridge within 10 feet of the chimney.
F. The use of a vent cap, where permitted by code, gives
additional protection against adverse wind conditions and precipitation.
G. Flue Connection: Connect flue pipe between top of boiler
and chimney. Horizontal sections of flue pipe must be pitched upward to the chimney at least 1/4" per foot. Flue must be inserted into, but not extend beyond, the inside wall of the chimney flue. Install draft regulator in flue pipe, as shown in figure 3.
AIR SUPPLY AND VENTILATION (see NFPA 31, latest edi­tion) Sufficient air for combustion and ventilation in the boiler room must be provided. Failure to do this will result in poor combus-
Figure 3.
Barometric Draft Regulator Location
Page 4
4
XL-2000
tion, heavy sooting and health hazards. Any oil-fired boiler must have a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney draft* is unreliable, CO
D
O NOT vent this boiler to the same chimney flue used by a
and overfire draft* will change unpredictably.
2
fireplace or coal or wood burning furnace or boiler. The draft* produced by solid fueled devices varies tremendously between high fire and low fire:
In modern, weather stripped, energy-saving buildings or older buildings which have been modified similarly, natural infiltra­t
ion may not supply enough air for combustion, particularly if other fuel burning appliances, exhaust fans or draft inducers are competing for the same air supply. Fireplaces, other solid fuel burning appliances and exhaust fans consume great quantities of air; if air supply is not ample, such an appliance
* Draft is negative or suction pressure
will create a downdraft in the oil-fired boiler flue. This can cre­ate a hazardous condition. Flue gases can be sucked out of t
he chimney through the vent regulator into the living space. DO NOT operate this boiler and a solid fuel burning appliance at the same time, unless the solid fuel burner is provided with i
ts own outside air supply.
See Table 2, “Provisions for Combustion and Ventilation Air Supply” for determining need and method of providing air for combustion and ventilation.
If fly screen must be used over air supply openings, areas cal­culated should be doubled; the screen should be inspected and cleaned frequently to maintain free air flow.
Protect air openings against closure by snow, debris, etc. Openings such as doors or windows, if used, must be locked open.
TABLE 2: Provisions for Combustion and Ventilation Air Supply. See NFPA 31, latest edition for more detailed information.
Boiler Location Air Supply
2.1 Unconfined space Is there sufficient air for combus-
Action Required
NONE tion by natural infiltration (see NOTE (1), “Test...” below)?
2.2 Unconfined space If there in NOT sufficient air for combustion by natural infiltration due to tight construction or other conditions, then it REQUIRES AIR
Provide air from outdoors directly through a permanent out­side wall opening or openings with a free open area of not less than 1 sq. in. per 4000 Btu/hr of TOTAL input of ALL fuel
burning appliances in the building. See Note (1) and (3). FROM OUTDOORS. SEE “ACTION REQUIRED” column at right. See Notes (1) and (2) below.
2.3 Confined space If there is sufficient air for combus­tion from within building but it comes from outside of the confined space, see “ACTION REQUIRED” column at right. See Note (1) below.
The confined space shall be provided with two permanent air openings, one near the top of the enclosure and one near the bottom. EACH opening shall have a free air opening of not less than 1 sq. in. per 1000 Btu/hr. of TOTAL input of ALL fuel burning appliances within the enclosure. The two openings shall freely communicate with the interior areas of the building which in turn would have to have adequate infiltration of air from outdoors. See Notes (1, 3) and Figure 3a.
2.4 Confined space If there is NOT sufficient air for combustion due to tight construc­tion or other conditions it REQUIRES AIR FROM OUT­DOORS. SEE “ACTION REQUIRED” column at right. See NOTE (2) below.
(a) Air from the outdoors shall be provided to the confined
space by two permanent openings, one in or near the top of the enclosure space and one in or near the bottom. The openings shall communicate directly, or by means of ducts, with outdoors or to such spaces (crawl or attic) that freely communicate with outdoors (See figures 3b, 3c and 3d).
(b) Where directly communicating with outdoors or by means
of vertical ducts, each opening shall have a free area of not less than 1 sq. in. per 4,000 Btu/hr. (35 sq. in. per gal. per hr.) of total input rating of all appliances in the enclo­sure. If horizontal ducts are used, each opening shall have a free area of not less than 1 sq. in. per 2,000 Btu/hr. (70 sq. in. per gal. per hr.) of total input of all appliances in the confined space. See Figures 3b, 3c and 3d.
(1) Test for sufficient air for combustion by infiltration by running this boiler for 30 minutes under all of the following conditions and at the same time: a) all doors, win-
dows and other like openings must be closed, b) all fuel burning appliances should be FIRING, c) all exhaust fans and clothes dryers turned ON. At the above conditions the CO2, smok
.04” W.C. negative pressure.) (2) Aside from tight construction, some of the conditions that steal air for combustion from a boiler are other fuel burning appliances, exhaust fans and clothes dryers. (3) Generally, louvers made of wood have a free open area of 20% and those made of metal have a 60% to 70% free open area. Screens also reduce the open area
of the louvers.
e and draft readings must be normal. (CO
betw
een 11% and 13%, smoke between ZERO and a TRACE, draft between .02” W.C. and
2
Page 5
XL-2000
5
Figure 3a.
Appliances located in confined spaces. Air from inside the building. See Table 2 (2.3).
Figure 3b.
Appliances located in confined spaces. Air from out­doors. See Table 2 (2.4).
Figure 3c.
Appliances located in confined spaces. Air from out­doors through ventilated attic. See Table 2 (2.4).
Figure 3d.
Appliances located in confined spaces. All air from outdoors through ventilated crawl space and outlet air to ventilated attic. See Table 2 (2.4).
Page 6
6
XL-2000
The opening size recommendation just given is for guidance only. It is the installer’s responsibility to provide air for combus­t
ion and ventilation to all appliances, under all operating con-
ditions, for each installation. See NFPA 31, latest edition for more specific details.
I
NSTALLING CONTROLS AND ACCESSORIES
ON BOILER UNITS
:Jacket must be installed on boiler units prior to installa-
Notes
tion of trim. WATER BOILER TRIM, see page 2, figures 1 and 2 for tap­ping locations.
WATER PIPING FOR HOT WATER HEATING BOILERS
NOTE: On knocked-down boiler only, jacket may be installed after supply piping connection, but must be installed prior to adding trim and piping returns and drain valve. I. CIRCULATING SYSTEM
A. FORCED CIRCULATION hot water heating system: Use
the top tapping as supply tapping, and use the front or rear bottom tappings for the return.
B. A FLOW CONTROL VALVE will prevent gravity circula-
tion and is required when an external tankless heater, an indirect water heater or multiple circulators are installed.
II. AIR CONTROL SYSTEMS
A. DIAPHRAGM-TYPE COMPRESSION TANKS are used
to control system pressure in an AIR ELIMINATING SYSTEM: an automatic air vent is used to REMOVE air from the system water. (See figures 5 and 6) If system pressure needs further control, add an addi­tional tank or install a larger capacity tank. The automatic air vent should be installed in the top of
the boiler, as in figures 5 and 6 and at radiation high points (see “C”).
B
. CONVENTIONAL COMPRESSION TANKS (non-
diaphragm type) are used to control system pressure in an AIR COLLECTING SYSTEM. Within the system, a
fter initial start-up and venting, air is collected in the tank and acts in contact with the water to control pres­sure (see dashed area in figure 5 and paragraph “E”). A
ir is not vented from this system except at radiation high points (see “C”). If system pressure needs further control, add another tank in parallel with the original tank or install a large capacity tank. Locate the tank at the inlet end of the p
ump near the boiler. (See figure 5)
C. HOT WATER RADIATION VENTING - Manual air vents
should be installed at the top of all "drops" (where pip­ing goes downward). Air must be vented or purged from all zone lines to permit proper system heating.
D. PUMP LOCATION - Locating low-head pump(s) on
return to boiler is only acceptable in residences of one or two stories. (See figure 6) The pump location shown in figure 5 is required in large, multi-story building instal­lations, especially when high-head pumps are used and is also recommended for all applications.
E. A conventional compression tank may be connected
directly to the 1/2" tapping on the boiler (see “Alternate Compression Tank”, figure 5).
IMPORTANT: Hot water heating systems containing high water volume, such as would occur with cast iron radiation, require special care with air elimination.
The circulator pump should be located on the boiler supply pipe and the expansion tank and air scoop should be located near the pump suction. (as shown in figures 5 and 6) For alternate circulator pump location on return for low-head pumps and one or two story buildings ONLY (see figure 6).
Figure 5. Air Eliminating System or Alternating Collecting
System
Figure 6. Alternate Air Eliminating System
Page 7
XL-2000
7
DOMESTIC HOT WATER
For Indirect-fired storage water heater application, see S
lant/Fin publication WH-10, Sizing Guide WH-SG and Installation manual WH-40. The installation manual includes several control systems and relay centers for space and domestic water heating in addition to plumbing.
INSTALLING THE BURNER
See Burner Data, pages 11 and 12, and Burner Manual sup­plied with burner. If burner is not mounted as received, mount t
o boiler, placing flange over mounting studs. Use gasket between flange and boiler. Distance between flange and nose of burner must be as shown on pages 11 and 12. Check to see that nozzle and settings are as given in burner data tables, pages 11 and 12.
OIL SUPPLY PIPING
Install the oil tank or tanks and piping from tank to burner. Follow local codes and practices, INSTALLATION OF OIL BURNING EQUIPMENT, NFPA 31, latest edition, and the instruction sheet attached to the oil burner pump. A one-pipe system should be used for gravity-fed fuel systems and for lift systems, where the total lift is less than 8 feet. Where the total lift is greater than 8 feet, a two-pipe system must be used. In some instances, local codes may require a two-pipe system for below grade fuel oil tanks. Be sure to set up the fuel oil pump for the piping system used; follow the instructions attached to the pump. Be sure to include a good quality, low pressure drop fuel oil filter in the supply line from the tank. This is necessary, especially at low fuel oil flow rates (small nozzle sizes), to prevent nozzle plugging. Fuel oil shutoff valves should be installed at the burner on the supply (and return if two-pipe) to facilitate servicing. See Slant/Fin publica­tion on one-pipe and two-pipe fuel oil systems.
WIRING THE BOILER
(see National Electric Code ANSI/NFPA 70-latest edition) A. The wiring diagrams for the burner and boiler may be found
on page 10.
B. 24 volt control wiring should be approved Safety Circuit
wire, protected as needed.
C. Power supply wiring to the burner must be 14 gauge, as
required, and should have a properly fused disconnect switch. 120 volt wiring to pumps and safety controls must also be 14 gauge. Wire must be enclosed in approved conduit.
D. The wires supplying power to the burner MUST go through
the quick disconnect plugs provided with the boiler.
E. All wiring must be installed in compliance with the National
Electric Code, or any local or insurance codes having juris­diction.
VENT PIPING AND DRAFT REGULATOR
(see NFPA 31, latest edition) A. Vent connectors must be the same diameter as the boiler
flue collar. (See page 2)
B. Vent pipes and breeching must be pitched upward a mini-
mum of 1/4" per foot.
C. Connect vent pipe to the chimney using as few elbows as
possible and as short as possible within NFPA 31 or authority.
D. Horizontal vent connector into the chimney should not be
inserted beyond the inside wall of the chimney.
E. Install barometric draft regulator on horizontal breeching,
near chimney, with hinge horizontal and face vertical condi­tions permitting as in Figure 3a. See Figure 3b as a second choice. See manufacturer's instructions packed in carton w
ith barometric draft regulator.
F. If two or more appliances are used on the same chimney,
see CHIMNEY, page 3.
G
. Make up all joints with minimum air leaks, secure with
sheet metal screws.
P
RECAUTIONS BEFORE STARTING OIL BURNER
Make a positive check of A through F before starting burner: A. Boiler and system are full of water. All air is vented from
system. See below.
B
. All wiring is completed. See page 10.
C. Oil supply is connected to the burner; nozzle is installed
correctly; oil valve is open at tank.
D. Main cast iron door on which burner is mounted is bolted
shut and fiberglass rope seal is making good contact. E. Smokepipe is connected to chimney. F. All combustible materials are cleared away. G. Combustion air supply is provided. See page 3. H. Burner settings are adjusted as per pages 7, 8, 11 and 12
and as shown on boiler jacket.
W
ARNING: NEVER OPERATE any natural draft* boiler (XL-2000 boiler is a natural draft boiler) with zero draft or overfire pressure: early failure of the burner, nozzle and chamber is inevitable if you do. Use a draft gauge, and make sure that overfire draft* is .02" to .04", during all operating conditions.
* Draft is negative or suction pressure.
START-UP (COMBUSTION TEST INSTRUMENTS MUST
BE USED)
A. Make sure the boiler is installed and wired properly and is full
of water.
B. The observation port cover is mounted on the hinged burner
mounting door (see figure 2 on page 2). NEVER touch the port cover or any surrounding surfaces with hands. They may be HOT. Use tools. Loosen the screw that fastens the obser­vation port cover, swing the cover open and tighten the screw. See the burner instructions for bleeding air, etc. Step away from the boiler and start the oil burner.
C. IMMEDIATELY, set burner air bands to obtain a bright fire
without smoke or oil stain. Set the DRAFT REGULATOR to obtain .02" overfire draft*. Take draft reading through slot in observation door after first closing the observation door.
D. Tighten the observation door screw. Allow the burner to fire
for at least one hour total firing time, to bake out the volatile binders in the combustion chamber before taking final com­bustion readings.
E. By alternate adjustment of the barometric draft regulator, the
burner air regulation and head regulation devices (whichever apply), set for a zero to a trace of smoke and 12% CO
.
2
Then open the air bands or shutter (whichever apply) an additional 1/8". This should result in zero smoke with NO raw oil on the smoke paper and a smooth light-off. DO NOT ATTEMPT TO SET FIRE BY EYE. Flame retention burners may appear efficient and smoke free from an inefficient 7% up to an overly high 14% CO
. However, a very low CO2can
2
also result in poor ignition and raw (unburned) oil entering the fire box. At very high CO
, any slight decrease in air flow for
2
any reason will cause incomplete combustion, with high
Page 8
8
XL-2000
smoke and dry soot formation in the fire box.
F. If smoke reading is satisfactory, but CO
can not be
2
increased to a satisfactory level (12%) or overfire draft of 0
.02" W.C. can not be obtained, check for proper sealing between sections, between the hinged burner mounting door and front section, around burner blast tube and a
round flue collector and collar. If seal is not satisfactory, reseal with furnace putty or silicone with a temperature rat­ing of at least 400° F. (All safety precautions indicated on material package must be followed.)
G. Once burner and draft have been set up, then smoke, CO
and stack temperature should be checked and recorded. If s
moke is greater than trace, review the burner instructions and replace the nozzle if necessary. Normal smoke to be expected is zero to a trace.
H. Make sure that the observation port cover is closed and
the screw is tightened.
CLEANING AND FILLING A NEW WATER BOILER
I. There are a number of commercial preparations available
from your distributor for cleaning and for corrosion protection conditioning the internal (waterside) surfaces of boilers. Follow the preparation manufacturer’s instructions. DANGER: Use CAUTION when handling chemicals and draining hot water from a boiler. Scalding water and/or chemicals can cause permanent injury to the skin, eyes and respiratory system.
II. Filling and venting the water boiler after cleaning
A. Refill the system with fresh water. B. Bring water temperature to at least 180° F promptly. C. Circulate water through entire system. D. Vent the system, including the radiation. E. The boiler is now ready to be put into service or on
standby.
F. If brand name air-control devices are used, venting
instructions furnished with the devices should be followed.
W
ATER CONTENT OF BOILER (GALLONS)
XL-20 XL-30
5.5 7.0
VOLUME OF WATER IN STANDARD PIPE OR TUBE
Nominal
Pipe Siz
e
Inches
3/8 — — 0.430 0.0075 1/2 40 0.622 0.0157 0.545 0.0121 5/8 0.666 0.0181 3/4 40 0.824 0.0277 0.785 0.0251 1 40 1.049 0.0449 1.025 0.0429 1 1/4 40 1.380 0.0779 1.265 0.0653 1 1/2 40 1.610 0.106 1.505 0.0924 2 40 2.067 0.174 1.985 0.161 2 1/2 40 2.469 0.249 2.465 0.248 3 40 3.068 0.384 2.945 0.354
Standard Steel Pipe Type L Copper Tube
Inside
.
Diameter
Inches
Schedule
No
XL-40
8.5 10.0
Gallons
per
Lin. Ft.
XL-50
Inside
Dia.
Inches
Gallons
per
Lin.
ft..
III. Safety check for control system
High limit control test: Set thermostat high enough for boiler water temperature to reach high limit control setting. When this temperature is reached, the high limit switch should o
pen, and the burner should shut off automatically. If the high limit does not operate to shut off the burner, the high limit or the wiring is faulty. Repair or replace immediately.
C
ARE AND MAINTENANCE
I. EXTENDED SHUTDOWN, CLEANING OR REMOVAL OF
2
BOILER FROM SERVICE. DANGER: Use CAUTION when handling chemicals and dra
ining hot water from a boiler
c
hemicals can cause per
. S
calding water and/or
manent injury to the skin, eyes and respiratory system. A.Shut down burner by disconnecting all electrical power to
the burner by turning OFF the BURNER EMERGENCY SWITCH of this boiler. After shutting down burner, while the boiler is still hot (180°F to 200°F), drain water from the bottom of the boiler until it runs clear.
B.Provide corrosion protection conditioning to the boiler
water in the heating system. There are a number of com­mercial heating system preparations available from your distributor. Follow the preparation manufacturer’s instruc­tions.
o clean the fireside boiler surfaces, first shut down
C.T
burner by disconnecting all electrical power to the burner by turning OFF the OIL BURNER EMERGENCY SWITCH of this boiler in order to perform the following work in (1) through (10) below.
1. Remove the flue pipe from the boiler flue collar and clean thoroughly.
2. Inspect the entire vent connector back to the chim­ney and clean if necessary.
3. Inspect the chimney for soot, debris and other unsafe conditions of the chimney and take the necessary action.
4. Remove the flue collector by first removing the top jacket panel. The flue collector is held in place by two hex 1/4-20 screws. Remove the screws and carefully remove the flue collector. Try not to disturb the flat fiberglass rope under the flue collector.
5. When necessary to clean the combustion chamber you must first CLOSE the suction valve (and return valve if two pipe). Then disconnect the oil lines from the burner. The flexible electric conduit connected from the junction box on the boiler to the burner via a plastic connector must be disconnected from the burner by grasping the plastic half of the connector closest to the flexible conduit and gently pulling it in the direction of the conduit until it is disconnected. Remove the single 3/8-16 hex head screw on the LEFT side of the swinging door. You will need a 9/16” drive socket. Open the door to completely expose the combustion chamber for thorough cleaning and for inspection of target wall, blanket (provided in certain models;
see rating plate), main cast iron burner door insulation and burner door fiberglass sealing rope. If combustion chamber parts above are badly deterio­rated then replace with or
iginal factory parts avail-
able at your distributor.
Page 9
XL-2000
9
6. Use the flue brush to clean the pinned flueways b
etween the sections.† A wire brush may be used to remove any carbon accumulation that may have d
eveloped in the combustion chamber. Vacuum the loose soot and debris from the boiler.
7. Inspect the burner combustion head. Clean if nec­essary and make sure all the adjustments are cor­rect. (See burner data pages for the burner installed.) Replace oil nozzle with new one and r
eadjust electrodes. To insure proper burner opera­tion ONLY THE NOZZLES SPECIFIED IN THIS M
ANUAL OR ON THE BURNER LABEL SHOULD
BE USED FOR REPLACEMENT.
8. Protect all of the fireside surf
aces by swabbing with
neutral mineral oil.
9. Close main cast iron b
urner door (door on which burner is mounted). Make sure that the entire seal (fiberglass rope) is making good contact with the boiler casting when replacing 3/8-16 x 1” long hex head bolt and tightening.
10. Check the flue collector seal. This is the flat rope seal on top of the heat exchanger. The rope must be in place adjacent to the long bosses on front and rear sections and adjacent to the short bosses on the intermediate sections. The rope should be directly under the flue collector flanges when the flue collector is replaced. Use the two 1/4-20 x 3/4” washer hex head screws to fasten the flue collector. In order to assure a proper seal be sure that the flue collector is compressing the flat rope and not hanging up on the section bosses. Tighten the two screws.
D.If boiler room is damp, provide ventilation.
II. PROVIDING PROTECTION FOR FREEZING
Anti-freeze is sometimes used in hydronic heating sys­tems to protect against freeze-up in the event of power failure, or safety control shutdown when the building is unoccupied. It should be recognized that unless the building is kept above freezing temperature by some means, the plumbing system is not protected.
PROPYLENE GLYCOL is used in the quick-freeze food industry; it is practically non-toxic. Its use may be permit­ted when indirect water heaters are used. When anti­freeze must be used, inhibited propylene glycol is recom-
mended. Useful information on the characteristics, mixing p
roportions, etc. of glycol in heating systems is given in Technical Topics No. 2A, available from the Hydronics D
ivision of GAMA, 35 Russo Place, Berkeley Heights, NJ
07922. Consult glycol manufacturers for sources of propy­lene glycol.
D
O NOT USE ETHYLENE GLYCOL BECAUSE IT IS TOXIC.
I
II. OIL BURNER
Inspect and clean annually and following any period of i
mproper operation. Recheck and adjust settings as speci­fied for burner model and nozzle size. Set burner air and draft regulator, using test instruments to obtain recommended CO
and draft without smoke.
2
See the Burner Data page in this manual that corre­sponds to the burner installed.
IV. GENERAL MAINTENANCE
These operations are recommended to be performed at regular intervals: A.BOILER HEATING SURFACES: clean off all coatings
found. Reseal covers.
B.BOILER CONTROLS: check contacts, settings, correct
functioning. C.PIPING: check piping and accessories for leaks. D.CHIMNEY or STUB VENT and BREECHING: check for
obstructions and leaks. E.COMBUSTION AIR TO BURNER: check for continued
POSITIVE supply of air as required. Air needs are
greatest in coldest weather. Refer to AIR SUPPLY,
page 3. F. WATER SYSTEM: check
1. System to be full of water and pressure to remain stable (between 12 psi and 25 psi).
2. Air-control system: noise and air binding in radiation should not occur.
3. Water lines: slightest leaks should be corrected.
G.BOILER ROOM AIR SUPPLY: air vents should be open
and free of obstruction. See page 3.
† A flue brush (2-1/4" dia.) is supplied with boiler.
Replacements are available from dealer or hardware stores.
Page 10
10
XL-2000
Page 11
XL-2000
BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY
11
NOZZLES
ANGLE
AND
TYPE
MFR.
OIL PUMP
PRESSURE
SETTING
(PSIG)
“A”
APPROXIMATE
HEAD SETTING
NO.
APPROXIMATE
AIR BAND
OPENING %
(1)
SHUTTER
NON-
ADJUSTABLE
BOILER
MODEL
CARLIN BURNER
MODEL (2) (3)
FIRING
RATE
NO. 2 OIL
(GPH)
SIZE
(GPH)
XL-20 99-FRD 0.65 0.65 70° A DELAVAN 100 0 50 Closed
71399-00F-XL-20 0.65 70° W DELAVAN 100 0 50 Closed
XL-30 99-FRD 1.00 1.00 70° A DELAVAN 100 2 80 Closed
71399-00F-XL-30 1.15 1.00 70° A DELAVAN 130 3 90 Closed
XL-40 99-FRD 1.35 1.35 60° W DELAVAN 100 4 50 Closed
71399-00F-XL-40 1.55 1.35 60° W DELAVAN 130 4 65 Closed
XL-50 99-FRD 1.80 1.75 60° B DELAVAN 105 4 20 Open
71399-00F-XL-50 2.00 1.75 60° B DELAVAN 130 5 40 Open
NO
TES: (1) Single slotted air band for XL-20 and XL-30, double slotted air band for XL-40 and XL-50. (2) See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 7 and burner figures on this page. (3) All burner models shown are single stage.
Page 12
12
EMBOSSED AIR BAND ADJUSTMENT OPENS WHEN ROTATED CLOCKWISE EXAMPLE: SHOWN AT
N° 2 POSITION
SEE TABLE FOR CORRECT SETTINGS
SHUTTER ADJUSTMENT SHUTTER OPENS WHEN ROTATED CLOCKWISE E
XAMPLE: SHOWN AT N°6 POSITION
AIR BAND ADJUSTMENT SCREW
OIL
PUMP
BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY
XL-2000
NOZZLES
ANGLE
AND
TYPE
MFR.
OIL PUMP
PRESSURE
SETTING
PSIG)
(
APPROXIMATE
AIR SHUTTER
SETTING NO.
1)
(
APPROXIMATE
AIR BAND
SETTING NO.
STATIC DISK
DIAMETER
INCHES
BOILER
MODEL
BECKETT
BURNER
MODEL
(2) (3)
BECKETT
BURNER
HEAD
FIRING
RATE
NO. 2 OIL
(GPH)
SIZE
(GPH)
XL-20 (4) AFG F0 0.65 0.65 80° A DELAVAN 100 7 Blank/Closed 3
SF2201
XL-30H
AFG F3 0.85 0.85 70° W DELAVAN 100 6
Blank/Closed
2
SF2204
XL-30 AFG F3 1.00 1.00 80° W DELAVAN 100 8 0 2
S
F2202 1.15 1.00 80° W DELAVAN 130 10 2 2
XL-40H
AF F6 1.25 1.25 80° W DELAVAN 100 10 2 None
SF2205
XL-40 AF F6 1.35 1.35 80° W DELAVAN 100 10 2
/
2
None
1
SF2203 1.55 1.35 80° W DELAVAN 130 10 5 None
XL-50 AF F12 1.80 1.75 70° B DELAVAN 105 10 3 None
SF2207
NOTES: (1) Blank (closed) air band for XL-20, 2 slot band for XL-30, 4 slot band for XL-40 and 8 slot air band for XL-50. (2) See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 7 and burner figures on this page. (3) All burner models shown are single stage. (4) XL-20 is supplied with a low fire baffle (Beckett No. 31760) installed.
3
/
8
3
/
4
3
/
4
3
/
4
TOP VIEW OF GUN ASSEMBLY
Page 13
XL-2000
BURNER DATA - RIELLO BURNERS FOR PACKAGED BOILERS ONLY (RIELLO R-40 SERIES W/SHORT TUBE)
13
BOILER
MODEL
RIELLO
BURNER
MODEL
XL-20 R-40 F-3 48-0242-100
X
L-30 R-40 F-5 48-0243-100
XL-40 R-40 F-5 48-0244-100
XL-50 R-40 F-10 48-0245-100
† Air shutter and head settings shown are approximate ONLY. See START-UP page 7
NOTE: For proper insertion into combustion chamber see figure 8
SLANT/FIN
B
URNER
P/N SINGLE
S
TAG E
OIL PUMP
S
TAGES
1 0.65 0.5
1 1 0.85 70˚ES
1
1 1.35 1.2 80˚B
1 1.5 1.2 80˚B
1 1.8 1.5 60˚B DELAVAN 145 1 3.8
FIRING
RATE
S
GPH
IZE
(
GPH)
1.15 0.85 70˚ES
Figure 7A. Riello 40 Series
Model F-3 & F-5 Electrode Setting
NOZZLES
P
ANGLE
&
TYPE
70˚SS
NOZZLE
M
FR.
H
AGO 170 1 3-1/2
80˚ES
HAGO 140 1 2.6
HAGO 185 1 3.2
DELAVAN 130 3 4
DELAVAN 160 4 4.75
Figure 7B. Riello 40 Series
Model F-10 Electrode Setting
OIL PUMP
RESSURE
SETTING
(PSIG)
APPROX.
HEAD
SETTING
NO. †
APPROX.
AIR
S
HUTTER
SETTING
NO. †
Figure 8
For proper inser
tion into combustion chamber
Page 14
14
XL-2000
BURNER DATA - RIELLO (continued)
REGULATION OF THE TURBULATOR AND AIR SHUTTER F
OR PROPER COMBUSTION
Turbulator Setting
1. Loosen nut, 1, then turn the screw, 2, until the index marker,
3, is aligned with the correct index number.
2. Retighten the retaining nut, 1.
TURBULATOR SETTINGS - RIELLO 40 SERIES
The numbers on the casting are there to denote the high and low end of the scale - in all cases the first mark is “Zero”. T
he air/oil ratio depends on accurate setting of the turbulator disc. Be careful when making this adjustment as an incorrect setting will result in an unsatisfactory installation. See figure 9A and 9B.
Figure 9A
1. Regulation of the combustion air flow is made by adjustment of the manual AIR ADJUSTMENT PLATE (4) after loosening the FIXING SCREWS (3&5). The initial setting of the air adjustment plate should be made according to page 13.
2. The proper number on the manual AIR ADJUSTMENT PLATE (
4) should line up with the SETTING INDICATOR (2) on the fan housing cover. Once set, the air adjustment plate should be secured in place by tightening SCREWS 3 and 5. For F-10 model, manually open and release the hydraulic air shutter to ensure it has free movement.
3. The final position of the air adjustment plate will vary on each installation. Use instruments to establish the proper settings for maximum CO
NOTE: Variations in flue gas, smoke, CO
and a smoke reading of zero.
2
and temperature
2
readings may be experienced when the burner cover is put in place. Therefore, the burner cover MUST be in place when making the final combustion instrument readings, to ensure proper test results.
Figure 10A
Model F-3, F-5 Air Adjustment
Figure 9B
SETTING THE AIR ADJUSTMENT PLATE
Note: For F-3 and F-5 models, the air shutter is
operated on a 120V 60 Hz.
motor, the burner will not operate until the air shutter is in its fully open position; and for F-10 model is operated by Hydraulic Jack. (see figures 10 A & B).
Figure 10B
Model F-10 Air Adjustment
Page 15
©Slant/Fin Corp. 1996.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
F
AX: (516) 484-5921 •
Canada:
Slant/Fin
L
TD/LTEE,
Mississauga, Ontar
www.slantfin.com
io
Loading...