Slant/Fin Galaxy, Galaxy GXH-300H Installation And Operating Instructions Manual

GAS-FIRED CAST IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
HOT WATER—Models GG-75H through GG-399H
GALAXY
LOW PRESSURE STEAM AND HOT WATER— Models GXH-105 through GXH-300H
INSTALLATION AND OPERATING INSTRUCTIONS
CONTENTS ...........................................................................PAGE
Dimensions...................................................................................2
Installation Requirements:
Boiler Location........................................................................ 3
Boiler Foundation.................................... ............................... 3
Chimney Requirements............................. ............................. 3
Minimum Clearance................................................................. 3–4
Vent Piping.............................................................................. 4
Gas Piping............................................. ...................................... 4
Boiler Room Air Supply and Ventilation.................................. 5
Draft Hood Installation............................................................ 5
Piping at Boiler—Water Boilers................... ........................... 5
Steam Controls Assembly and Installation............................. 6
Piping a Steam Boiler ......................................................... 6, 7
Vent Damper.................................................................. 7, 8, 12
Electrical Controls and Wiring.................... ............................ 9
Pump or Valve Zoning—Water Boilers.............. .................. 10–11
Boiler Water Temperature Control .......................................12–13
Filling and Venting Water Systems....................................... 14
Initial Start, Safety and Lighting Instructions........................ 15
Burner Adjustment, Checking Gas Input.............................. 15
Controls, Safety Check......................................................... 17
Low Water Cut-off Check-Out.................................................... 17
Pressure Control Check-Out ..................................................... 17
Blowing Off a Steam Boiler........................................................ 17
Care and Maintenance.................................. ............................ 18
Safety Check for Control System................ ......................... 18
Protection From Freezing..................................................... 18
Water Treatment.....................................................................18
Sequence of Operations............................................................ 21
Troubleshooting Guide...............................................................22
Appendix A & B.......................................................................... 23
Appendix C, D & E......................................................................24
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS AND
STATEMENTS BEFORE READING THE INSTALLATION
FOR LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition or
and propane
additional requirements in this Slant/Fin Instruction Book.
In addition, where required by the authority having juris dic ­tion, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1 or
149.1 latest edition for natural gas and propane
any conflict in the above requirements, then the more stringent requirement will apply.
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
. The installation must also conform to the
INSTRUCTIONS.
WARNING
SEE "WARNING" ON PAGE 3
CSA B 149.1 latest edition for natural gas
CSA B
. If there is
WARNING
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
Printed in Canada 0713 PUBLICATION GG-41 Part No. 41-0549
Revision B
2 GALAXY
Pressure Relief
Valve
3/4"
1/2" Vent
Tapping
Alternate 1-1/2"
return (except
GG-75 thru
GG-175
FRONT VIEW
All GG and GXH
RIGHT SIDE
GG / GXH-PT
RIGHT SIDE
GXH-PZT-PPZT
RIGHT SIDE
GXH-PZ
GG SERIES HOT WATER BOILERS—DIMENSIONS IN MM FOLLOWED BY INCHES
GG-75H GG-100H GG-125H GG-150H GG-175H GG-200H GG-225H GG-250H GG-275H GG-300 GG-325 GG-350 GG-350H GG-375 GG-375H GG-399H
502
193/4
A
335
B
133/16
127
C
5
3
1178
D
46
/8
171
E
63/
4
203
F
8
235
1
1
/4
2
11/
70
23/4 91/4
G H J K
502 335 152
1353
330 203
235
3
19
/4
133/16
6
1
53
/4
13
8
1
1
/4
2
11/
70
23/4 91/4
502 335 152
1353
330 203
235
3
19 133/16
6 53 13
8
1
11/
70
23/4
91/4
23
/4
584 421
16
152
1
1
6
1353
53
/4
330
13
248
9
/4
11/4
2
11/
70
23/4
235
91/4
23
584
9
/16
1
/4
3
4
/
421 152
1353
330 248
9
16
/16
6
1
53
/4
13
3
9
4
/
11/4
2
235
2
11/
70
23/4 91/4
673 506 178
1461
406 286
235
1
26
/2
1915/16
7
1
57
/2
16
1
11
4
/
11/4
2
11/
70
23/4 91/4
673 506 178
1461
406 286
235
1
26
/2
1915/16
7
1
57
/2
16
1
11
4
/
11/4
2
11/
70
23/4 91/4
756 592 203
1514
432 330
235
3
29
/4
235/16
8
5
59
/8 17 13
1
1
/4
2
11/
70
23/4 91/4
756 592 203
1514
432 330
235
3
29
/4
235/16
8
5
59
/8 17 13
1
1
/4
2
11/
70
23/4 91/4
845 662 203
1514
432 375
235
1
33
/4
261/16
8
5
59
/8
17
3
14
4
/
11/4
2
11/
70
23/4 91/4
845 662 203
1680
432 375
235
1
33
/4
261/16
8
1
66
/8
17
3
14
4
/
11/4
2
11/
70
23/4 91/4
927 764 229
1680
572 413
235
1
36
/2
301/16
9
1
66
/8
221/
2
4
161/
11/4
2
11/
70
23/4 91/4
927 764 229
1680
572 413
235
1
36
/2
301/16
9
1
66
/8
221/
2
4
161/
11/4
2
11/
70
23/4 91/4
927 764 229
1680
381 413
235
1
36
/2
301/16
9
1
66
/8
221/
2
4
161/
11/4
2
11/
70
23/4 91/4
927 764 254
1680
381 413
235
1
36
/2 301/16 10
1
66
/8 221/
2
4
161/
11/4
2
11/
70
23/4 91/4
GXH SERIES STEAM AND HOT WATER BOILERS - DIMENSIONS IN MM FOLLOWED BY INCHES
GXHA-100 GXH-105 GXH-125GXHA-120 GXH-150 GXH-170GXHA-160 GXH-190 GXH-210GXHA-200 GXH-230 GXH-250 GXH-275 GXH-300 GXH-300H
23
A
419
B
127
C D E
254
F G H J K L
M
727
584
1
16
/
5
10
9
421
2
127
1178
171 248
419
16
46
16
16
/
127
5
3
/8
63/4
254
93/4 11/4
2
21/
89
2
31/
248
93/4
1
2
5
28
/8
/
727
28
273 mm
3
(10
/
4")
622 mm
1
(24
/
")
2
LEFT SIDE
All GG and GXH
23
584
1
5
10
9
421
16
2
/
152
6
1353
53
330
13
248
9 11/4 21/
89
31/
248
93/4
5
/8
152 – 327 mm (6 – 12-7/8")
832 mm
3
(32
/4")
337 mm
1
(13
/4")
57 mm
1
(2
/4")
1
26
673
/
2
1915/
55 14 11
508
20
16
152
7
6
1
/2
1
298
11
/4
506
16
/
178
1
1410
/4
356
3
286
/4
11/4
2
2
1
2
/
89
248
2
21/
2
31/ 93/4
1
2
/
727
Install Man-
ual Shut­Off Valve
1524 mm (5
ft.) Above
When
Required
By Local
Code
28
1
26
673 506
1915/
178
7
1410
55
356
14
3
286
11
/4
11/4 21/
89
31/
248
93/4
5
/8
57
mm
1
(2
/4")
419 mm
1
(16
/2")
FRONT VIEW
All GG and GXH
1
26
/
673
2
1
1
/4
/
2
506
16
1915/
178
7
1
1410
55
/2
356 286
/2
14
1
11
/4
1
591
23
16
178
7
1
343
13
/2
11/4
2
2
1
2
/
248
2
21/
89
2
31/ 93/4
1
2
/
mm
76
(3")
727
5
28
/8
756 592
4
/
178
1410
356 286
89
248
Return Tap-
ping G on
right side of
boiler
673 mm
(26
3
29
/
4
16
239/
7
1
55
/2
14
1
11
/4
11/4
2
21/
2
31/ 93/4
3
4
/
1
/2")
184 mm
3
29
756
/
4
592
16
239/
178
7
1
1410
55
/2
356
14
330
13
1
1
/4
2
21/
89
2
31/
248
93/4
3
4
/
Tankless Heater Connections "L"
GXH-PT only
318 mm
1
/
")
(12
2
1
(
2
/4"
)
RIGHT SIDE
GG / GXH-PT
826 662 178
1410
356 375
248
70 mm
3
(2
1
32
/
261/
7
1
55
/
14
3
14
/ 11/4 21/2
89
31/2 93/4
3
/
4
/
")
660 mm
(26")
ORIFICE SIZES indicated for Sea Level are factory installed in boiler unless other-
wise specified by the local authority. See page 15 for burner adjustment. GAS VALVE CONNECTION Size is 1/2" f.p.t. for all sizes up to and including GG­125 and GXH-125 depending upon configuration (natural, L.P., IID). Larger boilers, gas valves are 3/4".
COMBUSTIBLE FLOOR KIT increases all height dimensions by 51 mm (2"). RAISED SLAB—When mounting boiler on a raised slab, the slab must extend at
least 51 mm (2") beyo
nd the boiler cabinet on all sides.
CHIMNEY HEIGHT: 4.5 m (15 ft.) minimum from draft hood skirt to top of chimney. CHIMNEY INSIDE DIAMETER must be same as Dimension “C” or larger. Larger
diameter and/or height may be required if two or more boilers or a boiler and another appliance are vented to a single chimney.
BOILER MODEL GAS TYPE
GG Natural 42 43 43
Except GG-399H Propane 54 55 55
GG-399H GXH-105 Natural 44 43 45
through 275 Propane 54 55 55 GXH-300 GXH-300H Natural 43 44 44
GG-350H Gas*
Natural 40 42 42
Propane 53 54 54
Natural 43 44 44
Propane 55 54 56
*For L.P. Propane gas, consult factory.
32
826
2
662
261/
16
178
1410
55
2
356
14
375
14
4
89
248
4
1-1/4"
Tapping on
Steam Boilers
648 mm
1
(25
Orifice Size for
Sea Level
1
2
/
16
7
1
/2
3
/4
11/4
2
21/ 31/2
4
93/
3
/4
Tankless Heater Connections "L"
except GXH-PZ
826 662 203
1718
635 375
248
2
321/
826
16
261/
662
8
229
5
67
/8
1502
25
3
14
/4
11/4
2
21/
89
31/2
4
93/
3
/4
318 mm
1
(12
/
")
2
/2")
419 mm
1
(16
/
")
2
184 mm
1
/4
(7
")
RIGHT SIDE
GXH--PZ-PZT-PPZT
ORIFICE SIZES AT HIGH ALTITUDES
610 to 1219 m
(2000 to 4000 ft.)
381 375
248
321/ 261/
59 15 14
89
70
mm
3
(2
/
2
16
Field Control (Effikal) Vent Damper
9
C H I
1
/8
127mm 152mm 122mm
(5") (6") (4-13/16")
152mm 165mm 135mm
3
/4
(6") (6-1/2") (5-5/16")
11/4
178mm 179mm 149mm
(7") (7-1/16") (5-7/8")
2
21/
203mm 205mm 175mm
31/2
(8") (8-1/16") (6-7/8")
228mm 276mm 225mm
4
93/
(9") (10-7/8") (8-7/8")
3
/4
254mm 327mm 276mm
(10") (12-7/8") (10-7/8")
"
4
)
660 mm
(26")
1219 to 1372 m
(4000 to 4500 ft.)
927 764 254
1680
457 413
235
1
36
/2 301/16 10
1
66
/8 221/
2
4
161/
11/4
2
11/
70
23/4 91/4
GALAXY 3
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the author­ity having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition or CSA B 149.1 latest edition for natural gas and propane.
This installation must also conform to the additional require­ments in this Slant/Fin instruction book. Installation and service to be performed by a qualified installer, service agency or the gas supplier.
NATURAL GAS-FIRED BOILER LOCATION—
Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
Automatic gas ignition system components shall be installed so these components will not be subjected to dripping water dur­ing installation or service.
WARNING
SPECIAL ATTENTION FOR LIQUEFIED
PETROLEUM(L.P.)
PROPANE GAS-FIRED BOILER INSTALLATIONS
LPG appliances (boilers) shall be installed in accordance with applicable provisions of NFPA 58 (Liquefied Petroleum Gas Code) latest edition for installations in US and CAN/CGA B149.1 latest edition for installations in Canada
Liquefied Petroleum (LP) propane gas is heavier than air therefore Propane gas can accumulate at floor level. If you suspect a leak, do not attempt to operate boiler. A spark or flame from the appliance (boiler) or other sources may ignite the accumulated propane gas causing an explosion or fire. It is recommended that inspections for gas leaks be performed periodically by a licensed professional and that leak detection devices be installed as a further safety measure.
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of supporting the
weight of the boiler filled with water, and extending at least 51 mm (2") past the jacket on all sides. See dimensions of
boilers, page 2. B. For installation on non-combustible floors only.* C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes
or the National Board of Fire Underwriters for specific
requirements.
* The Combustible Floor Kit part number printed on the boiler rating plate is
the only one to be used when installing on combustible floors. The boiler must NOT be installed on carpeting. DO NOT place boilers above floor area containing radiant tubing.
CHIMNEY REQUIREMENTS—
A. Galaxy boilers may be vented into a masonry vitreous tile-
lined chimney UL listed or Type “B” Venting system NOT EXPOSED to the OUTDOORS below the roof line. Venting and sizing of venting system must be in accordance with the requirements of the local gas utility, local building codes and other authorities having jurisdiction. If a masonry chimney is exposed to the outdoors on one or more sides below the roof line (exterior chimney), ONE of the following options apply:
1. Chimney must be re-lined with an approved metallic liner. When this is done, the chimney UL
listed will be considered NOT exposed to the outdoors and the requirements of the National Fuel Gas Code for NON-exposed chimneys and/or local codes will apply.
2. If an UL listed exposed tile-lined chimney is to be used WITHOUT a metallic liner, the boiler must first meet the requirements of the following tables and paragraphs of the National Fuel Gas Code:
I. For Single Galaxy Boiler—Paragraph 11.2.9 and table
11.11.
II. For multiple appliances—Paragraph 11.3.18 and table
11.12 (or 11.13 if applicable). In addition, all requirements of the local gas utility, local building codes and other authorities having jurisdiction apply.
B. If an existing boiler is removed from a common venting sys-
tem, the common venting system may be too large for proper venting of the remaining appliances connected to the com­mon vent. Follow the test procedure shown in Appendix "A" on page 23 of this manual to insure proper operation of vent­ing system and appliances.
C. Inspect for proper and tight construction. Any restrictions or
obstructions must be removed. An existing chimney may require cleaning.
D. Chimney or ven
t must extend at least 914 mm (3 feet) above its passage through a roof and at least 914 mm (3 feet) above any ridge within 3048 mm (10 feet) of the chimney.
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
A. Minimum boiler clearances shall be as follows:
GALAXY GG SERIES
MODELS GG-75H THROUGH GG-225H. MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUCTION. MINIMUM CLOSET CLEARANCE. Front 152 mm (6") Rear 152 mm (6") Left Side 152 mm (6") Right Side 152 mm (6") Top 914 mm (36")* Flue
Connector 152 mm (6")
Type 'B' Vent 25 mm (1")
MODELS GG-250 THROUGH GG-399H. MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUCTION. MINIMUM ALCOVE CLEARANCE. Front Alcove Rear 152 mm (6") Left Side 152 mm (6") Right Side 152 mm (6") Top 914 mm (36")* Flue
Connector 152 mm (6")
Type 'B' Vent 25 mm (1")
* Allow extra clearance from combustibles for additional venting.
GALAXY GXH SERIES
4 GALAXY
* Allow extra clearance from combustibles for additional venting.
B. Provide accessibility clearance of 610 mm (24") on sides
requiring servicing and 457 mm (18") on sides used for passage.
C. All minimum clearances shown above must be met. This may
result in increased values of some minimum clearances in order to maintain the minimum clearances of others.
D. Clearance from steam and hot water pipes shall be
25 mm (1"). **
** At points where hot water or steam pipes emerge from a floor, wall or ceil
ing, the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 13 mm (
1
/2"). Each such opening
shall be covered with a plate of noncombustible material.
SAFETY—
VENT PIPING—
A. Vent piping installation must be in accordance with the
requirements of the local gas utility, local building codes and other authorities having jurisdiction.
B. Boiler vent pipe must be the full diameter of the boiler draft
hood outlet. See dimensions, page 2. If a vent damper is added, its diameter must be equal to the hood outlet and must be located past the hood outlet. See installation instructions furnished with vent damper and in the section "Vent Damper Installation" of this instruction book.
C. If more than one appliance vents into a common breeching,
the area of the breeching must be equal to the area of the largest vent plus 50% of the area of the additional vent areas. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. Horizontal breeching or vent pipe should be as high as possible, con­sistent with codes, so that vertical vents from appliances will have a high rise above draft diverter openings. All horizontal runs must slope upwards not less than 20 mm/m (
1
/4 inch per foot) of run. Horizontal portions of the venting system must be supported to prevent sagging by securing each joint with metal screws and by providing hangers spaced no greater than 1524 mm (5 feet) apart.
D. Vent or breeching into chimney should not be inserted past
the inside wall of the chimney liner.
E. All venting means should be inspected frequently. See Care
and Maintenance and separate User's Information Manual.
GAS PIPING—
A. Local installation codes apply. The pipe joint compound used on
threads must be resistant to the action of liquefied petroleum gases.
B. The gas supply line to the boiler should be run directly from the
meter for natural gas or from the fuel tank for L.P. propane gas. See page 2 for location of union and manual main shut-off valve that may be specified locally. Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas-W/m
3
(BTU/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow in pip­ing (m
3
/hr) (cu. ft. per hour).
4. Use table below to select proper pipe size.
Example: Boiler model GG-300 is to be installed. Distance from gas meter to the boiler is 15.24 m (50 ft). Heating value of natural gas is 10560 W/m
3
(1020 BTU/cu. ft.) Select proper pipe size.
At 15.24 m (50 ft.) length of pipe, match required capacity from table below (choose higher capacity, in this case 12.5 m
3
(440 cu.
ft.) per hour). Required pipe size is 1
1
/4". Improper gas pipe sizing will result in pilot flame outages, insuffi­cient heat and other installation difficulties. For more information and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edi­tion or
CSA B 149.1 latest edition for natural gas and propane
.
C. The boiler and its gas connection must be leak tested before plac-
ing the boiler in operation. Use liquid soap solution for all gas leak testing. DO NOT use open flame. This boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 3.5 kPa (
1
/2 PSIG). This boiler must be isolated from the gas supply piping system by clos­ing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 3.5 kPa (
1
/2 PSIG).
D. All gas piping used should be inspected thoroughly for cleanliness
before makeup. A sediment trap must be provided, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the inlet of gas
valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
MODELS GXH-105 THROUGH GXH-190 MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUCTION. MINIMUM CLOSET CLEARANCE. Front 152 mm (6") Rear 152 mm (6") Left Side 152 mm (6") Right Side 457 mm (18") Top 914 mm (36")* Flue
Connector 152 mm (6")
Type 'B' Vent 25 mm (1")
MODELS GXH-210 TO GXH-300H. MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUCTION. MINIMUM ALCOVE CLEARANCE. Front Alcove Rear 152 mm (6") Left Side 152 mm (6") Right Side 457 mm (18") Top 914 mm (36")* Flue
Connector 152 mm (6")
Type 'B' Vent 25 mm (1")
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Gas flow =
= 8.3 m3/hr
87 930 W/hr
10 560 W/m
3
(Gas flow = = 294 cu. ft. per hour)
300,000 BTU/hour
1020 BTU/cu. ft.
1
/2"
3
/4"1"1
1
/4"1
1
/2"
mft
m3/hr cu.ft./ hr. m3/hr cu.ft./ hr. m3/hr cu.ft./ hr. m3/hr cu.ft./ hr. m3/hr cu.ft./ hr.
3.0 10 3.7 132 7.9 278 14.7 520 29.7 1050 45.3 1600
6.1 20 2.6 92 5.4 190 9.9 350 20.7 730 31.1 1100
9.1 30 2.1 73 4.3 152 8.1 285 16.7 590 25.2 890
12.2 40 1.8 63 3.7 130 6.9 245 14.2 500 21.5 760
15.2 50 1.6 56 3.3 115 6.1 215 12.5 440 19.0 670
18.3 60 1.4 50 3.0 105 5.5 195 11.3 400 17.3 610
21.3 70 1.3 46 2.7 96 5.1 180 10.5 370 15.9 560
24.3 80 1.2 43 2.5 90 4.8 170 9.9 350 15.0 530
27.4 90 1.1 40 2.4 84 4.5 160 9.1 320 13.9 490
30.5 100 1.1 38 2.2 79 4.2 150 8.6 305 13.0 460
Length of Pipe
Gas Flow In Piping
Pressure drop=8mm(0.3") water column, 0.60 specific gravity gas.
Iron Pipe Size (Ips) inches
At pressure drop of 0.3 in. water, specific gravity = 0.60 gas.
GALAXY 5
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required to obtain combustion and ven­tilation. ALL AIR COMES FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around win­dows, doors, etc. in the whole building. When buildings are insu­lated, caulked and weather stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings. Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-latest edition or CSA B 149.1 latest edition for natural gas and propane, or applicable provisions of the local building codes. The following recommen­dation applies to buildings of energy-saving construction, fully caulked and weather stripped:
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM:
A. Air drawn horizontally from outdoors DIRECTLY through
an outside wall; one louvered opening near the floor and one louvered opening near the ceiling, each opening with a minimum FREE air passage area of 550 mm
2
per kW (1
square inch per 4000 BTUH) of total appliances’ input.
B. Air drawn horizontally through HORIZONTAL DUCTS;
one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of
1100 mm2per kW (1 square inch per 2000 BTUH) of total appliances’ input.
C. Air drawn VERTICALLY from outdoors; one opening at the
floor and one opening at the ceiling, each opening with a minimum FREE air passage area of 550 mm
2
per kW (1
square inch per 4000 BTUH) of total appliances’ input.
D. Air drawn from inside the building; one opening near the
floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 2200 mm
2
per kW (1
square inch per 1000 BTUH) of total appliances’ input.
DRAFT HOOD—
The draft hood supplied is part of the listed boiler assembly. DO NOT alter the hood. See dimensions, page 2.
Attach the hood to the boiler flue outlet. Connect flue pipe full size of hood outlet. If a vent damper is added, it must be installed on the outlet side of the hood. See Vent Piping on page 4,7 and 8 ( Figures 4, 5, 6,7 ).
PIPING AT BOILER — WATER PIPING
A. CIRCULATING SYSTEMS
1. Packaged water boilers are equipped with a water circulat-
ing pump, mounted to return the water into the boiler. For some installations, the pump should be on the supply main. See PUMP LOCATION, on page 6.
B. AIR CONTROL SYSTEM
1. DIAPHRAGM-TYPE COMPRESSION TANKS are used to
SPECIAL FLUSHING INSTRUCTIONS
Installation of new boiler may break loose a heavy accumulation of sediment and scale from old pip ing and radiators. It is extremely important to blow down your McDonnell Cut off 67 more frequently the first week. First week 3 times Thereafter at least once a week * Exception: McDonnell Cut off 42A must be blown
down daily.
See "CARE & MAINTENANCE" for instructions.
3/4" RELIEF VALVE
3/4" RELIEF VALVE
1
/2" O.D. TUBE CUT TO SIZE AT THIS END
5
/8" COMP. ADAP.
FITTING
1
/4" × 1/4" × 1/4"
1
/4" SIPHON
3
/8" MALE PIPE TO 1/2"
O.D. COMP. ADAP.
NIPPLE 1/2 × 2"
TEE
1
/2 × 1/2 × 1/2"
TEE 1/2 × 5/8" ADAPTER
NIPPLE
1
/2 × 51/2 " THD AT
BOTH ENDS
NIPPLE 1/4 × 21/2"
ADAPTER
WATER LEVEL 648 mm (251/2")
OFF FLOOR
ELBOW
1/4" × 90°
NIPPLE 1/4" ×
CLOSE
NIPPLE
1
/2 × 6" THD AT
BOTH ENDS
RNATEALTE
WFLO
ALVV
TURNRE
TURN
D ANDEER FATEW
DUCI REURESSREP
NG
S)ERHY OT(BVE LVA
S)
TCT HOREDI
NER LATEWT
SNEIACH MNG
NGRIEPMTE
EALVV
EALVL VNTRO
)ytciap calio cses
rteaehet toln ir
y Sgintainlimir EA
mets
YPPLSU
YPPLSU
L NTRO COW
DEUSF , IEALV
PUMP
PUMP
NMA
CATIMAUTO
TANK
NT ER VAI
W
REP
REP
VA
RNATEALTE
MHRAGAPDI
ONIESSPROMC
D ANDEER FATEW
NGDUCI REURESSRE
NGDUCI REURESSRE
S)ERHY OT(BVE LVA
URESSREAND P
)RSTHEO
FLO
NCATIO LOPUMP
TURNRE
DEFERATE WRNATEALTE
BY(EALV VNGDUCIRE
NTRO
L NTRO
USF , IEALVV
DEUS
UMP
PUM
UMP
PUM
YPPLSU
INMA
RNATEALTE
RNATE
P MUP
CATILO
NOCATI
CATIMAUTO
NTER VAI
NATIIBMCO
HRAGAPDI
RPMCO
ALVLL VFI
URESSREP
VE LVA
RATEW
EEDF
NONATI
MHRAG
TANK,NOISSER
AND EALV
NGDUCI REURE
S)ERHY OT(B
NGIHAS WTO
SSTANKLE
S
RATEHE
NTROCOWFLO
esknato teziS(
TENO
rtewa
EATLD WCO
R
YPPLSU
EDERPEMT
RATET WHO
RATET WHO
STURE FIXTO
NDRAI
lo cow beevla vngirpeme tllatnsI:TE
d
control system pressure in an AIR ELIMINATING SYSTEM: an automatic air vent is used to REMOVE air from the sys­tem water. See illustration on page 5.
If system pressure needs further control, add an additional tank or install a larger capacity tank. Locate the tank near the boiler, as illustrated. An automatic air vent should be installed in the top of the boiler. See illustration on page 5.
2. PUMP LOCATION — Locating low-head pump(s) on return to boiler is acceptable for smaller boiler sizes in resi ­dences of one or two stories. The alternate pump location shown in illustration on page 5 is required in large, multi­story building installations, especially when high-head pumps are used. The compression tank must be at the boiler or between boiler and supply main pump(s).
3.On a hot water boiler installed above radiation level,the
boiler must be provided with a low water cut-off device at the time of installation by the installer.
Flow Control Valve: When domestic hot water tankless heater is used, a flow control valve should be installed in supply piping to heating sys tem, as shown in illustration on page 5.
INSTALLATION INSTRUCTIONS FOR GXH LOW PRESSURE STEAM BOILERS EQUIPPED WITH TANKLESS OR PROVISION FOR TANKLESS AND McDONNELL & MILLER TYPE 67 LOW WATER CUT-OFF.
STEAM CONTROLS ASSEMBLY AND INSTALLATION INSTRUCTIONS
Steam kit components for Galaxy packaged models are packed as follows: A. 1. Low water cut-off control
2. Fittings
3. L.W.C.O. instruction sheet
B. 1.Pressure gauge
2. High pressure limit control
3. Water level gauge
4. Fittings
5. Instruction sheet and assembly drawing
6. Steam safety valve and
3
/4" street coupling
7. Drain cock
Assemble above components exactly as shown in steam controls assembly. Two
1
/2" tappings are on right side of boiler for this assembly. Two holes are pre-punched in jackets. For conve­nience, start assembling in the following steps: C. 1. Install
1
/2" x 51/2" brass nipple onto tee of L.W.C.O.
2. Mount
1
/2" x 51/2" brass nipple into lower boiler tapping by
rotating low water cut-off.
3. Assemble 90° brass tubing to tee adapter and L.W.C.O.
4. Install
1
/2" x 6" brass nipple and 1/2" × 5/8" adapter tee in upper
boiler tapping.
5. Install syphon, high pressure limit and pressure gauge with
1
/4" brass fittings.
6. Install water level gauge (without glass) and its fittings.
7. Install water level glass, and mark the glass 648 mm (25
1
/2") from the bottom of the steel boiler base for the water level. (The steel boiler base should not be confused with a combustible floor kit when making the 648 mm (25
1
/2")
measurement.)
8. Drain cock will be installed in return tee at the lower right side of casting.
9. Safety valve and
3
/4" street coupling should be installed in 3/4"
tapping on top of boiler.
6 GALAXY
PIPING A LOW PRESSURE STEAM BOILER
Boilers must be piped with good engineering practice and must conform to the requirements of ANSI/ASME Boiler and Pres­sure Vessel Code section IV and to the authority having jurisdiction. Notes: A. Slant/Fin makes no recommendation, nor does Slant/Fin imply
that One Pipe Parallel and Counterflow Gravity Condensate Return systems shown on page 7 are the preferred systems. These systems are merely two examples of many possible sys­tems. Determination of the proper system is based upon the application and is therefore beyond the scope of this instruction.
B. The 457 mm (18") minimum height shown in figures 1-3, is the
minimum height between the top of the jacket of the boiler and the 2
1
/2" x 12" header centerline in the supply piping from the boiler. It must NOT be confused with the minimum height between the water level and the lowest return bend of the steam supply main. This height is "H" as shown in figures 2 and 3. The minimum height of "H" must be at least equal to the sum of the pressure drop of the system plus three times the friction loss of the wet return, but not less than 457 mm (18") for a system with a 0.9 kPa (
1
/8" psi) steam pressure drop and not less than
28" for a system with a 3.5 kPa (
1
/2 psi) steam pressure drop.
C. Modern steam boilers are smaller in water content than the
boilers that they replace, therefore a mechanical return system (pump, receiver, etc.) must be employed if conditions exist such that uniform condensate return flow to the boiler cannot be maintained. Pocketing of condensate and the inability to maintain the cor­rect minimum height between the steam supply main and the water level in the boiler are but a few of the many conditions that indicate the use of a mechanical return system. Any use of a receiver and pump must be coordinated with the makeup water and controlled by the boiler water level control on the boiler. This description is typical of a boiler feed pump as opposed to a condensate pump that pumps condensate regardless of the water level in the boiler.
D. In any steam system one of the requirements is the removal of
air from the system. A mechanical return system in most cases has an air vent on the receiver. A gravity return system has no receiver, so provisions for air removal must be made on the piping itself. A one pipe system has the air vents on the radia­tion, the heat exchanger and near the end of the steam supply main (see figures 2 and 3). Main air vents should be located fifteen inches from the drop and if possible eight inches above the pipe so that water hammer does not damage the vent and render the vent inoperable. For more information on air vents, check with any manufac­turer of steam accessories (steam traps, boiler feed pumps, air vents, etc.).
E. Process water applications involving steam boilers requires
the use of heat exchangers. Any process application that constantly uses fresh water into a steam boiler can and will cause scaling with deposits forming in the boiler and sur­rounding piping. This will damage the boiler.
F. If valves are used on the supply side of the boiler, the valve
port opening must be the same size as the surrounding pipe. (Full flow type valves.)
G. Piping should provide a means of cleaning and flushing the
heating system of the sediment for safe, efficient operation.
GALAXY 7
RECOMMENDED PIPING FOR A ONE PIPE PARALLEL FLOW LOW PRESSURE STEAM HEATING SYSTEM WITH A WET OR DRY GRAVITY (See Note No. C under "Piping a low pressure steam boiler") CONDENSATE RETURN AND A HARTFORD† LOOP. See Note No. A on page 6 under "Piping a low pressure steam boiler".
FIGURE 1
† A Hartford Loop is recommended for low pressure steam systems with
gravity condensate returns. Pipe sizes shown above for Hartford Loop are recommended by Slant/Fin. However, certain local codes may require larger pipe sizes. Consult with local authorities.
The equalizer should be full size from the steam supply to the operating
water level.
* Hot water fill is preferable. For auto feedings, see manufacturer's techni-
cal instructions.
FIGURE 2
* Hot water fill is preferable, but not required. For auto feeding, see manufac-
turer’s technical instructions.
** See item B, page 6, under "Piping a low pressure steam boiler"
Counter flow piping is sized one pipe size larger than a parallel flow piping. This allows steam to travel in one direction while the condensate travels in the other direction. This along with a steeper pitch is a must for safe, efficient operation. ** See item B, page 6, under "Piping a low pressure steam boiler"
FIGURE 3
HEADER 21/2"×12" CENTRE TO CENTRE
2-1/2 × 2-1/2 × 2-1/2" TEE
2-1/2" UNION
1-1/2" Union
1-1/2" Plug
1- 1/2 × 3/4 " Bushing
400 mm (15-
3/4")
337 mm (16-1/2")
648 mm
(25-1/2")
2-1/2" Supply
457mm (18") Minimum Height
1- 1/2" × 1-1/4 "
Reducing Cou-
pling
2-1/2 ×1-1/2×1-1/2" TEE
51 mm (2")
1-1/2" Cross
11/4" Nipple
1-1/2" Nipple
203 mm (8")
381
mm
(15")
400 mm (15-3/4")
419 mm
(16-1/2")
648 mm (25-1/2")
457 mm (18") Minimum Height
400 mm (15-3/4")
419 mm
(16-1/2")
648 mm (25-1/2")
457 mm (18") Minimum Height
**
**
WARNING—DANGER
Once you have begun vent damper installation procedure, DO NOT restore electric power and gas supply until installation and inspection have been completed (in order to prevent the main burners from operating). DO NOT operate the boiler until the vent damper harness "FEMALE PLUG" is plugged into "MALE PLUG" (as described in the installation instructions), and the vent damper installation and checkout procedures have been completed. Failure to observe this warning may create a hazardous condition that could cause an explosion or carbon monoxide poisoning.
51 mm (2")
VENT DAMPER INSTALLATION
The vent damper referred to in the following instructions is the Slant/Fin LTD/LTEE vent damper. A. This device is design certified by C.S.A. for use ONLY on spe-
cific Slant/Fin gas boiler models. These boilers must also be equipped with a plate which states that the boiler must or may be used with a Slant/Fin automatic vent damper device and indicates the proper vent damper model number.
8 GALAXY
B. INSTALLATION INSTRUCTIONS BEFORE YOU START TO
INSTALL
1. Read this installation manual, the "DANGER" plate attached to the top of the boiler, the "WARNING" on the wiring diagrams, vent damper carton and operator cover.
2. Perform pre-installation inspection as required by ANSI specification Z21.66 or CSA B 149.1 latest edition for nat­ural gas and propane.
3. Turn off all electrical power, gas supply and wait for sys­tem to cool (for previously installed boilers).
4. Carefully unpack the unit. DO NOT FORCE IT OPEN OR CLOSED! Forcing the damper may damage the gear train and void the warranty.
5. This device must be installed after the appliance draft hood (between the draft hood outlet and the connector to the outdoor chimney or vent) as close to the draft hood as practicable, and without modification of the draft hood or the damper. (See figures 4 and 5.)
6. The inlet size of the vent damper must be the same nomi­nal trade size as the outlet of the draft hood.
7. This device must be located in a venting system or section of a venting system so that it serves only the single appli­ance for which it is installed. (See fig. 10.)
8. Clearances of not less than 152 mm (6 inches) must be maintained from combustible materials, with provisions for access for service.
C. NOW, PROCEED AS FOLLOWS:
1. Separate the vent pipe directly on top of the draft hood or diverter and place damper in position as shown in figures 4–7 and 11–12. The vent damper must be installed so that the damper position indicator is in a visible location after installation. See figure 7 for position indicator description. The arrow imprint on the damper should point in direction of vent gas flow (towards chimney). Re-assemble the vent piping. Be sure the vent damper is well seated and fas­tened with 3 sheet metal screws. Screws should be no longer than 13 mm (
1
/2 inch). See figure 12 .
2. Be sure that undersized vent pipe does not block move­ment of damper vane (see figure 7).
3. Boilers that have a vent damper are factory wired with a male plug.
i) Attach the flexible metallic conduit vent damper harness
to the right hand side of the jacket by passing the free end of the harness through the 22 mm (
7
/8") diameter hole in the top of the jacket, and using the BX con ­nector at the free end of the metallic conduit, fasten to jacket.
ii) Connect "FEMALE PLUG" (free end of vent damper har-
ness) into "MALE PLUG" (see correct wiring diagram for intermittent pilot).
iii)The other end of the flexible metal conduit has a small
molex plug and a 90 degree metal conduit connector. Route the molex receptacle through the conduit bracket on the vent damper. Place the harness receptacle into the damper plug. Securely fasten the harness conduit connector to the conduit bracket by carefully pushing it into the hold in the bracket.
4. All Slant/Fin Galaxy steam boilers equipped with intermit­tent pilot ignition systems are factory wired except for the wires to the low water cut-off and pressure cut-off. Wire these controls with wire provided with boiler (see boiler wiring diagram on boiler). Then follow previous instruc­tions shown in #4 above.
5. Restore electrical power and turn on gas supply.
FIGURE 4
FIGURE 5
FIGURE 6
FIGURE 7
FEMALE PLUG
FEMALE PLUG
NOTE: DAMPER POSITION INDICATOR
MAY BE VIEWED THROUGH HOLE IN THE SIDE OPPOSITE THE OPERATOR.
UNDERSIZED VENT PIPE MAY BLOCK THE MOVEMENT OF THE DAMPER VANE. IF THIS OCCURS, CUT OFF 1/2 OF THE MALE (CRIMPED) END OF VENT PIPE AND REFIT.
* May be plugged with plug provided
ONLY if boiler is equipped with intermittent ignition pilot.
7/8"
DIA. K.O.
Continued on page 14
Loading...
+ 16 hidden pages