Slant-Fin GALAXY GXHA, GALAXY GG, GALAXY GXH, GALAXY GX User Manual

Page 1
User’s Information Manual
Galaxy GG, GX, GXH & GXHA Series, Sentry S/SX Series
and Sentinel SE Series Gas Boilers with Continuous Pilot
FOR YOUR SAFETY:
• Before operating this boiler, READ this manual.
• DO NOT attempt to install, service or repair this boiler yourself. There are no user serviceable parts. Contact a qualified service agency if your boiler needs repair or maintenance. Ask your gas supplier for a list of qualified service agencies.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
DO NOT try to light any appliance.
DO NOT touch any electrical switch; DO NOT use any phone in your b
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
uilding.
DO NOT use this boiler if any part has been underwater. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been underwater.
WARNING
Should overheating occur or the gas supply fail to shut off, DO NOT turn off or disconnect the electric supply to the circulator pump. Instead, shut off the gas supply at a location EXTERNAL to the appliance.
— Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
If your boiler is purchased with or will be equipped with an automatic vent damper, make certain that the damper is installed and wired by a qualified installer who has been certified by your local gas utility. See Vent Dampers page 7. Keep the boiler area clean and free of all materials that can burn.
Never close or reduce openings that supply air for the boiler combustion and for ventilation.
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier. The lack of proper service can result in a dangerous condition.
Printed in U.S.A. 1005 PUBLICA
TION NO. GS-UIM-CBP
P
ar
t No.
41-1824
Page 2
Figure 1.
SENTRY “S” SERIES HOT WATER BOILER
W
ITH INTEGRAL DRAFT DIVERTER
Location and identification of parts
Figure 2.
Burners
Pilot
Burner Access Door
Front and Right End View
Models S-60 thru S-150
Base Assembly
Gas Valve
* Vent damper may be installed horizontally on all models with use of a common vent elbow.
See lighting instructions on pages 7-8.
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier
. The lack of proper service can result in a dangerous condition.
2
Page 3
Figure 9.
SENTINEL “SE” SERIES and
SENTRY “SX” SERIES HOT WATER BOILER
W
ITH EXTERNAL DRAFT HOOD
Location and identification of parts
Figure 10.
Burners
Pilot
Burner Access Door
Base Assembly
Front and Right End View
MODELS SX-150 to SX-210 and SE-70 to SE-245
* Vent damper may be installed horizontally on all models with use of a common vent elbow.
Gas Valve
See lighting instructions on pages 7-8.
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier
. The lack of proper service can result in a dangerous condition.
3
Page 4
igure 14.
F
J
Name and
Rating Plate
Lighting
Instructions
(inside front
p
anel)
Gas Valve
B
urner
Access Door
Burners
Figure 15.
GALAXY GG/GX GXHA SERIES HOT WATER AND STEAM BOILER
L
ocation and identification of parts
Relief Valve
acket Top
Temperature and Pressure Gauge
Gas Manifold
Pop Safety Valve
Jacket Top
Figure 16 GXHA Ser
Pop Safety Valve
Jacket Top
Pressure Gauge
ies—Steam Boiler
Pressure Gauge
Figure 17.
Front Panel
Easy access front panel on standard extended jacket, is removed by simply pressing hand against panel and pushing up.
See lighting instructions on page 8.
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier. The lack of proper service can result in a dangerous condition.
4
Page 5
Inspection, cleaning, repair—
Chimney, flue pipe and boiler
Your boiler and heating system will last an indefinitely long time at full efficiency, if it is inspected regularly and is kept in good repair and adjustment.You, the user, should make regular inspections, and report any prob­lems to your service agency. At regular intervals, you should have that agency inspect the system, and clean
he boiler and make repairs and adjustments as neces-
t sary. What you and the service agency should do are listed below. Contact your gas supplier for a list of qualified service and repair agencies.
User inspection
At least once each month during the heating season and once just before cold weather starts:
(1) Look closely at the smokepipe and draft hood (see
Figure 18, 19 & 20). Make sure pipe joints are snug and are fastened with screws. Cement at the chim­ney joint should fill the joint and should not leak air. There should be no visible signs of rust (corrosion) or salts from water evaporation.
(2) Look at all water (or steam) piping. There should be
no leaks or signs of leaks at any pipe joints or around the boiler. Drain valves, other valves, and the relief valve (or steam safety valve) should not drip or leak.
(3A) On water boilers:
The temperature and pressure gauge indicates the pressure in the boiler at each water temperature. For most installations, it should indicate about 12 to 15 psi pressure when temperature is about 70 to 100 degrees F, and from 15 psi to 25 psi when tem­perature is up to 240 degrees F. FOR YOUR SYS­TEM, there is one correct pressure for each temper­ature
. ASK YOUR INSTALLER OR SERVICEPER­SON TO EXPLAIN AND SHOW YOU. Learn what normal pressures to look for. If pressure decreases from nor
mal, your system is losing water
. If pres-
ure rises from normal, the relief valve will open to
s relieve the pressure. Call your service organization if pressures are higher or lower than normal, and if
he relief valve spills water. Repair or adjustment is
t
eeded.
n (3B) On steam boilers: (a) The water level in the gauge glass must be kept
constant. You must have your installer or service
organization explain to you how water is added to
maintain water level. (b) Most boiler models are equipped with float type low
water cutoff.
You must be familiar with this LOW WATER CUT-
OFF, how it works and HOW TO BLOW IT DOWN.
Instructions are supplied with it. Ask your service
organization to e
The cutoff should be blown down three times the
first week and should be blown down weekly there-
after. Maintenance of the low water cutoff is vital in
protecting your steam boiler against breakage due
to loss of water.
If your boiler is equipped with an electronic probe
type low water cutoff, it requires periodic testing.
Ask your service agency to test this low water cutoff
twice a year. (4) Study the labels attached to your boiler, especially
the LIGHTING AND SHUTDOWN instructions. Have
your installer or service organization show you how
to start and shut down the boiler following those
instructions. The lighting instructions on your boiler
are also reproduced, with pictures, in this manual. (5) Stand near the boiler, look and listen. As the burners
start and shut off, there should be no unusual noise.
No fire should be visible coming out of the front
when the burners start or run. (6) Ample air is required for your boiler to burn fuel
cleanly and safely. Check to make sure the open-
ings provided in your house are not closed and are
not obstructed. This is most important in colder
weather, when most air is needed.
xplain and show you blowdown.
Figure 18. (Galaxy GG, GX, GXH,
Sentinel SE, Sentry SX boilers)
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier. The lack of proper service can result in a dangerous condition.
Figure 19.
Figure 20.
5
Page 6
(7) If equipped with vent damper, which can ONLY be
installed on boilers equipped with 24 volt gas valve:
(a) Your vent damper must be OPEN when the boiler is
operating (BURNERS ARE ON). Ask your installer or serviceperson to show you the vent damper posi­tion indicator, indicating the open and closed damper positions. Inspect for proper operation monthly. If damper position indicator indicates that the damper is closed when the boiler is operating, SHUTDOWN the boiler immediately and call your service agency.
(b) This device must be installed and inspected annually
by a qualified installer in accordance with the Slant/Fin vent damper installation instructions. If improperly installed, a hazardous condition such as explosion or carbon monoxide poisoning could result. If installed improperly, all vent damper and boiler warranties shall be voided.
If you find during your inspection any unusual noise, water leak, corroded smokepipe, abnor­mal water pressure or flame rollout, call for service immediately.
SERVICE INSPECTION
The selected service organization should make these inspections, pref weather begins: (1) Make the checks for leaks, corrosion, noise, flame,
heat and outside air supply described under User’s Inspection.
(2) Check safety operation of the HIGH LIMIT CON-
TR
OL (and, for steam boilers, the LOW WATER
CUT
OFF) and GAS VALVE. If the boiler is equipped with an automatic vent damper, check this device for saf
e and automatic operation.
(3) Check gas input rate, by clocking the gas meter.
Inspect burner flame. Clean and adjust burners and adjust gas rate as required.
(4)
Disconnect flue pipe from draft hood. Remove draft hood and inspect boiler heating surface below. If any soot, scale or rust is visible, clean the boiler as described in the next section.
erably once each year, before the cold
Figure 21.
CLEANING—BOILER, SMOKEPIPE, CHIMNEY
in (4) of Service Inspection section, the selected service organization should clean the boiler as follows: (1) Shut off electric power and gas supply.
(2) Disconnect smokepipe and remove draft hood.
(3) Remove jacket top panel. Remove flue cover
from boiler.
(4) Remove access door and remove burners, or place
cover over burners for dirt protection.
(5) Brush down boiler flues to bare metal. Clean all
debris from bottom of boiler after brushing. Clean b
(6) Replace flue cover and seal with furnace cement.
Replace burners if removed. Replace access door.
(7) Inspect draft hood and smokepipe. If corroded,
replace. If soot or deposits from condensation are found, clean out, and inspect inside of chimney for soot or other deposits. Clean if necessary.
(8) Reconnect hood and flue pipe and fasten and seal
all joints. Turn on gas and electric power.
(See Figure 21). If necessary as indicated
urner slots, if necessary.
(5) Replace any corroded smokepipe. Repair or re-
place other devices as found necessary. Check and adjust for normal operation. Explain to the user what was done and what to look for to prevent fu­ture problems.
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier. The lack of proper service can result in a dangerous condition.
(9) Check boiler performance after cleaning, and adjust
as necessary.
NOTE: Condensate (water), rust, scale and soot are not found in the boiler or smokepipe of normally operating system. If any of these is found, eliminate the cause. The most likely cause of condensate and corrosion or soot is (a) restr
6
icted air supply, or (b) a faulty chimney.
Page 7
VENT DAMPERS
A Slant/Fin vent damper is available only as part of a Slant/Fin gas boiler package equipped with a 24 volt gas valve.This vent damper is design certified by A.G.A.
or use only on specific Slant/Fin Corporation gas boiler
f
odels.
m
These boilers will be equipped with a plate which states that the boiler may be used with a Slant/Fin Corp. auto­matic vent damper device and indicates the proper vent damper model number.
OTHER VENT DAMPER OR DEVICES WITH SIMILAR PURPOSE ARE NOT PERMITTED.
WITH ANY VENT DAMPER OR PILOT SYSTEM
(a) DO NOT attempt to install or adjust or service it
yourself.
(b) Make certain that the installation is approved by your
local gas utility.
IGNITION SYSTEM—CONTINUOUS BURNING (STANDING) PILOT
Your gas boiler is equipped with the Honeywell VR8200 or VR8300 gas valves. See Safety and Lighting Instructions on pages 7 and 8 and Figure 22.
SAFETY AND LIGHTING INSTRUCTIONS
FOR IGNITION SYSTEMS EQUIPPED WITH GAS
VALVES VR8200 AND VR8300
SAFETY INFORMATION
For Your Safety Read Before Lighting
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these instruc­tions e
xactly.
Figure 22. Continuous (Standing) Pilot
Ignition System
WARNING
Should overheating occur or the gas supply fail to shut off, DO NOT turn
off or disconnect the electric supply to the circulator pump. Instead,
shut off the gas supply at a location EXTERNAL to the appliance.
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier. The lack of proper service can result in a dangerous condition.
7
Page 8
B. BEFORE OPERATING smell all around the appli-
ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electric switch; DO NOT use
ny phone in your building.
a
• Immediately call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in or turn the gas control
knob. NEVER use tools. If the knob will not push in or turn by hand, DON’T try to repair it, call a quali­fied service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information on page 7 and above.
2. Set the thermostat to lowest setting.
3. Turn off all electrical power to the appliance.
4. Remove control access panel. (Galaxy models only.)
5. Turn gas control knob clockwise to “OFF”.
7. Remove the pilot access panel located below and behind the gas control unit.
8. Find pilot, follow metal tube from gas control. The pilot is between two burner tubes behind the pilot access panel.
9. Turn knob on gas control counterclockwise to “PILOT”.
10. Push in red button all the way and hold in. Immediately light the pilot with a match. Continue to hold the red button in for about one (1) minute after the pilot is lit. Release button and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 10.
• If button does not pop up when released, stop
and immediately call your service technician or gas supplier.
• If the pilot will not stay lit after several tries, turn
the gas control knob to “OFF” and call your service technician or gas supplier.
11. Replace pilot access panel.
12. Turn gas control knob counterclockwise to “ON”.
13. Replace control access panel. (Galaxy models only.)
14. Turn on all electric power to the appliance.
15. Set thermostat to desired setting.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance, if service is to be performed.
3. Remove control access panel. (Galaxy models only.)
4. Turn gas control knob clockwise to “OFF”. DO NOT force.
5. Replace control access panel. (Galaxy models only
.)
6. Wait five (5) minutes (longer for propane) to clear out any gas, then smell for gas, including near the floor. If you then smell gas safety information above on this page, if you don’t smell gas, go to next step.
STOP! Follow “B” in the
Your gas boiler must be installed and serviced by a qualified service agency or
gas supplier. The lack of proper service can result in a dangerous condition.
©Slant/Fin Corp. 2004.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
These boilers are equipped with both a blocked vent saf
ety switch and a rollout safety s vent safety switch is located on the draft hood flue stack. This is a manual reset control used to prevent excessive spillage of flue gases from the draft hood. The rollout safety switch is a single use (one time) thermal fuse to prevent the boiler from operation if flue passages are b
locked. If either of these devices operate to shut down the burners, follow instructions in the section “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
witch. The blocked
www.slantfin.com
Loading...