Slant/Fin EC20 User Manual

E
Oil-Fired 217,000–350,000 BTU Models Up To 86.5% efficiency
UTECTIC
EC
A superior cast-iron, three pass, oil-fired boiler
The EC-20 has a proprietary cast iron eutectic heat exchang­er that is resistant to thermal shock and corrosion. The cast iron is flexible and resilient which allows for lower temperature operation especially with outdoor reset controls. This yields significant energy savings.
The EC Series efficiency is a result of the boiler’s unique three pass design heat exchanger with specially designed baffles for maximum heat exchanger contact, flue turbulation and heat transfer. AFUE is 86.5%.
The three pass design of the Eutectic makes it very quiet too. There is plenty of room for thermal expansion of the flue gasses to keep burner and flame noise to a very minimum. It is easy to clean, the door is reversible, the baffles are remov­able and brushing the flueways is a snap.
The Eutectic boiler, like other Slant/Fin oil boilers, will operate cleanly under all the different operating conditions. We’ve done the testing and have matched burners and components to this boiler to make sure the boiler will stay running clean after you leave the job.
-
20
EC-20 Oil-Fired Boiler
The EC Series efficiency is a result of the boiler’s unique three pass Eutectic cast iron heat e
xchanger.The three pass design along with 4 inches of insu­lation make it the quietest boiler in its class. The Eutectic heat exchanger allows for plenty of thermal expansion of the flue gasses to keep the flame noise to a minimum.
Features
• Quiet
• 86.5% Efficiency
• Three pass heat e
• Easy to clean, operates clean
• Resilient, flexible, Eutectic cast iron – Resistant to thermal shoc – Outdoor reset compatible with low water temps
• Hinged, reversible swing out door for fast, easy cleaning
• Available with Riello burners
• Standard operating control, Honeywell 7248C
Optional Thermatic Control
Total System management and boiler control, provides greater comfort and utmost in fuel conservation. Reduces cycling.
xchanger maximizes heat transfer
k and corrosion
Dimensions
Circulator
Optional
1 1-1/2" supply tapping 2 1-1/2" retur
n tapping
3 3/4" dr
ain tapping
4 Flue outlet 5 Bur
ner mounting plate
Boiler Model Specifications
Model Number EC-25 EC-26 EC-27 EC-28
Maxim
um Inputs
#2 Fuel Oil GPH 1.55 1.90 2.25 2.50 #2 Fuel Oil MBH 217 266 315 350
Gr
oss Outputs MBH
#2 Fuel Oil 190 232 272 302
Net IBR Outputs MBH
#2 Fuel Oil
AFUE Efficiency
#2 Fuel Oil 86.5% 86.5% N/A N/A
Thermal Efficiency N/A N/A 86.5 86.4
Weight (pounds) 567 655 741 827
Boiler Total Heating Surface Area (sq. ft.) 32 39 46 53
Flue Diameter Connection (inches)
Flue Pressure Drop sP (inches w.c.) .09 .12 .14 .16
Water Content (gallons) 11.0 13.0 15.0 17.0
Specifications Common to all Boilers
CO2 = 13% #2 Fuel Oil
165 202 237 263
6.0 7.0 7.0 7.0
Maximum operating pressure: 60 psi Maximum water temperature: 210°F
SLANT/FIN
©
Slant/Fin Corp. 2007. Printed in the U.S.A. 407. Publication No. EC-20-10
CORPORATION., Greenvale, N.Y. 11548 •
Phone: (516) 484-2600 • Fax: (516) 484-5921
In Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario • www.slantfin.can
www.slantfin.com