Slant/Fin EH User Manual

MODEL EH ELECTRIC BOILER
EH-08-135S through EH-40-135S 3 wire 120/208V, 120/240V single phase EH-12-345S through EH-40-345S 4 wire 120/208V three phase WYE
OPERATION AND INSTALLATION INSTRUCTIONS
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Wiring (Warning: DO NOT turn on breakers on unit) . . . . . . . . .2
Wall Thermostat Flow Switch and Circulator . . . . . . . . . . .2
Service Connections and Electrical Ratings . . . . . . . . . . . .3
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Fill System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Air Elimination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Bypass Flow Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Check for Proper Boiler and System Operation . . . . . . . . .6
Operation (models equipped with seq. control system) . . . . . . .6
Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
IMPORTANT:
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
Publication No. EH-40
Printed in U.S.A. 1213
Part No. 79-0820
DESCRIPTION
The Monitron boiler is a low pressure hot water heating electric boiler. The heating elements are sheathed resistance type. The heat exchanger is cast-iron. The heat exchanger is constructed, inspected, and stamped in accordance with Section IV of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code. In addition, the Monitron Boiler is equipped with a safety relief valve and an integral dual limit con­trol, conforming to ASME requirements. The Monitron boiler is Underwriters' Laboratories, Inc. listed.
MOUNTING
The Monitron is intended for wall mounting, utilizing the wall brackets attached to the boiler (see Figure 1). Allow sufficient space for piping and service. The boiler may be installed in an enclosed space (see Figure 1). The boiler must be INSTALLED LEVEL.
PIPING Air Separator and Expansion Tanks
The recommended piping arrangement is shown in Figures 2 through 4. Note that there is a built-in air eliminator in the heat exchanger (air vent, however, is by others). A 1/8" air vent may be used. Additional air vents should be installed at points just upstream from all drops in elevation of the piping system (high points).
Flow Switch
A FLOW SWITCH MUST BE INSTALLED. It is intended to pre­vent the burnout of heater elements should the circulator fail, or should air accumulate in the boiler due to faulty air elimination (see Table 3 for flow switch size required). FLOW SWITCH MUST BE INSTALLED IN HORIZONTAL POSITION.
Bypass
The bypass shown must be set so that a sufficient amount of water can circulate through the boiler when all zone valves are closed. See Figure 3.
Multi-zone Balancing
Raise all zone thermostat settings and verify that all zone valves are open (not bypassed). Close all electrical panels. Turn on 10 amp control circuit breaker ONLY. Pump should operate. Note the pressure reading on the pump discharge. Lower each zone thermostat setting to close corresponding zone valve. Adjust the corresponding balancing valve to maintain pump discharge pres­sure. The pump discharge pressure should remain the same when all zones are in bypass or when all zones are open or any combination of opened and closed. See Figure 4.
WIRING
To wire the electric boiler, perform the following procedures:
1. Wall Thermostat Flow Switch and Circulator
• All circuit breakers ahead of and at boiler must be OFF. Remove the Control Panel (left-hand front) Cover by removing 5 screws from top, bottom and side flanges.
• The right-hand compartment under the Control Panel Cover contains a terminal board marked, "TTFF". Wire a 2-wire 24V heating thermostat or the auxiliary end switch terminals of zone valves (see Figure 5) to "TT" at this time. The "FF" terminals are for the flow switch. You may draw the wires between the flow switch and the compart­ment containing the "TTFF" terminal board but the wires at the flow switch end may NOT be connected and the ends should be taped. The flow switch circuit is a low volt­age circuit (see wiring diagram, Figure 5).
• Wire the circulator and connect wires and conduit through 1/2" K.O. provided on bottom left hand corner, to the ter­minal board marked, "Circulator". Wire zone valve trans­former to terminals "A" and "B" of this terminal board (see Figure 6) if zone valves are used. Use 75°C. minimum wire, copper or aluminum.