Slant/Fin L-Series User Manual

Page 1
®
HOT WATER SUPPLY AND RETURN HEADERS PARTS LIST AND ASSEMBLY INSTRUCTIONS
L-Series: Oil-fired Modular Boilers
Header Parts List
43-2572
43-2573
Item Part No. 234 56 78910
1-1/2" Stub Header - 2 stub - 27" C-C (pkgd. separately) 43-0920 2–4 2– 42–4 1-1/2" Stub Header - 3 stub - 27" C-C (pkgd. separately) 43-0921 –2–24 2464 Flex Joint - 1-1/2" pipe 43-2023 244 68 810 12 12 Flex Joint - 3" pipe 41-1755 448 8812 12 12 16 Cast End Cap - 3/4" NPT 41-1780 111 11 1111 Cast End Cap - No tap 41-1753 111 11 1111 Nipple - 1-1/2" x 4" 43-0904 346 7810 11 12 14 Nipple - 1-1/2" x 15" 43-0923 234 56 78910 Nipple - 1-1/2" x 30" 43-0924 112 24 4566 Nipple - 1-1/2" x close 43-0927 234 56 78910 Square Nipple - 1-1/2" x 8" T.O.E. 43-0925 122 34 4566 Square Nipple - 1-1/2" x 34" T.O.E. 43-0926 122 46 5666 Union - 1-1/2" 902428071 224 44 6668 Tee - 1-1/2" 43-0917 234 56 78910 Bushing - 1-1/2" x 3/4" 902179321 23456 78910 Elbow - 1-1/2" 902454071 46810 12 14 16 18 20 Installation Instructions 43-0901 111 11 1111
Header Package Order Code
Number of Modules
Part No. 43-0901
Publication CH-40L
Printed in U.S.A. 906
Page 2
FACTORY SUPPLY AND RETURN HEADER ASSEMBLY — OIL
1
1
/2'' X 8'' SQUARE NIPPLE
3'' RETURN HEADER
1
WITH 1
/2'' STUBS
(3 MODULE)
1
/2'' FLEX JOINT
1 (SEE DETAIL "A")
3'' FLEX JOINTS
(SEE DETAIL "A")
3'' RETURN HEADER
1
WITH 1
/2'' STUBS
(2 MODULE)
CAST END CAP
1
1
/2'' X 4'' NIPPLE
*Building piping must be rigidly secured so it cannot move where connected to headers.
1
1
1
/2'' X 15'' NIPPLE
1
/2'' ELBOW
3'' FLEX JOINT
(SEE DETAIL "A")
3'' PIPE X 20'' (BY OTHERS)
1
1
/2'' UNION
1
/2'' PRESSURE
TEMPERATURE
GAUGE
3'' SUPPLY HEADER
1
WITH 1
/2'' STUBS
(2 MODULE)
1
/2'' X 11/2'' X 11/2'' TEE
1
*3'' BUILDIING PIPE
1
/2'' WELLS
CONTROL HEADER
1
/2'' x 1/2'' x 1/2''
3'' x
CONNECTION
* 3'' BUILDING
PIPING
(BY OTHERS)
1
1
/2'' X 34'' SQUARE NIPPLE
1
/2'' X 30'' NIPPLE
1
CAST END CAP
3
WITH
/4'' TAPPING.
SUPPLY OR RETURN.
FOR USE WITH LWCO.
1
1
/2'' X 4'' NIPPLE
3'' SUPPLY HEADER
1
WITH 1
/2'' STUBS
(3 MODULE)
NOTE: Shown reverse return (Preferred). For direct
return, header assembly piping connections may be made at the same end of the boiler bank, not as shown. Some governing agen­cies do not allow compression type couplings. Consult your local code requirements.
1
/2'' ELBOW
1
3
1
/2'' X CLOSE NIPPLE
1
/4'' DRAIN VALVE
1
/2'' X 3/4'' BUSHING
1
Page 3
Caravan Flex Joint Assembly Instructions
1. Slip the metal retainer on the system piping with the larger diameter side facing the end of the pipe to be joined. The 3" flex joint has a single piece serrated metal retaining ring. This retaining ring should be seated in the recess in the inner diameter of the gasket with its mounting tabs
overlapping slightly where the ring splits. The 1-1/2" flex joint has a 2 piece serrated retaining ring that must be installed in the inner recess of the gasket with its ends butting.
Work the gasket with the serrated metal retaining ring onto the pipe. When installing the gasket be sure the retaining rings seat properly around the pipe. On the 1-1/2" flex joint install the bottom half of the gasket first leaving the other half of the retaining ring
free at the top. Then stretch the top of the gasket with the ring over the top of the pipe. When installing the gaskets if a lubricant
is needed, use a soap and water solution only. DO NOT use any oil based lubricants.
2. The gasket must be fully seated in the metal retainer (press together with pliers if necessary). BE SURE THE GASKET IS SEATED ON AN UNTHREADED SECTION OF PIPE AT LEAST 1" FROM THE END. Slip the flared end of the Slant/Fin header tube over the pipe and seat against the gasket. Follow illustration a or b for cast end cap or piping.
a) b)
3. Open hinged metal clamp and slip over joint. Be sure that the flared end of the steel tubing, the retainer ring and the gasket are enclosed within the clamp.
4. Install the bolt and lock nut and tighten the lock nut to the following torque values: 1-1/2" flex joint is 140-160
inch-pounds, 3" flex joint is 220-240 inch-pounds.
NOTE: On 3” schedule 40 pipe, spacing between clamps is
approximately 3/8” when properly torqued.
On 1-1/2" schedule 40 pipe, spacing between clamps is approximately 1/4" when properly torqued.
Page 4
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Loading...