All Caravan installations must comply to local codes or, in the
absence of local codes, to the National Fuel Gas Code, ANSI,
Z223.1-latest edition.
In addition where required by the authority having jurisdiction, the
installation must conform to American Society of Mechanical
Engineers Safety Codes for controls and safety devices for
automatically fired boilers, No. CSD-1. The installation must also
conform to the additional requirements of Slant/Fin Instruction Book
publication no. GG-100-40 latest edition.
All electrical wiring is to be done in accordance with the National
Electrical Code ANSI/NFPA No. 70-latest edition and all local electri-
cal codes. The unit must be electrically grounded if an external
power source is used.
In Canada, the installation must be in accordance with standards
CGA B149.1 and B149.2, installation codes for gas burning
appliances and equipment and/or local codes. All electrical
connections are to be made in accordance with Standard C.S.A.
C22.1 Canadian Electrical Code Part 1 and/or local codes.
Many state and local codes require intermittent ignition devices for
gas boilers. Please specify if necessary.
LOCAL CODE APPROVALS
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can
cause scaling and leave deposits in the boiler and the surrounding
pipes. This will lead to inefficient boiler operation and breakdown.
Fresh water will enter the system as a result of hidden leaks such
as may occur in underground piping. Relief valves should be piped
to a location that shows visible signs of relief.
Process applications that use fresh water, require the use of heat
exchangers. Any process application that results in introduction of
fresh water into a boiler can cause scaling with deposits forming in
the boiler and surrounding piping. This will damage the boiler.
Introduction of fresh water from leaks will cause similar damage.
In some areas it may be necessary to use a feed water treatment to
control the corrosive makeup of the feed water. Check with the local
authority, to determine if the feed water will need a conditioning
treatment before being supplied to the boiler.
New York City:
GGT and GGHT Caravan Modules - MEA 283-93-E Vol. II
Slant/Fin vent damper NYS approval No. 8859
Pennsylvania:
Caravan boilers are approved in Pennsylvania by PA Cert. 174-BT-S
Publication No. CG-10-HWG
Printed in the U.S.A. 1212
www.slantfin.com
INTRODUCTION
This Caravan application manual is intended to simplify the selection
and application of Slant/Fin modular systems for a variety of space
heating and domestic hot water requirements. It applies to
gas-fired, hot water applications only. Where intermittent pilot, vent
B. Faster, easier installation - modules are completely factory
ass
embled, including individual jackets to save on-site labor.
Optional easy to install return and supply headers with flexible
quick connect fittings are available for hot water systems.
damper or any additional information is required, contact your local
wholesaler, Slant/Fin sales representative, or the Sla
nt/Fin factory.
C. Safety - each module contains an individual high limit control
and a dual combination gas valve. ASME relief valve is provided
Due to design flexibility of a Caravan modular boiler system, BTU
separately for mounting directly on each module.
input capacities are unlimited.
A. Boiler room design, size and flexibility - since Caravan
D. Fast domestic hot water recovery - Carava
heat exchanger of the positive circulating type.
n offers an external
modules have the burner and controls mounted to the front, they
can be installed with minimum clearances as per codes, thus
saving a significant amount of floor space.
Table 1: Gas Caravan ratings and dimension/hot water model—GGT Series (100 psi maximum working pressure)
* Specify gas by name, "Natural" or "Propane".
† Net ratings are based on piping and pick-up allowance of 1.15. Slant/Fin should
be consulted before selecting a boiler for installation having unusual piping and/or
pick-up requirements. Ratings must be reduced by 4% at 2,000 ft. elevation and
an additional 4% for every additional 1,000 ft. elevation over 2,000 ft.
e
‡ Net ratings in square feet based on
§ Refer to figures 1 and 8. Headers shown are optional.
‡‡All factory supplied headers use 3" system connections.
Modules in excess of 10 should be piped in parallel in two or more batteries.
Note: For higher capacities, specify correct combination of standard Caravan
modules shown.
mission rate of 150 Btuh/sq. ft.
2
Figure 1: Gas Caravan dimensions and typical piping/hot water models
Design Data
Max. ASME Working Pressure: 100 psi
Power Requirements: 120 volts, 60 HZ, .34 amps per module
3
RECOMMENDED PIPING
Figure 2. Recommended boiler piping for variable circulation
Figure 3. Supply and return piping locations
Figure 4. Instantaneous tankless coil—
two temperature with recirculation
Figure 5. Storage tank from tankless coil with recirculation
4
EQUIPMENT INCLUDED
GGT SERIES — Hot Water Models
One per module unless otherwise noted
• Pre-assembled heat exchangers with built-in air separators
and insulated jacket.
• Base.
• Flue collector.
• Gas burners, gas orifices and manifold assembly.
• Combination gas valve including manual shut-off pressure
regulator.
• Hi-limit control.
• System pressure and temperature gauge (unmounted, one
per system).
*Building piping must be rigidly secured so it cannot
move where connected to headers.
NOTE:
Shown reverse return (Preferred). For direct return,
header assembly piping connections may be made at
the same end of the boiler bank, not as shown.
Some governing agencies do not allow compression
type couplings. Consult your local code requirements.
Figure 6. Gas Caravan—optional header assembly for all models GGT hot water Caravan systems
5
BOILER ROOM DESIGN
Caravan modular boiler systems allow better utilization of floor
space and permit future expansion with minimum cost. Caravan
modules are hand truckable, fit through doorways and often may
be installed around an existing inoperative boiler. They can be
grouped in heating module batteries of single, multiple or angular
rows. Gas-fired boiler systems consisting of 11 or more modules
shou
ld be piped in parallel in two or more batteries. Illustrated on
the following page are typical boiler room layouts and dimensional
data on the size requirements of gas-fired hot water boilers.
Figure 7: Correct location of combustion-air supply ducts
BOILER ROOM AIR SUPPLY
To ensure safe, efficient operation, the modular boiler system must
be supplied with sufficient air to support complete combustion,
replacing air entering draft dampers or draft hoods and ventilating
the boiler room or areas.
For additional information, not listed below, see ANSI,Z223.1,
section 5.3.3.
I
NSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF
AIR INTO THE BOILER ROOM:
1. Air drawn horizontally from outdoors DIRECTLY
through an outside wall; one louvered opening near
the floor (below burner air inlet) and one louvered
opening near the ceiling
regulator), each opening with a minimum FREE air
passage area of 1 square inch per 4000 BTUH
system input.
2. Air drawn horizontally through HORIZONTAL DUCTS;
one opening near the floor (below burner inlet) and one
opening near the ceiling (above the highest draft
regulator), each opening with a minimum FREE air
passage area of 1 square inch per 2000 BTUH
system input.
3. Air drawn VERTICALLY from outdoors; one opening
at the floor and one opening at the ceiling, each opening
with a minimum FREE air passage area of
1 square inch per
4. Air drawn from inside the building; one opening near
the floor (below burner inlet) and one opening near the
ceiling (above the highest draft regulator), each opening
with a minimum FREE air passage area of
1 square inch per 1000 BTUH
(
above the highest draft
of total
of total
4000 BTUH of total system input.
of total system input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL
BURNING EQUIPMENT, THE AREA OF FREE OPENINGS
MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE
THE ADDITIONAL LOAD.
UNLESS PROPERLY CONTROLLED, AVOID THE USE OF
FORCED VENTILATION, SINCE IT CAN CREATE AN
UNDESIRABLE PRESSURE DIFFERENTIAL BETWEEN
BOILER ROOM AND AIR SOURCE.
6
Figure 8. Typical layouts for gas-fired systems
7
VENTING A GAS-FIRED SYSTEM
A boiler venting system provides an escape path for the products of
combustion. There are three major components for venting a gas-fired
Caravan: a draft hood for each module, a breeching manifold and a
chimney.
Draft Hood
The draft hood is part of each boiler module, although shipped in a
separate carton. It compensates for excessive draft that can be
caused by the venturi effect of winds passing over the top of the chim-
ney. The dimensional relationships between the draft hood, the boiler
and surface on which the boiler is mounted, are critical. These factors
are all interdependent in allowing the draft hood to function without
moving parts. Attempts to alter these dimensions can result in unsafe
operating conditions.
Note: When mounting the modules on a raised platform, be
the platform extends past the edge of the modules at least 3 inches
on all sides.
Breeching
Breeching is a term used to describe a manifold(s) that connects
individual boiler modules to a chimney. Breeching is usually constructed of sheet metal having a smooth interior surface with all joints made
tight against leakage. Pitch breeching up toward chimney. Horizontal
breeching size should be mai
ntained for the total length. Any transitions should be made after 4 modules. Connection should be made at
a 45° angle in the direction of the chimney. See figure 10.
Table 2. Breeching dimensions for gas-fired systems
Run breeching as high as clearance permits to obtain maximum
vertical rise of individual boiler vents. Note that this does not alter
chimney height (the height from hood skirt to chimney top). The
portion of chimney height rising directly above each hood is most
effective in preventing spillage. When the boiler room is in unheated
space, insulate vent pipe and breeching to maintain flue gas temperature and good chimney operation. It is not permitted to lower draft
hood skirt height to achieve pitch, or to compensate for low
ceilings. For some combinations of low chimneys, ceilings and long
breeching, a draft inducer may be needed
. Inducers when required
are locally specified and warrantied. The breeching should extend
into, but not beyond, the chimney liner.
Chimney
Caravan gas-fired modular boilers operate efficiently with masonry or
prefabricated chimneys as well as with “Type B” or double-walled
metal vent pipe. This latter type of chimney construction is generally
the least expensive. Chimney height is usually governed by th
e
building height and the size of the boilers (see Table 1). However, the
chimney should be high enough to minimize the effects of turbulent
winds and pressure common near roof-top obstruction. A vent cap
should be used where permitted for additional protection against
adverse wind conditions and precipitation. The National Board of Fire
Underwriters recommend that the chimney should extend at least 3
f
eet above the roof and be 2 feet higher than any obstruction within 10
feet.
Sizing Horizontal Breeching Connectors and Chimneys for GasFired Systems
Horizontal breeching connectors shall be constant sized. The chimney
and the horizontal breeching connector are sized using Table 2.
When there are multiple banks of boilers, the horizontal breeching
connector for each bank is sized using Table 2. To size
the common
horizontal breeching connector, add up the total input and refer to
Table 2 to size.
The minimum chimney opening will be equal to the size of the largest
horizontal breeching section connected to it.
Horizontal Breeching Connector Length
The MAXIMUM length of the horizontal breeching connector length
between the chimney and the closest boiler shall NOT be longer than
12 inches per inch of horizo
ntal breeching connector diameter, i.e. if
the horizontal breeching connector is 16" D., the MAXIMUM length
from the chimney to the first boiler would be 16" x 12" or 192 inches.
The MINIMUM length shall be 12 inches regardless of the horizontal
breeching connector diameter. See figure 9.
Based on single row of modules with no elbows.
* Height measured from top of draft hood to top of chimney.
NOTE: For conditions other than those shown, consult factory, or
National Fuel Gas Code NFPA 54
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.