Slant/Fin EM-10 Installation

MODEL EM-10
ELECTRIC BOILER CONTROL
OPERATION AND INSTRUCTION MANUAL
The EM-10 Boiler Temperature Control (BTC) is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, an alert output, and four stage outputs. The control regulates the boiler based upon setpoint, outdoor reset, and several options for external boiler control.
Features:
• Setpoint Operation
• Outdoor Reset with Reset Override
• Four Stage Outputs
• External Control through BMS Signal
• External Control through Tekmar Boiler Controls
• Boiler Pump Operation
• Parallel Piping
• Primary – Secondary Piping
• Display Backlight
See Service Manual (792840000) for:
• Tekmar 275 and other External Direct Drive Operation
• Two Setpoint Operation
• Dedicated DHW and Parallel Operation
• External Target/ Setpoint Operation
Publication No. EM-10-40
Printed in U.S.A. 809
Part No. 792820000
How to Use the Data Brochure
Item
Item
Item
This brochure is organized into three main sections. They are: 1) Sequence of Operation, 2) Installation, and
) Control Settings.
3
Table of Contents
User Interface ..................................................................2
Display and Symbol Description ......................................3
Modes of Operation..........................................................4
Setpoint Operation ..........................................................8
Outdoor Reset Operation ................................................9
Installation ......................................................................10
Control Settings..............................................................11
DIP Switch Settings........................................................11
User Interface
The BTC uses a Liquid Crystal Display (LCD) as a method of supplying information. You use the LCD in order to setup and monitor the operation of your system. The BTC uses three push buttons (Item, p,q) for selecting and adjusting settings. As you program your control, record your settings in the settings column of the Adjust menu. The table is found in the second half of this brochure.
MENU
The Control Settings section of this brochure describes the various items that are adjusted and displayed by the
ontrol. The control functions of each adjustable item are
c described in the Sequence of Operation.
Mode 4 and 5 - Outdoor Reset / Setpoint Operation ....12
Default Settings ........................................................13-16
View Menu......................................................................13
Adjust Menu ..................................................................14
View Menu......................................................................15
Error Messages ..............................................................17
Reload Factory Defaults ................................................18
Specifications ................................................................20
ITEM
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item in a menu, pressing and releasing the Item button will return the display to the first item in the selected menu.
All of the items displayed by the control are organized into two menus:
1) View
2) Adjust
These menus are listed on the upper right hand side of the display (Menu Field). The default menu for the BTC is the View menu. While in the View menu, the VIEW segment is displayed.
To select the Adjust menu, press and hold simultaneously all three buttons (Item, p,q) for 1 second.
The display then advances to the Adjust menu and the ADJUST segment is turned on in the display. The display will automatically revert back to the View menu after 20 seconds of keypad inactivity. Once in a menu, there will be a group of items that can be viewed within that menu.
ADJUST
To make an adjustment to a setting in the control, begin by selecting the Adjust menu by pressing and holding simultaneously all three buttons. Then select the desired item using the Item button. Finally, use the p or q button to make the adjustment.
STATUS FIELD
Additional information can be gained by observing the Status field of the LCD. The status field will indicate which of the control’s outputs are currently active. Symbols in the status field are only visible when the View menu is selected.
2
EM-10-40 Operation and Instruction Manual
Item
Number Field
Displays the current value of the selected item
Item Field
Displays the current
item selected.
Menu Field
Displays the c
urrent menu
Buttons
Selects Menus, Items and adjusts settings
Status Field
Displays the current status of the control’s inputs, outputs and operation
Display
BOILER PUMP
Displays when the boiler pump is in operation.
BURNER
Displays when stage 1, 2, 3, or 4 contact is on.
WWSD
Displays when the control is in Warm Weather Shut Down.
DEMAND 1
Displays when a call for heat on demand 1 is present.
DEMAND 2
Displays when a call for heat on demand 2 is present.
ERROR
Displays when an error message is present.
POINTERS
Displays operation as indicated by the text.
°F,°C
°F or°C
Displays the temperature units.
Symbol Description
EM-10-40 Operation and Instruction Manual
3
Symbol Description
Boiler Outlet
Sensor
Boiler Inlet
Sensor
Boiler Outlet
Sensor
Boiler Supply
Sensor
Boiler Inlet
Sensor
POWERING UP THE CONTROL
When the control is powered up, the control turns on all
egments in the display for 2 seconds. Next, the software
s version is displayed for 2 seconds. Last, the control enters into the normal operating mode.
ISPLAY BACKLIGHT
D
The control’s display has a backlight that is permanently on while the control is powered.
PIPING
The boiler can be piped in parallel or in primary/secondary to the system. The type of piping chosen affects the location of the control’s operating temperature sensor. The control can either use the boiler outlet sensor or the boiler supply sensor.
PARALLEL PIPING
In parallel piping applications, the boiler outlet temperature is typically the same as that delivered to the system. Therefore the operating temperature sensor is the boiler outlet sensor.
PRIMARY/SECONDARY PIPING
In primary/secondary applications, the boiler outlet
emperature (primary loop) is typically hotter than the
t system supply temperature (secondary loop). This occurs when the system supply pipe has a larger flow rate than the boiler outlet pipe. Therefore, the control requires an additional sensor (boiler supply) to measure the temperature delivered out to the system. The operating temperature sensor is the boiler supply sensor.
MODES OF OPERATION (MODE)
The control allows for seven modes of operation in order to define the control operation and piping arrangement used. The piping arrangement can be categorized into parallel and primary / secondary. The mode of operation is selected using the MODE item in the Adjust menu. The temperature being controlled out to the heating system is measured by the operating sensor.
The piping arrangement determines which sensor the control uses as the operating sensor. The operating sensor is either the boiler outlet sensor or the boiler supply sensor.
4
EM-10-40 Operation and Instruction Manual
MODE 4
BTC
Mode 5
Boiler Outlet Sensor
Boiler Inlet Sensor
Boiler Supply Sensor
Outdoor Sensor
Relay
BTC
Mode 4
Relay
Boiler Outlet Sensor
Boiler Inlet Sensor
Outdoor Sensor
(Outdoor Reset and Setpoint with Parallel Piping) Mode 4 is designed for outdoor reset and setpoint operation using parallel piping. The heat demand is available to provide outdoor reset for space heating systems. The setpoint can be used to heat an indirect domestic hot water tank.
Once a heat demand is present, the control stages the boiler to maintain the calculated outdoor reset target at the boiler outlet sensor. Refer to “Outdoor Reset Operation” section for a description of outdoor reset operation.
Once a setpoint demand is present, the control stages the boiler to maintain the boiler target at the boiler outlet sensor. If both demands are present at the same time, the control targets the higher of the two requirements. Refer to “Setpoint Operation” section for a description of setpoint operation.
MODE 5 (Outdoor Reset and Setpoint with Primary/ Secondary Piping) Mode 5 is designed for outdoor reset and setpoint operation using primary / secondary piping. The heat demand is available to provide outdoor reset for space heating systems. The setpoint demand can be used to heat an indirect domestic hot water tank.
Once a heat demand is present, the control stages the boiler to maintain the calculated outdoor reset target at the boiler supply sensor. Refer to “Outdoor Reset Operation” section for a description of outdoor reset operation.
Once a setpoint demand is present, the control stages the boiler to maintain the boiler target at the boiler supply sensor. If both demands are present at the same time, the control targets the higher of the two requirements. Refer to section “Setpoint Operation” for a description of setpoint operation.
EM-10-40 Operation and Instruction Manual
5
STAGING MODE (STGMODE)
175 °F 17 0°F
180°F Setpoint
Proportional Staging
185°F
190°F
155 °F 150°F 145 °F 140 °F
160°F
165°F
Stage 4
Stage 3
Stage 2
Stage 1
water
temperature
droop
water
temperature
droop
water
temperature
droop
175 °F 17 0°F
180°F Setpoint
P. I .D . Staging
very little temperature droop
185°F
165°F
Stage 4 Stage 3 Stage 2 Stage 1
P. I .D . = Proportional + Integral + Derivative
The control can operate up to four stages in order to supply the required target temperature. The method of staging used by the control is either P (proportional) or PID (Proportional & Integral & Derivative), and is selected using the STGMODE item in the Adjust menu.
STAGE DELAY (STG DLY)
The stage delay is the minimum time between firing first to second stage, second to third stage, and third to fourth stage and is determined by the Stage Delay setting. It can be manually set, or it can be set to automatic in which the boiler mass determines the stage delay time.
BOILER MASS (BOIL MASS)
The boiler mass setting allows the installer to adjust the control to the thermal mass of different types of heat sources used. The boiler mass setting automatically determines the stage delay on, stage delay off, minimum on time and minimum off time of the stages. A higher thermal mass setting provides slower staging, while a lower thermal mass provides faster staging.
Proportional (P)
Proportional staging, also known as step staging, is based on manually adjusted settings that determine when the next stage is required to turn on. These manual settings are based on temperature and time. The interstage differential sets the temperature drop at which the next stage turns on. However, in order for a stage to fire, the interstage delay on and minimum off times must first elapse.
Proportional & Integral & Derivative (PID)
PID staging allows the control to determine when the next stage is required to turn on. After a stage is turned on in the firing sequence, the control waits a minimum amount of time (Stage Delay) before turning on the next stage. After the minimum time delay between stages has expired, the control examines the control error to determine when the next stage is to fire. The control error is determined using PID logic.
Proportional logic compares the actual operating sensor temperature to the boiler target temperature. The colder the temperature, the sooner the next stage is turned on. Integral logic compares the actual operating sensor temperature to the boiler target temperature over a period of time.
Derivative logic determines how fast or slow the operating sensor temperature is changing. If the temperature is increasing slowly, the next stage is turned on sooner. If the temperature is increasing quickly, the next stage is turned on later, if at all.
6
Interstage Differential (STG DIFF)
The interstage differential is the temperature drop at which the next stage will turn on. Once a stage turns on, the next stage cannot turn on until the temperature drops the interstage differential below the temperature at which the previous stage turned on. The interstage differential is adjustable through the STG DIFF setting in the Adjust menu.
Interstage On Delay (ON DLY)
The interstage on delay is the amount of time that must elapse before turning on the next stage. Once a stage turns on, the next stage cannot turn on until the interstage delay on time elapses. The interstage on delay is adjustable through the ON DLY setting in the Adjust menu.
Interstage Off Delay (OFF DLY)
The interstage off delay is the amount of time that must elapse before turning off the next stage. Once a stage turns off, the next stage cannot turn off until the interstage delay off time elapses. The interstage off delay is adjustable through the OFF DLY setting in the Adjust menu.
Minimum On Time (MIN ON)
The minimum on time is the minimum amount of time that a stage must be on before it is allowed to turn off. Once a stage turns on, it cannot turn off until a minimum on time elapses. The minimum on time is adjustable through the MIN ON setting in the Adjust menu.
EM-10-40 Operation and Instruction Manual
Loading...
+ 14 hidden pages