Slant/Fin Jaguar Caravan Application Manual

HOT WATER/GAS MODULAR BOILERS
®
APPLICATION GUIDE
Guidelines for the design, purchase and installation of Slant/Fin Jaguar Caravan gas-fired, hot water modular boiler systems.
CONTENTS
Recommended Piping . . . . . . . . . . . . . . . . . . . . . .2
Optional factory supply and return headers . . . . . .7
SC- control bill of materials . . . . . . . . . . . . . . . . . .9
Field wiring at modules . . . . . . . . . . . . . . . . . . . . .12
SC-3 system wiring . . . . . . . . . . . . . . . . . . . . . . . .12
SC-9 space heating wiring . . . . . . . . . . . . . . . . . .14
SC-9 space and domestic hot water wiring . . . . .16
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the absence of local codes, to the National Fuel Gas Code, ANSI, Z223.1-latest edition.
In addition where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Codes for controls and safety devices for automatically fired boilers, No. CSD-1. The installation must also conform to the additional requirements of Slant/Fin Instruction Book publication no. J-40 latest edition.
All electrical wiring is to be done in accordance with the National Electrical Code ANSI/NFPA No. 70-latest edition and all local electri­cal codes. The unit must be electrically grounded if an external
wer source is used.
po
In Canada, the installation must be in accordance with standards CGA B149.1 and B149.2, installation codes for gas burning appliances and equipment and/or local codes. All electrical connections are to be made in accordance with Standard C.S.A. C22.1 Canadian Electrical Code Part 1 and/or local codes.
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can cause scaling and leave deposits in the boiler and the surrounding pipes. This will lead to inefficient boiler operation and breakdown. Fresh water will enter the system as a result of hidden leaks such as may occur in underground piping. Relief valves should be piped to a location that shows visible signs of relief.
Process applications that use fresh water exchangers. Any process application that results in introduction of
ater into a boiler can cause scaling with deposits for
fresh w the boiler and surrounding piping. This will damage the boiler. Introduction of fresh water from leaks will cause similar damage.
In some areas it ma control the corrosive makeup of the feed water. Check with the local authority, to determine if the feed water will need a conditioning treatment before being supplied to the boiler.
y be necessary to use a f
, require the use of heat
ming in
eed water treatment to
Printed in the U.S.A. 1008 Publication No. CJ-10-HWG
www.slantfin.com
Jaguar Caravan Modular Boilers2
INTRODUCTION
This application manual is intended to provide the piping and control method for applying multiple Jaguar J-390 boilers to a space heat-
ng and domestic hot water heating system. Use this manual, in
i conjunction with the Jaguar J-390 Installation and Operating Instructions, publication J-40.
The following sections of the Installation and Operating Instructions must be adhered to:
1. Boiler location and foundation
2. Clearances to combustibles
3. Contamination prevention . Air supply and ventilation
4
5. Venting application and materials*
6. Water treatment
7. Condensate disposal
8. Operating instructions
9. Care and Maintenance
*Common venting of these appliances is not permitted. Vent pipes in a non-direct venting system can be clustered together, at their termi­nation point. Direct vent terminals cannot be clustered together or stacked vertically. Direct vent terminals can be mounted side by side horizontally, provided there is a 12" minimum distance between them.
RECOMMENDED PIPING AND WATER FLOW
Good system design addresses flow rates through boilers. It is possible to have too little flow and too much flow. Most boiler sys­tem designs are based on a 20˚F to 30˚F temperature rise in the boiler when it is firing at full input.
When the flow rate is too high through a module the water flow tends to short circuit from the return tapping to the supply tapping of a module. When flow rate is too high the boiler efficiency may drop and there is excess electrical consumption by the circulator.
Primary/secondary piping is recommended for multiple Jaguar
oilers. This method ensures that each boiler will receive the
b same inlet water temperature, and only the boilers that are firing will have water flowing through them. Each boiler must have a dedicated circulator piped on it’s supply. See figures 1a through 4
or the location of components and piping layout.
f
If a single low water cutoff is installed in the common header water piping to protect all of the boilers, no isolation valves are permitted on the individual boiler piping between the low water cutoff and each boiler. See figures 1a and 2a.
If isolation valves are installed in the individual boiuler piping to the common headers, a dedicated low water cutoff must be installed on each boiler’s piping, as close to the boiler as possible and beneath the isolation valves. See figures 1b and 2b.
SPACE HEATING
The primary loop must have its own system pump, and closely spaced tees for the secondary loop interconnection. By keeping the pressure drop very low, water that is flowing in the primary loop will not flow into the secondary circuit until each boiler’s cir­culator turns on.
DOMESTIC HOT WATER HEATING
A motorized valve can be installed within the supply water heater to divert the water flow of one or more boilers to a heat exchang­er during a domestic water need. See figures 2a and 2b. This can provide instantaneous delivery or storage of the domestic hot water. See figures 2a through 4 for method.
Jaguar Caravan Modular Boilers 3
Figure 1a. Jaguar multiple boiler space heating primary- secondary pumping system with low water cutoff in common header.
Jaguar Caravan Modular Boilers4
Figure 1b. Jaguar multiple boiler space heating – Primary-secondary pumping system with low water cutoffs on each individual boiler.
Jaguar Caravan Modular Boilers 5
Figure 2a. Jaguar multiple boiler space heating and domestic hot water primary-secondary pumping system with low water cutoff in common header.
Jaguar Caravan Modular Boilers6
Figure 2b. Jaguar multiple boiler space heating and domestic hot water. Primary-secondary pumping with low water cutoffs on each individual boiler.
Loading...
+ 14 hidden pages