Slant/Fin Jaguar User Manual

HOT WATER/GAS MULTIPLE AND CASCADING BOILERS
®
APPLICATION GUIDE
Guidelines for the design, purchase and installation of Slant/Fin Jaguar J-390C Caravan gas-fired, hot water multiple boiler systems.
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . .2
Boiler room design & layout . . . . . . . . . . . . . . . . . . . . . .4
Fresh air and contamination prevention . . . . . . . . . . . . .6
Piping and Wiring Flow
Boiler room air supply & ventilation . . . . . . . . . . . . . . . . .6
Venting requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Water piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Condensate removal . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Gas line sizing and layout . . . . . . . . . . . . . . . . . . . . . . .16
Jaguar Multiple Boiler System Control . . . . . . . . . . . . .18
Cascading – Jaguar link method and wiring . . . . . . . . .19
Reset curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
External signal & energy management (Tekmar 275) . . . . . . .28
Hybrid Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . .34
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the absence of local codes, to the National Fuel Gas Code, ANSI, Z223.1-latest edition.
In addition where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Codes for controls and safety devices for automatically fired boilers, No. CSD-1. The installation must also conform to the additional requirements of Slant/Fin Instruction Book publication no. J-40 latest edition.
All electrical wiring is to be done in accordance with the National Electrical Code ANSI/NFPA No. 70-latest edition and all local electri­cal codes. The unit must be electrically grounded if an external power source is used.
In Canada, the installation must be in accordance with standards CGA B149.1 and B149.2, installation codes for gas burning appliances and equipment and/or local codes. All electrical connections are to be made in accordance with Standard C.S.A. C22.1 Canadian Electrical Code Part 1 and/or local codes.
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can cause scaling and leave deposits in the boiler and the surrounding pipes. This will lead to inefficient boiler operation and breakdown. Fresh water will enter the system as a result of hidden leaks such as may occur in underground piping. Relief valves should be piped to a location that shows visible signs of relief.
Process applications that use fresh water, require the use of heat exchangers. Any process application that results in introduction of fresh water into a boiler can cause scaling with deposits forming in the boiler and surrounding piping. This will damage the boiler. Introduction of fresh water from leaks will cause similar damage.
In some areas it may be necessary to use a feed water treatment to control the corrosive makeup of the feed water. Check with the local authority, to determine if the feed water will need a conditioning treatment before being supplied to the boiler.
Printed in the U.S.A. 711 Publication No. CJ-10-HWG
www.slantfin.com
Jaguar Caravan Multiple and Cascading Boilers2
1. INTRODUCTION
If additional information is desired please contact your local Slant/Fin Sales Representative or Slant/Fin Technical Services. Slant/Fin may be found on the web at www.slantfin.com
This application manual is intended to provide the piping and control method for applying multiple Jaguar J-390C boilers to a space heat­ing and domestic hot water heating system. Use this manual, in conjunction with the Jaguar J-390C Installation and Operating Instructions, publication J-40.
The following sections of the Installation and Operating Instructions (J-390C) must be adhered to:
1. Boiler location and foundation
2. Clearances to combustibles
3. Contamination prevention
4. Air supply and ventilation
5. Venting application and materials*
6. Water treatment
7. Condensate disposal
8. Operating instructions
9. Care and Maintenance
2. RATINGS AND DIMENSIONS
*Common venting of these appliances is not permitted. Direct vent terminals cannot be clustered together or stacked vertically. Direct vent terminals can be mounted side by side horizontally, provided there is a 12" minimum distance between them.
There are two methods available to control J-390C Caravan boilers:
1. Jaguar link method to operate up to 8 boilers. An optional system sensor is required for operation of this method. Supply water system sensor (Part no. 833433000) max be ordered to Slant/Fin boiler distributor.
2. External signal (0-10 Vdc input). Control such as Tekmar control 265 or 275 (operates up to 4 boilers). Energy Management System may be used with this method. One optional interface control is required for operation of each boiler in the system. Part number for interface control kit is 830130000.
Jaguar boilers may also be used in a heating system with a Caravan cast iron modular boiler system. Since high efficiency con­densing boilers only condense when the return water temperature is low, around 130 F or lower, it makes sense to use a lower cost Caravan cast iron boiler at higher water temperature. We call a com­bination Caravan Cast Iron Modular Boiler used in a system with a Jaguar Multiple Boiler a “Hybrid Boiler System”. We address Hybrid Boiler Systems within this manual.
Table 1: Gas multiple boiler ratings and dimension/hot water model 50 psi maximum working pressure
Model
No.
J-390C 2B J-390C 3B J-390C 4B J-390C 5B J-390C 6B J-390C 7B J-390C 8B
Model
No.
J-390C 2B J-390C 3B J-390C 4B J-390C 5B J-390C 6B J-390C 7B J-390C 8B
Consists of
No. of Htg.
Boiler
2 3 4 5 6 7 8
Water
Content
(gal.)
4 6
8 10 12 14 16
Boiler
Model No.
J-390C J-390C J-390C J-390C J-390C J-390C J-390C
Ship
Wt.
Lbs.
600
900 1200 1500 2340 2730 3120
CSA Input
(MBH)
Max Min Max Min Max Min Max Min
780 1170 1560 1950 2340 2730 3120
Vent
Conn
4" 4" 4" 4" 4" 4" 4"
Air
Intake.
4" 4" 4" 4" 4" 4" 4"
110 110 110 110 110 110 110
Water
Correction
at Boiler
1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4
CSA output
704 1056 1408 1760 2112 2464 2816
Space Btwn.
Boilers
3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4
(MBH)
106 106 106 106 106 106 106
**
Length
with
Header
50-1/2"
77-3/4" 104-1/4" 131-1/8"
158" 184-7/8" 211-3/4"
I=B=R Net
612
918 1224 1530 1836 2142 2448
**
Min.
Header
Size
2" 2" 3" 3" 3" 3" 3"
(MBH)
92 92 92 92 92 92 92
Combustion
Efficiency
91.6
91.6
91.6
91.6
91.6
91.6
91.6
System Turndown
Model
No.
J-390C 2B J-390C 3B J-390C 4B J-390C 5B J-390C 6B J-390C 7B J-390C 8B
96.7
96.7
96.7
96.7
96.7
96.7
96.7
Turndown
Ratio
7 to 1
10.6 to 1
14.2 to 1
17.7 to 1
21.3 to 1
24.8 to 1
28.4 to 1
Boiler Horse­Power
21
31.5 42
52.6
63.1
73.6
84.1
** “Length with headers allows for 3 1/4" between boiler.
Jaguar Caravan Multiple and Cascading Boilers 3
‘’
‘’
‘’‘’ ‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
‘’
** “L” Dimensions and spacing between boilers are for Slant/Fin headers.
Based on 150 BTUH per square foot E.D.R. at 170˚F water temperature.
No. of Boilers Model No. “L” inches
Figure 1. Dimensions
1 2 3 4 5 6 7 8
J-390C 1B J-390C 2B J-390C 3B J-390C 4B J-390C 5B J-390C 6B J-390C 7B J-390C 8B
104-1/4 131-1/8
184-7/8 211-3/4
23-5/8 50-1/2 77-3/8
158
BOILER DESIGN DATA
– Max. ASME Working Pressure: 50 PSI – Power Requirements
120 Volts, 60 Hz, 1 Phase
– 1.6 Amps per module, not including
primary circulator
Jaguar Caravan Multiple and Cascading Boilers4
3. BOILER ROOM DESIGN AND LAYOUT
Jaguar Caravan Multiple Boilers allow better utilization of floor space and permit future boiler system expansion with minimum cost. Jaguar boilers are hand truckable, fit through doorways and can often be installed around existing boilers. Boilers can be installed in line, back to back, at angles or in multiple rows. Layout is flexible. Figure 2 gives a typical layout using Slant/Fin Headers.
Boiler rooms and enclosures should comply with local code require­ments. Provide a level and solid foundation for the boilers. Equipment pads should be capable of supporting the boilers filled with water and extend past the boiler jackets by at least 2 inches. Jaguar boilers are approved for installation on combustible and non­combustible floors, however Jaguar boilers must not be installed on or above carpeting. All boiler components should be protected from water during installation, set up, operation and service.
Minimum clearances to combustible materials should comply with local code requirements. Slant/Fin minimum clearances are listed
below.
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
A. Minimum clearances to the exterior surfaces of the boiler shall
be as follows: MINIMUM ALCOVE AND CLOSET CLEARANCE
For Combustible Recommended
Surface
Construction for Service Front 0" 24" Rear 0" 8" Left Side 0" 0" Right Side 0" 0" Top 4" 6" Flue Connector:
Enclosed — 2" 6" Uninclosed — 1" 6"
B. Provide accessibility clearance of 8" on sides requiring servic-
ing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This may
result in increased values of some minimum clearances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor, wall or ceiling, the clear-
ance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Jaguar Caravan Multiple and Cascading Boilers 5
Figure 2. Typical layout of 3 Jaguar Boilers using Slant/Fin Headers (Minimum Clearance)
Jaguar Caravan Multiple and Cascading Boilers6
4. FRESH AIR AND CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contamina­tion sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause corrosion or other damage to the heat exchanger and components of the boiler, causing failure of these parts or unsafe operation.
Below is a list of products and areas which may cause contaminated combustion air:
PRODUCTS TO AVOID
• Spray cans containing chloro/fluorocarbons
• Permanent wave solutions
• Chlorinated waxes/cleaners
• Chlorine-based swimming pool chemicals
• Calcium chloride used for thawing
• Sodium chloride used for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid/muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
• Adhesives used to fasten building products and other similar products
AREAS LIKELY TO HAVE CONTAMINANTS
• Dry cleaning/laundry areas and establishments
• Swimming pools
• Metal fabrication plants
• Beauty shops
• Refrigeration repair shops
• Photo processing plants
• Auto body shops
• Plastic manufacturing plants
• Furniture refinishing areas and establishments
• New building construction
• Remodeling areas
• Garages with workshops
5. BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and ventilation. When buildings are insulated, caulked and weather-stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or appli­cable provisions of the local building codes. The following recom­mendation applies to buildings of energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM.
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the floor and one
louvered opening near the ceiling, each opening with a mini­mum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
2. Air drawn horizontally through HORIZONTAL DUCTS; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 2000 Btuh of total appliances’ input.
3. Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a mini­mum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of the boiler controls and boiler room. Openings for passage of air into the boiler room for direct-vent installation must be at least
1
2 of the openings required for the non-direct vent as mentioned above.
If additional non-direct vent appliances are installed in the same space and adequate air openings are provided for them, there are no additional air openings required for the Jaguar J-390C boiler.
For both direct and non-direct installation, the following must be considered:
-
Openings must never be reduced or closed. If doors or windows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently.
- No mechanical draft exhaust or supply fans are to be used in
or near the boiler area.
- Boiler area must never be under negative pressure. The flow of
combustion and ventilating air to the boiler must not be obstructed.
Jaguar Caravan Multiple and Cascading Boilers 7
6. VENTING REQUIREMENTS
The Jaguar J-390C is a sealed combustion type boiler, it may be installed and vented either as a direct vent boiler which all air for combustion is obtained directly from outside or as a non-direct vent boiler which air for combustion is taken from inside the boiler room.
The Jaguar J-390C boiler must be vented by 4" diameter PVC/CPVC schedule 40 pipe, or the proper 4” diameter stainless steel venting system (see “vent material” on this page) through the roof or sidewall.
FLUE GAS VENTING REQUIREMENTS
The Jaguar J-390C series boiler is a high efficiency, mechanically forced draft boiler and, therefore, require different venting arrange­ments than natural draft, lower efficiency boilers.
THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ­ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply.
The use of a vent damper is NOT permitted on this boiler series.
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
When the Jaguar is installed and used in the Commonwealth of Massachusetts, the following additional Massachusetts code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sus­tained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential pur­poses, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsi­hed grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qual­ified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adjacent floor level.
b. In th event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
requirements pursuant to
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monox­ide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less that one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or part for residential purposes.
VENT AND AIR INTAKE MATERIALS
The vent and air intake system for direct or non-direct vent instal­lation must be 4” diameter PVC/CPVC schedule. 40 pipe, or UL listed single wall 4” diameter AL29-4C* stainless steel material. The following manufacturers’ systems are approved for use within a specified minimum and maximum equivalent vent length in this manual.
Manufacturer Type/System Sealant
Heat-Fab. Inc.
ProTech System,
Inc.
Flex-L International
Inc.
Metal-Fab, Inc. Corr Guard Not Required
N/A
N/A
Saf-T Vent
EZ Seal
FasNSeal Not Required
StaR-34 GE-IS806
PVC pipe,
Schedule 40
CPVC pipe,
Schedule 40
Not Required
PVC primer and cement
CPVC primer
and cement
When joining the various components of the listed stainless steel vent systems, the manufacturers’ instructions should be closely followed to insure proper sealing. Use sealant specified by vent system manufac­turer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions provided in this manual. All connections must be liquid and pressure tight. DO NOT use galvanized flue pipe or any plastic-type materials other than PVC/CPVC Schedule 40.
* Maximum exhaust vent length = 100 feet * Maximum air intake length = 100 feet * Each elbow is eqivalent to 10 feet of straight pipe
Jaguar Caravan Multiple and Cascading Boilers8
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for all of the approved vent and air intake materials is 100 equivalent feet.
2. Equivalent of vent or air intake length is sum of the straight pipe lengths and equivalent length of elbows. Each 90˚ elbow is equivalent to 10 ft. of 4" pipe.
Figure 3.
3. The vent termination is in addition to the allowed equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus one 90˚ elbow.
5. Vent length restriction is for both direct and non-direct vent installations.
EXAMPLE: The combustion air is provided by air intake piping directly to the boiler (direct-vent installation). The vent piping will be PVC and installation location will require the use of 4 elbows for the vent to run the termination. The air intake piping will also be PVC, and also will require the use of 4 elbows. In this case, the maximum straight pipe vent length that can be utilized with the 4 elbows would be: 100’ - (4’ x 10’) = 60’. Since the air intake pipe also is PVC and requires the use of 4 elbows, the maximum straight pipe air intake length that can be utilized is also 60 feet.
If the air for combustion were taken from the boiler room (non-direct vent installation), still the maximum straight vent length would be 60 feet.
6. The Jaguar J-390C boiler is equipped with a built-in condensation drain and trap system. The traps must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system. Refer to the “Condensate Drainage” section of this manual. No additional condensation drain and trap is required on the vent piping system itself.
7. The horizontal vent pipe must be sloped upward from the boiler at a pitch of at least 1/4” per 1 foot of run, so that the condensate from the vent system runs to the boiler vent adapter pipe, then out the built-in condensation drain and trap.
8. The horizontal vent and air intake pipes must be supported with pipe
straps, at intervals no greater than 5 feet, when PVC/CPVC pipe is utilized. This support spacing applies also to stainless steel vent pipe, unless the manufacturer’s instructions permit otherwise. The vertical vent and air intake pipes also must be supported, wherever the building construction provides allowance for it, such as ceiling or roof passage openings where a firestop and support or braces can be affixed.
9. Minimum clearances of vent pipes from combustible constructions
must be maintained (Pub J-40). No clearance is required between the vent and air intake pipes of this boiler.
10. Common venting with other appliances or another Jaguar boiler is
not allowed.
11. DO NOT install a vent damper or similar devices in vent system or on
the boiler.
12. DO NOT insulate venting system.
VENTING INSTALLATION
Only PVC/CPVC and approved stainless steel materials listed on page 7 may be used for the venting system installation. If stainless steel vent sys­tems are used, follow the manufacturer’s instructions, in conjunction with these instructions.
I. Non-Direct Vent Installation
The air for combustion is taken from the ambient air surrounding the boil­er; therefore, ample supply of air is required for combustion and ventila­tion (see page 6.)
DO NOT use this installation method if the surrounding of the boiler is contaminated. See page 6 for the list of harmful contaminants and their sources, to avoid.
CAUTION: Flue gasses exiting from the vent terminal will condense. Building materials in the area of the vent terminal should be protected from discoloration and degradation.
VENT TERMINATION LOCATION AND CLEARANCES
1. The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.
2. The venting system shall terminate at least 12 inches below, or 12 inches horizontally from any door, window or gravity air inlet into any building. The bottom of the vent terminal or air intake terminal shall be at least 12 inches above grade or the normal snow level whichever is greater.
3. Through the wall vents shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. Minimum clearance of 4 feet horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
4. Vent termination must not be located in any confined space (i.e. window wells, alcoves, narrow alleys) or under any over hang or deck. Vent termination should not allow flue gas discharge towards neigh­bor’s windows or where personal injury or property damages can occur.
A. NON-DIRECT VENT - VERTICAL VENTING
Figure shows typical venting through the roof. The vent pipe must pass through the ceiling, floor and the roof vertically through a 8" minimum diam­eter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage, an appropriate UL listed roof flashing must be used.
An existing chimney may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe with in the chimney.
The vertical vent piping must terminate with a screened tee, combination of 45˚ elbow and a 90˚ screened elbow termination or a rain cap termination.
II. Direct Vent Installation
Air intake piping from outside to the boiler air intake adapter provides the air for combustion. The boiler surrounding may be contaminated (See page 6). Piping the air intake to the outside can prevent contaminants from the boiler surrounding from entering the combustion air supply.
B. SIDEWALL DIRECT VENTING Vent termination location and clearances for non-direct vent stated
in paragraph I, also applies to sidewall direct venting.
• See figure 4, 5 & 6 for direct vent side wall venting using the
Slant/Fin vent/air intake termination.
• See figure 6 for direct vent side wall venting with close spacing.
• See figure 7 & 8 for direct vent through the roof.
CAUTION: Flue gasses existing from the vent terminal will condense.
Building materials in the area of the terminal should be protected from discoloration and degradation.
Jaguar Caravan Multiple and Cascading Boilers 9
Wall opening for Slant/Fin vent air intake termination Height - 5 3/4" Width - 12 3/4” Wall thickness - 3” to 14”
Figure 4.
Jaguar Caravan Multiple and Cascading Boilers10
Figure 5.
Jaguar Caravan Multiple and Cascading Boilers 11
**
**
Figure 6. Alternative multiple side wall air intake & exhaust venting.
Note:
• Air intake opening must be 12 inches minimum above snow line or grade if it does not snow in area boilers are located.
• No minimum horizontal distance between outlets or inlets.
• Exhaust termination to extend beyond air intake, prevent condensation from falling onto air intake
** Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. This height should be used as the snow line.
Loading...
+ 25 hidden pages