Wiring at module .............................................................14-16
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the
absence of local codes, to the National Fuel Gas Code, ANSI,
Z223.1 latest edition.
In addition where required by the authority having jurisdiction,
the installation must conform to American Society of
Mechanical Engineers Safety Codes for controls and safety
devices for automatically fired boilers, No. CSD-1. The instal
ation must also conform to the additional requirements of
l
Slant/Fin Instruction book publication No. GG-100-40 latest
edition.
All electrical wiring is to be done in accordance with the
National Electrical Code ANSI/NFPA No. 7 latest edition and
all local electrical codes. The unit must be electrically grounded if an external power source is used.
In Canada, the installation must be in accordance wi
dards CGA B149.1 and B149.2, installation codes for gas
burning appliances and equipment and/or local codes. All
electrical connections are to be made in accordance with
Standard C.S.A. C22.1 Canadian Electrical Code Part 1
and/or local codes.
Many state and local codes require intermittent ignition
devices for gas boilers. Please specify if necessary.
th s
tan-
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can cause scaling and leave deposits in the boiler and
the surrounding water pipes. This will lead to inefficient boiler
operation and breakdown. Fresh water will enter the system
as a result of leaks such as may occur in underground piping.
-
Process applications that use fresh water require the use of
heat exch
duction of fresh water into a boiler can cause scaling, with
deposits forming in the boiler and surrounding piping. This will
damage the boiler. Introduction of fresh water from leaks will
cause similar damage.
In some areas it may be necessary to use a feed water treatment to control the corrosive makeup of the fill water. Check
with the local
a conditioning treatment before being supplied to the boiler.
angers. A
ny process application that results in intro-
uthority to determine if the feed water will need
a
INTRODUCTION
There are many varieties of steam heating systems. Because
of the wide range of field conditions, the design of these systems is beyond the scope of this manual. However, when
designing a steam Caravan boiler plant, certain guidelines
should be followed that are common to all modular steam
heating application.
This entire manual should be read prior to installing the
Slant/Fin Caravan steam system.
Safety – each module contains a dual combination gas valve,
ASME 15 lb Relief valve and pressure gauge.
Specify gas by name, “natural” or “propane”.
Net ratings are based on piping and pick-up
allowance of 1.33. Slant/Fin should be consulted before selecting a boiler for installation
having unusual piping and/or pick-up requirements.
Ratings must be reduced by 4% at 2000 ft.
elevation and an additional 4% for every
additional 1000 ft. elevation over 2000 ft.
Modules in excess of 5, should be piped
in banks of 5, parallel with each other.
Figure 1: For McDonnel & Miller PS 801-24 L.W.C.O Min. clearance 9"
2
BOILER PLANT SIZING
Older buildings may have a heat loss significantly less than that
of the original building. To size a replacement steam boiler plant,
consider the following: Replacement steam boiler plants must be
sized to match the connected radiation load. Under-sizing will
prevent steam from reaching distant radiation quickly.
BOILER ROOM DESIGN
Caravan modular boiler systems allow better utilization o
space and permit future expansion with minimum cost. The modules are hand truckable, fit through doorways and often may be
installed around an existing inoperative boiler. They can be
grouped in single or multiple banks. Systems consisting of five or
more modules should be piped in two or more banks.
f floor
BOILER ROOM AIR SUPPLY
To ensure safe, efficient operation, the modular boiler syst
st be supplied with sufficient air to support complete combus-
mu
tion, replacing air entering draft dampers or draft hoods and ventilating the boiler room or areas.
For additional information, not listed below, see ANSI. Z223.1,
section 5.3.3.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR
INTO THE BOILER ROOM:
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the
floor (below burner air inlet) and one louvered opening
near the ceiling (above the highest draft regulator), each
opening with a minimum FREE air passage area of
1 square inch per 4000 BTUH
of total system input.
em
Figure 2: Correct location of combustion-air supply ducts.
2. Air drawn horizontally through HORIZONTAL DUCTS;
one opening near the floor (below burner inlet) and one
opening near the ceiling (above the highest draft regulator),
each opening with a minimum FREE air passage area of
1 square inch per 2000 BTUH.
3. Air drawn VERTICALLY from outdoors; one opening at
the floor and one opening at the ceiling, each opening with
a minimum FREE air passage area of 1 square inch per 4000 BTUH of total system input.
4. Air drawn from inside the building; one opening near
the floor (below burner inlet) and one opening near the
ceiling (above the highest draft regulator), each opening
with a minimum FREE air passage area of 1 square inch per 1000 BTUH of total system input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL
BURNING EQUIPMENT, THE AREA OF FREE OPENINGS
MUST BE APPROPRIATELY INCREASSED TO ACCOMMODATE THE ADDITIONAL LOAD.
UNLESS PROPERLY CONTROLLED, AVOID THE USE OF
FORCED VENTILATION, SINCE IT CAN CREATE AN
UNDESIRABLE PRESSURE DIFFERENTIAL BETWEEN
BOILER ROOM AND AIR SOURCE.
3
VENTING A GAS-FIRED SYSTEM
A boiler venting system provides an escape path for the products
of combustion. There are three major components for venting a
gas-fired Caravan: a draft hood for each module, a breeching
manifold and a chimney.
Draft Hood
The draft hood is part of each boiler module, although shipped in
a separate carton. It compensates for excessive draft. The dimensional relationships betwe
en the draft hood, the boiler and surface on which the boiler is mounted, are critical. These factors
are all interdependent in allowing the draft hood to function without moving parts. Attempts to alter these dimensions will result in
unsafe operating conditions.
Breeching
Breeching is a term used to describe a manifold(s) that connects
individual boiler modules to a chimney. Breeching is usually
tructed of sheet metal having a smooth interior surface with all
s
con-
joints made tight against leakage. Pitch breeching up toward
chimney. Horizontal breeching size should be maintained for the
total length. Connections from the modules into the breeching are
best made at 45˚ angles in the direction of the chimney.
See figure 3.
The bottom portion of the breeching should be installed at least 3
feet above the top of modules’ draft hoods. If this height cannot be
obtained, install the breeching as high as possible. See Page 5,Table 3 for heights less than 3 feet. The portion of chimney height
rising directly above each draft hood is most effective in preventing
flue gas spillage. When the boiler room is in an unheated space,
insulate vent pipe and breeching to maintain flue gas temperature
and good chimney operation. Do not lower draft hoods’ skirtheight. For some combinations of low chimneys, low ceilings and
long breeching, a draft inducer may be needed. Inducers, when
required, are locally specified and warrantied. The breeching should
extend into but not beyond the chimney liner.
Chimney
Caravan gas-fired modular boilers
operate efficiently with masonry
or prefabricated chimneys as well as with “Type B” or double-walled
metal vent pipe. The latter type of chimney construction is generally
the least expensive. Chimney height is usually governed by the
building height and the size of the boilers (See Table 1). However,
the chimney should be high enough to minimize the effects of turbulent winds and pressure common ne
ar rooftop obstructions. A vent
cap should be used where permitted for additional protection
against adverse wind conditions and precipitation. The National
Board of Fire Underwriters recommends that the chimney should
extend at least 3 feet above the roof and be 2 feet higher than any
obstruction within 10 feet.
Sizing horizontal breeching connectors and chimneys for
gas-fired systems
Horizontal breechi
ng connectors shall be constant sized. The chimney and the horizontal breeching connector are sized using Table 2.
When there are multiple banks of boilers, the horizontal breeching
connector for each bank is sized using Table 2. To size the common
horizontal breeching connector, add up the total input and refer to
Table 2A.
The minimum chimney opening will be equal to the size of the
largest horizon
tal breeching section connected to it.
Based on single row of modules with no elbows.
• Height measured from the top of draft hood to top of chimney
Note: For conditions other than those shown, consult factory, or National
fuel gas code NFPA 54.
Table 2A: Chimney and breeching sizing for multiple banks **
Connector rise is the length of the pipe connecting the top of the
draft hood to the system breeching above. The diameter of this
pipe varies depending upon BTU input, chimney height and the
length of the connector. Fig.4 (Dim. “B”) shows the location of this
pipe in a typical application. Table 3 depicts the proper diameter
(Dim. ”C”) of the connector rise depending upon its total leng
(top of the draft hoods to the breeching above).
Table 3
Vent connector diameters (20Ft. Chimney “F” Dim.)
Model
Flue
Outlet
Connector Rise “B”
Size”A” 3’ High 2’ High 1’ High
“C”“C”“C”
GXH3009”9”10”10”
Based on single row of modules with no elbows.
Note: For conditions other than those shown, consult factory, or National
fuel gas code NFPA 54.
th
HORIZONTAL BREECHING
CONNECTOR LENGTH:
The maximum length of the horizontal breeching connector length
between the chimney and the closest boiler shall not be longer
than one foot per inch of horizontal breeching connector diameter,
i.e. if the horizontal breeching connector is 16” D., the maximum length from the chimney to the first boiler would be 16
X 1 FT. or 16 feet. The minimum length shall be on
less of the horizontal breeching connector diameter. See figure 4.
ot regard-
e fo
Figure 4: Connector Rise “B”
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.