Slant/Fin Gas Conversion Field User Manual

Page 1
Gas Conversion Field Assembly Kit
Natural Gas to Liquefied Petroleum (Propane) or Liquefied Petroleum (Propane) Gas to Natural
Only for use with Slant/Fin boilers equipped with Honeywell VR8200, VR8204, VR8300 and VR8304 gas valves, either standing (continuous burning) pilots or intermittent ignition systems.
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the informa­tion in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result causing prop­erty damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.
WARNING-IMPORTANT
1. This conversion kit is supplied with the same parts normally provided on SLANT/FIN factory built boilers which are Design Certified by CSA International. However, because we have no way of applying our own quality control procedures to field alterations made by others on this boiler, these alterations are not the respon­sibility of SLANT/FIN. These alterations are the responsibility of the installer of this con­version kit. The instructions below must be carefully followed in order to duplicate factory installation.
WARNING
LIQUEFIED PETROLEUM (L.P.) PROPANE GAS­FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION Liquefied Petroleum (LP) propane gas is heavier than air. Therefore, propane boilers, piping, valves must NOT be installed in locations where propane leaking from defective equipment and piping will "pool" in a basement or other space below the leak.
A spark or flame from the boiler or other source may ignite the accumulated propane gas causing an explosion or fire. Provide a level, solid founda­tion for the boiler. Location should be as near the chimney as possible so that the flue pipe from boil­er to chimney is short and direct.
THE UNIFORM MECHANICAL CODE may be in effect in your geographic area.
The following precautions are cited by the 1994 UNIFORM MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas­burning appliances shall not be installed in a pit, basement or similar location where heavier­than-air gas might collect. Appliances so fueled shall not be installed in an above-grade under­floor space or basement unless such location is provided with an approved means for removal of
unburned gas." Consult Chapter 5 of the 1994 UNIFORM MECHANICAL CODE for design criteria of the "approved" means for removal of unburned gas.
2. The installation must conform to the require­ments of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code ANSI Z223. 1-lat­est edition.
The boiler warranty is void unless this field assembly conversion kit has been properly installed,
labels completed and applied to boiler and registration card completed and received
by Slant/Fin within 10 days after kit has been installed in boiler.
PUBLICATION No. GCK-40
Part No. 46-0527
Printed in U.S.A. 708
Page 2
ENTRY SERIES BOILER
S
Location and identification of parts.
Base Assembly
Front and Right End View (Sentry “S” Series shown)
Burners
Pilot
Burner Access Door
Gas Valve
2
Page 3
VICTORY VSP AND VSPH SERIES BOILERS
ocation and identification of parts.
L
Base Assembly
3
Page 4
SENTINEL SERIES BOILER
ocation and identification of parts.
L
Burners
Pilot
LEFT END VIEW
Burner Access Door
RIGHT END VIEW
Gas Valve
4
Page 5
VICTORY II SERIES BOILER
ocation and identification of parts.
L
LEFT END VIEW FRONT VIEW RIGHT END VIEW
VICTORY II - VH, VHL BASE ASSSEMBLY
Location and identification of parts.
Burner
Pilot burner, ignitor and sensor
Smart Valve
VICTORY II - VHS, VHLS BASE ASSEMBLY
Location and identification of parts.
Burners
Pilot
Burner access door
Gas valve
Gas manifold
Roll-out safety
Gas Manifold
switch
5
Page 6
VICTORY V SERIES BOILER
ocation and identification of parts.
L
Pressure/
Temperature
Gauge
Air Flow
Proving Switch
Draft Inducer
Assembly
Ignition Control
Circulator
Gas Valve
Base Assembly
Burners
Pilot
Burner Access Door
Gas Valve
Right End View
6
Page 7
ALAXY BOILER
G
Remove front panel (Figure 1) by pressing hand against panel and pushing up. Remove burner access door (Figure 2) by removing 2 wing nuts, slide panel
orward and out.
f
Figure 1. Front Panel
Jacket Top
Name and Rating Plate
ighting
L
Instructions
(inside front
panel)
as Valve
G
Burner Access Door
Burners
Relief Valve
emperature
T
and Pressure
Gauge
Gas Manifold
EFORE STARTING
B
heck contents for kit:
C
All components are either marked with a red stripe, a label with a model number or a stamped number on them.
1. Honeywell Conversion Kit: a) Spring: propane = red; natural = stainless steel b) Regulator adjusting screw c) Cap screw: propane = black; natural = silver
) Instructions
d e) Label
2. Main Burner Orifices: See Table 1 for the correct size orifice as it applies to this conversion.
3. Pilot Burner Assembly: a) Pilot burner:
Standing pilot—Honeywell Q314A Intermittent ignition—Honeywell Q345A
b) Pilot orifice:
Propane—Honeywell BBR-10 Natural—Honeywell BCR-18
4. Ignition Control (for IID only): Honeywell S8600M (for Sentry, Sentinel or Victory V series boilers) or S8670E (for Galaxy boilers). Required for conversion to propane only.
5. Three Labels: Boiler Conversion Label, Affidavit Label and Gas Valve Label.
6. Registration Card
Caution: The gas supply shall be shut off prior to discon­necting the electrical power, before proceeding with the conversion.
Figure 2.
Pop Safety Valve
Jacket Top
INSTALLATION
1. Turn Off Gas to Appliance a) Set thermostat to lowest level. b) Turn off all electric power to the appliance. c) Turn the gas control knob clockwise to the off
position. d) Close all gas cocks. e) CAUTION: LET BOILER COOL. f) Remove front jacket panel. g) Remove burner access door.
2. Gas Valve Conversion a) Remove pressure regulator cap screw. b) Remove pressure regulator adjusting screw. c) Remove regulator spring.
d) Insert appropriate replacement spring (tapered
end down).
Pressure Gauge
Figure 3.
Figure 4. Conversion Kit Installation in Regulator
7
Page 8
) Install new pressure regulator adjustment screw
SHUTTER
BURNER
RETAINER CLIP
M ANIFOLD
MANIFOLD
BURNER
PILOT
e
until it is flush with the top of the casting.
f) After e) above, turn adjustment screw clockwise
as follows: Propane Gas — 5-
atural Gas — 6 full turns
N
3
4 full turns
g) Install the NEW cap screw.
) Place the gas valve conversion label from the
h
Honeywell kit over the gas valve model number.
3. Pilot Burner Conversion a) Disconnect pilot line from gas valve. b) Disconnect flame sensor.
Standing pilot— disconnect thermocouple from gas valve. Intermittent ignition — disconnect ignition wire from S8600 ignition control.
c) BE SURE BURNERS ARE COOL BEFORE
CONTINUING. NOTE LOCATION OF BURNER WITH PILOT. REMOVE THE BURNER RETAINER CLIP OF THE PILOT-BURNER. REMOVE THE BURNER. DISCONNECT THE PILOT TUBE AND EITHER THE THERMOCOUPLE FOR STANDING PILOT OR IGNITION WIRE FROM IGNITION CONTROL. (See figure 6).
d) Remove pilot burner and replace with new pilot
burner.
e) Replace pilot tubing on pilot burner. (It is best to
cut off old ferrule and use new one to ensure a proper seal.)
f) Replace thermocouple or ignition wire on pilot
assembly.
g) Remove existing main burner orifice from the
manifold and replace with an orifice from the kit. (See figure 7).
h) Replace the pilot-burner into the boiler. Replace
the burner retainer clip.
4. Orifice Replacement - Remove all other burner
retainer clips and remove the rest of the burners.
a) Remove existing main burner orifices from the
manifold.
b) Install the orifices from the kit. (There may be
more orifices than required.)
c) Reinstall the main burners making sure that the
pilot burner is in the same position as above.
5. Ignition Control Replacement (for IID only)
IMPORTANT
FOR CONVERSION OF BOILERS EQUIPPED
WITH AN INTERMITTENT IGNITION SYSTEM TO PROPANE, THE IGNITION CONTROL MUST BE CHANGED. FAILURE TO INSTALL THE COR­RECT IGNITION CONTROL COULD CAUSE A
AZARDOUS CONDITION RESULTING IN AN
H EXPLOSION OR CARBON MONOXIDE POISON­ING AND WOULD VOID ANY WARRANTY. a) Remove the S8600F Control from the right side of
the boiler. Note the location of the wires so that
hey may be installed on the proper terminals of
t the replacement control.
b) Install the NEW S8600M or S8670E control
supplied in the kit. Reconnect the wires, including the ignition wire. Check applicable wiring diagram on pages 9 to 15 or the diagram on the boiler to make certain that the wiring is correct.
6. Registration Card and Labels: a) Fill out the Boiler Conversion Label, Affidavit Label
and Gas Valve Label. Affix the Boiler Conversion Label adjacent to the rating plate on the boiler jacket. Affix the Affidavit Label to the front jacket panel adjacent to the Slant/Fin logo. Affix the Gas Valve label on the inside jacket panel above the gas valve.
b) Fill out the Registration Card. REMEMBER THAT
THIS CARD MUST BE RECEIVED WITHIN 10 DAYS OR THE WARRANTY COULD BE VOIDED.
FINAL CHECKS:
1. Are the burners installed correctly (ports are up)?
2. Is the pilot in the correct position?
3. All of the wiring is correct?
4. All the labels have been filled out and affixed to the boiler?
5. Has the Registration Card been filled out?
GAS LEAK TESTS
Warning: DO NOT OMIT these tests. Open all gas cocks
upstream of the boiler gas valve. Paint all pipe joints from the main gas cock to the gas valve with a rich soap and water solution. Bubbles indicate gas leakage. To stop the leak, tighten the joints and fittings. DO NOT USE AN OPEN FLAME FOR TESTING.
Figure 5. Gas Valve — top view
8
Figure 6. Burner/Manifold
Figure 7. Pilot/Burner
Page 9
Wiring Diagram - Victory “V” Series Boilers
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”
9
Page 10
Wiring Diagrams- Victory II - VH, VHL Series
10
Page 11
Wiring Diagrams- Victory II - VHS, VHLS Series (Spark Ignition)
11
Page 12
Wiring Diagrams- Victory, VSP, VSPH
12
Page 13
WIRING DIAGRAM - GALAXY/SENTRY—CONTINUOUS (STANDING) PILOT
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”
13
Page 14
WIRING DIAGRAM - GALAXY/SENTRY—INTERMITTENT PILOT IGNITION (IID)
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”
14
Page 15
WIRING DIAGRAMS FOR SENTINEL HOT WATER BOILERS
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”
Damper circuit is designed to be controlled by low voltage controls. DO NOT use line voltage operating
Models with Intermittent Pilot Ignition (IID) Models with Continuous Burning Pilot
controls to interrupt supply voltage to the L8148E aquastat.
15
Page 16
SENTRY AND SENTINEL SERIES
Boiler Model
All Sentinel models and
entry S-34
S
entry S-60 thru
S
S-150 & SX-150 thru
X-210
S
Gas
Type
atural 47 48 48 49 49 49 50 50 51 51
N Propane 56 56 56 57 57 57 58 59 59 60
Natural 50 51 51 51 51 52 52 52 53 53
ropane 57 58 59 59 60 60 61 62 63 63
P
VICTORY SERIES
Boiler
Model
-33
V
-60 thru V-180
V
SP, VSPH, VH & VHS
V
Gas
Type
Natural 48 49 50 50 50 51 51 52 52 52
ropane 56 56 56 57 57 57 58 59 59 6
P
atural 50 51 51 51 52 52 52 52 53 53
N Propane 57 58 59 59 60 60 61 62 63 63
atural 49 50 50 50 51 51 51 52 52 52
N
ropane 57 58 59 59 60 60 61 62 63 63
P
Orifice
Size
for
ea
S
Level*
Orifice
Size
for
Sea
Level*
TABLE 1
ORIFICE SIZE TABLE
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
levation - Feet
E
2000 3000 4000 5000 6000 7000 8000 9000 10000
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
2000 3000 4000 5000 6000 7000 8000 9000 10000
GALAXY SERIES
Orifice
Size
for
Boiler
Model
GG/GX Except Natural 42 43 43 43 43 44 44 45 46 47 GG-399H & GG-350H Propane 54 54 55 55 55 55 55 56 56 56 GG-399H Natural 40 41 42 42 42 43 43 44 44 45
GXH-105 Natural 44 45 45 45 46 47 47 48 48 49 through 275 Propane 54 54 55 55 55 55 55 56 56 56 GXH-300 Natural 43 44 44 44 45 45 46 47 47 48
GXH-300H Natural ** 42 43 43 43 43 44 45 45 46 47
GXHA Natural 45 46 47 47 47 48 48 49 49 50
Gas
Type
Propane 53 54 54 54 54 54 54 55 55 55
Propane 54 54 55 55 55 55 55 56 56 56
Gas Only
Gas Only 55 55 55 55 56 56 56 56 56 57
Sea
Level*
2000 3000 4000 5000 6000 7000 8000 9000 10000
Includes 4% Reduction for Each 1000 Feet
Orifice Sizes for High Altitudes
Elevation - Feet
SENTINEL SERIES
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
Boiler
Model
Sentinel
Orifice
Size
for
Gas
Type
Natural 47 48 48 49 49 49 50 50 51 51 Propane 56 56 56 57 57 57 58 59 59 60
Sea
Level*
2000 3000 4000 5000 6000 7000 8000 9000 10000
16
VICTORY II - VHL, VHLS Series (Under 2000 Ft. Only)
Orifice
Boiler
Model
VHL, VHLS
Size
Gas
Type
Natural 49 Propane 57
Sea
Level*
for
* Orifice indicated for sea level above are factory installed in boiler unless
otherwise specified by the local authority. See page 19 for burner input adjustment.
** For L.P. Propane consult factory.
Page 17
TABLE 2
INPUT RATING OF BOILERS
Note: All models of the boilers will have the same input rating after converted.
17
Page 18
LIGHTING INSTRUCTIONS
Continuous Burning Pilot (24V).
OR BOILERS EQUIPPED WITH GAS VALVES
F VR8200
and VR8300.
SAFETY INFORMATION
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these instruc­tions exactly.
B. BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
DO NOT try to light any appliance.
DO NOT touch any electric switch; DO NOT use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control
knob. NEVER use tools. If the knob will not push in or turn by hand, DON'T try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
Lighting Instructions
1. STOP! Read the safety information above on this page.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. Remove control access panel. (Galaxy models only.)
5. Push in gas control knob slightly and turn clockwise
to "OFF".
6. Wait five (5) minutes (longer for propane) to clear out any gas. If you then smell gas, STOP! Follow
"B" in the safety information. If you don't smell gas, go to next step.
. Remove the pilot access panel located
7
below and behind the gas control unit.
8. Find pilot—follow the aluminum tubing from the gas valve. The pilot is between two burner tubes behind the burner access panel.
9. Turn knob on gas control counterclockwise to
"PILOT".
10. Push in red button all the way and hold in. Immediately light the pilot with a match. Continue to hold the red button in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 10.
• If knob does not pop up when released, stop
and immediately call your service technician
or gas supplier.
• If the pilot will not stay lit after several tries,
turn the gas control knob to "OFF" and call
your service technician or gas supplier.
11. Replace pilot access panel.
12. Turn gas control knob counterclockwise to “ON".
13. Replace control access panel. (Galaxy models only.)
14. Turn on all electric power to the appliance.
15. Set thermostat to desired settings.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if serv­ice is to be performed.
3. Remove control access panel. (Galaxy models only.)
4. Turn gas control knob clockwise to "OFF". DO NOT force.
5. Replace control access panel. (Galaxy models only.)
VALVE VR8200 OR VR8300
RED BUTTON
18
GAS CONTROL KNOB SHOWN IN “OFF” POSITION.
Page 19
HONEYWELL IID SYSTEM . FOR BOILERS EQUIPPED WITH GAS VALVE VR8204 OR
VR8304
.
SAFETY INFORMATION
FOR YOUR SAFETY READ BEFORE LIGHTING
ARNING: If you do not follow these instructions exactly,
W a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
hich automatically lights the pilot. DO NOT try to
w light the pilot by hand.
B. BEFORE OPERATING smell all around the appli-
ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electric switch; DO NOT use any phone in your building.
• Immediately call your gas supplier from a neigh­bor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control
knob. NEVER use tools. If the knob will not push in or turn by hand, DON'T try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
Lighting Instructions
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service s to be performed.
i
3. Remove control access panel. (Galaxy models only.)
4. Turn gas control knob clockwise till knob stops,
then continue to "OFF". DO NOT force.
5. Replace control access panel. (Galaxy models only.)
VALVE VR8204 OR VR8304
BURNER ADJUSTMENT
A. Adjust gas input rate:
1. Consult gas supplier for higher heating value of gas (Btu/cu.ft.)
2. Set thermostat high enough so that boiler will remain on while checking rate.
3. Measure manifold pressure at 1/8" tapping. See label provided with the conversion kit for the correct manifold pressure for the gas that is being supplied. NOTE: Gas pressure may be adjusted by turning pressure regulator screw on combination gas valve (turn clockwise to increase pressure, counterclock wise to decrease pressure). See page 17 for the input rate of your boiler.
a. Input for PROPANE is approximately at rating shown on
rating plate when manifold pressure is 91/2" water column.
b. Input for NATURAL GAS is approximately at rating
when manifold pressure is 31/2" water column, but should be checked on the gas meter:
GAS VALVE VR8204 OR VR8304
GAS CONTROL KNOB SHOWN IN “OFF” POSITION
5. Remove control access panel. (Galaxy models only.)
6. Turn gas control knob clockwise till knob stops, continue to "OFF". DO NOT force.
7. Wait five (5) minutes (longer for propane) to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information. If you don't smell gas, go to next step.
8. Turn gas control knob counterclockwise to "ON".
9. Replace control access panel. (Galaxy models only.)
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
Btuh Input = Btu/cu. ft. x cu. ft. metered
in 3 minutes x 20
Example 1 For 1000 Btu/cu.ft. gas, this becomes: Btuh Input = cu. ft. metered in 3 minutes
Example 2 For 1050 Btu/cu.ft. gas, this becomes: Btuh Input = cu. ft. metered in 3 minutes
4. The higher* heating value of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Service Dept. for re-orificing procedures if any of the following apply: a. Boiler (burner) is overfiring. CAUTION! National
Fuel Gas Code ANSI Z223.1-latest edition does NOT permit firing at a higher input rate than the input rate indicated on the boiler rating plate in order to avoid hazardous conditions such as explosion or carbon monoxide poisoning.
b. Poor higher* heating value of gas is causing the actual
input to be substantially lower than
:
x 1,000 Btu/cu.ft. x 20
:
x 1050 Btu/cu.ft. x 20
the rating plate
indication.
* “Higher heating” value of gas is commonly known as “heating value”.
19
Page 20
GAS RATE TABLE
Cubic Feet
Boiler rated input Gas Consumption
cu. ft./hr. of 1000 Btu/cu. ft. 1000 Btu/cu.ft. gas, in 3
Natural Gas minutes, at rated input
33 1.65 34 1.70
60 3.00 70 3.50 75 3.75
90 4.50 100 5.00 105 5.25 120 6.00 125 6.25 140 7.00 150 7.50 175 8.75 180 9.00 200 10.00 210 10.50 225 11.25 245 12.25 250 12.50 275 13.75 300 15.00 325 16.25 350 17.50 375 18.75 399 19.95
The gas metered in 3 minutes to obtain rated input for each boiler model using 1000 Btu/cu.ft. gas is tabulated in the gas rate table.
B. Main Burner
1. Fire the boiler continuously for at least 15 minutes, to reach burner operating temperature.
2. Observe the flames, all burners. The base of all flame jets should be blue. The tips should be blue shading to orange. NOTE: Dust, disturbed by any movement, will cause bright orange flames. Wait for dust to settle.
3. For one burner, close the air shutter until some of its flame jet tips turn yellow-white, indicating insuf­ficient primary air. Then open shutter until whitish tips disappear completely. Set all burner shutters to the same opening. Observe to make sure that no yellow-white tips appear over any portion of the flame. Small yellow tips at the pilot location are permitted.
NOTE: This adjustment method gives MINIMUM primary air setting for safe combustion. DO NOT attempt to make this adjustment unless burners are at operating temperature. Adjustment should
e made with burner access panel in final operat-
b ing position. Use of a mirror may be helpful to observe flames. Note that burner ports are on top of main burner tube.
C.Main Burner Ignition Checkout and Pilot Adjustment
1. The pilot flame must not smother or snuff out when tested as follows: a. Main burner ignition from cold start-repeat. b. Continued operation of main burner. c. Main burner ignition with appliance at maxi
mum operating temperature after prolonged
operation. NOTE: Observe operation of the pilot burner with appliance doors in the final operating position. Use of a mirror may be helpful.
Flame Tips
Blue Flame Base
Main Burner
Manifold
Front-back sliding primary air shutter locking screw on top.
2. Safety Shutdown Checkout a. For proper operation the pilot should engulf the
thermocouple or flame sensor as shown below.
b. To adjust pilot, turn pilot flow adjustment screw
on valve clockwise or counterclockwise to give a steady flame enveloping 3/8" to 1/2" inch of the tip of the thermocouple or flame sensor. Note that turning the pilot adjustment screw clockwise will decrease the pilot flame.
Gas Pressure (inches of wc)
Gas Manifold Minimum Inlet Maximum Inlet Natural Gas 3.5” 5” 11” LP Propane 9.5” 11” 14”
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Loading...