Slant-Fin J-390 User Manual

This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER HOT WATER MODEL J-390
GAS-FIRED BOILER FOR NATURAL GAS
INSTALLATION AND OPERATING INSTRUCTIONS
TABLE OF CONTENTS
Boiler Dimensions and Rating ....................................................2
Identification of Parts..................................................................3
Installation Requirements ...........................................................4
Contamination Prevention...........................................................5
Venting Application .....................................................................5
Boiler Room Air Supply and Ventilation......................................5
Flue gas Venting Requirements..................................................6
Additional Installation Requirements for Massachusetts............6
Vent Material ..............................................................................6
Air Intake Material ......................................................................6
Vent and Air Intake Restrictions .................................................7
Non-Direct Vent Installation ........................................................8
Sidewall Venting, Non-Direct Vent ..............................................8
Vent Termination Location and Clearance ..................................8
Non-Direct Vent Vertical Venting .................................................8
Direct Vent Installation ................................................................8
Sidewall Venting, Direct Vent ......................................................8
Vent/Air Intake Termination Installation.....................................14
Direct Vent, Venting and Air Intake through a Roof ..................15
Venting and Air Intake Regular Inspection ...............................16
Condensate Removal System..................................................16
Gas Piping
Electrical Wiring ........................................................................17
Wiring Diagram.........................................................................18
Single and Multi Zoning
Water Piping .............................................................................24
Operating Instructions...............................................................30
Boiler Control Displa
Boiler Control............................................................................30
Sequence of Operation.............................................................36
Gas Input Rate Adjustment
Safety Check ...........................................................................38
Care and Maintenance .............................................................41
Gener
................................................................................16
............................................................
...............................................................30
y
......................................................
Troubleshooting Guide ................................................42
al
21
37
IMPORTANT
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
BEFORE READING
INSTALLATION INSTRUCTIONS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having juris­diction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the
ity having jur
author
The venting system of this boiler is under positive pressure. Leakage from this system can be hazardous and if not avoided can result in death or serious injury. In addition to the recom­mendations within this manual and the
l, the venting system, from the flue collector to the out
Manua door discharge fied service agency.
isdiction.
WARNING
ust be carefully chec
, m
THE
mation
s Infor
User’
-
ked annually by a quali-
Heating Contractor
dress
Ad
Phone Number
.A.
Printed in U
.S
Boiler Model Number
Boiler Serial Number
Installation Date
708 Part No. 83-5736
lication No.
Pub
J-40
REAR VIEW
SIDE VIEW
FRONT VIEW
TOP VIEW
95/8
25
WATER RETURN
1 1/4" NPT (MALE)
G
AS PIPE
3/4" NPT
5
1/8
16 3/8
35/8
55/8
CONDENSATE DRAIN - 3/4" DIA
41/4
4" AIR INTAKE CONNECTION
(
5 3/4)
26
52
23 5/8
41/4
5
25/8
9
5/8
51/2
37/8
(21 1/8)
4
" VENT CONNECTION
WATER SUPPLY
1 1/4" NPT (MALE)
46 7/8
13 1/2
(7/8)
2
Jaguar Model J-390
RATINGS AND DIMENSIONS
Figure 1. Dimensions data
SPECIFICATIONS:
Fuel Rate Input:
Boiler Water Volume:
ater Piping
W
Connections:
Weight of Boiler
(uncrated):
Gas Piping Connection:
ent Connection:
V
Air Intake Connection:
No or
*Note:
J-390 Boiler
ifice changes are required for high altitude installations.
390,000 BTUH max
110,000 BTUH min
2.0 gallon (16.5 lbs)
1-1/4” NPT (male)
190 lbs.
emale)
NPT (f
3/4”
4” nominal I.D. pipe (PVC, CPVC or
stainless steel)
4” nominal I.D. pipe (PVC, CPVC or
stainless steel)
Jaguar J-390 Boiler
Jaguar Model J-390
BOILER CONTROL
FIELD WIRING TERMINALS (24V)
FIELD WIRING TERMINALS (120V)
GAS VALVE
TRANFORMER
4" AIR INTAKE CONNECTION
4" VENT CONNECTION
SPARK ELECTRODE (IGNITER)
HEAT EXCHANGER
VENTURI
COMBUSTION BLOWER
WINDOW (SIGHT GLASS)
FLUE PIPE
FLUE SENSOR
GAS SUPPLY VALVE
WATER SUPPLY
WATER RETURN
BOILER CONDENSATE TRAP
WATER RETURN SENSOR
WATER SUPPLY SENSOR AND WATER HIGH LIMIT
FLUE SAMPLE PORT
GAS VALVE
CONTROL BOARD COVER
CONTROL PANEL
FLUE SAMPLE PORT
HEAT EXCHANGER
ENCLOSURE
FRONT COVER
CONTROL PANEL
DOOR
FIELD WIRING BX CONNECTORS
FRONT (INTERIOR)
RIGHT SIDE (INTERIOR)
3" MIN
VENTING CONDENSATE TRAP
SEDIMENT TRAP (REQUIET)
INSTALL MANUAL MAIN SHUTOFF VALVE 5' ABOVE FLOOR, WHEN RQUIRET BY LOCAL CODE
HEAT EXCHANGER ENCLOSURE FRONT COVER LATCH
HEAT EXCHANGER ENCLOSURE FRONT COVER LATCH
LOCATION AND IDENTIFICATION OF PARTS
3
Figure 2. Location and identification of parts
4
* 2" FOR ENCLOSED
Jaguar Model J-390
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition.
This installation must also conform to the additional require-
ents in this Slant/Fin Instruction Book.
m
BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct. (See para­graph heading “Vent Termination Location and Clearance” on page 8.) The location should also be such that all boiler components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
BOILER FOUNDATION
A.
Provide a solid, level foundation, capable of supporting the weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boilers, page 2.
B. Boiler can be installed on both combustible and
non-combustible floors, but must NOT be installed on or above carpeting.
C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
. Minimum clearances to the exterior surfaces of the boiler
A
shall be as follows:
INIMUM ALCOVE AND CLOSET CLEARANCE
M
or Combustible Recommended
F
Surf
ace Construction for Service
ront 0" 24"
F Rear 0" 6" Left Side 0" 0" Right Side 0" 0"
op 4" 6"
T Flue Connector:
Enclosed — 2" 6" Uninclosed — 1" 6"
B. Provide accessibility clearance of 8" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clear­ances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
t points where hot water pipes emerge from a floor,
** A
the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
wall or ceiling,
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Figure 3. Jaguar boiler min. clearances for combustible construction.
Jaguar Model J-390
5
CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contami­nation sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause
orrosion or other damage to the heat exchanger and compo-
c nents of the boiler, causing failure of these parts or unsafe operation.
Below is a list of products and areas which may cause contaminated combustion air:
PRODUCTS TO AVOID
• Spray cans containing chloro/fluorocarbons
• Permanent wave solutions
• Chlorinated waxes/cleaners
• Chlorine-based swimming pool chemicals
• Calcium chloride used for thawing
• Sodium chloride used for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid/muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
• Adhesives used to fasten building products and other similar products
AREAS LIKELY TO HAVE CONTAMINANTS
• Dry cleaning/laundry areas and establishments
• Swimming pools
• Metal fabrication plants
• Beauty shops
• Refrigeration repair shops
• Photo processing plants
• Auto body shops
• Plastic manufacturing plants
• Furniture refinishing areas and establishments
• New building construction
• Remodeling areas
• Garages with workshops
VENTING APPLICATION
The Jaguar J-390 is a sealed combustion type boiler, it may be installed and vented either as a direct vent boiler which all air for combustion is obtained directly from outside or as a non­direct vent boiler which air for combustion is taken from inside
he boiler room.
t The Jaguar J-390 boiler must be vented by 4" diameter
PVC/CPVC schedule 40 pipe, or the proper 4” diameter stain-
ess steel venting system (see “vent material” on page ???)
l through the roof or sidewall.
BOILER ROOM AIR SUPPLY AND VENTILATION
n ample supply of air is required for combustion and ventila-
A tion. When buildings are insulated, caulked and weather­stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventila­tion, of the National Fuel Gas Code, ANSI Z223.1-latest edi­tion, or applicable provisions of the local building codes. The following recommendation applies to buildings of energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM.
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall;
floor and one louvered opening near the ceiling, each opening with a minimum FREE air passage area of
square inch per 4000 Btuh of total appliances’ input. Air drawn horizontally through HORIZONTAL DUCTS;
2. one opening near the floor and one opening near the ceil­ing, each opening with a minimum FREE air passage area of
1 square inch per 2000 Btuh of total appliances’ input.
Air drawn VERTICALLY from outdoors; one opening at
3. the floor and one opening at the ceiling, each opening with a minimum FREE air passage area of 4000 Btuh of total appliances’
4.
Air drawn from inside the building; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of per 1000 Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPR
TE THE ADDITIONAL LO
A
D
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of the boiler controls and boiler room. air into the boiler room f
1
2 of the openings required for the non-direct vent as
least mentioned above.
If additional non-direct v same space and adequate air openings are pro there are no additional air openings required for the Jaguar J-390 boiler.
OPRIATEL
one louvered opening near the
input.
Y INCREASED T
AD.
or direct-v
ent appliances are installed in the
ent installation must be at
1 square inch per
1 square inch
CCOMMO-
O A
Openings for passage of
or them,
vided f
1
6
Jaguar Model J-390
For both direct and non-direct installation, the following must be considered:
-
Openings must never be reduced or closed. If doors or win­dows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris. Inspect frequently. No mechanical draft exhaust or supply fans are to be
-
sed in or near the boiler area.
u
- Boiler area must never be under negative pressure. The flow of combustion and ventilating air to the boiler must not be obstructed.
LUE GAS VENTING REQUIREMENTS
F
The Jaguar J-390 series boiler is a high efficiency, mechanical­ly forced draft boiler and, therefore, require different venting arrangements than natural draft, lower efficiency boilers.
THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ­ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
ent piping installation MUST be in accordance with these
The v instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply.
The use of a vent damper is NOT permitted on this boiler series.
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSA
When the Bobcat is installed and used in the Commonwealth of Massa­chusetts, the following additional code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sustained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsihed grade in the area of the venting, including but not limited to dec
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time
of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall obser wired carbon mono tional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the proper for the installation of hard wired carbon monoxide detectors.
a. is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adja­cent floor level.
.
b the time of completion of installation, the owner shall have a period of thir­ty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
CHUSETTS
requirements pursuant to Massachusetts
ks and porches
ty o
In the e
v
In th e
, the following requirements shall be satisfied:
e that a battery operated or hard
v
xide detector with an alar
wner to secure the ser
ent that the side wall horizontally vented gas fueld equipment
v
ent that the requirements of this subdivision can not be met at
vices of qualified licensed prof
m is installed on each addi
-
essionals
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the hori­zontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less that one-half (1/2) inch in size,
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment Not
1. Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equip­ment installed in a room or structure separate from the dwelling, build­ing or structure used in whole or par
t for residential purposes.
“GAS VENT
VENT AND AIR INTAKE MATERIALS
The vent and air intake system for direct or non-direct vent installation must be 4” diameter PVC/CPVC schedule. 40 pipe, or UL listed single wall 4” diameter AL29-4C* stainless steel material. The following manufacturers’ systems are approved for use within a specified minimum and maximum equivalent
vent length in this manual.
Manufacturer Type/System Sealant
Heat-Fab. Inc.
ProTech System,
Inc.
national
x-L Inter
Fle
Inc.
x, Inc.
Z-Fle
, Inc.
ab
Metal-F
N/A
N/A
When joining the var
ent systems
v
, the manufacturers’ instructions should be closely fol-
Saf-T Vent
EZ Seal
FasNSeal Not Required
StaR-34 GE-IS806
ent
Z-V
Corr Guard Not Required
PVC pipe,
Schedule 40
CPVC pipe
Schedule 40
,
Not Required
TV 106
GE, R
PVC primer
and cement
CPVC pr
imer
and cement
ious components of the listed stainless steel
lowed to insure proper sealing. Use sealant specified by vent sys­tem manufacturer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions pro-
All connections must be liquid and pressure
vided in this man
ual. tight. DO NOT use galvanized flue pipe or any plastic-type materi­als other than PVC/CPVC Schedule 40.
Jaguar Model J-390
4" PVC OR CPVC
AIR INTAKE PIPE
AIR INTAKE COLLAR
4" PVC OR CPVC VENT PIPE
7
he vent connector on the boiler is designed to directly accom-
T modate either PVC/CPVC Schedule 40 pipe or the listed stain­less steel vent systems by utilizing an adapter. The adapter has a built-in sealing ring, so no additional sealant is required.
ake sure the pipes are round and burr-free, and push down
M fully past the sealing ring, until snug. (See Figure 4). Liquid soap may be used to ease insertion.
he air intake collar on the boiler is designed to directly acco-
T modate PVC/CPVC schedule 40 pipe (See figure 4). A small bead of silicon should be applied between the collar and inside of the air antake pipe, to seal properly.
. For each joint, first apply a coat of primer to the outside
8
ealing surface of the pipe and the inside sealing surface of
s each fitting. Use only the primer type that is specified for either the PVC or CPVC pipe that is bing utilized.
9. Before the primer dries, apply a coat of cement over it. A
second coat of cement can be applied, if necessary, but must be done quickly and in a manner that avoids unnecessary build-up that would cause obstruction inside the system. Use only the cement type that is specified for
ither the PVC or CPVC pipe that is being utilized.
e
0. Before the cement dries, insert the pipe into the fitting. A
1
slight twisting motion while pushing the pipe into the fitting will aid in distributing the cement evenly and ensuring the parts fully engage.
11. Quickly wipe the excess cement from the outside areas of
the joint. Discard any rags used to avoid later getting the cement on hands, clothes and equipment.
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for
all of the approved vent and air intake materials is 100 equivalent feet.
2. Equivalent of vent or air intake length is sum of the
straight pipe lengths and equivalent length of elbows. Each 90˚ elbow is equivalent to 10 ft. of 4" pipe.
Figure 4. Vent & Air Intake Pipe installation into Boiler Adapter.
PVC/CPVC PIPE GENERAL ASSEMBLY METHOD
The following are the recommended methods for cutting, cleaning and connecting PVC and CPVC pipe, for both the vent and air intake piping system:
1. When laying out the piping system, work from the boiler
2. Cut the PVC/CPVC pipe to the required lengths, and
3. Once the pre-assembled PVC/CPVC pipe vent and air
4. De-b
5. Wipe or knock out any debris from inside the PVC or
6. Thoroughly clean the outside ends of each pipe, and the
7. Re-assembly of the PVC or CPVC pipe should be done in
vent and air intake adapter to the point of outside termination.
pre-assemb
le the entire system, bef
ore sealing. Disassembly after sealing, to make any corrections, will not be possible
.
intake system is verified to be of the proper length pipe and fitting orientation, begin disassembling and preparing the pipes and fittings for the sealing process.This can be done section by section, or the complete vent and air intake system can be disassemb
led. It is recommended to mark the various parts, before complete disassembly, to eliminate the possibility of errors during re-assembly.
y PVC/CPVC pipe, to
er
urr the inside and outside of e
ensure that the
y engage fully into the fittings, and flow is
v
not compromised. A small chamfer on the outside of each pipe can particularly aid in the final assembly process.
CPVC pipe, which may have accumulated there from the cutting process or stor
age. Debris can cause operational
problems with the boiler combustion components.
inside of each fitting. sealing agents to w lengths a
way from the cleaned ends, and handle the
ust be dr
The surf
or
aces m
k properly. Handle the prepared pipe
y for the
cleaned fittings, from the outside, to avoid contamination.
sections, to avoid the primer and cement drying before the parts are engaged.
Figure 5.
3. The vent termination is in addition to the allowed equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus one 90˚ elbow.
5. Vent length restriction is for both direct and non-direct vent installations.
EXAMPLE: The combustion air is provided by air intake piping directly to the boiler (direct-vent installation). The vent piping will be PVC and installation location will require the use of 4 elbows for the vent to run the termination. The air intake piping will also be PVC, and also will require the use of 4 elbows.
8
Jaguar Model J-390
In this case, the maximum straight pipe vent length that can be utilized with the 4 elbows would be: 100’ - (4’ x 10’) = 60’. Since the air intake pipe also is PVC and requires the use of
elbows, the maximum straight pipe air intake length that
4 can be utilized is also 60 feet.
If the air for combustion were taken from the boiler room (non-direct vent installation), still the maximum straight vent length would be 60 feet.
6. The Jaguar J-390 boiler is equipped with a built-in ondensation drain and trap system. The traps must be
c filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system. Refer to the “Condensate Drainage” section of this manual. No additional condensation drain and trap is required on the vent piping system itself.
7. The horizontal vent pipe must be sloped upward from the
boiler at a pitch of at least 1/4” per 1 foot of run, so that the condensate from the vent system runs to the boiler vent adapter pipe, then out the built-in condensation drain and trap.
8.
The horizontal vent and air intake pipes must be supported with pipe straps, at intervals no greater than 5 feet, when PVC/CPVC pipe is utilized. This support spacing applies also to stainless steel vent pipe, unless the manufacturer’s instructions permit otherwise. The vertical vent and air intake pipes also must be supported, wherever the building construction provides allowance for it, such as ceiling or roof passage openings where a firestop and support or braces can be affixed.
9. Minimum clearances of vent pipes from combustible
constructions must be maintained (see Page 4). No clearance is required between the vent and air intake pipes of this boiler.
10. Common venting with other appliances or another Jaguar
boiler is not allowed.
11. DO NOT install a vent damper or similar devices in vent
system or on the boiler.
12. DO NOT insulate venting system.
should be protected from discoloration and degradation.
ENT TERMINATION LOCATION AND CLEARANCES
V
. The venting system shall terminate at least 3 feet above
1
any forced air inlet located within 10 feet.
. The venting system shall terminate at least 4 feet below,
2
4 feet horizontally from, or 1 foot above any door, window or gravity air inlet into any building.The bottom of the vent terminal or air intake terminal shall be at least 12 inches
bove grade or the normal snow level whichever is
a greater.
3. Through the wall vents shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equip­ment. Minimum clearance of 4 feet horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
4. Vent termination must not be located in any confined space (i.e. window wells, alcoves, narrow alleys) or under any overhang or deck.Vent termination should not allow flue gas discharge towards neighbor’s windows or where personal injury or property damages can occur.
B. NON-DIRECT VENT - VERTICAL VENTING
Figure 8 shows typical venting through the roof.The vent pipe must pass through the ceiling, floor and the roof vertically through a 8" minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage, an appropriate UL listed roof flashing must be used.
An existing chimney (see Figure 9) may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe with in the chimney.
The vertical vent piping must terminate with a screened tee, combination of 45˚ elbow and a 90˚ screened elbo tion or a rain cap termination.
II. Direct Vent Installation
w termina-
VENTING
Only PVC/CPVC and approved stainless steel materials listed on page 6 may be used for the venting system installation. If stainless steel vent systems are used, f
s instructions
er’
I. Non-Direct Vent Installation
The air for comb surrounding the boiler for combustion and ventilation (see page 6.)
DO boiler is contaminated. See page 5 for the list of harmful contaminants and their sources, to avoid.
A.
Figures 6 and 7 show typical horizontal sidewall venting. For combustible wall passage of vent piping, a UL listed thimble or flashing and sealing boot must be used, providing the wall thickness from 3" minimum up to 14" maximum. The vent piping must terminate with a screened tee or elbow termination facing down.
CA
condense
INSTALLATION
actur-
w the man
, in conjunction with these instructions.
ustion is tak
NOT use this installation method if the surrounding of the
ALL VENTING - NON-DIRECT VENT
SIDEW
UTION:Flue gasses e
. Building materials in the area of the vent terminal
en from the ambient air
ore, ample supply of air is required
theref
;
xiting from the v
ollo
ent ter
uf
minal will
Air intake piping from outside to the boiler air intake adapter provides the air for combustion.The boiler surrounding may be contaminated (See page 5). can prev entering the combustion air supply.
A. SIDEWALL DIRECT VENTING
Figures 10 and 11 sho Slant/Fin vent/air intake termination.
CAUTION: Flue gasses existing from the vent terminal will con­dense. Building materials in the area of the terminal should be protected from discolor requirements of the vent termination location and clearances stated in this manual.
ent contaminants from the boiler surrounding from
Piping the air intak
all direct venting, using a
w typical side
ation and degradation, in addition to the
w
e to the outside
Jaguar Model J-390
AIR INTAKE (
DO NOT BL0CK)
A
U/L LISTED FLASHING AND SEALING BOOT MUST BE USED ON COMBUSTIBLE W
ALLS.
4
IN. DIA.
P
VC/CVPC PIPE FOR V
ENT
T
ERMINATION 90 ELBOW
WITH SCREEN
SNOW LINE
(
SEE DEFINITION)
OUTSIDE WALL
SLOPE UP 1/4 IN. P
ER FOOT MIN. FROM BOILER TO V
ENT TERMINATION
9
0 ELBOW
6" MIN.
1
0" MAX.
12" MIN
(DO NOT BL0CK)
AIR INTAKE
90 ELBOW
STANDARD
VENT TERMIN ATION
FROM BOILER TO
PER FOOT MIN.
SLOPE UP
1/4 IN.
VENT
MATERIAL FOR
STEEL VENTING
STAINLESS
4 INCH. DIA.
OUTSIDE V ENT TERMINATION ELBOW WITH SCREEN
OUTSIDE WALL
SNOW LINE
(SEE DEFINITION)
6" MIN
10" MAX
12" MIN
WALL THIMBLE MUST BE USED ON COMBUSTIBLE WALLS
JAGUAR J-390 NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
9
AL29-4C S.S.*. venting materials (See page 7).
Figure 6. Non-direct vent, side wall venting - utilizing PVC/CPVC pipe for venting.
Figure 7.
Non-direct vent, side wall venting - utilizing stainless steel vent materials for venting.
** Definition of Sno
w Line:
wledge of local conditions will re
Kno
The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED
*
TRADEMARK OF ALLEGHENY LUDLUM CORP
eal the maxim
v
.
um height that repeated sno
alls accumulate to.
wf
10
SUPPORT
FIRESTOP AND
R
AIN CAP TERMINATION MAY BE USED
*
ALTERNATE VERTICAL TERMINATION
E
LBOW WITH SCREEN
9
0°TERMINATION
*
4
5°ELBOW
PIPE OR STAINLESS STEEL
4 IN. DIA. PVC/CPVC
FIRESTOP AND SUPPORT
VENTING MATERIAL FOR VENT
2
"MIN
S
TORM C OLLAR
F
LASHING AND
4 IN. DIA. PVC/CPVC
VENTING MATERIAL FOR VENT
PIPE OR STAINLESS STEEL
T
EE WITH SCREEN
VENT TERMINATION
SLOPE UP 1/4 IN.
PER FOOT MIN.
(DO NOT BLOCK)
AIR INTAKE
90°ELBOW
2" MIN
1 FT. MIN
10 FT. MIN
Jaguar Model J-390
JAGUAR J-390 NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
AL29-4C S.S.*. venting materials (See page 7).
Figure 8. Jaguar J-390 - non-direct vent, venting through the roof
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP
*
.
Jaguar Model J-390
CHIMNEY T
OP PLATE
VENT TERMINATION T
EE WITH SCREEN
VENT
VENTING MATERIAL FOR
PIPE OR STAINLESS STEEL
4 INCH DIA. PVC/CPVC
SEAL CHIMNEY OPENING
VENT
VENTING MATERIAL FOR
PIPE OR STAINLESS STEEL
4 INCH DIA. PVC/CPVC
WITH MO R TAR OR CO VE R PLATE
45°ELBOW
R
AIN CAP TERMINATION MAY BE USED
ALTERNATE VERTICAL TERMINATION
*
E
LBOW WITH SCREEN
9
0°TERMINATION
PER FOOT MIN.
SLOPE UP
1/4 IN.
90°ELBOW
(DO NOT BLOCK)
AIR INTAKE
*
1FT.MIN
10 FT. MIN
JAGUAR J-390 NON - DIRECT VENT, UTILIZING AN EXISTING
All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
CHIMNEY AS A CHASE
AL29-4C S.S.*. venting materials (See page 7).
11
Figure 9. Jaguar J-390 - non-direct vent, utilizing an existing chimney as a chase.
AL 29-4C IS A REGISTERED
*
TRADEMARK OF ALLEGHENY LUDLUM CORP
.
12
SLANT/FIN VENT/AIR INTAKE TERMINATION KIT PART # 83 0802 000
AIR INTAKE LOUVERS
SNOW LINE ** (SEE DEFINITION)
OUTSIDE WALL
4" DIA PVC/CPVC PIPE FOR AIR INTAKE
3
" - 14" THICK WALL
90°ELBOW
4" DIA PVC/CPVC FLUE PIPE
4" DIA PVC/CPVC COUPLING WITH SCREEN
SLANT/FIN VENT/AIR INTAKE TERMINATION KIT PART # 83 0802 000 TOGETHER WITH SPECIAL KIT FOR STAINLESS STEEL VENT PIPE
AIR INTAKE LOUVERS
4" DIA STRIGHT SCREENED VENT TERMINATION
SNOW LINE ** (SEE DEFINITION)
OUTSIDE WALL
ADAPTOR
4" DIA STAINLESS STEEL PIPE FOR VENT
90°ELBOW
4" DIA PVC/CPVC PIPE FOR AIR INTAKE
3" - 14" THICK WALL
Jaguar Model J-390
JAGUAR J-390 - DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
AL29-4C S.S.*. venting materials (See page 7).
Figure 10. Direct vent, sidewall venting illustration; utilizing PVC/CPVC pipe for venting
Figure 11.
** Definition of Sno The height should be used as the SNOW LINE.
*
Direct vent,
w Line:
AL 29-4C IS A REGISTERED
wall venting illustration;
side
wledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
Kno
TRADEMARK OF ALLEGHENY LUDLUM CORP
utilizing stainless steel vent materials f
.
or venting.
Jaguar Model J-390
4" DIA PVC/CPVC PIPE FOR VENT
4
" DIA PVC/CPVC PIPE FOR AIR INTAKE
I
NSIDE TERMINATION P LATE
OUTSIDE TERMINATION P LATE
S
CREEN
4" DIA PVC/CPVC COUPLING
SCREW
W
ALL
(3" - 14 " THIC K)
COMBUSTIO N
A
IR
VENT
GASES
STOP FOR AIR/VENT O
UTSIDE TERMINAL
4
" DIA PVC/CPVC COUPLING
S
CREEN
L
OUVERS
S
EAL HERE
O
UTSIDE TERMINATION P LATE
INSIDE TERMINATION
P
LATE
4" DIA PVC/CPVC PIPE
FOR AIR INTAK E
4" DIA PVC/CPVC PIPE FOR VEN T
WALL (
3" - 14" THICK)
SCREW
4" PVC OR CPVC
A
IR IN TAKE PIPE
4" PVC OR CPVC VENT PIPE
AIR INTAKE COLLAR
4" DIA PVC/CPVC PIPE FOR AIR I NTAKE
4" DIA STAINLESS STEEL SLIP JOINT PIPE FOR VENT
I
SCREW
INSIDE TERMINATION PLATE
4" DIA STRAIGHT SCREEN TERMINATION
OUTSIDE TERMINATION PLATE
REDUCER RING FOR SLIP JOINT PIPE
REDUCER RING FOR SLIP JOINT PIPE
4" DIA STAINLESS STEEL SLIP JOINT PIPE FOR VENT
VENT
GASES
COMBUSTION
AIR
4" DIA PVC/CPVC PIPE
FOR AIR INTAKE
INSIDE TERM INATION
PLATE
SEAL HERE
WALL (3"-14"THICK)
OUTSIDE TERMINATION P LATE
LOUVERS
STOP FOR AIR/VENT OUTSIDE TERMINAL
SCREW
WALL (3"-14"THICK)
4" DIA STRAIGHT SCREEN TERMINATION
SCREW
A
IR IN TAKE COLLAR
R
EDUCER RING FOR USE WITH STAINLESS STEEL V
ENT PIPING
4" STAINLESS STEE L V ENT P IPE
4" PVC OR CPVC
AIR INTAKE PIPE
4
13
Figure 12a. Vent/Air intake termination; utilizing PVC/CPVC pipe for venting.
Figure 12b. Vent/Air intake termination; utilizing stainless steel venting materials.
14
Jaguar Model J-390
ENT/AIR INTAKE TERMINATION FOR PVC/CPVC
V
ENTING INSTALLATION
V
This termination is designed specifically for 4” diameter PVC or CPVC Schedule 40 pipe to be used as the vent and air intake piping material, only. It can be used on a combustible wall, provided that the wall passage is cut out as specified in step 5.
. Termination must be installed horizontally.
1
. Refer to Figure 12a for installation details.
2
3. Wall thickness should be 3” to 14” thick.
4. Follow instruction for “vent termination location and clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in the wall. Height: 5 Width: 12
3
4
3
4
6. From outside of the wall, install outside termination plate using 4 screws. Make sure the louvers are at right side. Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the out side termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #9.
8. From inside, install the inside termination plate, using 4 screws. Make sure that the holes for the vent and air intake pipe visually line up with the vent passage hole and air intake collar on the outside termination plate.
9. Cut the PVC or CPVC air intake pipe to the proper dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
10. Cut the PVC or CPVC vent pipe so that it will extend out past the outer surface of the outside termination plate by 2”.
11. Cement a 4”
diameter PVC or CPVC coupling onto the PVC or CPVC vent pipe, and install a stainless steel screen into the coupling.
12. From outside the wall, insert the bare end of the PVC or CPVC vent pipe through the outside and inside terminal
, until the coupling is flush with the outside wall plate.
plates
13. From inside, proceed with the air intake and vent pipe
w the proper PVC/CPVC assemb
installation. F
actices specified on page 7, and venting system
pr restr
ictions specified on page 7 of this manual.
ollo
ly
ENT/AIR INTAKE TERMINATION FOR STAINLESS STEEL
V
ENTING INSTALLATION
V
This termination is easily modified for Heat-Fab Saf-T vent 4” diameter stainless steel venting system to be used as the vent, by installing the special reducing rings provided in the optional stainless steel flue pipe kit, with 4” diameter PVC or CPVC schedule 40 pipe to be used as the air intake piping material,
nly. It can be used on a combustible wall, provided that the
o
all passage is cut out as specified in step 5.
w
1. Termination must be installed horizontally.
2. Refer to Figure 12b for installation details.
3. Wall thickness should be 3” to 14” thick.
4. Follow instruction for “vent termination location and clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in the wall. Height: 5 Width: 12
3
4
3
4
6. Install the reducing rings on the inner facing side of the outside and inside termination plates (see figure 12b).
7. From outside of the wall, install outside termination plate using 4 screws. Make sure the louvers are at right side. Seal the plate perimeter with silicon.
8. Apply a bead of silicon around the outer surface of the outside termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #10.
9. From inside, install inside termination plate using 4 screws.
10. Cut the PVC or CPVC air intake pipe to the proper dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #8.
11. Assemble and seal straight screened termination to the slip joint connector.
12. From outside of the building, insert vent pipe (slip joint connector and termination assembly) through the 4” holes of the outside and inside termination plate.
From inside, proceed with air intake and vent pipe
13. installation. Follow vent manufacturer’s instructions and restrictions specified on page 7 of this manual.
Jaguar Model J-390
S
N
O
W
L
I
N
E
SUPPORT
FIRESTOPAND
PER FOOT MIN.
SLOPE UP
1/4 IN.
PIPE
W
ITH SCREEN
S
TORM COLLA R
STRAIGHT TERMINATION
FLASHING AND
180°ELBOW
WITH SC REEN
AIR INTAKE
AIR INTAKE
4" DIA. PVC/CPVC PIPE FOR
SUPPORT
SUPPORT
FIRESTOP AND
4" DIA PVC/CPVC OR STAINLESS STEEL MATERIAL FOR VENT
2" MIN.
10FT.MIN.
1FT.MIN.
1FT.MIN
B. DIRECT VENT - VENTING AND AIR INTAKE
THROUGH A ROOF
igure 13 shows typical vertical venting. The vent pipe must
F
ass through the ceiling, floor and the roof vertically through a
p 8” minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage an appropriate UL listed roof flashing must be used.
The vertical vent piping must terminate with a screened straight termination. The air intake termination should be a screened 180˚ elbow facing down.The air intake opening must
e at least 1 foot below the vent opening.
b
JAGUAR J-390 - DIRECT VENT, VENTING AND AIR INTAKE
THROUGH A ROOF
All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
AL29-4C S.S.*. venting materials (See page 7).
or PVC/CPVC pipe, follow the proper assembly practices
F
pecified on page 7, and venting system restrictions specified
s on page 7 of this manual. For stainless steel venting systems, follow the vent manufacturer’s instructions and the restrictions specified on page 7 of this manual
15
Figure 13. Direct vent, venting and air intake through a roof.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP
*
.
16
NEUTRALIZING UNIT (IF REQUIRED)
CONDENSATE PUMP (IF REQUIRED)
DRAIN INSIDE BUILDING
PLASTIC TUBING
DRAIN VACUUM BREAKER, LEAVE OPEN
Jaguar Model J-390
VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION
A. Inspect the system regularly for condensation, corrosion,
sagging and/or physical damage. A qualified professional should service the boiler annually and include such an
nspection at that time. The homeowner should look over the
i system monthly for damage, water stains, any signs of rust, other corrosions or separation of the vent and air intake piping (if direct-vent).
B. Should an inspection turn up signs of condensation,
corrosion, sagging or damage, the boiler should be shut down immediately and the condition should be corrected by a qualified professional.
CONDENSATE REMOVAL SYSTEM
aguar J-390 boiler is equipped with a built-in condensation
The J drain and trap system. This system consists of two traps, one being dedicated to the condensate produced by the boiler, and another being dedicated to the condensate produced within the vent piping. (See page 13 for the location of each of the traps). Both of these traps must be filled with water. This is most easily accomplished by pouring water from a small container into the vent connector at the top of the boiler, before the vent pipe is attached, until the tubing loop trap in the rear of the boiler is visi­bly filled. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. Periodic inspection should be made of this assembly for deterioration of the tubing and components, and to insure that the traps are not plugged. If any part is plugged or appears to have excessive sediment within, it should be removed from the drain assembly, have the obstruc­tion cleared, refilled with water and reinstalled as before.
A 3/4” PVC tee assembly, located in the rear of the boiler jacket, is provided to run the condensate liquid from the boiler. Connect the plastic tubing that will be run to the drain to the bottom take­off of the tee. Leave the top take-off of the tee open, to act as a vacuum breaker. If the building drain is above the bottom portion of the tee, a condensate removal pump will be required.This pump must have an overflow switch, and be compatible with the acidic condensate liquid, as must all fittings and the tubing used in this condensate removal system. (See Figure 14).
No part of the condensate removal system can be exposed to freezing temperatures, or any other conditions that could cause blockage. DO NOT run drain tubing to the outside of the building. In addition, certain jurisdictions or drain pipe materials may require a neutralization unit to be installed in the condensate removal system. Any piping other than plastic types will be subject to corrosion or deter
ioration from the acidic conden
sate, which may have a pH level as low as 3.0. A condensate filter containing lime, marble, or phosphate chips can neutralize the condensate to a pH level above 6.5, which is safe for all drain piping materials. (See Figure 14).The neutralizing filter medium will require periodic changing, to ensure it’s affective­ness. Replacing the medium on an annual basis is recom­mended, or refer to the manufacturer’s instructions for systems
hat are available for neutralizing condensate.
t
COMMONWEALTH OF MASSACHUSETTS SPECIAL REQUIREMENT
When the Jaguar J-390 is installed and used in the Common­wealth of Massachusetts, a neutralization unit MUST be installed in the condensate removal system.
GAS PIPING
A. Local installation codes apply.The pipe joint compound
used on threads must be resistant to the action of liquefied petroleum gases.
he gas supply line to the boiler should run directly from the meter
B. T
A manual gas supply shut-off valve is provided on the boiler’s gas supply pipe. (See Figure 2, on page 3). Local codes may specify a manual main gas supply shut-off valve to be 5’ above the floor, and a disconnection union at the gas piping entrance to the boiler. In this case, the gas supply shut-off valve must be relocated to the specified location. If the gas supply pipe must be upsized for flow considerations, then the same size main gas supply shut-off valve must be used.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (Btu/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow in piping (cu. ft. per hour).
4. Use table below to select proper pipe size.
EXAMPLE: Distance from gas meter to the boiler is 30ft. Heating value of natural gas is 1020 Btu/cu. Ft. Select proper pipe size.
Gas flow = 390,000 Btu/hr
= 382 cu. ft. per hour
1020 Btu/cu. ft.
Figure 14. Condensate disposal system
Jaguar Model J-390
17
t 30 ft. length of pipe, match required capacity from table on
A
his page (choose higher capacity, in this case is 590 cu. ft. per
t hour). Required pipe size is 1
mproper gas pipe sizing will result in flame outages, insuffi-
I
1
4".
cient heat and other installation difficulties. For more informa­tion and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested
before replacing the boiler in operation. Use liquid soap solution for all gas leak testing. DO NOT use open flame. This boiler and it’s individual shutoff valve must be disconnected from the gas supply piping system during and pressure testing of that system at test pressures in excess
1
of
2 PSIG. This boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
1
2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap is required, as illustrated on page 3.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
Length of pipe in Feet
Gas Flow In piping -- cu. ft. per hr.
Iron Pipe Size (IPS) — inches
1/2
3
/4 11
1
/4
11/2
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
vity = 0.6.
At pressure drop of 0.3 in. w
, specific gr
ater
a
oiler must be electrically grounded in accordance with the
B
equirements of the authority having jurisdiction, or, in the
r absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.
Proper polarity is critical for the power supply connections. Reversed polarity will cause system lockout. Proper ground­ing is critical for boiler operation, connect the ground wire to the green ground screw next to the line voltage terminal
trip.
s
2. Circulator(s)
A set of terminals are provided for the boiler (primary loop) circulator. Only wire this circulator to these terminals, additional (secondary loop) circulators for space heating require the use of relays and a separate power source.
For multiple zoning, either zone valves or circulators maybe used.
For zone valve system (See Figure 16a).
For pump zoning system (See Figure 16b and 16c).
DO NOT use boiler transformer to power external accessories like zone valve and relays, overload and/or burned out transformer and boiler malfunction can result. Use separate transformer to power such components.
A second set of terminals are provided for the domestic hot water tank circulator (if used). The primary loop circulator is always de-energized when the DHW tank circulator is energized, for priority.
3. SPACE HEATING THERMOSTAT(S)
Install thermostat on an inside wall and away from any heat sources, sunshine and drafts. A set of terminals are provid­ed for connection of 24 volt style thermostats, relays or zone valve end switches (isolated contacts). (See wiring diagram Figure 15a).
Thermostat heat anticipator: For a non-zoned system set thermostat heat anticipator to 0.1 Amps, for zoned system set to match power requirements of zone valves or relays. Refer to man see instr
uctions with ther
ufacturer’
s instructions and specifications. Also
mostat.
ELECTRICAL WIRING
All field wiring to the boiler is connected to the 2 sets of
minal str
ter
ips, located under the jacket top panel.
(See Figure 2, on page 3)
DANGER: Before wiring always turn off electric power supply. Otherwise, shock or death can result.
1. Power Supply
A separately fused circuit is recommended. Use standard 15 Amp. fuse or breaker and 14 gage conductors in BX
le or conduit.
cab
Provide disconnect means and overload protection as
am (Figure 15a) boiler
required.
See boiler wir
ing diag
r
control (Figure15b) and ladder diagram (Figure 15c).
4. DOMESTIC HOT WATER TANK THERMOSTAT
A set of terminals are provided for connection of the DHW tank thermostat (if used). (See wiring diagram Figure 15a).
5. OUTDOOR AIR SENSOR
A set of terminals are provided for connection of an outdoor air sensor (if this method is used). (See wir
ing diagr
am
Figure 15a).
Mount on
The outdoor air sensor m
ust be a 12k ohm type
. an outside wall, shielded from direct sunlight or flow of heat or cooling form other sources. See instructions provided with sensor.
6. LOW WATER CUTOFF
or connection of a LWCO. If
A set of ter this de
minals are pro
vice is used, remove the factory installed jumper from
vided f
these terminals. (See wiring diagram Figure 15a).
18
WIRE LEGEND:
1
CAUTION:
1
2
3
4
5
678
9
10
11
12
13
14
15
16
12
3
4
56
78
HN
H
N
HN
1 2 3 4 5 6
12
3
1 2 3
4
W W
BL
R
B
L
DISPLAY
BK
BK
G
BK
BK
G
W
G
ROUND
R
Y
PR
PK
BR
BK
PR
BK
W
1 2 3 4 5 6 7
BK
R
Y
W
1
W
W
W
BK
BK
BK
W
W
W
Y
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. "VERIFY PROPER OPERATION AFTER SERVICING".
COMBUSTION
BLOWER
J9
L
OW WATER
CUT OFF
(
IF USED,REMOVE
7
-8 JUMPER)
12 Kohm
OUTDOOR
SENSER
(IF USED)
1
20V
60HZ
L
1
HOT
L
2
N
EUTRAL
BOILER
C
IRCULATOR
P
OWER
O
N/OFF
S
WITCH
FLUE GAS SENSOR
(1/4" TABS)
RETURN WATER SENSOR
(BLUE CONNECTOR)
S
UPPLY WATER SENSOR
(RED CONNECTOR)
WATER HIGH
LIMIT
(1/4" TABS)
3PIN
CONNECTOR
GAS VALVE
3PIN
CONNECTOR
D
HW TANK
THERMOSTAT
(
IF USED)
DHW
C
IRCULATOR
(IF USED)
120V/24V
TRANSFORMER
F
IELD WIRING
TERMINALS
2
4V ROOM THERMOSTAT
O
R ISOLATED CONTACT
J13
J6
J2
J5
PROVIDE DISCONNECT MEANS & OVERLOAD PROTECTION AS REQUIRED. IF ANY OF THE ORIGINAL W IRE AS SUPPLIED WITH THE APPLIIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C OR ITS EQUIVALENT.
FACTORY WIRED FIELD WIRED, FIELD SUPPLIED
"
CALL FOR HEAT"
BL
BR
W
G
W
W
B
K
W
G
Jaguar Model J-390
Figure 15a. Schematic wiring diagram.
Jaguar Model J-390
ARGUS VISION CONTROL
NOT
USED
NOT
USED
T2
J12
J13
SPARK
IGNITOR
SPARK
CABLE
GROUND
FUSE
J9
J6
J2
J5
BOILER CONTROL
19
Figure 15b. Boiler Control.
20
GND
NEUTRAL
HOT
L2
L1
120V/60HZ
120V
10V
120V
24V
DISPLAY
WATER HIGH
LIMIT
"CALL FOR HEAT"
24V ROOM THERMOSTAT
DHW THERMOSTAT
(IF USED) OR SENSOR
LOW WATER CUT OFF
(IF USED) OR JUMPER
120V SECTION OF CONTROL BOARD
MICRO
PROCESSOR
ON CONTROL
BOARD
OUTDOOR SENSOR
(IF USED)
FLUE GAS
SENSOR
RETURN WATER
SENSOR
SUPPLY WATER
SENSOR
GAS
VALVE
BOILER ON/OFF
SWITCH
COMBUSTION
BLOWER
BOILER
CIRCULATOR
DHW CIRCULATOR
(IF USED)
SPARK
ELECTRODE
DISCONNECT
SWITCH
CHASSIS
GND
OR ISOLATED CONTACT
COMBUSTION
BLOWER
M
M
Jaguar Model J-390
Figure 15c. Ladder wiring diagram.
Jaguar Model J-390
1
END
SWITCH
TH-TR
MOTOR
2
T
T T T T T T T T T T T T T T
T
T
3 4 5 6
SPACE
HEATING
SYSTEM
CIRCULATOR
END
SWITCH
TH-TR
MOTOR
ZONE 2
THERMOSTAT
V8043E/F
END
SWITCH
TH-TR
MOTOR
ZONE 3
THERMOSTAT
V8043E/F
1 2 3 4 5 6 7 8
FIELD WIRING
TERMINALS
ON BOILER
JUMPER
R845A
RELAY
LI
L2
1
ZONE 1
THERMOSTAT
120V/24V
TRANSFORMER
1
POWER SUPPLY, P ROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
MULTIZONING OF "JAGUAR" BOILER;
ZONE VA LVE SYSTEM USING V8043E/F ZONE VALVES AND R845A RELAY
DISCONNECT
SWITCH
V8043E/F
21
Figure 16a. Multizoning of Jaguar boiler; zone valve system.
22
1 2 3 4 5 6 7 8
FIELD WIRING
TERMINALS
ON BOILER
1
2
T T
3 4 5 6
T T T T
LI
L2
DISCONNECT
SWITCH
1
R845A
RELAY ZONE 3
CIRC.
ZONE 3
R845A
RELAY ZONE 2
CIRC.
ZONE 2
R845A
RELAY ZONE 1
CIRC.
ZONE 1
ZONE 3
THERMOSTAT
ZONE 2
THERMOSTAT
ZONE 1
THERMOSTAT
1
POWER SUPPLY, PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
MULTIZONING OF "JAGUAR" BOILER;
PUMP ZONING SYSTEM USING R845A RELAY
1
2 3 4 5 6
1
2 3 4 5 6
Jaguar Model J-390
Figure 16b. Multizoning of Bobcat Jaguar; pump zoning system using R845A relay.
Jaguar Model J-390
LI
L2
1
DISCONNECT
SWITCH
120V/24V
TRANSFORMER
FIELD WIRING
TERMINALS ON BOILER
CIRC.
ZONE 3
ZONE 3
THERMOSTAT
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MULTIZONING OF "JAGUAR" BOILER;
PUMP ZONING SYSTEM USING R882A/B RELAYS
CIRC.
ZONE 2
R882A/B
R882A/B
ZONE 2
THERMOSTAT
CIRC.
ZONE 1
R882A/B
ZONE 1
THERMOSTAT
120V/60HZ
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1
2
TT
3
4
56
LI
L2
1
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DISCONNECT SWITCH
R845A RELAY
THERMOSTAT
CIRCULATOR
FIELD WIRING TERMINALS ON BOILER
LI
L2
1
1
1 2 3 4 5 6 7 8
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DISCONNECT SWITCH
THERMOSTAT
CIRCULATOR
R 882A/B RELAY
120 V / 24 V TRANSFORMER
FIELD WIRING TERMINALS ON BOILER
23
Figure 16c. Multizoning of Jaguar boiler; pump zoning system using R882A/B relays.
Figure 16d. Single zoning of Jaguar boiler; pump zoning system using R845A relay.
Figure 16e. Single zoning of Jaguar boiler; pump zoning sys­tem using R882A/B relay.
24
Jaguar Model J-390
WATER PIPING
1. Connection of system to boiler:
rimary/secondary piping of the system is recommended, to
P
nsure the proper flow through the boiler. (See Figures 19
e through 21). The boiler loop piping must be the same diameter as the water outlet (supply) and inlet (return) piping connections provided on the boiler, particularly on longer loops. See page 2 for piping connection size.
2. Circulator Pumps:
The boiler loop piping must utilize the Taco 1400-20 circulator
hat is supplied with the boiler, to ensure the proper flow
t
hrough the boiler. Refer to Figure 18 for the boiler water side
t pressure drop and Table 2 for the recommended pump models for the domestic hot water system. Install the pumps in the orientation shown in Figures 19 through 21.
3. Relief Valve(supplied with boiler):
Tee the relief valve into the boiler water outlet (supply) piping as close to the water outlet (supply) connection as possible. (See Figure 17). The relief valve’s discharge piping must be the same size or larger than the relief valve’s outlet, and must terminate 6” minimum from floor with a plain (no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT hard-pipe to drain piping, or any place where freezing could occur. No shut-off valve is permitted between the relief valve and boiler, or in the discharge line.
4. Air Control System:
An appropriately sized diaphragm-type expansion tank must be used to control the system pressure. See boiler volume data on page 2, and the recommended location in Figures 19 through 21. An air vent is recommended to be installed on an air separator in close proximity to the expansion tank.
5. Cold Water Fill:
A pressure reducing (fill) valve, with a shut-off valve upstream of it, should be installed in close proximity of the expansion tank. (See Figures 19 through 21). Use a back flow check valve in the cold water supply as required by local codes.
Low Water Cutoff:
6.
On a hot water boiler installed abo must be provided with a low water cutoff device at the time of installation by the installer (see Figure 17 for piping arrangement).
ve radiation level, the boiler
7. Water Treatment and Freeze Protection:
A good water treatment program will not only extend the useful life of this boiler but it will also save much of the time
nd expense of repairs made necessary by preventable
a
ccurrences. A reputable water treatment company should be
o consulted to evaluate and determine the best overall treatment program for your boiler equipment.
The heat exchanger is made of aluminum, so the system water must be maintained between 7.0 and 8.5 PH level.
horoughly flush the system, before connecting the boiler, to
T
emove any sediment or glycol.
r
Anti-freeze is sometimes used in hydronic systems to protect against freeze-up in the event of power failure or boiler shut down in the cold winter.
(Propyleneglycol with Pro-Tek 922 inhibitor) by Rhomar Water Management, Inc.
instructions for proper application and proper mixture for
um ambient temperature.
minim
other than that supplied by Slant-Fin or specifically approved and/or recommended for use by Slant-Fin will void this warranty. Never use Ethylene Glycol as it is toxic to humans.
Never use any types of automotive or standard gylcol freeze protection fluids.
8. Piping a heating - cooling system to a water boiler and chiller:
Figure 21 illustrates a method of piping a heating-cooling system to a water boiler and a chiller. Hand valves (shown) or automatic valves must be installed to prevent circulation of chilled water in the boiler or hot water in the chiller.
The air control system and pressure control system must operate with chiller only, or the boiler only, being valved to the piping system. Separate control devices on the boiler and chiller may be used, or a single set of air and pres­sure controls on the common piping may be preferred.
If the boiler is used to supply hot water to heating coils in air handling units, flow control valves or other devices must be installed to prevent gravity circulation of water in the coils during the cooling cycle.
Follow the manufacturer’s
Use RhoGard
y use of anti-freeze
An
Jaguar Model J-390
PIPING ORIENTATION FOR REFERENCE ONLY.
WATER OUTLET PIPING TO REST OF THE SYSTEM
PROBE TYPE LOW WATER CUTOFF (IF REQUIRED)
PRESSURE RELIEF VALVE (SUPPLIED WITH BOILER)
1 1/4" x 1 1/4" x 3/4" NPT TEE
3/4" NPT STREET ELBOW
1 1/4" NPT STREET ELBOW
WATER OUTLET (SUPPLY) PIPE 1 1/4" DIAMETER
WATER INLET (RETURN) PIPE 1 1/4" DIAMETER
RELIEF VALVE DISCHARGE PIPING
1 1/4" NPT TEE
INSTALL MANUAL MAIN SHUTOFF VALVE 5' ABOVE FLOOR, WHEN REQUIRED BY LOCAL CODE
GAS SUPPLY VALVE
SEDIMENT TRAP
1 1/4" X 1/4" NPT REDUCER BUSHING
PRESSURE & TEMPERATURE GAUGE *
(SUPPLIED WITH BOILER) LOW WATER CUTOFF MANIFOLD (IF LWCO UTILIZED)
*
Gauge must face front of boiler, in clear view
25
Figure 17. Relief v
alve, pressure/temperature gauge and low water cutoff installation.
26
PRESSURE DROP
Boiler heat los
ORIGINAL
gpm Feet w .c DATA
28 16 14.53
23.4 11.77 11.77
20.04 9 8.77
17.55 7.38 7.38
14.04 5.3 5.3
11.7 4.2 3.46 0
00
column modif ied
8
/25/2007
JAGUAR
0
5
10
15
20
0 5 10 15 20 25 30
F
low Rate (GPM)
Head
(feet w.c.)
Figure 18. Boiler water side pressure drop
Jaguar Model J-390
Flow Rate
(gpm)
28.0 25˚ 16 6.5
23.5 30˚ 11.5 6.0
20.0 35˚ 8.5 5.5 9.0 18.0 32.0
17.5* 40˚ 7.0 5.0 11.5 21.5 35.0
able 2. Jaguar boiler recommended pump models for domestic hot water tank piping.
T
Notes:
*** Refer to the DHW Tank Manufacturer’s water flow rate requirements and associated pressure drop head loss, to select
Available Head Capability for Various Model
Circulators to Overcome DHW Tank Head Loss
(Feet w.c.) ***
(2 in series)
Taco 1400-20 Taco 1400-45 Taco 1400-20
Not Recommended
Not Recommended
4.5 9.5
11.5 20.5
Temp
Rise
(˚F)
Boiler
Head
Loss
(Feet w.c.)
Domestic Water
Tank Piping
Head Loss **
(Feet w.c.)
* This is the minimum flow rate recommended for Jaguar boiler.
Domestic w
**
ater tank piping head is based on 1” inside diameter piping and full port valves.
the appropriate circulator.
If 2 circulators are specified, they must be piped in series in order to provide the head capacity shown. Power to
circulator(s) must be supplied through an appropr
iate relay to protect the boiler control’s fuse.
Jaguar Model J-390
I
SOLATION
VALVE
B
OILER LOOP
P
URGE/
VALVE
D
RAIN
T
HE BOILER)
CIRCULATOR (SUPPLIED WITH
I
SOLATION
V
ALVE
FLOW CHECK VALVE
F
igure20.Zoningw ithcirculators.
2
-
D
E
T
A
I
L
_
M
A
I
N
8
.592
ISOLATION
VALVE
DONOTEXCEED
12"APAR
T
FROM REST OF SYSTEM
FLOWCHECK
VALVE
SPACEHEAT
ZONE#
1
ADDITIONA
L
ZONES
AIRVENT
ZON
E
CIRCULATO
R
BOILERWATER
INLET(RETURN)
VALVE
FLOWCHECK
RELIE
F
VALVE
BOILERWATER
OUTLET(SUPPLY
)
DHW
CIRCULATO
R
ISOLATION
VALVE
(DIAPHRAMTYPE
)
EXPANSIONTANK
T+P
VALVE
RELIE
F
BACKFLO
W
PREVENTOR
(IFREQUIRED
)
PRESSUR
E
REDUCIN
G
VALVE
SHUTOFF
VALVE
HOTWATE
R
OUTLE
T
AIRSEPARATO
R
T
OREST
OF SYSTEM
MAKEU
P
WATER
SUPPL
Y
ISOLATION
VALVE
DRAINVALV
E
DRAINVALV
E
COL
D
WATER
INLET
TAN
K
HOTWATE
R
DOMESTI
C
SHUTOFF
VALVE
.
27
Figure 19. Zoning with circulators.
28
ISOLATION VALVE
B
OILER LOOP
P
URGE/
VALVE
DRAIN
THE BOILER)
CIRCULATOR (
SUPPLIED WITH
ISOLAT ION VALVE
FLOW CHECK VALVE
Figure20.Zoningwithcirculators.
2
-
D
E
T
A
I
L
M
A
I
N
8.592
ISOLATION
VALVE
DONOTEXCEED
12"APAR
T
SPACE HEAT
ZONE #1
A
DDITIONAL
ZONES
AIRVENT
BOILERWATER
INLET(RETURN)
VALVE
FLOWCHECK
RELIE
F
VALVE
BOILERWATER
OUTLET(SUPPLY
)
DHW
CIRCULATO
R
ZON
E
VALVE
(DIAPHRAMTYPE
)
EXPANSIONTANK
T+P
VALVE
RELIE
F
BACKFLO
W
PREVENTOR
(IFREQUIRED
)
PRESSUR
E
REDUCIN
G
VALVE
SHUTOFF
VALVE
HOT WATER
OUTLET
AIRSEPARATO
R
MAKE UP
W
ATER
SUPPLY
ISOLATION
VALVE
DRAINVALV
E
DRAINVALV
E
COLD
WATER
INLET
TANK
HOT WATER
DOMESTIC
SHUTOFF
VALVE
PRESSURE BYPASS VALVE (IF USED )
P
DIFFERENTIAL
SYSTEM C
IRCULATOR
Jaguar Model J-390
Figure 20. Zoning with zone v
alves.
Jaguar Model J-390
C
HILLER
W
ATER
VALVE
VALVE
UNIT
STRAINER
INLET (RETURN)
BOILER WATER
CIRCULATOR
BOILER LOOP
VALVE
I
SOLATION
1
2" APART
D
ONOTEXCEED
DRAIN VALVE
P
URGE/
VALVE
SHUTOFF
VALVE
RELIEF
T+P
VALVE
ISOLATION
DRAIN VALVE
DOMESTIC
HOT WATER
TANK
OUTLET
HOT WATER
DRAIN VALVE
INLET
WATER
COLD
CIRCULATOR
DHW
OUTLET (SUPPLY)
BOILER WATER
THE BOILER)
FLOW CHECK VALVE
(SUPPLIE D WITH
VALVE
ISOLATION
2
-
D
E
T
A
I
L
M
A
I
N
Figure20.Zoningwithcirculators.
8.592
VALVE
RELIEF
VALVE
ISOLATION
VALVE
FLOW CHECK
EXPANSION TANK (DIAPHRAM TYPE)
P
VALVE
Z
ONES
A
DDITIONAL
ZONE
SPACE HEAT
ZONE #1
AIR SEPARATOR
VALVE
REDUCING
PRESSURE
(IF REQUIRE D)
PREVENTOR
BACK FLOW
D
IFFERENTIAL
VALVE (IF US ED)
PRESSURE BYPASS
SUPPLY
WATER
MAKE UP
VALVE
SHUTOFF
ISOLATION
FLOW CHECK
SYSTEM CIRCULATOR
AIR VENT
B
ALANCING
VALVE
29
Figure 21. Piping a heating-cooling system to the boiler and a chiller.
30
OPERATING INSTRUCTIONS
I. FILLING AND VENTING WATER SYSTEMS
Jaguar Model J-390
. While “t” is blinking, DHW tank temperature may be
3
et to desired temperature (if tank is equipped with
s sensor). The setting range is between 104˚ to 185˚F.
. Fill the system with water. Vent or purge of air.
A
B. Fire the boiler as soon as possible (see following warning
and instructions) and bring water temperature in the system.
C. Vent air and add water as needed to achieve operating
pressure on boiler gauge. Pressure must be between
pproximately 12 psi (cold water) and 25 psi at water
a
emperature setting of high limit control, for boilers
t equipped with 30 psi relief valves. Boilers rated for a higher pressure and equipped with a matching relief valve may operate at a higher pressure, but no higher than 5 psi
w the relief valve opening pressure.
belo
D. Check for and repair any leaks before placing system in
service.
BEFORE FIRING BOILER, make these checks:
Before firing boiler, review the “Boiler Control and Display Features” section of this manual. Understanding the features and programming the applicable parameters is essential for setting up the boiler to operate properly on the heating system it is installed on.
1. System is full of water. Air is vented or purged.
2. Relief valve is installed in accordance with ASME Boiler and Pressure Vessel Code, Section IV. Valve opening is not closed or reduced in size.
3. Venting is installed according to instructions under “FLUE GAS VENTING REQUIREMENTS”.
4. View actual boiler supply & return water tempera­ture, domestic hot water tank temperature (if tank equipped with sensor), flue temperature and outside temperature (if outside sensor is used) on “Temperature Display” by selecting 1, 2, 3, 4, or 5 on
Mode Display”.
• These numbers are steady on display and are
not settable.
• All sensor inputs to the control must be
connected to a 12k ohm sensor.
C.
Viewing and changing system setting:
A trained, experienced service technician or installer should perform following adjustments. See table 5 for details.
1. Space heating and DHW post pump time may be changed.
2. Space heating and DHW modes may be chosen.
3. Weather compensation slope and set point temperature may be changed (if outside sensor is used). (See Figure 23 for graph).
4. Read actual blower RPM
5. Adjust blower RPM for high and low input adjustment.
6. Read flame current in micro amp.
7. Run boiler on high, low or ignition input steady for 20 minutes for test purposes.
Display and push buttons:
D.
4. All wiring is completed, following applicable wiring diagrams.
5. Using soap solution, check for gas leaks in all gas piping from meter to boiler gas supply pipe flame.
II. BOILER CONTROL AND DISPLAY FEATURES
(See Figure 23)
A. Boiler Operation Status:
“Mode Display” shows status of boiler operation (see table 3).
.
B
View and Changing Temperatures:
Setting boiler supply w temperature (see table 4). Press “Select” button for viewing following different modes on “Mode Display”
1. While “c” is blinking, boiler supply water temperature for space heating may be set to desired temperature The setting r
“d”
While
2. for DHW may be set to desired temperature. The setting range is between 104˚ to 185˚F.
ater temperature and water tank
ange is betw
linking, boiler supply w
is b
DO NOT use open
.
een 90˚ to 185˚F
ater temper
.
ature
1. Reset - Used to clear a Lock out error (indicated with an
“A” in the “Mode Display”).
Select - Used to scroll through the modes in the “View
2. and Changing Temperatures” and “Viewing and Changing System Setting” men
Enter - Used to store values that are changed in the “View
3. and Changing Temperatures” and “Viewing and Changing System Setting” menus.
4.
Up- Used to increase v Temperatures” and “Viewing and Changing System Setting” menus.
wn -
5.
Do
Changing Temperatures” and “Viewing and Changing System Setting”
Used to decrease v
us.
alues in the “View and Changing
alues in the “View and
.
us
men
Jaguar Model J-390
"TEMPERATURE" DISPLAY (3 DIGITS)
"UP" PUSH BUTTON
"DOWN" PUSH BUTTON
"ENTER" PUSH BUTTON
"SELECT" PUSH BUTTON
"BURNER STATUS"
STEADY DOT = BURNER ON
BLINKING DOT = BURNER OFF
"MODE" DISPLAY
"RESET" PUSH BUTTON
Table 3
Table 3
Table 3
Table 3
Table 3
Table 3
Table 1
Table 3
31
Figure 22. Display Board
MODE
DISPLAY
Table 3
JAGUAR BOILER DISPLAY BOARD
“Boiler Operation Status”
DESCRIPTION & TEMPERATURE DISPLAY
Boiler is on stand-by mode.
Temperature display shows supply water Temp.
Space heating mode.
Temperature display shows supply water Temp.
Domestic hot water mode.
Temperature display shows supply water Temp.
Temperature display shows supply water Temp.
emper
T
Reset button must be pressed to resume normal operation.
Temperature display indicates the error code.
Temperature display indicates the error code.
Frost protection mode. **
Lockout (Alarm) condition.
ature Display indicates the lockout code
Error Condition. *
Warning Condition. ***
TE:
NO
Blinking dot on Steady dot indicates b
Error m
*:
The boiler loop circulator is energiz
**:
Error m
***:
the “Reset” button is not required.
“Mode Displa
ust be corrected to resume boiler oper
ust be corrected to resume DHW oper
ner is on.
ur
indicates activ
y”
e heating control, b
Pressing the
ation.
ed, if the boiler w
ater temper
Space heating not aff
ation.
urner off.
“Reset”
ature drops belo
utton is not required.
b
.
w 50˚F
Pressing
ected.
32
T
able 1
T
able 3
Table 1
Table 3
T
able 1
T
able 3
T
able 3
Table 3
Table 3
T
able 3
Table 3
Jaguar Model J-390
Table 4
VIEWING AND CHANGING TEMPERATURES
Press “SELECT” button for viewing different modes on “MODE DISPLAY”
ODE
M
DISPLAY
Space heating supply water temperature could be changed by
blinking
Domestic hot water supply temperature could be changed by
blinking
blinking
DESCRIPTION & TEMPERATURE DISPLAY
pressing “Up/Down” button. Settable from 90˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 1)
pressing”Up/Down” button. Settable from 104˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 2)
Domestic hot water tank temperature could be changed by
pressing “Up/Down” button. Settable from 104˚F to 160˚F
(steps of 1 F). The default value is 140˚F.
Press “Enter” button to store.
(see note 3)
NOTE:
Temperature display shows actual supply water temperature.
Temperature display shows actual return water temperature.
Temperature display shows actual DHW tank temperature.
(if the water tank is equipped with sensor).
Temperature display shows actual flue gas temperature.
Temperature display shows actual outside temperature.
(if outdoor sensor is used)
or space heating mode “0”
1- F 2- For DHW mode “2” (storage tank with Aquastat) 3- For DHW mode “1” (storage tank with sensor)
(boilers not utilizing outdoor sensor))
Jaguar Model J-390
Table 3
Table 3
Table 3
Table 3
Table 3
VIEWING AND CHANGING SYSTEM SETTING - Table 5
“To change system setting or perform system test”
he menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change
T
WARNING: Only a trained, experienced service technician or installer should use this table.
33
system setting: Press “UP or DOWN” button, then press “ENTER”
MODE DISPLAY
*
*
*
*
*
*
*
DESCRIPTION
Changing space heating post pump time. Settable from 10 to 900 seconds.
(steps of 10 seconds). The default value is 30 seconds.
Changing DHW post pump time. Settable from 1 to 255 seconds.
(steps of 1 seconds). The default value is 15 seconds.
hanging space heating control mode
C
0: Thermostat only (default) - boiler without outdoor sensor
: Outside sensor and Thermostat
1
Outside sensor only
2: 3: Permanent heat demand (boiler circulator always on)
C
hanging domestic hot water (DHW) mode
0: No DHW 1: Storage tank with sensor 2: Storage tank with thermostat (default value)
Plate heat e
3:
Changing DHW or space heating priority mode
0: DHW priority (no time limit) 1: Space heating priority (no time limit) 2: DHW priority for limited time (default) 3: Space heating priority for limited time
Changing priority limited time. Settable from 20 to 80 minutes.
Boiler model selection, value is 5 for model J-390
xchanger
The default value is 30 minutes.
**
**
*
*
(space heating mode 1 or 2). Settab
*
*
Changing weather compensation set point (space heating mode 2 only).
*
*
*
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
*
Boiler model confirmation, value is 5 for model J-390
Weather compensation supply water reference temperature
The def
Changing compensation slope (space heating mode 1 or 2).
Displa
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
Settable from 32˚F to 122˚F (steps of 1˚F).
y sho
System test – Display shows flame current
The default value is 68˚F.
ws blower RPM (mutiply reading by 10 for actual RPM)
Display shows flame current in micro amps
0: System test off L: Steady low input (20 minutes) I: Steady ignition input (20 minutes) H: Steady high input (20 minutes)
le from 16˚F to 122˚F (steps of 1 F).
alue is 86˚F.
ault v
Not Utilized
NOTE: *: Alternating **: Steady
34
70
70 60 -20-10 -3001020304050
Outdoor Temp. (°F)
Water
Supply
Target Temp.
(°F)
185 °F
140
150
130
190
180
170
160
120
110
100
80
90
2
00
S
l
o
p
e
=
4
.
0
S
l
o
p
e
=
3
.
0
S
l
o
p
e
=
0
.
1
(
m
i
n
.
)
S
l
o
p
e
=
2
.
0
S
l
o
p
e
=
0
.
5
S
l
o
p
e
=
1
.
2
S
l
o
p
e
=
5
.
0
(
m
a
x
.
)
-40
S
l
o
p
e
=
1
.
5
S
l
o
p
e
=
1
.
0
(
d
e
f
a
u
l
t
)
S
l
o
p
e
=
1
.
8
Ma
ximum water target temp.
Water reference temp.(default of86°F)
Minimum
watertarget
temp.
68°F
Jaguar Model J-390
Figure 23. Space Heating mode with outside sensor water set point graph.
Jaguar Model J-390
G
AS SUPPLY SHUTOFF VALVE
IN "OPEN" POSITION
G
AS SUPPLY SHUTOFF VALVE
IN "CLOSED" POSITION
T
URN 90˚
TO CLOSE
TURN 90˚ T
O OPEN
III. INITIAL START
Safe lighting and other performance criteria were met when testing various gas manifold and control assemblies used on the Jaguar J-390 boiler under the ANSI Z21.13 - latest edition.
Instructions
Follow the lighting instructions in this manual.These instructions are also attached to the boiler.
. Use only your hand to turn the gas supply shut-off valve.
C
Never use tools. If the supply shut-off valve will not turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
STOP! Read the safety information above.
1.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
35
Figure 24. Gas supply shutoff valve operation.
SAFETY INFORMATION
For Your Safety Read Before Operating
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
This appliance does not have a pilot. It is equipped with
A.
an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
BEFORE OPERATING smell all around the appliance area
.
B
for gas. Be sure to smell next to the floor because some gas
vier than air and will settle on the floor
is hea
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
.
• DO NOT touch any electric switch: DO NOT use any phone in your building.
• Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
tment.
depar
5. Open the gas supply shut-off valve, by turning the handle to be parallel to the gas piping (See Figure 24).
6. Wait five (5) minutes (longer for propane) to clear out any gas, then smell for gas, including near the floor. If you then smell gas, STOP! Follow “B” in the safety information above on this page. If you don’t smell gas, go to next step.
7. Turn on all electric power to the appliance.
8. Set thermostat to desired setting. If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting.
n off all electric po
ur
T
2.
ormed.
be perf
er to the appliance if ser
w
vice is to
3. Close the gas supply shut off valve, by turning the handle to be per
pendicular to the gas piping. (See Figure 24).
36
Jaguar Model J-390
JAGUAR MODEL J-390 SEQUENCE OF OPERATION
THERMOSTAT CALLS FOR HEAT
CIRCULATOR(S) ON
COMBUSTION BLOWER ON
(AT MEDIUM SPEED)
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 33”
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 03”
NO
NO
BLOWER SPEED CONFIRMED?
YES
5 SECOND PRE-PURGE
TRIAL FOR IGNITION - 6 SECONDS
SPARK IGNITOR ENERGIZED
GAS VALVE OPENS
WATER HIGH LIMIT CLOSED?
YES
GAS VALVE REMAINS OPEN
FOR 4 SECONDS
PERIOD
NO
3 TRIALS FOR
IGNITION
WITH NO FLAME SENSED?
2 TIMES RETRIALS
FOR IGNITION
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 01”
YES
SPARK IGNITOR DE-ENERGIZED
NO
FLAME SIGNAL SENSED?
YES
GAS VALVE REMAINS OPEN. CONTROL
CONTINUOUSLY MONITORS
, HIGH LIMIT, WATER
T
THERMOST
SENSORS, BLOWER SPEED, FLAME
SIGNAL, AND LWCO (IF USED).
THERMOST
10 SECOND
15 SECOND
A
CALL FOR HEAT ENDS
T
A
CLOSES
VE
AL
V
GAS
POST PURGE.
WER
BLO
CIRCULATOR POST PURGE.
GAS VALVE CLOSED.
BLOWER POST PURGE
10 SECONDS.
Jaguar Model J-390
INLET PRESSURE TAP
OUTLET PRESSURE TAP
GAS VALVE
VENTURI
COMBUSTION BLOWER
GAS PIPE
OFFSET ADJUSTMENT SCREW (BELOW CAP)
37
IV. CHECK COMBUSTION AND FUEL INPUT RATE
A. Start and run the burner at the high firing rate, by using the
“System Test” mode in the “View and changing system setting” menu. Refer to Table 5 on page 33.
1. Measure the CO, and CO2of the flue gas. A flue sample port is provided in the vent pipe (See Figure 2 on page 3). The CO should not exceed 100 ppm, when the combustion is correct. The CO2 is not field adjustable, and should be in the range of 8.5% to
9.5% (9.0% is the nominal reading). Record the actu-
l high firing rate CO2, as it will be used as a refer-
a
nce in setting the low firing rate CO2 (in Step B).
e
2. Once the correct combustion is confirmed at the high firing rate, check the fuel input rate on the gas meter.
BTUH INPUT = cu. ft. metered in 3 minutes x
* The higher heating value of the gas can vary for
different localities. Consult the gas supplier for this value in BTU/cu.ft.
3. If the fuel input is not at the rate specified on page 2 at the high firing rate, then the blower speed should be adjusted to attain the specified input rate. This can be done by using the “Change blower RPM for high input” mode in the “View and changing System Setting” menu. Refer to Table 5 on page 33. Increas­ing the blower rpm will increase the fuel input rate, and decreasing the blower rpm will decrease the fuel input rate.
B. In the “System Test” mode in the “View and Changing
System Setting” menu, use the “down” push button to switch to the low firing rate. Refer to Table 5 on page 33.
1. Measure the CO and CO2of the flue gas. The CO should not exceed 30 ppm, when the combustion is correct. The CO high firing rate CO2(recorded in Step A). If this reading is obtained, then proceed to Step 4.
heating value of the gas* x 20
should be 0.2% lower than the
2
2. If the CO2is not 0.2% at the low firing rate, then the gas valve needs to be accessed for proper adjust­ment. Remove the boiler jacket top cover, 3 front cover panels, and enclosure front cover (see figure 2 on page 3 for locations.
3. Remove the cap that covers the gas valve offset screw (see figure 25 for location). Adjust the low fire CO2to be 0.2% lower than the recorded high fire CO2. Turn the offset clockwise to increase the CO
alue. Turn the offset counter-clockwise to decrease
v
he CO
t
ent is complete.
m
4. Once the correct combustion is confirmed at the low firing rate, check the fuel input rate of the gas meter. BTUH Input = cu. ft. metered in 3 minutes x heating valve of the gas * x 20.
5. If the fuel input is not at the rate specified on page 2 at the low firing rate, then the blower speed should be adjusted to attain the specified input rate. This can be done by using the “Change blower RPM
or low input” mode in the “View and changing
f System Setting” menu. Refer to Table 5 on page 33. Increasing the blower rpm will increase the fuel input rate, and decreasing the blower rpm will decrease the fuel input rate.
6. Replace the boiler enclosure front cover, 3 jacket front cover panels, and top cover (see figure 2 on page 3 for locations).
C Exit the “System Test” mode, once the combustion and fuel
input rate has been checked and adjusted, if necessary. Refer to Table 5 on page 33.
alue. Replace the offset cap when adjust-
v
2
2
Figure 25. Gas valve adjustment.
38
Jaguar Model J-390
. SAFETY CHECK
V
A. Check for gas leaks:
Using soap solution, check for gas leaks from meter to gas valve including all pipes and fittings and gas valve connections. Use liquid soap solution for all gas testing. DO NOT use open flame.
B.
Thermostat Test:
et thermostat setting to low enough to end call for heat.
S
as valve should close and burner should stop firing.
G
lower and circulator pump should go into a post purge,
B then shut off.
A. LOCKOUT ERRORS: Indicated by an “A” in the mode display.The reset button must be pressed to clear the error
and retry operation. The temperature display shows the error code.
.
C
ontrol Safety Shutdown test:
C
ith the burner firing, disconnect the spark cable from the
W spark ignitor. Gas valve should close and burner should stop firing. The boiler will try for ignition three times after this, then should lock out with an “A 01” error shown on the display. Reconnect the spark cable to the spark ignitor, and press the “Reset” button to return to normal operation.
I. DIAGNOSTIC ERROR CODES
V
ARNING:
W
should perform troubleshooting. Turn off all electric power to the boiler before service.
nly a trained, experienced service technician
O
ERROR CODE INDICATION REMEDY
Check for steady sparking at electrodes. If spark not steady - check spark gap to be .125”, clean or replace spark ignitor, check power supply voltage and grounding. If spark is steady - check for proper gas supply pressure.
01
Ignition Failure - 3 unsuccessful
ignition attempts in a row.
Check combustion, if able to ignite, or replace gas valve.
02
03
04, 05, 09, 10, 12, 13, 14, 15,
16, 18, 32
19, 20
33
Flame Failure - 3 losses of flame
signal during one demand.
Water High Limit Open
Control Failure
Flame Detected at
ailure - RPM error
an F
F
Wrong
Time
Check for proper combustion, at both max. and min. input firing rates. If combustion is within the range specified on page 37, clean or replace spark ignitor, check power supply voltage and grounding.
Check to see if the water outlet temperature reaches 203˚F. If it does, replace the water outlet 12k ohm sensor. If it does not, replace the water high limit switch.
Replace control board. Make sure the proper boiler model selection and confirmation code is entered. See Table 5 on page 33.
If a flame is still observed after a call for heat is stopped,
If the burner seems to be shutting
.
e
replace the gas v
alv
down properly, replace the spark ignitor.
Check wire harness connections going to the blower. Replace blower.
Jaguar Model J-390
B. BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the
condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset”
utton is not required.
b
ERROR CODE INDICATION REMEDY
Check wire harness connections going to the
01
02
03
Water Outlet Sensor Open
Water Inlet Sensor Open
Flue Gas Sensor Open
sensor. Replace the sensor.
Check wire harness connections going to the sensor. Replace the sensor.
Check wire harness connections going to the sensor. Replace the sensor.
39
11 12 13
19, 42, 45,
46, 47, 48
20
21
22
24
Water Outlet Sensor Shorted Replace the sensor.
Water Inlet Sensor Shorted Replace the sensor.
Flue Gas Sensor Shorted Replace the sensor.
Replace control board. Make sure the proper
Control Failure
Flame Detected at Wrong Time
Polarity Error Reverse the hot and neutral power supply wires.
Frequency Error
Earth Connection Faulty Check grounding of control and boiler chassis.
boiler model selection and confirmation code is entered. See Table 5 on page 33.
If a flame is still observed after a call for heat is stopped, replace the gas valve, If the burner seems to be shutting down properly, replace the spark ignitor.
Check power supply frequency to be 60 hz, certain power supplies may not provide the proper frequency
.
contin
ued on pa
g
e 39
40
continued from page 38
ERROR CODE INDICATION REMEDY
Check flue gas temperature, at the maximum firing rate and high water temperature. If the flue gas
30
31
32
Excess Flue Temperature
Low Water Cutoff Error
Excess Water Inlet Temperature
temperature reaches 212˚F, check the fuel input rate and combustion. Check the condition of the heat exchanger. If the flue gas temperature does not reach 212˚F, replace the flue sensor.
If a low water cutoff is installed, check the system water pressure and content. Check the condition of the LWCO. If no LWCO is installed, check the jumper is in place at the wiring terminal board. See Figure 15a on page 18.
Check that the wire harnesses to the water inlet and outlet sensors are not reversed.The water inlet sensor harness should have a blue colored connector, the water outlet sensor harness should have a red colored connector. Check that the pumping flow direction is correct.
Jaguar Model J-390
51
52
ARNING ERR
C. W
ed, and the warning is displayed intermittently. Operation of the DHW mode is automatically restored, once the condition is fixed. The temperature display shows the error code. Pressing the “reset” button is not required.
04
ORS:
Indicated b
Domestic Hot Water Tank Sensor Open
14
Reset Button Error
Boiler Model Selection Error
“H” in the mode display
y an
Domestic Hot Water Tank
Sensor Shorted
Try turning power supply off and on again. If error returns, replace the display board.
Check that the proper boiler model selection and confirmation code is entered in the display. See Table 5 on page 33.
Operation of the space heating mode is not aff
.
If sensor is utilized, check wire harness connections going to the sensor sor is utilized, check the proper DHW mode is pro-
ammed.
r
g
If sensor is utilized, replace the sensor. If no sensor is utiliz grammed. See Table 5 on page 33.
See Table 5 on page 33.
ed, chec
, or replace the sensor
k the proper DHW mode is pro
. If no sen-
-
ect-
Jaguar Model J-390
41
CARE AND MAINTENANCE
This section must be brought to the attention of the owner by the installer so that the owner can make the necessary arrange­ments with a qualified service agency for the periodic care and maintenance of the boiler.The installer must also inform the owner that the lack of proper care and maintenance of this boiler and any fuel burning equipment may result in a hazardous condi­tion. Installer should discuss contents of the User’s Information Manual (Publication J-UIM) with the owner.
A trained and qualified service technician should perform the inspection listed in these instructions before each heating season and at regular intervals.
I. GENERAL MAINTENANCE
A. Safety check, see page 38.
B. Vent and air intake system inspection
1. Check for obstruction, condensation, corrosion and physical damage.
2. Check outside termination. Screen and louvers should be free of any debris and must be cleaned as required.
3. Perform “Venting and Air intake System Regular Inspection”, see page 16.
C. Piping
Check the following:
1. Water piping and accessories for leaks. Slightest leaks should be corrected.
2. System to be full of water and pressure to remain stable at correct setting on gauge.
B. Check venting system. See “Venting and Air Intake System
Regular Inspection” on page 16.
C. Check condensation drain trap to be full of water. Check for
deterioration of the tubing. Check that the trap is not plugged.
. The combustion blower does not require or have provisions
D
or lubrication.
f
E. If required, lubricate the circulator as per the manufacturer’s
instruction.
III. CLEANING
A. Heat Exchanger: In the unlikely event of flue passage or
water passage blockage, service to remedy situation must be performed only by an authorized Slant/FIn representative.
Burner: In the unlikely event of blockage or deterioration,
B.
service to remedy situation must be performed only by an authorized Slant/Fin representative.
IF REPLACEMENT PARTS ARE NEEDED
When parts are needed, refer to boiler model and serial number shown on the boiler name/rating plate. Refer to publication number J-10PL replacement parts for part numbers. Whenever possible refer to the original order by number and date.
Control identification and replacement should not be attempted by unskilled personnel. Only, simple easily - identified controls and parts may be obtained locally. All other control and parts should be identified by and ordered form Slant./Fin. Relief/Safety valves must be ASME rated for the pressure and gross output of the boiler.
3. Air-control system. Noise and air binding in radiation should not occur.
4. Low water cutoff for operation (see instruction furnished with unit).
D. Boiler Room Air Supply
Check air vents for continuous positive supply of air as required. installation is non-direct vent method. Air vents must open and free of obstruction.
WARNING: The flow of combustion and ventilating air to the
II. INSPECTION DURING HEATING SEASON
A. Check water pressure regularly and add water slowly to
system when needed. If m necessary indicate either a system leak, or a f a faulty automatic fill valve.
Air needs are greatest in cold weather if boiler
boiler should not be obstructed.
enting ma
Regular loss of w
.
uch water is added, v
ater from boiler system may
aulty air control system, or
For replacement parts, heating contractors should contact their Slant/Fin boiler distributor.
y be
42
Jaguar Model J-390
GENERAL TROUBLESHOOTING GUIDE FOR SERVICE PERSONNEL
WARNING: Only a trained, experienced service technician should perform troubleshooting.
Turn off all electrical power to the boiler before servicing.
A. BURNER FAILS TO OPERATE - NO HEAT
CA
USE REMEDY
1. No power, display off, power switch off. Main electric 1. Close switch. Check or replace fuse. switch open. Blown or defective line fuse.
2. Gas supply valve shut off. 2. Open gas supply valve. Check gas pressure.
3. Harnesses plug-in connectors are not securely connected. 3. Check connectors on boiler control.
4. Operational problem, detected by control. 4. Error code on display can be correlated to
specific problems and remedy. Refer to page 38-40 for error codes.
B. NOT ENOUGH HEAT
1. Thermostat setting is too low. 1. Set thermostat at higher setting.
2. Boiler water maintained at too low temperature. 2. Increase space heating set point temperature.
Refer to Table 4 on page 32.
3. Circulator not running. 3. With thermostat calling for heat, check for power
to circulator. If power is O.K. but circulator is not running, replace circulator.
4. Boiler water level too low. 4. Carefully snap open relief valve handle to
determine if boiler is full of water, if not full of
, check for system leaks and check water
ater
w pressure regulator. Repair any system leaks. Adjust or replace water pressure reducing valve.
5. Fuel input rate too low. 5. Check the maximum fuel input firing rate.
Refer to page 37 for the procedure.
C. FUMES AND GAS ODORS
1. Leaks in gas piping or accessories. 1. Locate leaks and repair.
2. Gas leaks in service line or meter connections. 2. Close service supply valve - shut down boiler
and notify utility.
3. Condensation traps are not full of water. 3. Check and fill with water
4. Venting system is physically damaged. 4. Check carefully and repair. Also, see “Venting
System Regular Inspection”.
5. Over - firing or poor combustion. 5. Check the maximum fuel input firing rate and
combustion. Refer to page 37 for procedure.
Jaguar Model J-390
43
NOTES
©Slant/Fin Corp. 2008.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
(516) 484-5921
AX:
F
Canada:
Slant/Fin
TD/L
L
TEE
, Mississauga, Ontar
.slantfin.com
www
io
Loading...