Slant/Fin Galaxy GG-300 Installation And Operating Instructions Manual

Page 1
CONTENTS..........................................................................PAGE
Dimensions ..................................................................................2
Gas Orifice Sizes ........................................................................2
Installation Requirements:
Boiler Location ........................................................................3
Boiler Foundation....................................................................3
Chimney Requirements ..........................................................3
Minimum Clearance ....................................................................4
Vent Piping ..............................................................................4
Gas Piping ..................................................................................4
Boiler Room Air Supply and Ventilation ..................................5
Draft Hood Installation ............................................................5
Piping at Boiler—Water Boilers ..............................................5
Vent Damper Installation ........................................................6
Operating Instructions..................................................................7
Filling and Venting Water Systems..........................................7
Initial Start, Safety & Lighting Instructions ..............................8
Controls, Safety Check ..........................................................9
Care and Maintenance ................................................................9
Safety Check for Control System ..........................................10
Protection From Freezing......................................................10
Water Treatment....................................................................10
Sequence of Operations ............................................................11
Wiring Diagram ..........................................................................12
Trouble Shooting Guide ............................................................13
Piping a Heating and Cooling System ......................................14
Replacement Parts ....................................................................14
Appendix A ................................................................................15
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS
AND STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE FIRED GAS BOILERS
Installation location ONLY as permitted in paragraph entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE GAS FIRED BOILER LOCATION" on page 3 of this instruction book. The above warning does not apply to NATURAL gas fired boilers.
The installation must conform to the requirements of the authori­ty having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed, con­nected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
HOT WATER—Models GG-300 through GG-399HES
INSTALLATION AND OPERATING INSTRUCTIONS
GALAXY
GAS-FIRED CAST IRON BOILERS FOR NATURAL
AND L.P. PROPANE GASES
INTERMITTENT PILOT IGNITION
Printed in U.S.A. 1115 PUBLICATION GG-40S
Part No. 41-2842
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
CANADIAN ENERGY
PERFORMANCE
VERIFIED
RENDEMENT
ENERGETIQUE
VERIFIE
Page 2
2 GALAXY
ORIFICE SIZES indicated for Sea Level are
factory installed in boiler unless otherwise specified by the local authority. See VII, page 8 for burner input adjustment. GAS VALVE CONNECTION Size may be 3/4" or 1/2" depending upon configuration (natural, L.P.). COMBUSTIBLE FLOOR KIT increases all height dimensions by 1". RAISED SLAB - When mounting boiler on a raised slab, the slab must extend at least 2" beyond the boiler cabinet on all sides. CHIMNEY HEIGHT: 15 FT. Minimum from draft hood skirt to top of chimney. CHIMNEY INSIDE DIAMETER must be same as Dimension “C” or larger. Larger diameter &/or height may be required if two or more boilers or a boiler and another appli­ance are vented to a single chimney.
ORIFICE SIZES AT HIGH ALTITUDES
INCLUDES 4% INPUT REDUCTION FOR EACH 1000 FEET
ELEVATION — FEET
BOILER MODEL
GG
Except GG-399H
GG-399H
GAS TYPE
Natural Propane
Natural Propane
Orifice
Size for
Sea Level
41 54
40 53
42 54
41 54
42 55
42 54
42 55
42 54
43 55
42 54
43 55
43 54
44 55
43 54
44 56
44 55
45 56
44 55
46 56
45 55
2,000
3,000
4,000
5,000
6,000 7,000 8,000 9,000 10,000
A B C D E F G
H J K
GG-300
33-1/4 26-3/4
8
59-5/8
17
14-3/4
1-1/2 1-1/2
2-3/4 9-1/4
GG-325
33-1/4 26-3/4
8
66-1/8
17
14-3/4
1-1/2 1-1/2
2-3/4 9-1/4
GG-350
36-1/2
30
9 66-1/8 22-1/2 16-1/4
1-1/2 1-1/2
2-3/4 9-1/4
GG-375H
36-1/2
30
9
59-5/8
15
16-1/4
1-1/2 1-1/2
2-3/4 9-1/4
GG-399H
36-1/2
30 10
66-5/8
22
16-1/4
1-1/2 1-1/2
2-3/4 9-1/4
GG SERIES HOT WATER BOILERS - DIMENSIONS IN INCHES
FRONT VIEW
LEFT SIDE FRONT VIEW
RIGHT SIDE
RIGHT SIDE
DIMENSIONS
Page 3
GALAXY 3
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the author­ity having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition.
This installation must also conform to the additional require­ments in this Slant/Fin instruction book. Installation and service to be performed by a qualified installer, service agency or the gas supplier.
NATURAL GAS FIRED BOILER LOCATION—
Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
Automatic gas ignition system components shall be installed so these components will not be subjected to dripping water during installation or service.
CHIMNEY REQUIREMENTS—
A. Galaxy boilers may be vented into a masonry vitreous tile-
lined chimney or UL LISTED type “B” venting system NOT EXPOSED to the OUTDOORS below the roof line. Venting and sizing of venting system must be in accordance with Part 7, Part 11 and Appendix G of the National Fuel Gas Code ANSI Z223.1, NFPA 54, -latest edition which will be referred to as the National Fuel Gas Code. Local codes apply. If a masonry chimney is exposed to the outdoors on one or more sides below the roof line (exterior chimney), ONE of the following options apply:
1. Chimney must be re-lined with a UL LISTED metallic liner. When this is done, the chimney will be considered NOT exposed to the outdoors and the requirements of the National Fuel Gas Code for NON-exposed chimneys and/or local codes will apply.
2. If an exposed tile-lined chimney is to be used WITHOUT a
UL LISTED metallic liner, the boiler must meet the require­ments of the National Fuel Gas Code:
B. If an existing boiler is removed from a common venting sys-
tem, the common venting system may be too large for prop­er venting of the remaining appliances connected to the common vent. Follow the test procedure shown in Appendix "A" on page 15 of this manual to insure proper operation of venting system and appliances.
C. Inspect for proper and tight construction. Any restrictions or
obstructions must be removed. An existing chimney may require cleaning.
D.Chimney or vent must extend at least 3 feet above its pas-
sage through a roof and at least 2 feet above any ridge within 10 feet of the chimney.
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of supporting the
weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boilers,
page 2. B. For installation on non-combustible floors only.* C. If boiler is to be located over buried conduit containing elec-
tric wires or telephone cables, consult local codes or the
National Board of Fire Underwriters for specific require-
ments.
* The Combustible Floor Kit part number printed on the boiler rating plate is
the only one to be used when installing on combustible floors. The boiler must not be installed on carpeting.
WARNING
SPECIAL ATTENTION FOR LIQUEFIED PETROLEUM
(L.P.) PROPANE GAS-FIRED BOILER INSTALLATIONS
LPG appliances (boilers) shall be installed in accordance
with applicable provisions of NFPA 58 ( Liquefied Petroleum
Gas Code) latest edition for installations in US and
CAN/CGA B149.1 latest edition for installations in Canada.
Liquefied Petroleum (LP) propane gas is heavier than air
therefore Propane gas accumulate at floor level. If you sus-
pect a leak, do not attempt to operate boiler. A spark or
flame from the appliance (boiler) or other sources may ignite
the accumulated propane gas causing an explosion or fire.
It is recommended that inspections for gas leaks be per-
formed periodically by licensed professional and that leak
detection devices be installed as a further safety measure.
Page 4
4 GALAXY
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
A. Minimum boiler clearances shall be as follows:
B. Provide accessibility clearance of 24" on sides requiring ser-
vicing and 18" on sides used for passage. C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clearances
in order to maintain the minimum clearances of others. D. Clearance from steam and hot water pipes shall be 1". **
** At points where hot water or steam pipes emerge from a floor, wall or ceil-
ing, the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2". Each such opening shall be covered with a plate of noncombustible material.
SAFETY—
KEEP THE BOILER AREA CLEAR AND FREE FROM
COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.
VENT PIPING—
A. Vent piping installation must be in accordance with ANSI
Z223.1-latest edition, National Fuel Gas Code, Part 7,
Venting of Equipment. Other local codes may also apply
and must be followed. B. Boiler vent pipe must be the full diameter of the boiler draft
hood outlet. See dimensions, page 2. If a vent damper is
added, its diameter must be equal to the hood outlet and
must be located past the hood outlet. See installation
instructions furnished with vent damper and in the section
"Vent Damper Installation" of this instruction book. C. If more than one appliance vents into a common breeching,
the area of the breeching must be equal to the area of the
largest vent plus 50% of the area of the additional vent
areas. Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of mechanical
draft systems operating under positive pressure. Horizontal
breeching or vent pipe should be as high as possible, con-
sistent with codes, so that vertical vents from appliances will
have a high rise above draft diverter openings. All horizontal-
runs must slope upwards not less than 1/4 inch per foot of
run. Horizontal portions of the venting system must be sup-
ported to prevent sagging by securing each joint with metal
screws and by providing hangers spaced no greater than 5
feet apart. D. Vent or breeching into chimney should not be inserted past
the inside wall of the chimney liner. E. All venting means should be inspected frequently. See Care
and Maintenance and separate User's Information Manual.
GAS PIPING—
A. Local installation codes apply. The pipe joint compound used
on threads must be resistant to the action of liquefied petro­leum gases.
B. The gas supply line to the boiler should be run directly from
the meter for natural gas or from the fuel tank for L.P. propane gas. See page 2 for location of union and manual main shut-off valve that may be specified locally. Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (BTU/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow
in piping (cu. ft. per hour).
4. Use table below to select proper pipe size.
Example: Boiler model GG-300 is to be installed. Distance from gas meter to the boiler is 50 ft. Heating value of natural gas is 1020 BTU/cu. ft. Select proper pipe size.
At 50 ft. length of pipe, match required capacity from table below (choose higher capacity, in this case is 440 cu. ft. per hour). Required pipe size is 1-1/4". Improper gas pipe sizing will result in pilot flame outages, insufficient heat and other installation difficulties. For more information and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested before
placing the boiler in operation. Use liquid soap solution for all gas leak testing. Do not use open flame. This boiler and its individual shut-off valve must be discon­nected from the gas supply piping system during any pres­sure testing of that system at test pressures in excess of 1/2 PSIG. This boiler must be isolated from the gas supply piping sys­tem by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap must be provid­ed, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
1/2 3/4 1 1-1/4 1-1/2
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Length of Pipe in Feet
Gas Flow In Piping -- cu. ft. per hr.
Iron Pipe Size (Ips)—inches
Gas flow = 300,000 BTU/hour = 294 cu. ft. per hour
1020 BTU/cu. ft.
GALAXY GG SERIES
MODELS GG-300 THROUGH GG-399H. MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUCTION. MINIMUM ALCOVE CLEARANCE.
Front ..............................................................Alcove
Rear ......................................................................6"
Left Side................................................................6"
Right Side..............................................................6"
Top ......................................................................36"
Flue Connector......................................................6"
Type 'B' Vent..........................................................1"
Page 5
GALAXY 5
ELECTRICAL WIRING
DANGER: Before wiring, always turn off electric power supply, otherwise shock or death can result.
Power Supply
A separately fused circuit is recommended. Use a standard 15 Amp. fuse or breaker and 14 gauge conductors in BX cable or circuit.Provide disconnect means and overload protec­tion as required. See boiler wiring diagram (Figure 6). Boiler must be electrically grounded in accordance with requirements of the authority having jurisdiction, or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required to obtain combustion and ventilation. Room temperature over 100°F may cause nuisance tripping of the Blocked Vent Safety Switch.
ALL AIR MUST COME FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around windows, doors, etc. in the whole building. When buildings are insulated, caulked and weather-stripped, now or later on, direct opening to outside may be required and should be provided. If the boiler is not on an outside wall, air may be ducted to it from outside wall openings.
The National Fuel Gas Code, ANSI Z223.1-latest edition speci­fies openings for air under various conditions. Local codes may
specify minimum opening sizes and locations. The following recommendation applies to buildings of energy-saving construc­tion, fully caulked and weather stripped:
Provide one GRILLED opening near the floor and one near the ceiling on an outside wall near the boiler (or duct from such openings to the boiler), EACH opening to be a minimum of one square inch per 2000 Btuh input to ALL APPLIANCES in the area. For a total appliance input of 200,000 Btuh, each open­ing will be 100 square inches. A grilled opening 10" x 10" has 100 square inches of area. If fly screen must be used over openings, double the area and inspect and clean the screen frequently.
Openings must NEVER be reduced or closed. If doors or win­dows are used for air supply, they must be locked open. Protect against closure of openings by snow and debris. Inspect frequently.
NO MECHANICAL DRAFT EXHAUST OR SUPPLY FANS ARE TO BE USED IN OR NEAR THE BOILER AREA.
The flow of combustion and ventilating air to the boiler must NOT be obstructed.
DRAFT HOOD—
The draft hood supplied is part of the listed boiler assembly. DO NOT alter the hood. See dimensions, page 2.
Attach the hood to the boiler flue outlet. Connect flue pipe full size of hood outlet. If a vent damper is added, it must be installed on the outlet side of the hood. See Vent Piping,
PIPING AT BOILER — WATER PIPING
I. CIRCULATING SYSTEMS
A.Packaged water boilers are equipped with a water circulat-
ing pump, mounted to return the water into the boiler. For some installations, the pump should be on the supply main. See PUMP LOCATION.
II. AIR CONTROL SYSTEM
A.DIAPHRAGM-TYPE COMPRESSION TANKS are used to
control system pressure in an AIR ELIMINATING SYS­TEM: an automatic air vent is used to REMOVE air from the system water. See illustration. If system pressure needs further control, add an additional tank or install a larger capacity tank. Locate the tank near the boiler, as illustrated.
An automatic air vent should be installed in the top of the boiler. See illustration.
B.PUMP LOCATION — Locating low-head pump(s) on
return to boiler is acceptable for smaller boiler sizes in residences of one or two stories. The alternate pump location shown in illustration, is required in large, multi­story building installations, especially when high-head pumps are used. The compression tank must be at the boiler or between boiler and supply main pump(s).
C.On a hot water boiler installed above radiation level,the
boiler must be provided with a low water cut-off device at the time of installation by the installer.
Page 6
6 GALAXY
VENT DAMPER INSTALLATION
The vent damper referred to in the following instructions is the Slant/Fin Corporation vent damper. I. This device is design certified by C.S.A. for use ONLY on
specific Slant/Fin Corp. gas boiler models. These boilers must also be equipped with a plate which states that the boiler must or may be used with a Slant/Fin Corp. automatic vent damper device and indicates the proper vent damper model number.
II. A.INSTALLATION INSTRUCTIONS BEFORE YOU START
TO INSTALL
1. Read this installation manual, the "DANGER" plate attached to the top of the boiler, the "WARNING" on the wiring diagrams, vent damper carton and operator cover.
2. Perform pre-installation inspection as required by ANSI specification Z21.66.
3. Turn off all electrical power, gas supply and wait for sys­tem to cool (for previously installed boilers).
4. Select a proper, convenient location (see figures 1 & 2).
5. Carefully unpack the unit. DO NOT FORCE IT OPEN OR CLOSED! Forcing the damper may damage the gear train and void the warranty.
WARNING—DANGER
Once you have begun vent damper installation procedure, DO NOT restore electric power and gas supply until installation and inspection have been completed (in order to prevent the main burners from operating). DO NOT operate the boiler until the vent damper harness "RECEPTACLE B" is plugged into "MALE PLUG" (as described in the installation instructions), and the vent damper installation and checkout procedures have been completed. Failure to observe this warning may create a haz­ardous condition that could cause an explosion or carbon monoxide poisoning.
B.1. This device must be installed after the appliance draft
hood (between the draft hood outlet and the connector to the outdoor chimney or vent) as close to the draft hood as practicable, and without modification of the draft hood or the damper. (See figures 1 & 2.)
2. The inlet size of the vent damper must be the same nominal trade size as the outlet of the draft hood.
3. This device must be located in a venting system or sec­tion of a venting system so that it serves only the single appliance for which it is installed. (See figure 3.)
4. Clearances of not less than 6 inches (152MM) must be maintained from combustible materials, with provisions for access for service.
C.NOW, PROCEED AS FOLLOWS:
1. Remove the front cover of the boiler exposing the wiring compartment. With all electrical power to boiler off, locate "MALE PLUG" and "Receptacle A" (see wiring diagram attached to boiler); a copy of this may also be found in this manual. Cut the RED wire connected between numbers 3 and 4 of "RECEPTACLE A" (the only wire connected to this receptacle) and then disconnect "RECEPTACLE A" from "MALE PLUG". Remove "RECEPTACLE A" from job site and discard.
2. Separate the vent pipe directly on top of the draft hood and place damper in position as shown in figures 1& 2. The vent damper must be installed so that the damper position indicator is in a visible location after installation. The arrow imprint on the damper should point in direc-
Figure 1. Vertical installation of vent damper on Galaxy Boilers
Figure 2. Horizontal or sloping installation of vent damper
* Install operator in any position as shown above. DO NOT install the operator above the vent pipe (to avoid excessive heat) or below the vent pipe (to avoid possible condensation damage).
Galaxy
Boiler
Page 7
GALAXY 7
tion of vent gas flow (towards chimney). Re-assemble the vent piping. Be sure the vent damper is well seated and fastened with 3 sheet metal screws. Screws should be no longer than 1/2 inch. See figure 3.
3. Boilers that may have vent damper are factory wired with plug and "RECEPTACLE A". To install the vent damper all that is required is removal of the "RECEPTA­CLE A" and connection of the vent damper harness to the boiler plug. Boilers that must have a vent damper are factory wired with plug only. (Remove "RECEPTA­CLE A" from job site and discard.) a)Attach the flexible metallic conduit vent damper har-
ness to the right hand side of the jacket by passing the free end of the harness through the 7/8 diameter hole in the top of the jacket, and using the BX con­nector at the free end of the metallic conduit, fasten to jacket.
b)Connect "RECEPTACLE B" (free end of vent damper
harness) into "MALE PLUG" (see wiring diagram).
4. Restore electrical power and turn on gas supply.
D.AFTER INSTALLATION:
1. Operate system through two complete cycles to check for opening and closing in proper sequence, and proper burner operation. DAMPER MUST BE IN OPEN POSI­TION WHEN BOILER MAIN BURNERS ARE OPERAT­ING.
2. Perform installation checks as required by ANSI specifi­cation Z21.66.
3. Replace the front cover of the boiler.
4. Check the trouble-shooting section if problems arise with the installation.
E.THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS
If the 24v room thermostat that controls this boiler has an adjustable heat anticipator, connect entire system to thermostat and run the system while measuring the current drawn through the thermostat wires. Set the heat anticipator at the value measured. The set current should match power requirements by zone valves and relays. Add an additional
0.1 Amp to the measured currrent for vent damper. Refer to
the manufacturer’s instruction of zone valve, vent damper and relays. Also, see instructions with the thermostat.
Figure 3.
OPERATING INSTRUCTIONS, BASIC
Before firing boiler, make these checks:
1. Relief valve is installed. Installation of the relief valve shall be consistent with the ANSI/ASME Boiler Pressure Vessel Code. Valve opening is NOT closed or reduced in size.
2. Draft hood is installed and vented to chimney.
3. All wiring is completed, following wiring diagram.
4. If a vent damper is added, damper is in full open posi­tion. See instructions furnished with vent damper.
5. Using soap solution, check for gas leaks in all gas piping from meter to boiler pilot and manifold. DO NOT use open flame.
FILLING AND VENTING WATER SYSTEMS
A.Fill the system with water. Vent or purge off air. B.Fire the boiler as soon as possible (see following warning
and instructions) and bring water temperature to at least 180 degrees, while circulating water in the system.
C.Vent air and add water as needed to achieve operating
pressure on boiler gauge. Pressure must be between approximately 12 psi (cold water) and 25 psi (at water temperature setting of high limit control), for boilers equipped with 30 psi relief valves. Boilers rated for a high­er pressure and equipped with a matching relief valve may operate at a higher pressure, but no higher than 5 psi below the relief valve opening pressure.
D.Check for and repair any leaks before placing system in
service. Make sure that none of the automatic gas ignition system components are exposed to water.
Page 8
8 GALAXY
BURNER ADJUSTMENT
A.Adjust gas input rate:
1. Consult gas supplier for heating value of gas (Btu/cu.ft.).
2. Set thermostat high enough so that boiler will remain on
while checking rate.
3. Measure manifold pressure at 1/8" tapping. Correct
manifold pressure for gas used is printed on boiler rat­ing plate. NOTE: Gas pressure may be adjusted by turning pressure regulator screw on combination gas valve (Turn clockwise to increase pressure, counter clockwise to decrease pressure). a. Input for PROPANE is approximately at rating shown
on rating plate when manifold pressure is 9-1/2" water column.
b. Input for NATURAL GAS is approximately at rating
when manifold pressure is 3-1/2" water column, but should be checked on the gas meter: Btuh Input = Btuh/cu. ft. x cu. ft. metered in 3 minutes
x 20
SAFETY INFORMATION
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which
automatically lights the pilot. DO NOT try to light the pilot by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electric switch; DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire depart­ment.
C. Use only your hand to push in or turn the gas control knob.
NEVER use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Operating Instructions
1. STOP! Read the safety information on this page.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
5. Remove control access panel.
6. Turn gas control knob clockwise to "OFF". Do NOT force.
7. Wait five (5) minutes (longer for propane) to clear out any gas, then smell for gas, including near the floor. If you then smell gas, STOP! Follow "B" in the safety information on this page. If you don't smell gas, go to next step.
8. Turn gas control knob counterclockwise to "ON".
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
FIGURE 4. INTERMITTENT PILOT (IID) SYSTEM FOR BOILERS
EQUIPPED WITH HONEYWELL GAS VALVE VR8204 & VR8304 (see figures 4 & 5).
FIGURE 5. Gas Valve VR8204 & VR8304
To Turn off gas to appliance
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
4. Turn gas control knob clockwise to "OFF". Do NOT force.
5. Replace control access panel.
Page 9
GALAXY 9
C. Main Burner Ignition Check-out and Pilot Adjustment
1. The pilot flame must not smother or snuff out when tested as follows:
a. Main burner ignition from cold start-repeat. b. Continued operation of main burner. c. Main burner ignition with appliance at maximum operating
temperature after prolonged operation. NOTE: Observe operation of the pilot burner with appli­ance doors in the final operating position. Use of a mirror may be helpful.
2. Safety Shutdown Check-out
a. Make certain the pilot burner holds in, and opens properly,
when the pilot is burning normally; and that safety shut­down occurs within 2-1/2 minutes after the pilot flame is extinguished. Observe operation for at least one cycle under automatic control to be sure the system is function­ing normally.
b. For proper operation the pilot should engulf the flame sen-
sor as shown below.
c. To adjust pilot, turn pilot flow adjustment screw on valve
clockwise or counterclockwise to give a steady flame enveloping 3/8" to 1/2" of the tip of the flame sensor. Note that turning the pilot adjustment screw clockwise will decrease the pilot flame.
d. Check safety shutdown of gas valve by following proce-
dure outlined "CARE AND MAINTENANCE" section.
CONTROLS, SAFETY CHECK Check all safety controls not previously mentioned. Also, follow directions in "CARE AND MAINTENANCE" section, paragraphs IV through VII.
These boilers are equipped with both a draft hood blocked vent safety switch and a rollout safety switch. The blocked vent safety switch is located on the draft hood flue stack. This is a manual reset control used to prevent excessive spillage of flue gases from the draft hood. The rollout safety switch is a single use (one time) thermal fuse to prevent the boiler from operating if flue passages are blocked. If either of these devices shut down the burners, fol­low instructions in the section "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
CARE AND MAINTENANCE
WARNING: THE FLOW OF COMBUSTION AND VENTILATING AIR TO THE BOILER SHOULD NOT BE OBSTRUCTED.
This section must be brought to the attention of the owner by the installer so that the owner can make the necessary arrangements with a qualified service agency for the periodic care and mainte­nance of this boiler. The installer must inform the owner that the gas supplier can recommend a number of qualified service agen­cies. The installer must also inform the owner that the lack of prop­er care and maintenance of this boiler and any fuel burning equip­ment may result in a hazardous condition.
(Continued on next page)
300 15.00 325 16.25 350 17.50 375 18.75 399 19.95
Boiler rated input in
cu. ft./hr. of 1000 Btu/cu.ft.
Natural Gas
Cubic Feet Gas Consumption
1000 Btu/cu. ft. gas, in 3 min-
utes, at rated output
B.Main Burner
1. Fire the boiler continuously for at least 15 minutes, to reach burner operating temperature.
2. Observe the flames, all burners. The base of all flame jets should be blue. The tips should be blue shading to orange. NOTE: Dust, disturbed by any movement, will cause bright orange flames. Wait for dust to settle.
3. For one burner, close the air shutter until some of its flame jet tips turn yellow-white, indicating insufficient primary air. Then open shutter until whitish tips disappear completely. Set all burner shutters to the same opening. Observe to make sure that no yellow-white tips appear over any portion of the flame. Small yellow tips at the pilot location are per­mitted.
NOTE: This adjustment method gives MINIMUM primary air setting for safe combustion. DO NOT attempt to make this adjustment unless burners are at operating temperature. Adjustment should be made with jackets in final operating position. Use of mirror may be helpful to observe flames. Note that burner ports are on top of main burner tube.
Example #1: For 1000 Btu/cu. ft. gas, this becomes: Btuh Input = cu. ft. metered in 3 minutes x 1000
Btu/cu.ft. x 20 Example #2: For 1050 Btu/cu. ft. gas, this becomes: Btuh Input = cu. ft. metered in 3 minutes x 1050
Btu/cu.ft. x 20
4. The higher* heating value of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Service Dept. for re-orificing procedures if any of the fol­lowing apply: a. Boiler (burner) is overfiring. CAUTION! National Fuel
Gas Code (ANSI Z223.1-latest edition) does NOT permit firing at a higher input rate than the input rate indicated on the boiler rating plate in order to avoid hazardous conditions such as explosion or carbon monoxide poisoning.
b. Poor higher* heating value of gas is causing the actu-
al input to be substantially lower than the rating plate indication.
* “Higher heating value” of gas is commonly known as “heating value”
GAS RATE TABLE
The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu. ft. gas is tabulated in gas rate table.
Page 10
10 GALAXY
I. GENERAL MAINTENANCE
These operations are recommended to be performed at regular intervals: A.BOILER HEATING SURFACES: clean off all coatings found. B.BOILER CONTROLS: check contacts, settings, correct func-
tioning. C.PIPING: check piping and accessories for leaks. D.CHIMNEY and BREECHING: check for obstructions and
leaks. E.BOILER ROOM AIR SUPPLY: check air vents for continued
POSITIVE supply of air as required. Air needs are greatest in
cold weather. Air vents must be open and free of obstruction. F. WATER SYSTEM: check
1. System to be full of water, and pressure to remain stable at correct setting on gauge.
2. Air-control system: noise and air binding in radiation should not occur.
3. Water lines: slightest leaks should be corrected.
4. Low water cut-off, for operation (see instructions furnished with unit.)
II. WATER LEVEL CHECK DURING HEATING SEASON:
Regular loss of water from water boiler system may indicate either a system leak, or a faulty air-control system, or a faulty automatic fill valve.
III. ANNUAL INSPECTION AND CLEANING:
A.It is important that this boiler be inspected by a competent
serviceperson to help insure safe and reliable operation.
B.Check for gas leaks from valve and gas piping to burners and
pilot. If leaks are found, repair or replace as required.
C.This inspection should include:
1. Controls check. See SAFETY CHECK, IV.
2. Recheck of input gas rate to burners. See "Initial Start" paragraph in "Operating Instructions" section.
3. Re-adjusting for best flame characteristics of main flame and pilot. See "Initial Start" paragraph in "Operating Instructions" sec­tion and see "Burner Adjustment" section.
4. Burner and boiler flue passage cleanliness: BURNER AND FLUE CLEANING (see sketch). It is suggested that paper be placed on burners to collect any foreign material in cleaning flues.
5. Remove draft hood, jacket top and flue cover.
6. Use wire brush to clean flueways.
7. Replace flue cover and re-seal with furnace cement. Replace jacket top and draft hood and reconnect to smoke pipe, using screws. Remove and dispose of paper and accumulated material.
8. If burner surfaces are not clean, or if uneven flame indi­cates plugged burner ports, remove and clean burners.
NOTE—TO REMOVE BURNERS: a. Remove holding wire clip at orifice. b. Disconnect pilot at pilot mount, or disconnect pilot gas line at
gas valve, before removing burners next to pilot. c. Lift rear of burner and remove burner from orifice. d. Clean and replace burners* and pilot. Adjust burners as
described on “Burner Adjustment”. * To clean burners run a clean flue brush up the tube until all
foreign matter is removed.
Boiler Cleaning
IV. SAFETY CHECK FOR CONTROL SYSTEM
A.High limit control test: Set thermostat high enough for boiler
water temperature to reach high limit control setting. When this temperature is reached, the high limit switch should open, and the main gas valve should close automatically. If the high limit does not close the main gas valve, the valve, the high limit or the wiring is faulty. Repair or replace immediately.
B.Gas valve safety shutdown test:
With main burners firing, disconnect the ignition cable from the Ignition Control. The gas valve should shut off the main burners. If the gas valve fails to shut down main burners when the test is performed, replace the gas valve.
C.Check for gas leaks from valve and gas piping to burners and
pilot. If leaks are found, repair or replace as required.
V. A. Providing Protection from Freezing.
Anti-freeze is sometimes used in hydronic heating systems to protect against freeze-up in the event of power failure or con­trol shutdown when the building is unoccupied. It should be recognized that unless the building is kept above freezing temperature by some means, the plumbing system is not pro­tected. Two types of anti-freeze may be used: ETHYLENE GLYCOL, used in automobiles, has desirable properties, but is toxic. Its use may be prohibited when system water/glycol solution is in contact with a potable water vessel (as with a tankless heater). PROPYLENE GLYCOL is used in the quick-freeze food industry; it is practically non-toxic. Its use may be permit­ted when tankless heaters are used. When anti-freeze must be used, inhibited propylene glycol is recommended. Useful information on the characteristics, mixing proportions, etc. of glycol in heating systems is given in Technical Topics No. 2A, available from the Hydronics Institute 34 Russo Place, Berkeley Heights, NJ 07922. Consult glycol manufacturers for sources of propylene glycol.
B.Water Treatment:
A good water treatment program will not only extend the use­ful life of this boiler but it will also save much of the time and expense of repairs made necessary by preventable occur­rences. A reputable water treatment company should be consulted to evaluate and determine the best overall treatment program for your boiler equipment.
VI. KEEP THE BOILER AREA CLEAR AND FREE FROM COM­BUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Page 11
GALAXY 11
SEQUENCE OF OPERATION FOR GALAXY BOILERS EQUIPPED WITH
INTERMITTENT PILOT IGNITION SYSTEM (IID).
HIGH-LIMIT CONTACTS CLOSED?
VENT DAMPER RELAY ENERGIZED.
VENT DAMPER MOTOR MOVES OPEN VENT DAMPER.
END SWITCH CLOSES.
IGNITION CONTROL ENERGIZED
SPARK GENERATOR MODULE POWERED
IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS..
L.P. PROPANE GAS
(S8600M & S8670E) IGNI-
TION TRIAL CONTINUES
FOR 90 SECONDS. AFTER
TRIAL FOR IGNITION, SYS-
TEM SHUTS OFF. AFTER 5
MINUTES MODULE RE-
INSTATES TRIAL FOR IGNI-
TION. IF PILOT FLAME NOT
ESTABLISHED, IGNITION
TRIAL, SYSTEM SHUT-OFF
AND 5 MINUTES WAIT SEQUENCE REPEATS
CONTINUOUSLY.
NATURAL GAS
IGNITION SPARK CON-
TINUES. PILOT VALVE
REMAINS OPEN UNTIL
SYSTEM IS RESET.
SPARK GENERATOR OFF. MAIN VALVE OPERATOR OPENS. MODULE MONITORS PILOT FLAME.
THERMOSTAT CALLS
FOR HEAT
MODELS WITH
VENT DAMPERS
THE PILOT FLAME ESTABLISHED?
WHEN THERMOSTAT IS SATISFIED OR WHEN HIGH LIMIT, OR LOW WATER CUT-OFF CONTACTS ARE OPEN, VALVE OPERA-
TORS CLOSE, VENT DAMPER CLOSES. SYSTEM GOES TO STANDBY.
NO FURTHER
ACTION
NO
NONO
YES
YES
Page 12
12 GALAXY
CAUTION: Label all wires prior to disconnection when servicing control.
Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”
FIGURE 6. Schematic wiring diagram
Page 13
GALAXY 13
BURNERS FAIL TO OPERATE CAUSE
1. Safety pilot out, or flame too low.
2. Gas supply valve shut off.
3. Electric switch open.
4. Blown or defective line fuse.
5. Operating or limit control contacts open or dirty.
6. Defective gas valve or pressure regulator; or plugged bleed line.
7. Defective low voltage transformer.
8. Obstruction at main burner orifice.
9. Break in wiring or loose contact at control terminals.
10. Improper wiring.
11. Improper controls.
12. Rollout or blocked vent safety switch open.
BURNERS WILL NOT SHUT OFF CAUSE
1. Defective operating control, gas valve, or high limit control.
2. Improper wiring or short circuit.
FLASH BACK - BURNING AT ORIFICES CAUSE
1. Manifold gas pressure too low.
2. Improper primary air adjustment.
3. Gas regulator bleed too slow.
4. Burrs on orifice.
5. Improperly drilled orifice plugs.
6. Leaking automatic gas valve.
7. Adverse draft condition in boiler room.
8. Low main gas pressure.
9. Safety pilot improperly installed.
DELAYED IGNITION CAUSE
1. Pilot flame too low.
2. Pilot burner ports or pilot orifice clogged.
3. Burners or orifices out of alignment.
4. Excessive primary air.
5. Excessive burner input.
6. Adverse draft condition in boiler room.
FUMES AND GAS ODORS CAUSE
1. Leaks in gas piping or accessories.
2. Gas leaks in service line or meter connections.
3. Blocked chimney.
4. Boiler flueways blocked with soot.
5. Undersized breeching or too many turns in breeching.
6. Adverse draft condition in boiler room.
7. Overfiring.
CONDENSATION IN BOILER FLUES OR IN VENT SYSTEM CAUSE
1. Underfiring.
2. Boiler water maintained at too low a temperature level.
3. Long horizontal run of smokepipe.
4. Inadequate chimney or venting system.
REMEDY
1. Check, clean, re-light. See instructions.
2. Open gas valve(s).
3. Close Switch.
4. Replace fuse.
5. Check Control. Clean contacts or replace control.
6. Repair or replace.
7. Replace aquastat.
8. Check, clean and reinstall.
9. Check with test-light and correct.
10. Check and correct in accordance with wiring diagrams included with appliance instructions.
11. Install proper controls.
12. Replace rollout switch (inspect flue passages prior to replacement) or reset blocked vent safety switch by depressing the reset button
REMEDY
1. Check, repair or replace.
2. Check wiring and controls.
REMEDY
1. Adjust to proper manifold pressure.
2. Adjust air to produce soft, clean flame.
3. Adjust bleed opening.
4. Remove burrs.
5. Install orifice plugs with proper drilling.
6. Repair or replace.
7. Check air supply and venting system.
8. Contact utility.
9. Correct to manufacturer's recommendations.
REMEDY
1. Increase gas supply to pilot.
2. Clean ports or orifices.
3. Realign burners or manifold.
4. Adjust primary air shutters.
5. Check and reduce to input shown on rating plate.
6. Check air supply and venting system.
REMEDY
1. Locate leaks and repair.
2. Close service supply valve - shut down appliance and noti­fy utility.
3. Check and repair chimney.
4. Clean flueways and adjust burners as described in the installation instructions.
5. Check manufacturer's recommendations.
6. Check air supply and venting system.
7. Adjust gas input to that shown on boiler rating plate.
REMEDY
1. Increase firing rate to that shown on rating plate.
2. Set low limit controls to maintain a higher water tempera­ture. If boiler is not equipped with low limit replace with one which has a combination low limit/high limit aquastat.
3. Relocate boiler or insulate breeching.
4. Check chimney and venting recommendations.
GENERAL TROUBLE SHOOTING GUIDE FOR SERVICEPEOPLE
Page 14
14 GALAXY
PIPING A HEATING — COOLING SYSTEM TO A WATER BOILER AND CHILLER
Figure below illustrates a method of piping a heating-cooling system to a water boiler and a chiller. Hand valves (shown) or automatic valves must be installed to prevent circulation of chilled water in the boiler or hot water in the chiller.
IF REPLACEMENT PARTS ARE NEEDED
When parts are needed, refer to boiler model and serial num­ber shown on the boiler name/rating plate. Refer to the following parts lists for part numbers; publication number GG-10PL for Galaxy GG Series. Whenever possible refer to the original order by number and date.
Control identification and replacement should not be attempted by unskilled personnel. Only simple, easily identified controls and parts may be obtained locally. All other controls and parts should be identified by and ordered from Slant/Fin. Relief/Safety valves must be ASME rated for the pressure and gross output of the boiler.
Replacement parts are available from:
Slant/Fin Corp. 100 Forest Drive Greenvale, NY 11548 Attn: Technical Service Dept.
The air-control system and pressure control system must oper­ate with chiller only, or the boiler only, being valved to the piping system. Separate control devices on the boiler and chiller may be used, or a single set of air and pressure controls on the common piping may be preferred.
If the boiler is used to supply hot water to heating coils in air handling units, flow control valves or other devices must be installed to prevent gravity circulation of water in the coils dur­ing the cooling cycle.
GENERAL TROUBLE SHOOTING GUIDE FOR SERVICEPEOPLE
Page 15
GALAXY 15
APPENDIX A
Removal of Existing Boiler from Common Vent System
"At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the com­mon venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation."
(a) Seal any unused openings in the common venting system.
(b) Visually inspect the venting system for proper size and hori-
zontal pitch and determine there is no blockage or restric­tion, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maxi­mum speed. DO NOT operate a summer exhaust fan. Close fireplace dampers.
(d) Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance will operate continuously.
(e) Test for spillage at the draft hood relief opening after 5 min-
utes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each appliance remaining
connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use."
(g) Any improper operation of the common venting system
should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1­latest edition.
Page 16
©Slant/Fin Corp. 2015 • Printed in U.S.A. 1115 • Publication GG-40S
U.S.A.
Slant/Fin Corporation • 100 Forest Drive Greenvale, NY 11548 • 516-484-0933
www.slantfin.com
Canada
Slant/Fin LTD/LTEE • 400 Ambassador Drive, Mississauga, Ontario L5T 2 J3 • 905-677-8400 www.slantfin.ca
Loading...