Slant/Fin VSL-160C User Manual Part C

Page 1
13 - USE
13.10.6 – Outdoor reset with room compensation
While in the “Installers’ Menu” (section
13.17) set the parameter to 02. The system will function exactly as described in the previous “Outdoor reset adjustment” sections except that now the boiler pump will stay on permanently . The opening of the room thermostat contacts will translate into a parallel downward movement of the curve in Figures 13-2 and 13-3. The value by which the curve moves downwards can be adjusted by the
parameter present in the
“Installers’ Menu”, see section 13.17. The parameter can range
from 1 °F (1 °C) to 36 °F, (20°C). The suggested values for this parameter are:
- 18 °F (10°C) for high temperature radiator systems;
- 6 °F (3°C) for low temperature radiant panel systems
Calculated temperature (°F)
Outside temperature (°F)
Figure 13-2 - Graph of the outdoor reset adjustment
(infl uence of parameters “br”, “OA”, “Ob” and “Oc”)
Calculated temperature (°F)
Outside temperature (°F)
Figure 13-3 - Graphs of the outdoor reset adjustment
(infl uence of parameter “b”)
V alues of this parameter that are too high may translate into room temperature instability . Values that are too low may make the action of the room thermostat ineffective.
Climatic adjustment with room compensation can be used in all the systems described in Section 13.10.1. The advantage being that the constant running of the pump will stabilize and standardize the room temperatures. This is especially true when some loops in the heating system have considerably greater volume than others.
OA = Slope of the line Ob = Minimum heating
temperature
Oc = Maximum heating
temperature
br = “Fix point” of the angle
fulcrum of the line
b = parallel shift of the line
(adjusted by the heating knob, item “7” of fi gure 13-1)
73
Page 2
13 - USE
13.11 - Boiler switch settings
The control board shown in Figure 3-1, item “14”, contains a series of switches that allow the boiler to be confi gured to match the application. The table below lists each switch and its corresponding funtions.
SWITCH Position Description
1 OFF Boiler without production of D.H.W ON Boiler with production of D.H.W. via storage tank 2 OFF Boiler with production of instantaneous D.H.W. ON Position not available for this serie of boilers 3 OFF Heating pressure switch, disabled ON Heating pressure switch, enabled 4 OFF EBM PAPST brand fan ON Position not available for this serie of boilers 5 OFF Combination boiler for heating and D.H.W. ON Boiler for heating only 6 OFF High temperature heating service, 86°F (30°C) to 176°F (80°C) ON Low temperature heating service, 68°F (20°C) to 113°F (45°C) 7 OFF Boiler confi guration change, disabled ON Boiler confi guration change, enabled 8 OFF Maximum heating supply water temperature of 176°F (80°C) ON Position not available for this kind of boilers
CAUTION!!!
of these switches could cause the boiler to malfunction resulting in improper system performance. Only a qualifi ed technician, with an in-depth knowledge of the boilers’ control system, should change them.
Improper setting
13.12 - Delays, alarms and protective actions
To protect the life of the appliance, improve comfort, and maximize energy savings, the following timings have been incorporated into the control logic: a - Pump delay: each time the room
thermostat is satisfi ed, the circulator pump continues to run for 1 minute;
b - DHW delay: each time the domestic
hot water demand is satisfi ed, a 2 minutes delay must pass before the heating service is allowed to restart;
c - Protection against legionnaires
bacteria: if the boiler is connected to a DHW storage tank the boiler will increase the tank temperature to 140 °F (60 °C) every seven days, prevent the formation of legionnaires bacteria. This function is displayed
by
d - DHW alarm: if the call for domestic
hot water lasts for longer than two hours, an
This function is only for boilers set up to provide instantaneous DHW.
.
01 alarm is generated.
e - Time delay in restarting the burner:
in its normal functioning state, except when providing domestic water, every time the burner stops, there is a delay time of 3 minutes before the boiler restarts again.
13.13 - Circulator pump and three way valve protection
During the summer months, the circulator is run once a day for around 15 seconds to prevent it from seizing. At the same time, the three way valve (if present) is activated for the same reason.
13.14 - Boiler’s Freeze protection
CAUTION!!!
protection function to work, the boiler must remain connected to the electrical and gas supplies with knobs “7” and “11” in Figure 13-1, in the OFF position.
For the freeze
CAUTION!!!
protection function is conceived to protect the boiler only, not the heating system.
CAUTION!!!
boiler’s freeze protection function depends from the electrical supply and from the gas supply, it is mandatory install a safety device that alarm the user in a case the boiler room will reach a temperature near 35°F (2°C)
Once the boiler has reached a temperature of 45 °F (7 °C), the heating pump will automatically comes on. If the temperature falls below 35 °F (2 °C), the burner will light to prevent the boiler from freezing. If the boiler will not be used for long time it should be drained per Sections
14.10 and 14.11.
This freeze
Because the
74
Page 3
13 - USE
13.15 - Display in energy saving mode
If desired, the display, item “1” and “2” in Figure 13-1, can be switched permanently off, with the exception of when it displays errors or settings. To switch the display off, access the “Installers’ Menu”, in section 13.17
and set the other than zero. Keep in mind that each value will correspond to a delay in minutes until the display goes into Energy Saving mode.
PARAMETER DESCRIPTION INFORMATION ON DISPLAY ITEM “2” of Figure 13-1
parameter at a value
Adjustment of the curve angel as shown in Figure 13-2 when outdoor reset is active per section 13.9.
13.16 - “Users’ menu”
When entering the “Users’ menu”, the display, item “1” in Figure 13-1, will start blinking indicating that a change of mode has taken place. To access the “Users’ menu” (see also Section 17 to better understand the several menus):
1. press the button for 2 seconds until the display starts blinking;
2. press and release the button several times until the desired parameter is displayed;
3. use the or keys, to change the value of the selected parameter;
Setting range: 0,1 to 5,0
4. press to save the parameter change before going to the next parameter.
When the last parameter has been reached and the button
pressed, the display will stop blinking indicating exit from the menu.
NOTE: If no key is pressed for more than 60 seconds, the control automatically exits the “Users’ menu”. Any parameter change not saved
using the button, will be lost. The table below lists each “Users’
menu” parameter, what it affects and its adjustment range.
Adjustment of the “Minimum heating temperature” as shown in Figure 13-2 when outdoor reset is active per section 13.9.
Adjustment of the “Maximum heating temperature” as shown in Figure 13-2 when outdoor reset is active per section 13.9.
Adjustment of the parallel shift of the curve as shown in Figure 13-3 when outdoor reset is active per section 13.9.
Display of the calculated heating temperature when outdoor reset is active per section 13.9, or display of the temperature set by knob “7” shown in Figure 13-1.
Display of the domestic hot water temperature when set by knob “11” shown in Figure 13-1.
Display of last error code registered, Section
13.18.2
Setting range: see section 13.10.3
Setting range: see section 13.10.3
The adjustment is made by turning knob “7” shown in Figure 13-1. The selected curve can be shifted up or down by 36 °F (20 °C).
Temperature display only, with a range between 68 °F (20 °C) and 189 °F (87 °C).
Temperature display only with a range between 104 °F (40 °C) and 158 °F (70 °C), see section 13.7.
Error code display per section 13.18.2
Display of last lockout occurred, Section
13.18.1
Lockout code per section 13.18.1
75
Page 4
13 - USE
13.17 - “Installer’s menu”
CAUTION!!!
parameters could cause the boiler and therefore the system to malfunction. For this reason, only a qualifi ed technician who has in-depth knowledge of the boiler should change them.
The boiler’s micro-processor makes this menu of parameters available to the qualifi ed technician for the analysis of the functioning and adjustment of the appliance to the system. When entering the “Installers’ Menu”, the display item “1” in Figure 13-1, will start to blink indicating that a change of mode has taken place. To access the “Installers’ Menu” just (see also Section 17 to better understand the several menus):
Changing these
1. press and hold the button down for 12 seconds until the
parameter is displayed;
2. press and release the button to scroll through the list of the parameters;
3. once the parameter has been displayed, it can be changed using
the or keys;
4. press and release the button to confi rm the amended data before moving to the next parameter.
When the last parameter has been reached and the button
pressed, the display will stop blinking indicating the exit from the menu.
NOTE: If no key is pressed for more than 60 seconds, the control automatically exits the “Installers’ menu”. Any parameter change not
saved using the button, will be lost.
The next table lists each “Installers’ menu” parameter, what it affects and its adjustment range.
PARAMETER DESCRIPTION INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1
Boiler temperature, measured by U1 sensor
DHW temperature, measured by U2 sensor
Domestic cold water (or ind. water heater) temperature , measured by U3 sensor
Outdoor temperature, measured by U4 sensor
Ionization current value
High limit temperature, measured by U6 sensor
Flue gas temperature, measured by U7 sensor
Heating return temperature, measured by U8 sensor
Type of basic setting of control board
Status of room thermostat contact
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed) Value in °F (cannot be changed) (displayed only if outdoor reset is
active, as per section 13.9) Value from 0 to 99 (cannot be changed)
(30 corresponds to a current of 1uA) (99 corresponds to a current of 5.5 uA)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Can be changed in accordance with Section 11.6 00 = contact open (heating service off)
01 = contact closed (heating service on)
Measurement of fan speed rotation
BTU input for heating service
Value in g/1’/100 (rpm/100) (cannot be changed)
Adjustable according to the instructions of section 12.10
Continue
76
Page 5
13 - USE
Continued
PARAMETER DESCRIPTION INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1
Can be changed (see Section 13.9):
Heating service functioning mode
00 = thermostatic adjustment; 01 = outdoor reset; 02 = outdoor reset with room compensation;
Reaction to external temperature
Angle fulcrum of climatic adjustment
Reduction of temperature generated by the opening of the room thermostat
Boiler knobs’ status
Display “1” and “2” as per fi gure 13-1 energy saver
Parameter disabled for this kind of boiler
Domestic sensitivity setting
Minimum domestic setpoint during sleep mode
Proportional band of the heating PID modulation
Keep always at value of 1 Can be changed from 16°F (-9°C) to 149°F (65°C) (active only with
outdoor reset). See section 13.10.3 for its adjustment.
Can be changed: from 1°F (1°C) to 36°F (20°C) (active only with outdoor reset featuring room compensation) See section 13.10.6 for its adjustment.
Can be changed: 01 = knobs presents; 00 = knobs absent.
Can be changed: 00 = display always on; any other value, corresponds to a delay in the switching off of the display, expressed in minutes (see also Section 13.15)
No infl uence in this kind of boiler
No infl uence in this kind of boiler
Must be maintained at 20 value
Integral of the heating PID modulation
Burner Anticycling: minimum delay from a burner light-off to the sequent light-on. Value expressed in sec x 10
Indirect water heater priority selection: Value expressed in minutes.
Must be maintained at 40 value
Can be changed between 1 and 54. Default value is 18 (180 sec). Can be modifi ed only in conjunction with factory technicians.
Can be changed between 00 (function disabled) and 99 minutes. Default value is 00 (See also section 9.1.1).
77
Page 6
13 - USE
13.18 ­Diagnostics
During the normal operation of the boiler, the display, of Figure 13-1, continually shows the operating status of the boiler as shown below (see also section 17):
PARAMETER
PARAMETER REFERENCE DISPLAY READ OUT (ITEM “2”, FIGURE 13-1)
Boiler in stand-by mode or pause (no request for heating or domestic hot water)
Anti-freeze function active
Boiler not in lock-out mode but in Attention mode.
System pressure too low, system must be fi lled. See section 13.1.
Domestic hot water service active
Heating service active
Boiler in lock-out mode. To reset it, press the the lock-out occurs frequently, contact a professionally qualifi ed
technician Blocking error. Contact a professionally qualifi ed technician. Blocking
errors automatically reset if the condition causing the block disappears
.
button. If
Boiler temperature (°F)
Boiler temperature (°F) 01 = Boiler temperature (°F) Domestic hot
water service active for more than 120 minutes. Turn domestic hot water to OFF position to reinstate heating. 02 = Data connection interrupted between cascade boilers
No display Domestic hot water temperature (°F)
Heating temperature (°F)
Lock-out code (see section 13.18.1 for decodifi cation).
Error code (see section 13.18.2 for decodifi cation).
Auto-purging procedure that last 3 minutes in progress (see section 13.4).
Boiler in Anti-legionella functioning (see section 13.12)
78
Boiler temperature (°F)
Storage tank temperature (°F)
Page 7
13 - USE
13.18.1 - Diagnostics: “L” lock-outs
“L” Code
L01
L02
L03
L04 L05
L06
Lock-out description
No fl ame detected after three ignition attempts.
Flame extinguishes three times.
Boiler temperature is over 203° F (95°C).
Gas valve command relay Safety relay
Flue gas sensor over 210°F (99°C)
Checks to make
Check: a-correct gas supply pressure (see
section 12.7); b-ignition spark (see section 14.4); c-correct combustion air pressure (see
section 12.8); d-120Vac at the gas valve; e-resistance of the two gas valve coils
should be 0.18 kohm and 1.1 kohm; f- If the burner lights, but goes out at the
end of the ignition attempt, check: that
the ionization current is set at a value
greater than 60 (follow procedure in
section 14.12.4)
Check: a-that the ionization current is set
at a value greater than 60 (follow
procedure in section 14.12.4); b-check that gas valve open fast
enough;
a-Check that the circulator pump is working; b-Check if the water fl ow is not less than 5 GPM
Check for correct polarity of the wires to the pump. Try to switch the wires.
Check: a - that the electrical resistance of the ue gas sensor complies with the graph in Section 14.13; b - that the effi ciency of the boiler is over 86%
Solutions
a-If the gas supply pressure is incorrect, it must be adjusted to
the correct pressure;
b-If spark is not present, check for correct ignition ectrode
position and gap as per section 14.4; If position is correct, check for 120Vac at the supply of the spark generator.
c-if the combustion air pressure is incorrect, inspect the vent
system and eliminate any obstructions;
d-if the voltage to the gas valve is not 120Vac the power control
board must be replaced;
e-if the resitance of the gas valve coils is not 0.18 kohm and/or
1.10 kohm, the gas valve must be replaced.
f-If the ionization current is not greater than 60, confi rm that
the the CO2 content is adjusted properly (see section
12.9). Check the fl ame detection electrode (section 14.4) and if necessary replace it, check the integrity of the fl ame detection electrode electrical wires.
a-If the ionization current is not greater than 60, confi rm that
the the CO2 content is adjusted properly (see section
12.9). Check the fl ame detection electrode (section 14.4) and if necessary replace it, check the integrity of the fl ame detection electrode electrical wires.
b-Following procedure as per Section 14.12.4, check few times
if passing from low fi re to high fi re the fl ame estinguish. If estinguish, change the gas valve.
a-If the circulator pump is bad, replace it, if is good, replace the power control board. b-If the water fl ow is less than 5 GPM check for any zone
valves that must be opened. Replace the power control board
If the pump won’t run replace it. If the pump is good try to replace the power control board.
a-If the fl ue gas sensor resistance does not correspond with the
correct values, replace it;
b-if the boiler effi ciency is less than 86% and the CO2 content
is correct, the primary heat exchanger has to be replaced and proper water treatment methods employed to prevent mineral build up on the water side
L07
L08 L09
L10 L12 L13 L14 L15 L16
L17
Electrical circuit of fl ue gas sensor is interrupted
Spark generator relay
RAM memory E2prom memory damaged
E2prom memory damaged Program error Program error Program error Program error The temperature
difference between the U1 and U6 sensors is too great
Check that the electrical resistance of the fl ue gas sensor corresponds with the
graph in section 14.13;
Check that: a - the electrical resistance of the two sensors corresponds with the graph in section 14.13; b -check that the heating water fl ow is not too low.
79
If the sensor resistance does not correspond with the correct values, replace it;
Replace the power control board Replace the power control board
Replace the power control board Replace the power control board
Replace the power control board Replace the power control board Replace the power control board Replace the power control board a-If one or both sensors does not have the correct resistance
value, it must be replaced;
b-If temperature difference between U1 and U8 is higher than
55°F at maximum input, the heating water fl ow rate is too low. The heating water fl ow rate must be corrected.
Page 8
13 - USE
13.18.1 - Diagnostics: “L” lock-outs (continued)
“L” Code
L18
L19
L20
L21
L25
L32 L33
L45
L46
Lock-out description
Program error
Flame sensed for 10 seconds, after the closure of the gas valve
Flame sensed before opening of the gas valve.
Boiler in blocking state for more than 20 hours
U1 or U6 sensor increase its temperature too fast
Program error Fan rotation error
Heating circuit fi lling time longer than 10 minutes.
Filling of heating circuit repeated 16 times in 24 hours
Controls
Check: a - that the heating water fl ow is not too
low;
b - that the circulator pump is working
Check that the voltage to the fan is 163(±10)Vdc.
Check: a - that the heating pressure switch
setting pressure, FILL appears when the pressure drops below 8.7 psi (0,6 bar), and disappears when the pressure rises above 22 psi (1.5 bar);
b - check that there are no water leaks
in the heating system.
Solutions
Replace the power control board
Call technical service
Call technical service
Press RESET button and check the blocking error “E” on Section 13.18.2
a - If temperature difference between U1 and U8 is higher than
55°F (31°C), at maximum input, the heating water fl ow rate is too low. The heating water fl ow rate must be corrected.
b - If the pump works, replace the power control board.
Replace the power control board
If the fan is powered with 163Vdc, replace the fan. If the voltage to the fan is not 163 Vdc, replace the board.
a -If the heating pressure switch is not correctly set, it must be
replaced;
b - if the system has a leak, it must be fi xed.
L47
Flue pressure switch open time longer than 60 minutes
Check: a - that no obstructions are in the fl ue
discharge/air intake line
b - check the fl ue pressure switch
setting point, setting is 4.5 in.W.C
c - check that the electrical resistance of
the fl ue gas sensor corresponds with the graph in section 14.13;
d - check that the electrical connection
cables between the fl ue pressure switch, the fl ue sensor and the power control board.
a -If ther’is an obstruction, it must be removed; b - If the fl ue pressure switch is not correctly set, it must be
replaced;
c - If the fl ue sensor resistance does not correspond, it must be
replaced;
d - if the electrical circuit is damaged, it must be repaired; if the previous four cases do not apply, replace the power
control board
80
Page 9
13 - USE
13.18.2 - Diagnostics: “E” blocking errors “E”
Code
E01
E02
E04
E07
Blocking description
U1 boiler temperature sensor circuit interrupted.
U2 domestic hot water temperature sensor circuit interrupted.
U8 return temperature sensor circuit interrupted
U3 cold water or indirect water heater sensor circuit interrupted
Checks to make
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Solutions
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
E08
E11
E12
E13
U6 boiler temperature sensor circuit interrupted.
U1 boiler temperature sensor circuit short­circuited.
U2 domestic hot water temperature sensor circuit short-circuited
Erroneous temperature reading.
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
Replace the power control board
81
Page 10
13 - USE
13.18.2 - Diagnostics: “E” blocking errors (continued)
“E” Code
E14
E15
E16 E17
E18
E19 E20
E21 E22
E23
E30
Blocking description
U8 return temperature sensor short-circuited
U4 outside sensor short­circuited
Erroneous temperature reading.
U3 cold water temperature or indirect water heater temperature sensor circuit shorted
U6 boiler temperature sensor circuit shorted
E2prom memory damaged
Flame presence with gas valve closed
Phase and neutral inverted
Electrical supply frequency other than 60Hz
Ground connection is absent
Erroneous temperature reading.
Checks to make
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current Check that the electrical resistance of the sensor corresponds with the graph in section 14.14; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Check that the electrical resistance of the sensor corresponds with the graph in section 14.13; check that the electrical connection cables between the sensor and the power control board have continuity and carry current
Invert phase and neutral Check the electrical frequency of the
system. Check if CS parameter is at 03 (see section 17)
Check if the boiler is properly grounded
Solutions
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
Replace the power control board If the sensor resistance does not correspond, it must be
replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
If the sensor resistance does not correspond, it must be replaced; if the electrical circuit is damaged, it must be repaired; if the previous two cases do not apply, replace the power control board
Replace the command and control board
Replace the gas valve
If phase and neutral are correctly wired, replace the power and control board
If the electrical supply frequency is other than 60Hz, contact the electric company; if the mains frequency is 60Hz, replace the command and control board. Make sure that the CS parameter is at 03.
if the boiler is properly grounded, replace the power control board
Replace the power control board
E31
E32 E33
E42 E50
E51
E52 E53
Erroneous temperature reading.
Erroneous temperature reading.
Erroneous temperature reading.
Program error
Error in the boiler tY parameter selection
Reset button pressed too often in a short period time
Heating fl ow switch closed
Heating fl ow switch open
Move ON switches 7 an set again the correct tY value (see section 17)
Check if the heating pump is running. Check if the fl ow switch contact is stuck
Check if the heating pump is running. Check if the fl ow switch contact is broken
82
Replace the power control board
Replace the power control board
Replace the power control board
Replace the power control board
If tY value is correct, change the power control board
The pump should not run and the contanct should open The contact must be open
The pump should run and the contact should closed The contact must be closed
Page 11
14 - MAINTENANCE
14.1 - Care and maintenance
This section must be brought to the attention of the user by the installer so that the user can make the necessary arrangements with a qualifi ed service agency for the periodic care and maintenance of the boiler. User must check its boiler follow Table 14-1 column “User maintenance”. The installer must also inform the user that the lack of proper care and maintenance of this boiler and any fuel burning equipment may result in a hazardous condition. Installer should discuss contents of the Section 13 (User’s section) with the user.
Service and maintenance schedules
Service Technician User maintenance
Annual Startup:
A trained and qualifi ed service technician should perform the inspection listed in these instructions before each heating season and at regular intervals.
WARNING!!!
inspection and adjustment must be done by a trained technician in accordance with all applicable local and national codes. Improper servicing or adjustment could damage the boiler! Failure to comply with this warning can result in a fi re or explosion causing property damage, personal injury or loss of life!
Servicing,
Daily:
WARNING!!!
combustible materials, gasoline or any product containing fl ammable vapors and liquids in the vicinity of the boiler. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
Never store
- Address reported problems (Follow section 14.1.1);
- Check all piping for leaks (Follow section 14.1.2)
- Verify fl ue and air lines in good condition and sealed tight (Follow section 14.1.3);
- Check system water pressure/system piping/ expansion tank (Follow section 14.1.4);
- Check control settings (Follow section 14.1.5);
- Check ignition and fl ame sense electrodes (Follow section 14.1.6);
- Check wiring and connections (Follow section
14.1.7);
- Perform performance verifi cation (Follow section
14.1.8);
- Flame inspection (Follow section 14.1.9);
- Check fl ame signal (Follow section 14.1.10);
- Clean the heat exchanger if fl ue temperature is more than 72°F (40°C) above return water temperature (Follow section 14.3).
- Clean condensate trap (Follow section 14.5).
- Check combustion air pressure (Follow section
12.8).
- Check relief valve (Follow section 14.1.11);
- Check for any air inside the domestic heat exchanger (Follow section 12.1.4);
- Check any domestic water softener if need any maintenance (follow softener’s manufacturer instructions)
- Check boiler area (Follow section 14.1.12);
- Check pressure gauge (Follow section 14.1.13);
Monthly:
- Check vent piping (Follow section 14.1.14);
- Check air piping (Follow section 14.1.15);
- Check condensate drain system (Follow section
14.1.16);
Every six month:
- Check boiler piping (gas and water) for leaks (Follow section 14.1.17);
End of season months:
- Shut boiler down (unless boiler used for domestic hot water) (Follow section 14.1.18);
Table 14-1 - Service and Maintenance Schedules
83
Page 12
14 - MAINTENANCE
WARNING!!!
obstruct the fl ow of combustion and ventilation air. Failure to provide adequate combustion air for this boiler can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
WARNING!!!
maintenance is performed on the vent-air intake system it must be properly reassembled and sealed. Failure to properly maintain the vent-air system can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
WARNING!!!
performing any maintenance operations, shut the boiler off, close the manual gas shut-off valve (Figure 11-1) and shut off electrical power to the boiler. Follow the Operating Instructions outlined in the section “SAFETY INSTRUCTIONS” (Beginning of the manual).
Never
If
Before
14.1.1 - Address reported problems
Inspect any problems reported by the owner and correct before proceeding.
14.1.2 - Check all piping for leaks
CAUTION!!!
or boiler leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
Eliminate all system
3. Check for gas leaks: using soap solution, check for gas leaks from meter to boiler including all pipes and ttings and boier connections. Use liquid soap solution for all gas testing.
WARNING!!!
check for gas leaks with an open fl ame. Use the bubble test. Failure to use the bubble test or check for gas leaks with an open fl ame can cause explosion, severe personal injury, death, or substantial property damage.
Do not
14.1.3 - Verify fl ue and air
lines in good condition and sealed tight;
1. Check for obstruction, condensation, corrosion and physical damage, water stains, any signs of rust, other corrosions or separation of the vent and air intake piping.
2. Check outside terminations. Screens and louvers should be free of any debris and must be cleaned as required.
14.1.4 - Check system
water pressure/system piping/expansion tank;
1. Check water piping and accessories for leaks. Slightest leaks should be corrected.
2. Check the system to be full of water and pressure to remain stable at correct setting on gauge.
14.1.5 - Check control
settings
1. Thermostat Test (control knobs items “7” and “11”, Figure 13-1): Set knobs setting to low enough to end call for heat. Gas valve should close and burner should stop fi ring. Fan go into a post purge, then shuts off.
2. Control Safety Shutdown test: with the burner fi ring, close the manual gas shut off valve (Figure 11-1) . Gas valve should close and burner should stop fi ring. The boiler will try for ignition three times after this, then should lock out with an “L 01” error shown on the display. Open the manual gas shut-off valve, and press the “Reset” button to return to normal operation.
84
14.1.6 - Check ignition and ame sense electrodes
1. Remove the fan-burner assembly unit (see section 14.3)
2. Remove any deposits accumulated on the ignition/fl ame sense electrode using sand paper.
3. Check electrodes positioning meet Section 14.4
14.1.7 - Check wiring and
connections
Inspect all boiler wiring, making sure wires are in good condition and securely attached.
14.1.8 - Perform
performance verifi cation.
1. Start boiler and perform a combustion test as per section 12.9.
2. Verify cold fi ll pressure is correct and that operating pressure does not go too high (could be a problem on the expansion tank).
14.1.9 - Flame inspection
1. Inspect fl ame through observation window.
2. If the fl ame is unsatisfactory at either high fi re or low fi re, clean the burner following section 14.3.
14.1.10 - Check fl ame
signal
1. Follow section 14.12.4 to check the ame signal.
2. At high fi re and low fi re the fl ame signal shown on the display should be within values given in Section 15, header “ionisation current”. A lower ame signal may indicate a fouled or damaged fl ame sense electrode. If cleaning the fl ame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the ame sense electrode.
14.1.11 - Check relief valve
Inspect the relief valve and lift the lever to verify fl ow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section
7.2.2 before proceeding further. Relief
vavle should be re-inspected at least once every three years, by a licensed
Page 13
14 - MAINTENANCE
plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the user.
WARNING!!!
re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
Failure to
14.1.12 - Check boiler area
WARNING!!!
potential of severe personal injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet.
If contaminants are found: Remove products immediately from the area. If they have been there for an extended period, call a qualifi ed service technician to inspect the boiler for possible damage from acid corrosion.
If products cannot be removed, immediately call a qualifi ed service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas.
1. Combustible/fl ammable materials -- Do not store combustible materials, gasoline or any other fl ammable vapors or liquids near the boiler. Remove immediately if found.
To prevent
2. Air contaminants -- Products containing chlorine or fl uorine, if allowed to contaminate the boiler intake air, will cause acidic condensate in the boiler. This will cause signifi cant damage to the boiler if allowed to continue. Read the list of potential materials listed in Section 10.2. If any of these products are in the room from which the boiler takes its combustion air, they must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another area.
14.1.13 - Check pressure
gauge
1. Make sure the pressure reading on the boiler pressure gauge does not exceed 25 psi. Higher pressure may indicate a problem with the expansion tank.
2. Contact a qualifi ed service technician if problem persists.
14.1.14 - Check vent
piping
1. Visually inspect the fl ue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualifi ed service technician at once if you fi nd any problems.
WARNING!!!
to inspect the vent system as noted above and have it repaired by a qualifi ed service technician can result in vent system failure, causing severe personal injury or death.
Failure
14.1.15 - Check air piping
1. Visually inspect the air inlet termination to be sure it is unobstructed. Inspect the entire length of air piping to ensure piping is intact and all joints are properly sealed.
2. Call your qualifi ed service technician if you notice any problems.
14.1.16 - Check condensate drain system
1. Inspect the condensate drain line, condensate fi ttings and condensate trap for signs of weeping or leakage.
2. If you detect signs of leakage, immediately contact your qualifi ed service technician to inspect the boiler and system.
14.1.17 - Check boiler
piping (gas and water)
1. If gas odor or leak is detected, immediately shut down the boiler following the procedures on page 3. Call a qualifi ed service technician.
2. Visually inspect for leaks around water piping. Also inspect the circulators, relief valve, and fi ttings. Immediately call a qualifi ed service technician to repair any leaks.
WARNING!!!
xed at once by a qualifi ed service technician. Failure to comply could result in severe personal injury, death, or substantial property damage.
Have leaks
14.1.18 - Shut boiler down
(unless boiler is used for Domestic Water)
1. Follow “To Turn Off Gas to Appliance” on page 3 of this manual.
2. Do not drain the system unless exposure to freezing temperatures will occur.
3. Do not drain the system if it is fi lled with an antifreeze solution.
4. DO NOT shut down boilers used for domestic water heating, they must operate year-round.
85
Page 14
14 - MAINTENANCE
14.2 - Removing the
casing
In order to remove the casing, follow the steps below while refering to Figure 14-1:
1. remove screws “A”;
2. raise latch “C”;
3. remove the front cover;
4. press the two plastic springs, item “L”, down;
5. lower the electrical box;
6. lift latch “G”;
7. pull the bottom of cover “H” out by around 4 in (10 cm);
8. lift cover “H” up by around 1in (2 cm) and remove it.
Figure 14-1 Removing the casing
86
Page 15
14 - MAINTENANCE
14.3 - Cleaning the burner and primary heat exchanger, ue gas side
Burner and primary heat exchanger must be checked every year and cleaned if required. To correctly clean the burner and the fl ue gas side of the heat exchanger follow the steps below:
WARNING!!!
proceeding to the next step, verify that the electrical supply to the boiler, and any other electrical supply near the boiler, is off. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
1. follow the steps in Section 14.2 to gain access to the sealing chamber;
2. unscrew nut “D” (Figure 14-2) from the gas valve (taking care not to lose gasket “E” in Figure 14-4);
3. disconnect the two wires from the ignition electrodes and the wire from the fl ame detection electrode, Figure 3-1, details “47” and “50”;
4. disconnect the wire from safety sensor “F” in Figure 14-2;
5. unscrew the four nuts “C” in Figure 14-2;
Before
6. prepare a suitable cover for the gas valve outlet under nut “D” so that no dirt, water, or other foreign objects can fall into the gas valve during cleaning;
7. remove the entire fan - burner assembly, detail “A” in Figure 14-2;
8. use a cylindrical brush with plastic bristles to clean the inside of the combustion chamber, detail “H” in Figure 14-2;
9. use a vacuum cleaner to remove any unburned residue from the combustion chamber “H” in fi gure 14-2;
10. using the same vacuum cleaner, clean the surfaces of the burner and around the electrodes;
WARNING!!!
performing the next step, carefully wash only the inside of the combustion chamber “H” of Figure 14-2, and do not get water on the outside of the combustion chamber opening. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
while
11. using only water, wash the inside of the combustion chamber, detail “H” in Figure 14-2. The water, will drain into the condensate drain. Clean the condensate trap (see Section 14.6) before reassembling components;
12. reassemble the components by proceeding in reverse order;
13. open the manual gas shutoff valve;
14. restore electrical power to the boiler;
15. check that there are no gas leaks.
WARNING!!!
an open fl ame to test for gas leaks. Always use an approved leak detection method. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Never use
Figure 14-2 Remove the fan-burner assembly unit
87
Page 16
14 - MAINTENANCE
14.4 - Correct
positioning of the ignition and ame detection electrodes
For the boiler to work properly the electrodes must be positioned as shown in Figure 14-3:
the distance between the ignition
electrodes “A” and “B”, must be between 0.08 in (2 mm), and 0.10 in (2.5 mm);
the distance of the ignition
electrodes to the burner surface must be between 0.20 in (5.0 mm), and 0.22 in (5.5 mm);
the distance of the fl ame detection
electrode to the burner surface must be between 0.23 in (6.0 mm), and 0.27 in (7.0 mm).
A = Left ignition electrode B = Right ignition electrode C = Flame detection electrode
Figure 14-3 Positioning electrodes on burner
(Use a hand caliper to verify the distances of the electrodes)
NOTE: To insure correct functioning of boiler the distances listed above shall be verifi ed with a hand caliper.
14.5 - Domestic
hot water heat exchanger (only for 160-C model)
The production of DHW takes place in the secondary heat exchanger, detail “42” in Figure 3-1. If this heat exchanger loses effi ciency over time, it may be necessary to clean or replace it.
88
Page 17
14 - MAINTENANCE
14.6 - Condensate trap cleaning
The condensate trap must be checked every year and cleaned if required. Follow the steps below to properly clean the condensate trap and its associated components while referring to Figure 14-4:
1. turn the power switch to on, item “12” in Figure 13-1;
2. press the and keys together for more than 10 seconds,
until a blinking is displayed;
3. the combustion blower will run at maximum speed for 10 minutes. During this time the burner will not light. This will minimize the amount of liquid present in the trap, item “A”;
4. press the button
WARNING!!!
proceeding to the next step, verify that the electrical supply to the boiler, and any other electrical supply near the boiler, is off. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
5. follow the steps in Section 14.2 to gain access the internal components;
6. carefully cover the electrical panel “B” with a waterproof material to prevent water from entering the electrical system;
7. grip spring clamp “G” with a pair of pliers and slide it downwards;
8. pull the condensation trap hose “H” off the trap;
9. remove the fan-burner assembly unit, follow steps of section 14.3;
10. cover the gas valve outlet to ensure that no objects or condensate water enters the gas valve;
11. disconnect the condensate hose “O” from the condensate trap “A”.
12. unscrew nut “I” from the bottom of the trap, “A”, and pull it upwards, taking care not to spill the condensation;
13. open the condensate trap taking care not to lose o ring “L” and clean the inside “M”;
14. re-assemble everything in reverse order, taking care that oring “L” is placed in the proper location;
15. refi ll the condensate trap per Section 12.1.2.
16. open the manual gas shutoff valve;
17. restore electrical power to the boiler;
18. check that there are no gas leaks.
Before
Figure 14-4 Removing the condensing trap
89
WARNING!!!
an open fl ame to test for gas leaks. Always use an approved leak detection method. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Never use
Page 18
14 - MAINTENANCE
Figure 14-5 Replacing the pump motor (only for 160-C model)
14.7 - Circulator
pump motor replacement (only for 160-C model)
To replace the circulator pump follow the steps below while, refering to Figure 14-5:
1. follow the steps in Section 14.10 to isolate and drain the water from the boiler;
2. follow the steps in Section 14.2 to gain access the internal components;
3. remove screws “B”;
4. remove the circulator pump motor “A”;
5. label the electrical wires of the circulator pump motor, phase and neutral must be respected;
6. disconnect the electrical wires from the circulator pump motor
7. install the new circulator pump motor and reassemble the boiler
8. open the heating system isolation valves and heating system fi ll valve
9. follow the steps in Section 12.1.3 to bleed the air from the heating system.
NOTE: If display shows L05 reverse polarity (phase and neutral) to the pump
90
14.8 - Expansion
tank pressure (only for 160-C model)
To check the expansion tank pressure follow the steps below:
1. follow the steps in Section 14.10 to isolate and drain the water from the boiler
2. follow the steps in Section 14.2, to gain access the internal components;
3. check the pressure of the expansion tank, item “4” of Figure 3-1 (The air inlet probe is on the top of the expansion tank). It must be 14 psi (1 bar). If the pressure is lower recharge the expansion tank while letting the water run out of the heating system drain valve.
Page 19
14 - MAINTENANCE
Figure 14-6 Supply fi ttings removal (only for 160-C model)
14.9 - 3-way valve
removal (only for 160-C model)
The 3-way valve, details “M” and “Q” in Figures 14-6 and 14-7, directs hot water produced by the primary heat exchanger to the heating circuit or to the secondary heat exchanger for the production of D.H.W. To replace or clean it, follow the steps below while referring to Figures 14-6 and 14-7:
1. follow the steps in Section 14.10 and 14-11 to isolate and drain the water from the boiler;
2. follow the steps in Section 14.2, to gain access the internal components;
3. disconnect fi ttings “A”;
4. remove screws “C”;
5. rotate “D” fl ange in the direction of the black arrow (See particular fi g.
1);
6. remove the bracket “E”;
5. remove fi tting “F”;
6. remove fi tting “L”;
7. remove fi tting “M” and check its state.
8. remove spring “N”;
9. remove servomotor “O”;
10. remove the fi tting “P”
11. remove the spring “Q” and check for any dirt.
Figure 14-7 3-way valve servomotor removal
91
Page 20
14 - MAINTENANCE
14.10 - Draining the heating side of the boiler
To drain the heating side of the boiler follow the steps below:
1. cool boiler turning knob “7” in Figure 13-1 to 114°F (45°C). Wait until the display, item “1” in Figure 13-1, shows a temperature less than 114°F (45°C);
2. turn off the boiler;
3. shut off electrical power to the boiler;
4. close the manual gas shutoff valve, Figure 11-1;
5. close the boiler isolation valves, in the heating system. If isolation valves haven’t been installed, the entire heating system will have to be drained.
6. close the heating system fi ll valve;
7. follow the steps in Section 14.2, to gain access the internal components;
8. connect a hose to the boiler drain valve intem “4” in Figure 7-6 and 7-7, and place the other end in a sink or some other suitable drain;
9. open the boiler drain valve and drain the boiler;
10. if boiler isolation valves have not been installed in the heating system open any bleed valves at the highest point of the system;
11. after draining out all the water, close the bleed valves and the boiler drain valve;
NOTICE: The boiler cannot be drained completely of water without purging the unit with an air pressure of 15 psi.
WARNING!!!
recover and/or re-use water drained from the heating circuit for any purpose as it could be contaminated. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Do not
14.11 - Draining the domestic hot water side of the boiler
To drain the domestic hot water side of the boiler follow the steps below:
1. turn off the boiler;
2. close the valve in the water main supplying the DHW system;
3. open all the hot and cold faucets in the building;
4. if there isn’t a faucet or drain valve below the boiler level, disconnect DHW connections “10” and “12” in Figure 3-1.
14.12 – Overrides
To carry out specifi c checks covered in the manual, it is possible to override the control logic of the boiler. See the following sections:
14.12.1 - Auto-purging
To reset the auto-purging procedure press the and keys
together for 10 seconds. When the blinking appears on the display,
press .
14.12.2 - Fan
To run just the fan at full speed press the and keys together
for 10 seconds, until the blinking
appears on the display. The fan will run at full speed for 10 minutes. To shut the fan off before the 10 minutes
is up press the
14.12.3 – Minimum and maximum output
The boiler can be run at its minimum or maximum output in both the heating and domestic hot water modes by following the steps below:
1. generate a demand for the mode to
be overridden:
- for heating turn up the room thermostat and turn knob “7” in Figure 13-1 to its maximum;
key.
- for domestic hot water turn knob “11” in Figure 13-1 to its maximum and fully open a hot water faucet;
2. press the and keys together for more than 10 seconds,
until a blinking appears on the display;
3. press the key until the display shows:
- for minimum heating output;
- for maximum heating output adjusted by P parameter, see section 12.10;
- for maximum heating output;
- for minimum DHW output;
- for maximum DHW output;
4. press the key in order to restore the boiler to normal running conditions.
14.12.4 – Checking the
ame current
While running at the minimum and maximum output described in Section
14.12.3, the display will show the
letter of the mode checked. In the second part of the display the value of the ionization current will be shown. 30 corresponds to a current of 1 uA, 99 to a current of 5.5 uA. The fl ame current must always be at the correspondent value as shown in Section 15, header “ionisation current”. If the value is not within the above values, check: a - positioning of the fl ame sensor
electrod as per section 14.4;
b - CO2 content as per section 12.9; c - combustion air pressure as per
section 12.8.
92
Page 21
14 - MAINTENANCE
14.13 - Water and
ue temperature sensor
The boiler has a number of sensors that measure temperature. The electrical resistance between the sensor wires must correspond with the values shown in Figure 14-8.
The temperature sensors are: U1; U2, U3, U5, U6, U7 and U8. The location of each sensor can be found in Figure 3-1 and Section 14.15 and 14.16.
Figure 14-8 Water temperature sensors’ curve
14.14 - Outdoor
temperature sensor (optional)
An outdoor temperature sensor can be connected to the boiler (see section 8.1.4). The electrical resistance existing between the sensor wires must correspond with the values shown in Figure 14-9.
Figure 14-9 Outdoor temperature sensor curve
93
Page 22
WARNING!!!
14 - MAINTENANCE
14.15 - Functional wiring diagram
WARNING!!!
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation! Verify proper operation after servicing Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
ATTENTION!!!
Au moment de l’entretien des commandes, étiquetez tous les fi ls avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S’assurer que l’appareil fonctionne adéquatement une fois l’entretien est terminé.
LEGEND: ALA - Alarm output
CM - Power control board CR - Remote command (only for outdoor models) EA - Ignition electrode ER - Flame detection electrode EPO - External pump (REQUIRED FOR MODEL 160-B) EV3V - External three way valve (optional) F1 - Fuse 2Amps FPS - Flue pressure switch GS - Spark generator IG - Main electrical switch J1 - Six poles connector J2 - Four poles connector J3 - Twelve poles connector J4 - Four poles connector J5 - Sixteen poles connector J10 - Ten poles connector J18 - Height poles connector U1 - Supply temperature sensor U2 - Domestic hot water temperature sensor U3 - Domestic cold water temperature sensor U3 TANK - Storage tank temperature sensor (optional) U4 - Outside temperature sensor (optional) U6 - Heating Safety high limit temperature sensor U7 - Flue gases temperature sensor with integrated safety
high limit switch U8 - Return temperature sensor PO1 - Heating pump PR - Heating pressure switch SDC - Electrical connection board RT1 - Room thermostat connection RT2 - Room thermostat connection on remote control
“CR” (optional) VE - Fan VG1 - Gas valve V3V - Three way valve
94
Page 23
14 - MAINTENANCE
95
Page 24
WARNING!!!
14 - MAINTENANCE
14.16 - Multiwire wiring diagram
WARNING!!!
wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation! Verify proper operation after servicing Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
ATTENTION!!!
de l’entretien des commandes, étiquetez tous les fi ls avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S’assurer que l’appareil fonctionne adéquatement une fois l’entretien est terminé.
Label all
Au moment
LEGEND: ALA - Alarm output
CM - Power control board CR - Remote command (only for outdoor models) EA - Ignition electrode ER - Flame detection electrode EPO - External pump (REQUIRED FOR 160-B model) EV3V - External three way valve (optional) F1 - Fuse 2Amps FPS - Flue pressure switch GS - Spark generator IG - Main electrical switch J1 - Six poles connector J2 - Four poles connector J3 - Twelve poles connector J4 - Four poles connector J5 - Sixteen poles connector J10 - Ten poles connector J18 - Height poles connector U1 - Supply temperature sensor U2 - Domestic hot water temperature sensor U3 - Domestic cold water temperature sensor U3 TANK - Storage tank temperature sensor (optional) U4 - Outside temperature sensor (optional) U6 - Heating Safety high limit temperature sensor U7 - Flue gases temperature sensor with integrated safety high limit switch U8 - Return temperature sensor PO1 - Heating pump PR - Heating pressure switch SDC - Electrical connection board RT1 - Room thermostat connection RT2 - Room thermostat connection on remote control “CR” (optional) VE - Fan VG1 - Gas valve V3V - Three way valve
96
Page 25
14 - MAINTENANCE
97
Page 26
15 - TECHNICAL DATA
MODEL VSL-160-B; VSL-160-C;
Country of destination USA and Canada Type of boiler Direct Vent and room combustion air Category of discharge chimney IV CSA certifi cate N° 2045300 (114696) Maximum Heat input Btu/hr 160,000 Minimum heat input Btu/hr 30,000 Effi ciency at maximum heat input (160°F/140°F) % 93 Maximum Heat output (160°F/140°F) Btu/hr 148,800 Effi ciency at minimum heat input (122°F/86°F) % 97 Minimum heat output (122°F/86°F) Btu/hr 29,100 Certifi ed AFUE rate % 91.5 Gas fl ow rate Natural gas ft3/hr 156 LP Gas gal/hr 1.75 Gas supply pressure Natural gas In.W.C. 7 LP Gas In.W.C. 11 Minimum gas supply pressure Natural gas In.W.C. 3 LP Gas In.W.C. 3 Maximum gas supply pressure Natural gas In.W.C. 13 LP Gas In.W.C. 13 Combustion air pressure with min. length Natural gas In.W.C. 2.5 to 3.1 LP Gas In.W.C. 2.1 to 2.7 Combustion air pressure with max. length Natural gas In.W.C. 2.1 to 2.7 LP Gas In.W.C. 1.8 to 2.4 Instantaneous d.h.w production [rise 75°F (42°C)] gal/min 4.32 Maximum heating temperature °F 189 Minimum heating temperature °F 68 Maximum heating pressure PSI 30 Minimum heating pressure PSI 8 Maximum pressure of domestic hot water circuit PSI 150 Minimum pressure of domestic hot water circuit PSI 1 Capacity of expansion tank (160-C model only) gal 2.64 Supply voltage 120Vac - 60Hz Absorbed electric power W 170 Flue gas pipes diameter (split) “ (mm) 3.15” (80) Max. length fl ue gas pipes (split) ft 300 Flue gas pipes diameter (coaxial) “ (mm) 2.36/3.94 (60/100) Max. length fl ue gas pipes (coaxial) ft 70 Equivalent length of one elbow ft 45° elbow = 3ft, 90° elbow = 5ft CO (Carbon monoxide) with natural gas ppm <150 CO (Carbon monoxide) with LP gas ppm <250 NOx (0% O2 with natural gas) ppm <30
CO2 (Carbon dioxide) for Natural gas at high fi re % 9.1 to 9.3 CO2 (Carbon dioxide) for Natural gas at low fi re % 8.4 to 9 CO2 (Carbon dioxide) for LP gas at high fi re % 9.3 to 9.7 CO2 (Carbon dioxide) for LP gas at low fi re % 9.2 to 9.8 O2 (Oxygen) for Natural gas at high fi re % 4.4 to 4.6 O2 (Oxygen) for Natural gas at low fi re % 5.1 to 5.7 O2 (Oxygen) for LP gas at high fi re % 5.7 to 5.9 O2 (Oxygen) for LP gas at low fi re % 6.1 to 6.7 Ionisation current 71 to 90
Maximum fl ue gas temperature °F 210 Flue gas mass-fl ow lb/hr 160 Head pressure available for fl ue vent/air intake line In.W.C. 3.6 Maximum condensation fl ow rate gal/hr 1.32 Average acidity of condensation PH 4 Boiler weight (empty of water) (160-C model) lb 125 Boiler weight (empty of water) (160-B model) lb 93
98
Page 27
16 - SPARE PARTS
99
Page 28
16 - SPARE PARTS
100
Page 29
16 - SPARE PARTS
101
Page 30
16 - SPARE PARTS
Bottom side of the 160-B model
Spare parts list
1 - 81 9010 000 - CABLE UL IGNITOR CONN 90° L155 2 - 81 9011 000 - NUT ZINC COATED 6MA 3 - 81 9012 000 - SILICONE PIPE D 4X8 4 - 81 9013 000 - TEE FOR DRY WATER CONDENSATION 5 - 81 9014 000 - SPARK GENERATOR NO CABLE UL 6 - 81 9015 000 - SENSOR NTC 10 KOHM A KLIP DIAM.22 7 - 81 9016 000 - COPPER PIPE D22 M/F 3/4”G-1”G 8 - 81 9017 000 - 3/4” RING NUT 9 - 81 9018 000 - O-RING NBR 2,62 X 20,63 10 - 81 9019 000 - PRIMARY HEAT EXCHANGER C.R.R ASME 11 - 81 9020 000 - GASKET EPDM X OSSIDO D84 H7 12 - 81 9021 000 - SENSOR NTC 10 KOHM 1/8” 13 - 81 9022 000 - GASKET COPPER 1/8” SP.1,5 14 - 81 9023 000 - SILICONE TAP 15 - 81 9024 000 - SCREW 6X35 ZINC TC-CR 16 - 81 9025 000 - WASHER 6X18X1,5 PIA-ZIN-LAR UNI6593 17 - 81 9026 000 - BRACKET SIPHON L84 H130 P32
18 - 81 9027 000 - O-RING 134 EPDM 3,53 X 25,8 19 - 81 9028 000 - SCREW SELFTAPPING 3.9 X 9.5 CROSS HEAD 20 - 81 9029 000 - SIPHON 21 - 81 9030 000 - SCREW SELFTAPPING 2.9 X 6.5 CROSS HEAD 22 - 81 9031 000 - SPRING 28,7 23 - 81 9032 000 - PRESSURE SWITCH ON 4,5 INWC 24 - 81 9033 000 - BRACKET PRESSURE SWITCH 25 - 81 9034 000 - POLIETYLENE PIPE L=1000 26 - 81 9035 000 - SEALING CHAMBER DOOR 27 - 81 9036 000 - 1P GASKET 28 - 81 9006 000 - PUMP GRUNDFOS UP 15/58U BRUTE USA 29 - 81 9038 000 - COPPER PIPE D22 RETURN SEALING CHAMBER 30 - 81 9039 000 - SENSOR NTC 10K BAIO 31 - 81 9040 000 - OUTDOOR SENSOR 32 - 81 9041 000 - SCREW 4,8X19 ZINC AF TC-CR UNI6954 33 - 81 9042 000 - PLUG FOR FLUE AIR FITTING 34 - 81 9043 000 - O-RING 2050 EPDM 1,78 X 12,42 35 - 81 9044 000 - DISCHARGE RACCORD PP 36 - 81 9045 000 - GASKET ROUND SPONGE D.3,5 MM IP44 S3 37 - 81 9046 000 - AUTOMATIC AIR VENT
102
Page 31
16 - SPARE PARTS
38 - 81 9047 000 - 3/8G MALE to 1/8NPT FEMALE BUSHING 39 - 81 9048 000 - GASKET EPDM D38 F20 SP6 40 - 81 9049 000 - 45xx WALL MOUNTING BRACKET 41 - 81 9050 000 - SCREW SELFTAPPING 5X50 WOOD 42 - 81 9051 000 - EXP TANK LT. 8 561X203X80 RETT. 43 - 81 9052 000 - GLASS WINDOW WITH GASKET 44 - 81 9053 000 - 3/8” G GASKET 45 - 81 9054 000 - FAIRLEAD 6 POLES SILICONE 46 - 81 9055 000 - EXP TANK PIPE 47 - 81 9056 000 - PLASTIC CAP TPP 8.5 48 - 81 9057 000 - TANK SENSOR 49a - 81 9058 000 - EXTERNAL JACKET 500X840X245 WITHOUT DOOR 50 - not used 51 - not used 52a - 81 9191 000 - VSL 160 LP TO NATURAL CONVERSION KIT 53a - 81 9190 000 - VSL 160 NATURAL TO LP CONVERSION KIT 54a - 81 9063 000 - VSL 160 USER’S INSTRUCTIONS 55a - 81 9506 000 - VSL 160 INSTALLER’S INSTRUCTIONS FROM S/N 12130000 56 - 81 9065 000 - BURNER HEAD 57 - 81 9066 000 - EXTRUSION L.25MM 58 - 81 9067 000 - THERM. INSULATION VERMICULITE D117 F74 SP21,5 59 - 81 9068 000 - GASKET. SIL. D157 F145 H6,7 60 - 81 9069 000 - BASE MANIFOLD AIR ALUMINUM 61 - 81 9070 000 - GASKET SIL.MANIFOLD FAN D83 SP3,5 62 - 81 9071 000 - SCREW SELFTAPPING 4X12 TC S-TT UNI-8112 63 - 81 9072 000 - MANIFOLD AIR CUTTED 64 - 81 9073 000 - MIXER AIR/GAS “COSMOMIX” 65 - 81 9074 000 - O-RING 3350 NBR 2,62 X 88,57 66 - 81 9075 000 - O-RING 3200 NBR 2,62 X 50,47 67 - 81 9076 000 - DIAPHRAGM COSMOMIX 9 HOLES D.10 68 - 81 9077 000 - O-RING 165 NBR 3,53 X 61,91 69 - 81 9078 000 - FAN 45 KW USA 70 - 81 9079 000 - BACK FLUE-GASES PREVENTER 71 - 81 9080 000 - O-RING 3825 SIL 2,62 X 209,22 72 - 81 9081 000 - COVER MANIFOLD AIR ALUMINUM 73 - 81 9082 000 - SCREW SELFTAPPING 4X10 TC S-TT UNI-8112 74 - 81 9083 000 - SELFTAPPING BOLT 6.3X38 75 - 81 9084 000 - GASKET FRIZITE D15,5 F11,5 SP1,5 76 - 81 9085 000 - GLASS PIREX D15,5 SP3,3 77 - 81 9086 000 - FLANGE L21,2 H34 78 - 81 9087 000 - SCREW SELFTAPPING 4X8 TC S-TT NI-8112 79 - 81 9088 000 - LEFT IGNITION ELECTRODE 80 - 81 9089 000 - RIGHT IGNITION ELECTRODE 81 - 81 9090 000 - DETECTION ELECTRODE 82 - 81 9091 000 - SCREW 5X12 EXAGONAL HEAD 83 - 81 9092 000 - SPRING MIXER 84 - 81 9093 000 - O-RING 3056 NBR (118) 2,62X13,95 85 - 81 9094 000 - GAS PIPE (SIT) USA 86 - 81 9095 000 - GASKET 3/4P 24X15X2 KLINSIL 87 - 81 9096 000 - SCREW 4X10 ZINC TC-CR 88 - 81 9097 000 - FLANGE GAS 32X32 3/4P 89 - 81 9098 000 - O-RING 130 2,62 X 22,22 90 - 81 9099 000 - GAS VALVE SIGMA848 120V 91 - 81 9100 000 - BOLT 5X12 CROSS HEAD 92 - 81 9101 000 - PIPE D18 F/F 3/4P-3/4P SIT USA 93 - 81 9102 000 - CONTROL KNOB S3 94 - 81 9103 000 - O-RING NBR 1,6 X 11,1 95 - 81 9104 000 - FRONT INTERFACE 96 - 81 9105 000 - TREE POTMETER-KNOB 97 - 81 9106 000 - KEYS RUBBER 3 POSITIONS 98 - 81 9107 000 - PRESSURE GAUGE DIAM.38 - 1/4” PSI 99 - 81 9108 000 - MAIN SWITCH 100 - 81 9109 000 - BASE ELECTRICAL BOX 101 - 81 9110 000 - FAIRLEAD SX 102 - 81 9111 000 - FAIRLEAD DX 103 - 81 9112 000 - POWER CONTROL BOARD PHC 120V 104 - 81 9113 000 - SCREW 4X8 ZINC TC-CR DIN4042 105 - 81 9114 000 - JUNCTION BOARD 45 106 - 81 9115 000 - INTERFACE OPENTERM 107 - 81 9116 000 - COVER ELECTRICAL BOX 108 - 81 9117 000 - FAIRLEAD 7 EXIT 109 - 81 9118 000 - COVER JUNCTION BOX 110 - 81 9119 000 - COPPER PIPE D.22 SUPPLY SEALING CHAMBER 111 - 81 9120 000 - 3 WAY VALVE MOTOR 120V 112 - 81 9121 000 - PLUG PISTON BODY OT. 113 - 81 9122 000 - SPRING FORCK 3V
114 - 81 9123 000 - UPPER PISTON 115 - 81 9124 000 - HYDRONIC SUPPLY GROUP. 116 - 81 9125 000 - HEATING PRESSURE SWITCH 117 - 81 9126 000 - GASKET COPPER 1/4P 118 - 81 9127 000 - SCREW 5X18 ZINC TC-ES-INC UNI5931 119 - 81 9128 000 - ASME SAFETY RELIEF VALVE 120 - 81 9129 000 - BRASS NIPPLE 1” - 3/4” 121 - 81 9130 000 - COVER PISTON HEATING 122 - 81 9131 000 - PISTON HEATING SIDE 123 - 81 9132 000 - PLUG BRASS 1/4P M WITH O-RING 124 - 81 9133 000 - NIPPLE OT 1”-22X1,5 MM 125 - 81 9134 000 - O-RING 2075 EPDM 1,78 X 18,77 126 - 81 9135 000 - HYDRONIC RETURN GROUP 127 - 81 9136 000 - BY-PASS VALVE 128 - 81 9137 000 - 3/8” MALE CAP 129 - 81 9138 000 - DOMESTIC HEAT EXCHANGER “ACQUAJET” 130 - 81 9139 000 - SENSOR NTC 10 KOHM KLIP WITH SCREW 131 - 81 9140 000 - NUT ZINC COATED 4MA 132 - 81 9141 000 - O-RING 3037 EPDM 2,62 X 9,19 133 - 81 9142 000 - PURGING PIPE 134 - 81 9143 000 - PURGING VALVE M10X1 135 - 81 9144 000 - FORCK BY-PASS PIPE 136 - 81 9145 000 - BY-PASS PIPE 137 - 81 9146 000 - O-RING 4075 EPDM 3,53 X 18,64 138 - 81 9147 000 - FRONT THERM. INSULATION “ACQUAJET” 139 - 81 9148 000 - REAR THERM. INSULATION “ACQUAJET” 140 - 81 9149 000 - BRACKET EXAGONAL HOLES SHORT 141 - 81 9150 000 - BRACKET EXAGONAL HOLES LONG 142 - 81 9151 000 - NIPPLE OTT 3/4NPT-3/4P USA 143 - 81 9152 000 - BRACKET EXAGONAL HOLE SMALL 144 - 81 9153 000 - 1/2” G GASKET 145 - 81 9154 000 - FAIRLEAD PA 107 SCREW HILO 3,5X14,5 146 - 81 9155 000 - CONNECTION BRASS 3/4P TO 1P 147 - 81 9156 000 - CONNECTION BRASS 1/2P TO 1P 148 - 81 9157 000 - 3/4” NUT 149 - 81 9158 000 - SCREW 6X8 ZINC TC-CR DIN7985 150 - 81 9159 000 - COPPER PIPE 1P TO 3/4P 151 - 81 9160 000 - BRASS 3/4P FEMALE TEE 152 - 81 9161 000 - HYDRONIC SUPPLY GROUP ONLY HEAT 153 - 81 9162 000 - 1/2P CAP 154 - 81 9163 000 - 1/2”-1/4” FF BRASS FITTING 155 - 81 9164 000 - PLUG BRASS 3/4P F 156 - 81 9165 000 - BRASS ELBOW 3/4P MF 157 - 81 9166 000 - 3/4 NUT 158 - 81 9167 000 - PLUG BRASS 3/8P F 159 - 81 9168 000 - HYDRONIC RETURN GROUP ONLY HEATING 162 - 81 9169 000 - BRASS 1/2P MALE CAP 163a – 81 9188 000 - 9.1MM NATURAL GAS INJECTOR 163b – 81 9189 000 - 5.7MM LP GAS INJECTOR 164 - 81 9200 000 - 2.62X13.10 NBR O-RING 165 – 81 9192 000 - Ø6/4-1/4”FEMALE FITTING 166 – 81 9193 000 - 1/4” TAP 167 – 81 9194 000 - Ø6/4-Ø6/4-1/8”MALE TEE FITTING 168 – 81 9195 000 - 4X6 PTFE FLEXIBLE PIPE 169 – 81 9196 000 - 24X17X2 AISI316L WASHER 170 – 81 9197 000 - 24X17X1.5 AISI316L WASHER 171 – 81 9198 000 - 1/2”-1/4” MF BRASS FITTING 172 – 81 9199 000 - Ø6/4-1/4”MALE BRASS ELBOW FITTING (WITH VITON O-RING)
If replacement parts are needed
When parts are needed, refer to boiler model and serial number shown on the boiler name/rating plate. Control identifi cation and replacement should be attempted only by a qualifi ed technician. Relief/Safety valves must be ASME rated for the pressure and gross output of the boiler.
103
Page 32
17 - READ OUT FLOW CHART
Only fan
in run
Heating
at low
re
Heating
at regul.
re
Heating
at high
Supply
temp.
D.H.W.
temp.
D.C.W.
re
Domestic
at low
temp./ tank
temp.
re
Domestic
Outdoor
temp.
Curve
angle
at high
re
Ionisation
current
Min.
heat.
Domestic
at high
re
High limit
temp.
Max.
temp.
heat.
temp.
Flue
temp.
Return
temp.
Basic
setting
Room
therm.
state
Push and hold together the + and -
keys, for a time, in seconds, indicated
Push and hold the RESET
key for a time, in seconds,
Push and release the - key
by the number
indicated by the number
Push and release the + key
Push and release the RESET
key
Overrides menu (see
section 14.12)
Installer’s menu
(see section 13.17)
Parallel shift
Central heating
temp. setting
D.H.W. temp.
setting
Calculated heat.
temp.
D.H.W. temp.
setting
Last blocking error
Last lock out error
User’s menu, with outdoor
reset, CH settings to 01 or
02 (see section 13.16)
User’s menu, with
104
thermostatic CH
settings to 00 (see
section 13.16)
Boiler in stand-by
Read out in normal
operating condition
(see section 13.18 )
Domestic hot water
Page 33
17 - READ OUT FLOW CHART
Setting
output for
Fan speed
rpm/100
heating
Heating
service
mode
Reaction
to outdoor
temp.
Angle
fulcrum
Heat. temp.
reduction by
open RT
State of the
knobs
Energy
saver
display
Disabled
parameter
Domestic sensitivity
regulator parameter
Minimum domestic
stpoint in sleep mode
Heating proportional
band setting
Heating integral band
setting
Anty cicling during
central heating
DHW priority selection
Last blocking error
Last lock out error
Central heating
Anti Freeze protection
Lock-out
Blocking error
D.H.W. active more than
120 min.
Anti legionella protection
105
Page 34
17 - READ OUT FLOW CHART
CAUTION!!!
Changing these parameters could cause the boiler and therefore the system to malfunction. For this reason, only a qualifi ed technician who has in-depth knowledge of the boiler should change them.
The boiler’s micro-processor makes this menu of parameters available to the qualifi ed technician for the setting of the appliance . To enter this menu you must:
1. turn the main electrical supply Off;
2. move the switch #7 (see Figure 9-2, item “D”) to the ON position;
3. turn the main electrical supply On.
Basic functionalities selection and Speed blower selection (see below for more explications)
Main electrical supply and temperature unit selection (see below for more explications)
Domestic functionalities selection. Must be always at 00
Master or slave selection in a module confi guration. Must be always at 00.
Rotating selection in a module confi guration. Must be always at 00.
Now “ty” is displayed. Use plus and minus keys to change the value; use RESET key to save the value and swap to the next parameter. To exit this menu you must:
1. turn the main electrical supply Off;
2. move the switch # 7 (see Figure 9-2, item “D”) to the Off position;
may assume the follow values: 61 - for boilers at NATURAL gas; 62 - for boilers at LP gas;
may assume the follow values: 00 - 230Vac, 50Hz, °C; 01 - 230Vac, 50Hz, °F; 02 - 120Vac, 60Hz, °C; 03 - 120Vac, 60Hz, °F
may assume the follow values: 00, 01 and 02. Must be always at 00.
Heating Water Flow Switch. (Function present only for certain boilers) (See below for more explications)
Outdoor temperature sensor range (See below for more explications)
If readable, may assume the follow values:
00, 01, 02, 03, 04, 05, 06, 07 and 08. Must be always at
00.
if readable, may assume the follow values:
00 = Flow Switch disabled; 01 = Flow Switch enabled;
if readable, may assume the follow values: 00 = Outdoor minimum temperature of 14°F; 01 = Outdoor minimum temperature of -39°F; (add a 68 kohm 1/4W resistor in parallel with the outdoor sensor).
If readable, may assume the follow values:
00, 01, 02, 03, 04, 05, 06, 07 and 08. Must be always at
00.
106
Page 35
NOTE
107
62403559 R00 May 03, 2012
Page 36
©Slant/Fin Corp. 2013
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Loading...