13.17) set the parameter to 02.
The system will function exactly as
described in the previous “Outdoor
reset adjustment” sections except
that now the boiler pump will stay on
permanently . The opening of the room
thermostat contacts will translate into
a parallel downward movement of
the curve in Figures 13-2 and 13-3.
The value by which the curve moves
downwards can be adjusted by the
parameter present in the
“Installers’ Menu”, see section 13.17.
The parameter can range
from 1 °F (1 °C) to 36 °F, (20°C). The
suggested values for this parameter
are:
- 18 °F (10°C) for high temperature
radiator systems;
- 6 °F (3°C) for low temperature radiant
panel systems
Calculated temperature (°F)
Outside temperature (°F)
Figure 13-2 - Graph of the outdoor reset adjustment
(infl uence of parameters “br”, “OA”, “Ob” and “Oc”)
Calculated temperature (°F)
Outside temperature (°F)
Figure 13-3 - Graphs of the outdoor reset adjustment
(infl uence of parameter “b”)
V alues of this parameter that are
too high may translate into room
temperature instability . Values that are
too low may make the action of the
room thermostat ineffective.
Climatic adjustment with room
compensation can be used in all the
systems described in Section 13.10.1.
The advantage being that the constant
running of the pump will stabilize and
standardize the room temperatures.
This is especially true when some loops
in the heating system have considerably
greater volume than others.
OA = Slope of the line
Ob = Minimum heating
temperature
Oc = Maximum heating
temperature
br = “Fix point” of the angle
fulcrum of the line
b = parallel shift of the line
(adjusted by the heating
knob, item “7” of fi gure 13-1)
73
13 - USE
13.11 - Boiler
switch settings
The control board shown in Figure
3-1, item “14”, contains a series of
switches that allow the boiler to be
confi gured to match the application.
The table below lists each switch and
its corresponding funtions.
SWITCH Position Description
1 OFF Boiler without production of D.H.W
ON Boiler with production of D.H.W. via storage tank
2 OFF Boiler with production of instantaneous D.H.W.
ON Position not available for this serie of boilers
3 OFF Heating pressure switch, disabled
ON Heating pressure switch, enabled
4 OFF EBM PAPST brand fan
ON Position not available for this serie of boilers
5 OFF Combination boiler for heating and D.H.W.
ON Boiler for heating only
6 OFF High temperature heating service, 86°F (30°C) to 176°F (80°C)
ON Low temperature heating service, 68°F (20°C) to 113°F (45°C)
7 OFF Boiler confi guration change, disabled
ON Boiler confi guration change, enabled
8 OFF Maximum heating supply water temperature of 176°F (80°C)
ON Position not available for this kind of boilers
CAUTION!!!
of these switches could cause the
boiler to malfunction resulting in
improper system performance.
Only a qualifi ed technician, with an
in-depth knowledge of the boilers’
control system, should change
them.
Improper setting
13.12 - Delays,
alarms and
protective actions
To protect the life of the appliance,
improve comfort, and maximize energy
savings, the following timings have
been incorporated into the control
logic:
a - Pump delay: each time the room
thermostat is satisfi ed, the circulator
pump continues to run for 1 minute;
b - DHW delay: each time the domestic
hot water demand is satisfi ed, a 2
minutes delay must pass before the
heating service is allowed to restart;
c - Protection against legionnaires
bacteria: if the boiler is connected
to a DHW storage tank the boiler
will increase the tank temperature
to 140 °F (60 °C) every seven days,
prevent the formation of legionnaires
bacteria. This function is displayed
by
d - DHW alarm: if the call for domestic
hot water lasts for longer than two
hours, an
This function is only for boilers set
up to provide instantaneous DHW.
.
01 alarm is generated.
e - Time delay in restarting the burner:
in its normal functioning state, except
when providing domestic water,
every time the burner stops, there is
a delay time of 3 minutes before the
boiler restarts again.
13.13 - Circulator
pump and three way
valve protection
During the summer months, the
circulator is run once a day for around
15 seconds to prevent it from seizing.
At the same time, the three way valve
(if present) is activated for the same
reason.
13.14 - Boiler’s
Freeze protection
CAUTION!!!
protection function to work, the
boiler must remain connected
to the electrical and gas
supplies with knobs “7” and
“11” in Figure 13-1, in the OFF
position.
For the freeze
CAUTION!!!
protection function is
conceived to protect the boiler
only, not the heating system.
CAUTION!!!
boiler’s freeze protection
function depends from the
electrical supply and from the
gas supply, it is mandatory
install a safety device that
alarm the user in a case
the boiler room will reach a
temperature near 35°F (2°C)
Once the boiler has reached a
temperature of 45 °F (7 °C), the
heating pump will automatically
comes on. If the temperature falls
below 35 °F (2 °C), the burner
will light to prevent the boiler from
freezing.
If the boiler will not be used for long
time it should be drained per Sections
14.10 and 14.11.
This freeze
Because the
74
13 - USE
13.15 - Display
in energy saving
mode
If desired, the display, item “1” and
“2” in Figure 13-1, can be switched
permanently off, with the exception
of when it displays errors or settings.
To switch the display off, access the
“Installers’ Menu”, in section 13.17
and set the
other than zero. Keep in mind that
each value will correspond to a delay
in minutes until the display goes into
Energy Saving mode.
PARAMETER DESCRIPTION INFORMATION ON DISPLAY ITEM “2” of Figure 13-1
parameter at a value
Adjustment of the curve angel as shown in
Figure 13-2 when outdoor reset is active per
section 13.9.
13.16 - “Users’
menu”
When entering the “Users’ menu”, the
display, item “1” in Figure 13-1, will
start blinking indicating that a change
of mode has taken place. To access
the “Users’ menu” (see also Section
17 to better understand the several
menus):
1. press the button for 2
seconds until the display starts
blinking;
2. press and release the button
several times until the desired
parameter is displayed;
3. use the or keys, to
change the value of the selected
parameter;
Setting range: 0,1 to 5,0
4. press to save the parameter
change before going to the next
parameter.
When the last parameter has been
reached and the button
pressed, the display will stop blinking
indicating exit from the menu.
NOTE: If no key is pressed for
more than 60 seconds, the control
automatically exits the “Users’ menu”.
Any parameter change not saved
using the button, will be lost.
The table below lists each “Users’
menu” parameter, what it affects and
its adjustment range.
Adjustment of the “Minimum heating
temperature” as shown in Figure 13-2 when
outdoor reset is active per section 13.9.
Adjustment of the “Maximum heating
temperature” as shown in Figure 13-2 when
outdoor reset is active per section 13.9.
Adjustment of the parallel shift of the curve as
shown in Figure 13-3 when outdoor reset is
active per section 13.9.
Display of the calculated heating temperature
when outdoor reset is active per section 13.9,
or display of the temperature set by knob “7”
shown in Figure 13-1.
Display of the domestic hot water temperature
when set by knob “11” shown in Figure 13-1.
Display of last error code registered, Section
13.18.2
Setting range: see section 13.10.3
Setting range: see section 13.10.3
The adjustment is made by turning knob “7” shown
in Figure 13-1. The selected curve can be shifted
up or down by 36 °F (20 °C).
Temperature display only, with a range between 68
°F (20 °C) and 189 °F (87 °C).
Temperature display only with a range between 104
°F (40 °C) and 158 °F (70 °C), see section 13.7.
Error code display per section 13.18.2
Display of last lockout occurred, Section
13.18.1
Lockout code per section 13.18.1
75
13 - USE
13.17 - “Installer’s
menu”
CAUTION!!!
parameters could cause the
boiler and therefore the system
to malfunction. For this reason,
only a qualifi ed technician who
has in-depth knowledge of the
boiler should change them.
The boiler’s micro-processor makes
this menu of parameters available
to the qualifi ed technician for the
analysis of the functioning and
adjustment of the appliance to the
system. When entering the “Installers’
Menu”, the display item “1” in Figure
13-1, will start to blink indicating that
a change of mode has taken place. To
access the “Installers’ Menu” just (see
also Section 17 to better understand
the several menus):
Changing these
1. press and hold the button
down for 12 seconds until the
parameter is displayed;
2. press and release the button
to scroll through the list of the
parameters;
3. once the parameter has been
displayed, it can be changed using
the or keys;
4. press and release the button
to confi rm the amended data before
moving to the next parameter.
When the last parameter has been
reached and the button
pressed, the display will stop blinking
indicating the exit from the menu.
NOTE: If no key is pressed for
more than 60 seconds, the control
automatically exits the “Installers’
menu”. Any parameter change not
saved using the button, will be
lost.
The next table lists each “Installers’
menu” parameter, what it affects and
its adjustment range.
PARAMETER DESCRIPTION INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1
Boiler temperature, measured by U1
sensor
DHW temperature, measured by U2
sensor
Domestic cold water (or ind. water heater)
temperature , measured by U3 sensor
Outdoor temperature, measured by U4
sensor
Ionization current value
High limit temperature, measured by U6
sensor
Flue gas temperature, measured by U7
sensor
Heating return temperature, measured
by U8 sensor
Type of basic setting of control board
Status of room thermostat contact
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed) (displayed only if outdoor reset is
active, as per section 13.9)
Value from 0 to 99 (cannot be changed)
(30 corresponds to a current of 1uA)
(99 corresponds to a current of 5.5 uA)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Can be changed in accordance with Section 11.6
00 = contact open (heating service off)
01 = contact closed (heating service on)
Measurement of fan speed rotation
BTU input for heating service
Value in g/1’/100 (rpm/100) (cannot be changed)
Adjustable according to the instructions of section 12.10
Continue
76
13 - USE
Continued
PARAMETER DESCRIPTION INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1
Reduction of temperature generated by
the opening of the room thermostat
Boiler knobs’ status
Display “1” and “2” as per fi gure 13-1
energy saver
Parameter disabled for this kind of boiler
Domestic sensitivity setting
Minimum domestic setpoint during sleep
mode
Proportional band of the heating PID
modulation
Keep always at value of 1
Can be changed from 16°F (-9°C) to 149°F (65°C) (active only with
outdoor reset).
See section 13.10.3 for its adjustment.
Can be changed: from 1°F (1°C) to 36°F (20°C) (active only with
outdoor reset featuring room compensation)
See section 13.10.6 for its adjustment.
Can be changed:
01 = knobs presents;
00 = knobs absent.
Can be changed: 00 = display always on; any other value,
corresponds to a delay in the switching off of the display, expressed
in minutes (see also Section 13.15)
No infl uence in this kind of boiler
No infl uence in this kind of boiler
Must be maintained at 20 value
Integral of the heating PID modulation
Burner Anticycling: minimum delay from
a burner light-off to the sequent light-on.
Value expressed in sec x 10
Indirect water heater priority selection:
Value expressed in minutes.
Must be maintained at 40 value
Can be changed between 1 and 54. Default value is 18 (180 sec).
Can be modifi ed only in conjunction with factory technicians.
Can be changed between 00 (function disabled) and 99 minutes.
Default value is 00 (See also section 9.1.1).
77
13 - USE
13.18 Diagnostics
During the normal operation of the
boiler, the display, of Figure 13-1,
continually shows the operating
status of the boiler as shown below
(see also section 17):
PARAMETER
PARAMETER REFERENCE DISPLAY READ OUT (ITEM “2”, FIGURE 13-1)
Boiler in stand-by mode or pause (no request for heating or
domestic hot water)
Anti-freeze function active
Boiler not in lock-out mode but in Attention mode.
System pressure too low, system must be fi lled. See section 13.1.
Domestic hot water service active
Heating service active
Boiler in lock-out mode. To reset it, press the
the lock-out occurs frequently, contact a professionally qualifi ed
technician
Blocking error. Contact a professionally qualifi ed technician. Blocking
errors automatically reset if the condition causing the block disappears
.
button. If
Boiler temperature (°F)
Boiler temperature (°F)
01 = Boiler temperature (°F) Domestic hot
water service active for more than 120
minutes. Turn domestic hot water to OFF
position to reinstate heating.
02 = Data connection interrupted between
cascade boilers
No display
Domestic hot water temperature (°F)
Heating temperature (°F)
Lock-out code (see section 13.18.1 for
decodifi cation).
Error code (see section 13.18.2 for
decodifi cation).
Auto-purging procedure that last 3 minutes in progress (see
section 13.4).
Boiler in Anti-legionella functioning (see section 13.12)
78
Boiler temperature (°F)
Storage tank temperature (°F)
13 - USE
13.18.1 - Diagnostics: “L” lock-outs
“L”
Code
L01
L02
L03
L04
L05
L06
Lock-out
description
No fl ame detected after
three ignition attempts.
Flame extinguishes three
times.
Boiler temperature is over
203° F (95°C).
Gas valve command relay
Safety relay
Flue gas sensor over
210°F (99°C)
Checks to make
Check:
a-correct gas supply pressure (see
section 12.7);
b-ignition spark (see section 14.4);
c-correct combustion air pressure (see
section 12.8);
d-120Vac at the gas valve;
e-resistance of the two gas valve coils
should be 0.18 kohm and 1.1 kohm;
f- If the burner lights, but goes out at the
end of the ignition attempt, check: that
the ionization current is set at a value
greater than 60 (follow procedure in
section 14.12.4)
Check:
a-that the ionization current is set
at a value greater than 60 (follow
procedure in section 14.12.4);
b-check that gas valve open fast
enough;
a-Check that the circulator pump is
working;
b-Check if the water fl ow is not less than
5 GPM
Check for correct polarity of the wires to
the pump. Try to switch the wires.
Check:
a - that the electrical resistance of the
fl ue gas sensor complies with the graph
in Section 14.13;
b - that the effi ciency of the boiler is
over 86%
Solutions
a-If the gas supply pressure is incorrect, it must be adjusted to
the correct pressure;
b-If spark is not present, check for correct ignition ectrode
position and gap as per section 14.4; If position is correct,
check for 120Vac at the supply of the spark generator.
c-if the combustion air pressure is incorrect, inspect the vent
system and eliminate any obstructions;
d-if the voltage to the gas valve is not 120Vac the power control
board must be replaced;
e-if the resitance of the gas valve coils is not 0.18 kohm and/or
1.10 kohm, the gas valve must be replaced.
f-If the ionization current is not greater than 60, confi rm that
the the CO2 content is adjusted properly (see section
12.9). Check the fl ame detection electrode (section 14.4)
and if necessary replace it, check the integrity of the fl ame
detection electrode electrical wires.
a-If the ionization current is not greater than 60, confi rm that
the the CO2 content is adjusted properly (see section
12.9). Check the fl ame detection electrode (section 14.4)
and if necessary replace it, check the integrity of the fl ame
detection electrode electrical wires.
b-Following procedure as per Section 14.12.4, check few times
if passing from low fi re to high fi re the fl ame estinguish. If
estinguish, change the gas valve.
a-If the circulator pump is bad, replace it, if is good, replace the
power control board.
b-If the water fl ow is less than 5 GPM check for any zone
valves that must be opened.
Replace the power control board
If the pump won’t run replace it. If the pump is good try to
replace the power control board.
a-If the fl ue gas sensor resistance does not correspond with the
correct values, replace it;
b-if the boiler effi ciency is less than 86% and the CO2 content
is correct, the primary heat exchanger has to be replaced
and proper water treatment methods employed to prevent
mineral build up on the water side
L07
L08
L09
L10
L12
L13
L14
L15
L16
L17
Electrical circuit of fl ue
gas sensor is interrupted
Spark generator relay
RAM memory
E2prom memory damaged
E2prom memory damaged
Program error
Program error
Program error
Program error
The temperature
difference between the
U1 and U6 sensors is too
great
Check that the electrical resistance of
the fl ue gas sensor corresponds with the
graph in section 14.13;
Check that:
a - the electrical resistance of the two
sensors corresponds with the graph in
section 14.13;
b -check that the heating water fl ow is
not too low.
79
If the sensor resistance does not correspond with the correct
values, replace it;
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
a-If one or both sensors does not have the correct resistance
value, it must be replaced;
b-If temperature difference between U1 and U8 is higher than
55°F at maximum input, the heating water fl ow rate is too
low. The heating water fl ow rate must be corrected.
13 - USE
13.18.1 - Diagnostics: “L” lock-outs (continued)
“L”
Code
L18
L19
L20
L21
L25
L32
L33
L45
L46
Lock-out
description
Program error
Flame sensed for 10
seconds, after the closure
of the gas valve
Flame sensed before
opening of the gas valve.
Boiler in blocking state for
more than 20 hours
U1 or U6 sensor increase
its temperature too fast
Program error
Fan rotation error
Heating circuit fi lling time
longer than 10 minutes.
Filling of heating circuit
repeated 16 times in 24
hours
Controls
Check:
a - that the heating water fl ow is not too
low;
b - that the circulator pump is working
Check that the voltage to the fan is
163(±10)Vdc.
Check:
a - that the heating pressure switch
setting pressure, FILL appears when
the pressure drops below 8.7 psi
(0,6 bar), and disappears when the
pressure rises above 22 psi (1.5
bar);
b - check that there are no water leaks
in the heating system.
Solutions
Replace the power control board
Call technical service
Call technical service
Press RESET button and check the blocking error “E” on
Section 13.18.2
a - If temperature difference between U1 and U8 is higher than
55°F (31°C), at maximum input, the heating water fl ow rate
is too low. The heating water fl ow rate must be corrected.
b - If the pump works, replace the power control board.
Replace the power control board
If the fan is powered with 163Vdc, replace the fan. If the voltage
to the fan is not 163 Vdc, replace the board.
a -If the heating pressure switch is not correctly set, it must be
replaced;
b - if the system has a leak, it must be fi xed.
L47
Flue pressure switch
open time longer than 60
minutes
Check:
a - that no obstructions are in the fl ue
discharge/air intake line
b - check the fl ue pressure switch
setting point, setting is 4.5 in.W.C
c - check that the electrical resistance of
the fl ue gas sensor corresponds with
the graph in section 14.13;
d - check that the electrical connection
cables between the fl ue pressure
switch, the fl ue sensor and the
power control board.
a -If ther’is an obstruction, it must be removed;
b - If the fl ue pressure switch is not correctly set, it must be
replaced;
c - If the fl ue sensor resistance does not correspond, it must be
replaced;
d - if the electrical circuit is damaged, it must be repaired;
if the previous four cases do not apply, replace the power
control board
80
13 - USE
13.18.2 - Diagnostics: “E” blocking errors
“E”
Code
E01
E02
E04
E07
Blocking
description
U1 boiler temperature
sensor circuit interrupted.
U2 domestic hot water
temperature sensor circuit
interrupted.
U8 return temperature
sensor circuit interrupted
U3 cold water or indirect
water heater sensor circuit
interrupted
Checks to make
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Solutions
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
E08
E11
E12
E13
U6 boiler temperature
sensor circuit interrupted.
U1 boiler temperature
sensor circuit shortcircuited.
U2 domestic hot water
temperature sensor circuit
short-circuited
Erroneous temperature
reading.
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
U3 cold water temperature
or indirect water heater
temperature sensor circuit
shorted
U6 boiler temperature
sensor circuit shorted
E2prom memory damaged
Flame presence with gas
valve closed
Phase and neutral inverted
Electrical supply frequency
other than 60Hz
Ground connection is
absent
Erroneous temperature
reading.
Checks to make
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.14;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Invert phase and neutral
Check the electrical frequency of the
system.
Check if CS parameter is at 03 (see
section 17)
Check if the boiler is properly grounded
Solutions
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
Replace the power control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board
Replace the command and control board
Replace the gas valve
If phase and neutral are correctly wired, replace the power and
control board
If the electrical supply frequency is other than 60Hz, contact
the electric company;
if the mains frequency is 60Hz, replace the command and
control board.
Make sure that the CS parameter is at 03.
if the boiler is properly grounded, replace the power control
board
Replace the power control board
E31
E32
E33
E42
E50
E51
E52
E53
Erroneous temperature
reading.
Erroneous temperature
reading.
Erroneous temperature
reading.
Program error
Error in the boiler tY
parameter selection
Reset button pressed too
often in a short period time
Heating fl ow switch
closed
Heating fl ow switch
open
Move ON switches 7 an set again the
correct tY value (see section 17)
Check if the heating pump is running.
Check if the fl ow switch contact is stuck
Check if the heating pump is running.
Check if the fl ow switch contact is
broken
82
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
If tY value is correct, change the power control board
The pump should not run and the contanct should open
The contact must be open
The pump should run and the contact should closed
The contact must be closed
14 - MAINTENANCE
14.1 - Care and
maintenance
This section must be brought to the attention
of the user by the installer so that the user
can make the necessary arrangements with
a qualifi ed service agency for the periodic
care and maintenance of the boiler. User
must check its boiler follow Table 14-1
column “User maintenance”.
The installer must also inform the user that
the lack of proper care and maintenance of
this boiler and any fuel burning equipment
may result in a hazardous condition.
Installer should discuss contents of the
Section 13 (User’s section) with the user.
Service and maintenance schedules
Service TechnicianUser maintenance
Annual Startup:
A trained and qualifi ed service technician
should perform the inspection listed in these
instructions before each heating season and
at regular intervals.
WARNING!!!
inspection and adjustment must
be done by a trained technician
in accordance with all applicable
local and national codes. Improper
servicing or adjustment could
damage the boiler! Failure to
comply with this warning can
result in a fi re or explosion
causing property damage,
personal injury or loss of life!
Servicing,
Daily:
WARNING!!!
combustible materials, gasoline or
any product containing fl ammable
vapors and liquids in the vicinity
of the boiler. Failure to comply
with this warning can result in
extensive property damage, severe
personal injury or death!