Slant/Fin VSL-160C User Manual Part B

10 - INSTALLATION - Vent and combustion air
2. insert the clamp “D” into convertor “A” in the “C” side.
3. insert the adapter “E” into connection “C” of the convertor “A”;
4. use the precedent clamp “D” to mechanically secure the adapter “E” to the adapter “A”. To do this tighten the half clamp on the adapter “A” and half clamp on the adapter “E”.
Tight the clamps with a tork of 1.5 - 2 lbf ft (2-3 Nm).
5. insert the clamp “F” into convertor “E”.
6. insert the air inlet PVC/CPVC pipe, for 2” into the adapter “E”;
7. use the precedent clamp “F” to mechanically secure the pipe to
the adapter “E”. To do this tighten the half clamp on the pipe and half clamp to the adapter “E”. Tight the clamps with a tork of 1.5 - 2 lbf ft (2-3 Nm).
Vent connection (see Figure 10-8 Item “B”). This connection
is used to provide a passageway for conveying combustion gas to the outside. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate. To connect a PVC/CPVC pipe to the vent connection proceed as follow while referring to Figure 10-8:
1. install boiler adapter “A” above boiler. Rotate boiler adapter “A” so as air intake and vent connections are in the desired left or right side. Check stamped arrow to understand which is the vent and air intake connection.
A = Two pipes boiler adapter B = Flue exhaust connection C = Air intake connection D = Fixing clamp E = PVC/CPVC adapter F = Fixing clamp G = PVC/CPVC pipe H = 90° elbow
WARNING!!!
arrow on boiler adapter for the correct side of fl ue exhaust and air intake. Failure to follow this warning could result in excessive levels of carbon monoxide or a re, which can result in severe personal injury or death!
WARNING!!!
PVC/CPVC exhaust pipe nor install into an enclosure or any other obstruction thereby preventing the cooling of the exhaust pipe. Failure to follow this warning could result in excessive levels of carbon monoxide or a fi re, which can result in severe personal injury or death!
Check stamped
Do not insulate
WARNING!!!
stamped arrow on boiler adapter for the correct side of vent. Failure to follow this warning could result in excessive levels of carbon monoxide or a fi re, which can result in severe personal injury or death!
2. Insert one side of clamp “D” onto the air intake of boiler adapter “A” (side C).
3. Insert adapter “E” into side “C” of boiler adapter “A”;
4. Use clamp “D” to mechanically secure adapter “E” to boiler adapter “A”. To do this, tighten one side of clamp “D” onto boiler adapter “A” and the other half of clamp “D” onto adapter “E”. Tight the clamps with a tork of 1.5 - 2 lbf ft (2-3 Nm).
5. Insert clamp “F” into adapter “E”.
6. Insert the PVC/CPVC pipe “G”, into adapter “E” for at least 2”;
7. Use clamp “F” to mechanically secure pipe “G” to adapter “E”. To do this, tighten one side of clamp “F” onto pipe “G” and the other side of clamp “F” to the adapter “E”. Tight the clamps with a tork of 1.5 - 2 lbf ft (2-3 Nm).
Check
Figure 10-8 PVC/CPVC Venting connection
37
10 - INSTALLATION - Vent and combustion air
10.8 - Stainless steel vent piping materials
WARNING!!!
materials, vent systems, and terminations listed in Tables 10-1 and 10-2. DO NOT mix vent systems of different types or manufacturers, unless listed in this manual. Failure to comply could result in severe personal injury, death, or substantial property damage.
Use only the
WARNING!!!
appliance requires a special venting system. The fi eld provided vent fi ttings must be connected to the boiler following Section 10.8.1. Failure to follow this warning could result in fi re, personal injury, or death.
WARNING!!!
installation of Stainless steel systems may result in injury or death.
WARNING!!!
water-based lubricants on joints. Never use hydrocarbons-based lubricants because they would destroy gaskets. follow this warning could result in excessive levels of carbon monoxide, which can result in severe personal injury or death!
This
Improper
Use only
Failure to
A = Flue exhaust connection B = Combustion air intake connection C = Fixing clamp D = Stainless steel elbow E = Stainless steel adaptor F = Stainless steel extension G = Air intake pipe
WARNING!!!
arrow on boiler adapter for the correct side of fl ue exhaust and air intake. Failure to follow this warning could result in excessive levels of carbon monoxide or a re, which can result in severe personal injury or death!
Check stamped
NOTICE Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
For installation in Canada, vent pipe system must be certifi ed to ULC-S636 (see Table 10-1).
NOTICE All vent pipes connections must be secured following manufacturer instruction, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the boiler (to allow drainage of condensate).
NOTICE Installation of a stainless steel vent system should adhere to the stainless steel vent manufacturer’s installation instructions supplied with the vent system.
NOTICE The installer must use a specifi c vent starter adapter at the ue collar connection, supplied by the vent manufacturer to adapt to its vent system. See Table 10-2 for approved vent adapters.
Figure 10-9 Stainless Steel Venting connection
38
10 - INSTALLATION - Vent and combustion air
10.8.1 - Stainless steel air intake/vent connections
Combustion Air Intake connection (see Figure 10-9 Item “C”). This connection is used
to provide combustion air directly to the boiler from outdoors. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate. To connect a PVC/CPVC pipe to the air intake connection follow section
10.7.2.
Vent connection (Figure 10-9 item “A”) is used to provide
a passageway for conveying combustion gases to the outside. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.
To connect a stainless steel pipe to the vent connection proceed as follow: while referring to Figure 10-9:
1. install boiler adapter “A” above boiler. Rotate boiler adapter “A” so as air intake and vent connections are in the desired left or right side. Check stamped arrow to understand which is the vent and air intake connection.
WARNING!!!
stamped arrow on boiler adapter for the correct side of vent. Failure to follow this warning could result in excessive levels of carbon monoxide or a fi re, which can result in severe personal injury or death!
Check
2. Insert clamp “D” onto side “B” of boiler adapter “A” .
3. Insert adapter “E” into side “B” of boiler adapter “A”;
4. Use clamp “D” to mechanically secure adapter “E” to boiler adapter “A”. To do this tighten one side of clamp “D” onto boiler adapter “A” and the other half of clamp “D” onto adapter “E”. tork of 1.5 - 2 lbf ft (2-3 Nm).
5. Insert vent pipe “G”, into adapter “E”, following instruction of stainless steel pipe manufacturer.
Tight the clamps with a
39
10 - INSTALLATION - Vent and combustion air
10.9 - Polypropylene vent piping materials
WARNING!!!
the materials listed in Tables 10-1 and 10-2 for vent pipe, and fi ttings. systems of different types or manufacturers, unless listed in this manual. could result in severe personal injury, death, or substantial property damage.
WARNING!!!
requires a special venting system. The fi eld provided vent ttings must be connected to the boiler following Section 10.9.1. Failure to follow this warning could result in fi re, personal injury, or death.
WARNING!!!
installation of Polypropylene systems may result in injury or death.
Use only
DO NOT mix vent
Failure to comply
This appliance
Improper
WARNING!!!
water-based lubricants on joints. Never use hydrocarbons-based lubricants because they would destroy gaskets. follow this warning could result in excessive levels of carbon monoxide, which can result in severe personal injury or death!
NOTICE Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
For installation in Canada, vent pipe system must be certifi ed to ULC-S636 (see Table 10-1).
NOTICE All vent pipes connections must be secured following manufacturer instruction, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the boiler (to allow drainage of condensate).
NOTICE Installation of a Polypropylene vent system should adhere to the polypropylene vent manufacturer’s installation instructions supplied with the vent system.
Use only
Failure to
Figure 10-10 Polypropylene boiler adaptor
40
10 - INSTALLATION - Vent and combustion air
10.9.1 - Polypropylene two pipes air intake/vent connections
Combustion air piping and vent piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.
The boiler is not supplied with the ttings needed for separate vent and combustion air systems. A special kit must be ordered to connect the boiler to separate vent and combustion air
systems. Figure 10-10 shows fi tting “A” that can freely turn 360 degrees for optimum installation versatility (see section 10.9.2 for P/N of “A” fi tting). Tork screws “D” at 2 lbf ft (3 Nm).
Pipes or elbows connected directly to the boiler, must be mechanically secure. Follow these instructions to connect pipes to the boiler (make reference to Figure 10-11):
1. Prepare the two collars “G” with Band Clamps “E” and “F”;
2. Insert the end of Band Clamp “L”
into hole “M” of boiler adapter “A”
3. Insert vent pipe “N” into boiler adapter “A”
4. Tight the two Band Clamps “O” to mechanically secure vent pipe “N” to boiler adapter “A”. Tight band clamps with a tork of 1.5 - 2 lbf ft (2-3 Nm).
The vent system must be both gas tight and watertight. All seams and joints must be joined and sealed in accordance with the vent system manufacturer’s instructions.
WARNING!!!
follow the installation steps below for the assembling the two pipes venting system (elbows and extensions), as illustrated in Figure 10-12. it is necessary to properly insert the male side onto the female side and mechanically secure them by using the proper clamps. Improper venting can result in excessive levels of carbon monoxide or a fi re, which can result in severe personal injury or death!
Carefully
Figure 10-11 Polypropylene Venting connection
Mechanically secure each joint
with the supplied band clamps as shown in Figure 10-12. Follow this procedure:
1. Insert the Male side (“B”) of a vent pipe into the Female side “A” of another;
2. Use Band Clamp “C” to keep the two pipes together;
3. Use screws “E” to tighten the Band Clamp onto both pipes. Tight band clamps with a tork of 1.5 - 2 lbf ft (2-3 Nm).
Figure 10-12 Connecting extensions and elbows
41
10 - INSTALLATION - Vent and combustion air
10.9.2 - Polypropylene two pipes system components
Some of the most commonly used components for installing the two pipes polypropylene vent and combustion air systems are listed below:
P/N 81 9001 000 - Two pipes adaptor 80/80 PP P/N 81 9171 000 - 3ft PP M/F extension P/N 81 9772 000 - 60 ft PP fl exible extension P/N 81 9173 000 - Spacer for PP fl exible extension P/N 81 9003 000 - 90° PP M/F in line elbow P/N 81 9174 000 - 45° PP M/F in line elbow P/N 81 9175 000 - Secure clamp for PP extensions P/N 81 9177 000 - Split vertical terminal P/N 81 9181 000 - Air intake grid P/N 81 9182 000 - Flue exhaust grid
Figure 10-13 Dimensions of two pipes system
81 9001 000
81 9182 000
81 9181 000
81 9177 000
81 9772 000
81 9173 000
81 9003 000
81 9171 000
81 9175 000
42
81 9174 000
10 - INSTALLATION - Vent and combustion air
10.9.3 - Polypropylene
concentric system
The boiler is not supplied with the ttings needed for connecting a coaxial vent/combustion air system. A special kit must be ordered to connect the boiler with the Coaxial polypropylene vent. Figure 10-14 shows how to install the Coaxial fi tting above the boiler. Tight the screws “D” of Figure 10-14 with a tork of 2 lbf ft (3 Nm)
B = Connection fl ange C = Fasten clip D = Fasten clip screw F = Coaxial vertical adaptor
Figure 10-14 Installation of the coaxial fi tting
WARNING!!!
follow installation steps below, for the coaxial pipe assembly (elbows and extensions), as illustrated in Figure 10-15. It is necessary to properly insert the internal and external pipe and mechanically secure them by using a stainless steel self tapping screw. Improper venting can result in excessive levels of carbon monoxide or a re, which can result in severe personal injury or death!
In particular:
1. slip-fi t the extension “1” and “2” (see Figure 10-15) together;
2. drill a suitable hole “3” with a drill “4” (see Figure 10-15) in a position where the two pipes “1” and “2” are overlapped;
3. insert a suitable stainless steel self tapping screw “5” and tight it with a screwdriver “6”
Carefully
Figure 10-15 Securing extensions and elbows together
43
It is recommended that wall sleeve
be used when installing the coaxial system through an exterior wall. This will allow the system to be easily slipped out for access during routine maintenance.
Horizontal coaxial systems must
always be pitched by at least 1/4 in/ ft, (21 mm/m) towards the boiler.
10 - INSTALLATION - Vent and combustion air
10.9.4 - Polypropylene concentric system components
The following coaxial polypropylene vent and combustion air system components are available, on request, for installing the Coaxial system
P/N 81 9183 000 - In line 90° PP coaxial M/F elbow P/N 81 9176 000 - In line 45° PP coaxial M/F elbow
81 9183 000
P/N 81 9170 000 - 3ft (1m) PP coaxial extension P/N 81 9005 000 - PP coaxial roof end piece P/N 81 9184 000 - PP Coaxial wall end piece P/N 81 9185 000 - PP straight coaxial adaptor
81 9176 000
81 9185 000
81 9170 000
81 9005 000
81 9184 000
44
10 - INSTALLATION - Vent and combustion air
10.10 - Single pipe vent (not sealed combustion)
WARNING!!!
utilizing the single pipe method, provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
Commercial applications utilizing this boiler may be installed with a single pipe carrying the fl ue products to the outside while using combustion air from the equipment room. In this case the following conditions and considerations must be followed.
WARNING!!!
equipment room MUST be provided with properly sized openings to assure adequate combustion air from outside. Failure to comply could result in severe personal injury, death, or substantial property damage.
• There will be a noticeable increase in the noise level during normal operation from the inlet air opening.
• Vent system and terminations must comply with the venting instructions set forth in sections 10.1, 10.2,
10.3, 10.4, 10.5, 10.7, 10.8 and
10.9.
WARNING!!!
materials, vent systems, and terminations listed in Tables 10-1 and 10-2. DO NOT mix vent systems of different types or manufacturers, unless listed in this manual. Failure to comply could result in severe personal injury, death, or substantial property damage.
When
The
Use only the
WARNING!!!
due to fl ammable materials or liquids. Do not store fl ammable materials and liquids in the immediate vicinity of the boiler.
WARNING!!!
must be clear and free from combustible materials, gasoline and other fl ammable vapors and liquids, and corrosive liquids and vapors. Never use chlorine and hydrocarbon containing chemicals (such as spray chemicals, solution and cleaning agents, paints, glues etc.) in the vicinity of the boiler. Do not store and use these chemicals in the boiler room. Avoid excessive dust formation and build-up.
WARNING!!!
fans, clothes dryers, and kitchen ventilation systems interfere with the operation of appliances, makeup air shall be provided.
NOTICE Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
For installation in Canada, vent pipe system must be certifi ed to ULC-S636 (see Table 10-1).
NOTICE All vent pipes connections must be secured following manufacturer instruction, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the boiler (to allow drainage of condensate).
Fire danger
Boiler
Where exhaust
10.10.1 - Combustion Air and Ventilation openings
Outdoor combustion air shall be provided through opening(s) to the outdoors. The minimum dimension of air openings shall not be less than 3 in. (80 mm) diameter.
Two Permanent Openings Method.
Two permanent openings, one commencing within 12 in. (300 mm) of the top and one commencing within 12 in. (300 mm) of the bottom, of the room shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows:
1. Where directly communicating with the
2. Where communicating with the
One Permanent Opening Method. One permanent opening, commencing within 12 in. (300 mm) of the top of the room, shall be provided. The appliances shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front of the appliance. The opening shall directIy communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of 1 in2 each 3000 Btu/hr (700 mm2 /kW) of the total input rating of all appliances located in the room
45
WARNING!!!
combustion air and ventilation openings are suffi ciently sized and no reduction or closure of openings takes place. Please note these restrictions and its dangers to the operator of the boiler and to the homeowner. Failure to comply could result in severe personal injury, death, or substantial property damage.
outdoors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2 each 4000 Btu/hr (550 mm2/kW) of total input rating of all appliances located in the room.
outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2 each 2000 Btu/hr (1100 mm2/kW) of total input rating of all appliances located in the room.
Make sure that
10 - INSTALLATION - Vent and combustion air
10.10.2 - Determine location
Locate the vent termination using the following guidelines:
1. The total length of piping for vent must not exceed the limits given in the Section 10.4.
2. You must consider the surroundings when terminating the vent: a. Position the vent termination where
vapors will not damage nearby shrubs, plants or air conditioning equipment or be objectionable.
b. The fl ue products will form a
noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views.
c. Prevailing winds could cause
freezing of condensate and water/ ice buildup where fl ue products impinge on building surfaces or plants.
d. Avoid possibility of accidental
contact of fl ue products with people or animals.
e. Do not locate the terminations
where wind eddies could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.
f. Do not terminate above any door or
window. Condensate can freeze, causing ice formations.
g. Locate or guard vent to prevent
condensate damage to exterior nishes.
4. The vent piping must terminate in an elbow pointed outward as shown in Figure 10-12 or 10.13.
WARNING!!!
exceed the maximum lengths of the outside vent piping shown in Figures 10-12 or 10-13. Excessive length exposed to the outside could cause freezing of condensate in the vent pipe, resulting in potential boiler shutdown.
Do not
5. Maintain clearances as shown in Figure 10-11 (get references to
“Mechanical draft vent terminal” only). Also maintain the following:
a. Vent must terminate:
• At least 6 feet from adjacent walls.
• No closer than 12 inches below roof overhang.
• At least 7 feet above any public walkway.
• At least 3 feet above any forced air intake within 10 feet.
• No closer than 4 feet below or horizontally from any door or window or any other gravity air inlet.
b. Do not terminate closer than 4
feet horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet horizontally.Item
unique to CANADA: vent system shall terminate at least 6 ft from electrical and gas meters.
6. Locate termination so it is not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.
CAUTION!!!
Increase the grade clearances of the snow line quote
Figure 10-16 Vent position of a Direct vent boiler and of a Mechanical draft boiler (not sealed)
46
10 - INSTALLATION - Vent and combustion air
10.11 - Sidewall termination - Two pipes
10.11.1 - Vent/air termination
WARNING!!!
extending through an exterior wall shall not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING!!!
connect any other appliance to the vent pipe or multiple boilers to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.
NOTICE Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
A gas vent
Do not
10.11.2 - Determine location
Locate the vent/air terminations using the following guidelines:
1. The total length of piping for vent or air must not exceed the limits given in the Section 10.4.
2. You must consider the surroundings when terminating the vent and air: a. Position the vent termination
where vapors will not damage nearby shrubs, plants or air conditioning equipment or be objectionable.
b. The fl ue products will form
a noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views.
c. Prevailing winds could cause
freezing of condensate and water/ice buildup where fl ue products impinge on building surfaces or plants.
d. Avoid possibility of accidental
contact of fl ue products with people or animals.
e. Do not locate the terminations
where wind eddies could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.
f. Do not terminate above any door
or window. Condensate can freeze, causing ice formations.
g. Locate or guard vent to prevent
condensate damage to exterior nishes.
47
Loading...
+ 25 hidden pages