Slant/Fin Gas Steam User Manual

®
STEAM / GAS
APPLICATION GUIDE
WET-BASE CAST-IRON MODULAR BOILERS
Guidelines for the design, purchase and installation of Slant/Fin gas-fired steam modular boiler systems.
CONTENTS
Introduction .............................................................................1
Ratings and dimensions .........................................................2
Boiler room air supply.............................................................3
Venting gas fired system .....................................................4,5
Gas main sizing ...................................................................6,7
Typical steam system layout ...................................................8
Steam piping design ...............................................................9
Installation and piping ......................................................10,11
Boiler feed pump sizing ...................................................12,13
Wiring at module .............................................................14-16
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the absence of local codes, to the National Fuel Gas Code, ANSI, Z223.1 latest edition.
In addition where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Codes for controls and safety devices for automatically fired boilers, No. CSD-1. The instal
ation must also conform to the additional requirements of
l Slant/Fin Instruction book publication No. GG-100-40 latest edition.
All electrical wiring is to be done in accordance with the National Electrical Code ANSI/NFPA No. 7 latest edition and all local electrical codes. The unit must be electrically ground­ed if an external power source is used.
In Canada, the installation must be in accordance wi dards CGA B149.1 and B149.2, installation codes for gas burning appliances and equipment and/or local codes. All electrical connections are to be made in accordance with Standard C.S.A. C22.1 Canadian Electrical Code Part 1 and/or local codes.
Many state and local codes require intermittent ignition devices for gas boilers. Please specify if necessary.
th s
tan-
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a sys­tem can cause scaling and leave deposits in the boiler and the surrounding water pipes. This will lead to inefficient boiler operation and breakdown. Fresh water will enter the system as a result of leaks such as may occur in underground piping.
-
Process applications that use fresh water require the use of heat exch duction of fresh water into a boiler can cause scaling, with deposits forming in the boiler and surrounding piping. This will damage the boiler. Introduction of fresh water from leaks will cause similar damage.
In some areas it may be necessary to use a feed water treat­ment to control the corrosive makeup of the fill water. Check with the local a conditioning treatment before being supplied to the boiler.
angers. A
ny process application that results in intro-
uthority to determine if the feed water will need
a
INTRODUCTION
There are many varieties of steam heating systems. Because of the wide range of field conditions, the design of these sys­tems is beyond the scope of this manual. However, when designing a steam Caravan boiler plant, certain guidelines should be followed that are common to all modular steam heating application.
This entire manual should be read prior to installing the Slant/Fin Caravan steam system.
Safety – each module contains a dual combination gas valve, ASME 15 lb Relief valve and pressure gauge.
Publication No. CG-10-SG
Printed in the U.S.A. 1112
Table 1: Ratings and dimensions
Net
Output
M.B.H
AHRI
Net Sq. Ft. Steam
Horsepower
Boiler
Water
Content
(Gals)
Shipping
Weight
Lbs.
“A” Dim
“B” Dim
“C” Dim
Minimum
Space Between Modules
Recommended
Header
Size
“D” Dim
“L”
Dim
Model No.
Number
of
Modules
Module
Model
Number
Input
M.B.H
CSA
Gross
Output
.B.H
M
GXHT-600 Z 2 GXH-300 600 478 358 1492 14.78 16.8 1075 26 1⁄16 59 1⁄8 9” 7” 3” 11 17⁄32 4’ 11 1⁄8
GXHT-900 Z 3 GXH-300 900 717 537 2238 21.42 25.2 1595 26 1⁄16 59 1⁄8 9” 7” 4” 11 17⁄32 7’ 8 3⁄16
GXHT-1200 Z 4 GXH-300 1200 956 716 2983 28.56 33.6 2115 26 1⁄16 59 1⁄8 9” 7” 5” 11 17⁄32 10’ 5 1⁄4
GXHT-1500 Z 5 GXH-300 1500 1195 895 3729 35.70 42 2635 26 1⁄16 59 1⁄8 9” 7” 6” 11 17⁄32” 13’ 2 5⁄16
For larger sizes, use multiple of the above
Specify gas by name, “natural” or “propane”. Net ratings are based on piping and pick-up allowance of 1.33. Slant/Fin should be con­sulted before selecting a boiler for installation having unusual piping and/or pick-up require­ments.
Ratings must be reduced by 4% at 2000 ft. elevation and an additional 4% for every additional 1000 ft. elevation over 2000 ft.
Modules in excess of 5, should be piped in banks of 5, parallel with each other.
Figure 1: For McDonnel & Miller PS 801-24 L.W.C.O Min. clearance 9"
2
BOILER PLANT SIZING
Older buildings may have a heat loss significantly less than that of the original building. To size a replacement steam boiler plant, consider the following: Replacement steam boiler plants must be sized to match the connected radiation load. Under-sizing will prevent steam from reaching distant radiation quickly.
BOILER ROOM DESIGN
Caravan modular boiler systems allow better utilization o space and permit future expansion with minimum cost. The mod­ules are hand truckable, fit through doorways and often may be installed around an existing inoperative boiler. They can be grouped in single or multiple banks. Systems consisting of five or more modules should be piped in two or more banks.
f floor
BOILER ROOM AIR SUPPLY
To ensure safe, efficient operation, the modular boiler syst
st be supplied with sufficient air to support complete combus-
mu tion, replacing air entering draft dampers or draft hoods and ven­tilating the boiler room or areas.
For additional information, not listed below, see ANSI. Z223.1, section 5.3.3.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM:
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the floor (below burner air inlet) and one louvered opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of
1 square inch per 4000 BTUH
of total system input.
em
Figure 2: Correct location of combustion-air supply ducts.
2. Air drawn horizontally through HORIZONTAL DUCTS; one opening near the floor (below burner inlet) and one opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of
1 square inch per 2000 BTUH.
3. Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with
a minimum FREE air passage area of 1 square inch per 4000 BTUH of total system input.
4. Air drawn from inside the building; one opening near the floor (below burner inlet) and one opening near the ceiling (above the highest draft regulator), each opening
with a minimum FREE air passage area of 1 square inch per 1000 BTUH of total system input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASSED TO ACCOMMO­DATE THE ADDITIONAL LOAD.
UNLESS PROPERLY CONTROLLED, AVOID THE USE OF FORCED VENTILATION, SINCE IT CAN CREATE AN UNDESIRABLE PRESSURE DIFFERENTIAL BETWEEN BOILER ROOM AND AIR SOURCE.
3
VENTING A GAS-FIRED SYSTEM
A boiler venting system provides an escape path for the products of combustion. There are three major components for venting a gas-fired Caravan: a draft hood for each module, a breeching manifold and a chimney.
Draft Hood
The draft hood is part of each boiler module, although shipped in a separate carton. It compensates for excessive draft. The dimen­sional relationships betwe
en the draft hood, the boiler and sur­face on which the boiler is mounted, are critical. These factors are all interdependent in allowing the draft hood to function with­out moving parts. Attempts to alter these dimensions will result in unsafe operating conditions.
Breeching
Breeching is a term used to describe a manifold(s) that connects individual boiler modules to a chimney. Breeching is usually
tructed of sheet metal having a smooth interior surface with all
s
con-
joints made tight against leakage. Pitch breeching up toward chimney. Horizontal breeching size should be maintained for the total length. Connections from the modules into the breeching are best made at 45˚ angles in the direction of the chimney. See figure 3.
Table 2: Breeching dimensions: gas fired systems
Model No.
Consist of
No. of
Modules
Module
No.
Chimney Height*
25
20
Feet30Feet50Feet
Feet
GXHT600Z 2 GXH300 12” 10” 10” 9” GXHT900Z 3 GXH300 14” 12” 12” 12” GXHT1200Z 4 GXH300 16” 14” 14” 12” GXHT1500Z 5 GXH300 16” 16” 16” 14”
The bottom portion of the breeching should be installed at least 3 feet above the top of modules’ draft hoods. If this height cannot be obtained, install the breeching as high as possible. See Page 5, Table 3 for heights less than 3 feet. The portion of chimney height rising directly above each draft hood is most effective in preventing flue gas spillage. When the boiler room is in an unheated space, insulate vent pipe and breeching to maintain flue gas temperature and good chimney operation. Do not lower draft hoods’ skirt height. For some combinations of low chimneys, low ceilings and long breeching, a draft inducer may be needed. Inducers, when required, are locally specified and warrantied. The breeching should extend into but not beyond the chimney liner.
Chimney
Caravan gas-fired modular boilers
operate efficiently with masonry or prefabricated chimneys as well as with “Type B” or double-walled metal vent pipe. The latter type of chimney construction is generally the least expensive. Chimney height is usually governed by the building height and the size of the boilers (See Table 1). However, the chimney should be high enough to minimize the effects of turbu­lent winds and pressure common ne
ar rooftop obstructions. A vent cap should be used where permitted for additional protection against adverse wind conditions and precipitation. The National Board of Fire Underwriters recommends that the chimney should extend at least 3 feet above the roof and be 2 feet higher than any obstruction within 10 feet.
Sizing horizontal breeching connectors and chimneys for gas-fired systems
Horizontal breechi
ng connectors shall be constant sized. The chim­ney and the horizontal breeching connector are sized using Table 2. When there are multiple banks of boilers, the horizontal breeching connector for each bank is sized using Table 2. To size the common horizontal breeching connector, add up the total input and refer to Table 2A. The minimum chimney opening will be equal to the size of the
largest horizon
tal breeching section connected to it.
Based on single row of modules with no elbows.
• Height measured from the top of draft hood to top of chimney Note: For conditions other than those shown, consult factory, or National
fuel gas code NFPA 54.
Table 2A: Chimney and breeching sizing for multiple banks **
Chimney Height*
25
20
Feet30Feet50Feet
BTU Input
Feet
1,800,000 18” 18” 18” 16” 2,100,000 20” 18” 18” 16” 2,400,000 20” 20” 20” 18” 2,700,000 22” 22” 20” 18’ 3,000,000 24” 22” 22” 20” 3,300,000 24” 24” 22” 20” 3,600,000 26” 24” 24” 20” 3,900,000 26” 26” 24” 22” 4,200,000 26” 26” 24” 22” 4,500,000 28” 26” 26” 24”
•• Based upon system total BTU input
Figure 3: Suggested venting system constructions.
4
CONNECTOR RISE:
Connector rise is the length of the pipe connecting the top of the draft hood to the system breeching above. The diameter of this pipe varies depending upon BTU input, chimney height and the length of the connector. Fig.4 (Dim. “B”) shows the location of this pipe in a typical application. Table 3 depicts the proper diameter (Dim. ”C”) of the connector rise depending upon its total leng (top of the draft hoods to the breeching above).
Table 3
Vent connector diameters (20Ft. Chimney “F” Dim.)
Model
Flue
Outlet
Connector Rise “B”
Size”A” 3’ High 2’ High 1’ High
“C” “C” “C”
GXH300 9” 9” 10” 10”
Based on single row of modules with no elbows. Note: For conditions other than those shown, consult factory, or National fuel gas code NFPA 54.
th
HORIZONTAL BREECHING CONNECTOR LENGTH:
The maximum length of the horizontal breeching connector length between the chimney and the closest boiler shall not be longer than one foot per inch of horizontal breeching connector diameter,
i.e. if the horizontal breeching connector is 16” D., the maxi­mum length from the chimney to the first boiler would be 16 X 1 FT. or 16 feet. The minimum length shall be on
less of the horizontal breeching connector diameter. See figure 4.
ot regard-
e fo
Figure 4: Connector Rise “B”
5
Loading...
+ 11 hidden pages