Slant/Fin EC-10DV User Manual

EUTECTIC
EC-10DV Series
DIRECT VENT OIL-FIRED WATER BOILER/NO. 2 OIL
INSTALLATION AND OPERATING INSTRUCTIONS
SAFETY WARNING:
KEEP BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO ABOVE SAFETY WARNING, MAY RESULT IN PERSONAL INJURY OR DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAG E
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Vent Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installing Water trim . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operating Instructions:
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning and Filling New Water Boiler . . . . . . . . . . . . . .5
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Burner Data:
Riello . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-9
Care and Maintenance:
Extended Shutdo
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
al Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .
Gener
THIS BOILER OPERA THE FLUE AND OVER FIRE, ALL SEALS MUST BE IN PLACE WHEN OPERATING THE BOILER. ALL VENTING MUST BE INSTALLED AND SEALED ACCORDING TO THE VENT MANUFA
wn . . . . . . . . . . . . . . . . . . . . . . . . . . .
TES WITH POSITIVE PRESSURE IN
CTURER’S INSTRUCTIONS
.
10
10
IMPORTANT: The installation of this equipment must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the Installation of Oil
ning Equipment, ANSI/NFPA 31, latest edition, and to the
Bur National Electrical Code ANSI/NFPA 70, latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Manual. Where there is any differ­ence, the more stringent requirement shall govern.
In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety
vices for A
De edition.
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJ
utomatically Fired Boilers, No. CSD-1, latest
BOILER FOR REFERENCE.
CENT
A
THE
O
T
UTION
CA
The information in this manual must be followed exactly to avoid personal injury, property damage or loss of life.
IMPORTANT: This boiler must be installed by a trained,
ienced, ser
xper
e
vicing of oil b
and ser the author
vice technician, licensed f
ning equipment or otherwise qualified by
ur
ities having jurisdiction over the installation.
Part No. 470908000 Publication No. EC-10DV-40
or the installation
Printed in U.S.A. 407
2
1
-1/4 threaded s
upply
Flue outlet øD
1
-1/4 threaded
r
eturn pipe
D
rain outlet
R
elief valve 3/4’’
Supply Pipe Mounted
T
ridicator
P
anel Mounted Tridicator Pressure Sensor Well
Panel Mounted Tridicator Temperature S
ensor Well
A
Figure 1: Dimensions (inches)
EUTECTIC EC-10 DV
TABLE 1: Ratings and Dimensions
BOILER MODEL
NO.
I=B=R
BURNER
CAPACITY
OIL INPUT †
GPH BTUH
D.O.E.
HEATING
CAPACITY
MBH *
WATER
I=B=R
WATER
NET
RATING
MBH *
AFUE %
APPROX.
OVERALL
LENGTH
“A”
BOILER
LENGTH
“B”
DIMENSIONS (inches) #
BOILER
LENGTH
“C”
FLUE
DIA.
“D”
DISTANCE BETWEEN
LEGS
“E”
OUTLET LENGTH
EC-13DV 0.65 91,000 79 69 87 36 22-1/4 27 5 11-13/16 2
EC-14DV 0.80 112,000 98 85 87 41 27-1/4 32 5 16-13/16 2
EC-15DV 1.00 140,000 123 107 87 46 32-1/4 37 5 21-13/16 2
EC-16DV 1.15 161,000 141 123 87 51 37-1/4 42 6 26-13/16 4
Maximum operating pressure 60 psi. All boilers h
ydrostatically tested — A.S
.M.E.
* For forced hot water heating systems where the boiler and all piping are
located within the area to be heated, the boiler may be selected on the basis
capacity output. The net I=B=R output ratings shown are based on
.E.
of D.O an allowance for piping and pickup of 1.15 (water). D.O.E. capacity output is divided by the allowance to obtain net rating. The Slant/Fin Technical Service department should be consulted before selecting a boiler for unusual piping and pickup requirements such as intermittent system operation, extensive piping, etc.
† Ratings apply to the use of light oil at 140,000 Btu per gallon and apply only
ner models listed on pages 8 of this manual are used, and are
ur
when b properly adjusted to produce 13% CO2.
ufacturing tolerance.
All dimensions subject to nor
#
mal man NOTE: All boilers under 300,000 Btuh (87.9 kw) input are tested and rated for capacity under the U.S. Depar tment of Energy (D.O.E.) Test Procedures for Boilers.
FLUE
“F”
UTECTIC EC-10 DV
E
3
I
NSTALLATION REQUIREMENTS
BOILER LOCATION
Provide a level, solid foundation for the boiler.
A. The foundation must be capable of supporting the weight of
the boiler when filled with water:
Boiler Approximate Total Weight of Boiler
Size Assembly*, filled with water
EC-13-DV 353 EC-14-DV 426 EC-15-DV 501 EC-16-DV 575
* Includes burner, circulator and controls
B. These boilers have full wet base sections which surround fire­box for maximum heat absorption of burning fuel, and low floor
temperature.
. If boiler is to be located over buried conduit containing electric wires
C
or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
MINIMUM CLEARANCE
Provide accessibility clearance of 24" from surfaces requiring servicing (top and front) and 18" on any side requiring passage. The boiler shall be installed with the following MINIMUM clearances from combustible materials: BACK AND SIDES- 6" NOTE: Except in closets and alcoves, clearances above in (A) and (B) may be reduced by providing forms of protection as specified in NFPA 31, latest edition.
VENTING REQUIREMENTS
• The terminal shall not be closer than 3 feet above or 10 feet horizon­tally from any forced air inlet into the building.
• The terminal shall not be closer than 4 feet below, 4 feet horizontally or 1 foot above any door, window or gravity air inlet into the building.
• The terminal shall not be less than 3 ft from an inside corner of an “L” shaped building.
• The terminal shall not be less than 7 ft above grade when located adjacent to public walkways.
• The terminal shall not be less than 2 ft from an adjacent building.
• The terminal shall be located at a height not liable to blockage from leaves, snow or other debris, at least 1 ft above grade or anticipated snow line.
• The terminal shall be positioned so that flue gases are not directed where they can jeopardize people, overheat combustible structures or enter buildings.
• Vent terminal should be away from shrubbery or other obstructions that would prevent free air flow to and from vent terminal. Do not ter-
ent under dec
minate v locations under windows should be avoided.
mination should not be mounted directly abo
ent ter
V
• horizontally from an oil tank vent.
, stairways or car ports. When ever possible,
ks
e or within 3 ft
v
BOILER INTERNAL BAFFLES
TANT: EC-10 series boilers Direct Vent version is different from
IMPOR
standard series. Direct Vent version boilers usually have fewer internal cast iron baffles.
E
E
C-14 & 15
EC-16
C-13
e
S
rsion
tandard V
(
3) Baffle Plates
(
2) Baffle Plates
c
enter & right side
when viewing from
front
(0)
e
nt Version
D
irect V
(
2) Baffle Plates center & right side when
viewing from front
(
0)
(0)
VENT PIPING
A. The vent piping minimum bend radius is 12”. B. Place metal strapping every 36” to support vent pipe and prevent it
from sagging.
C. Maximum wall thickness is 14”. Contact Slant/Fin Corp. for
recommendations in case of thicker wall. D. Gases will form white plume in winter. Plume could obstruct window view. E. Prevailing winds could cause freezing of condensate and water/ice
buildup on building, plants or roof.
. Locate or guard vent to prevent accidental contact by people or pets, and
F
condensate from damaging exterior finish. G.Do not terminate vent in window well, stairwell, alcove, courtyard, or other
recessed areas.
All venting kits must be double wall construction for the flue gas piping.
Field
Controls is the only approved manufacturer for venting kits. When installing
the vent kits the manufacturers instructions must be followed.
I
NSTALLING WATER TRIM
Notes: Jacket must be installed on boiler units prior to installation of trim.
PIPING
IMPORTANT: Boilers are to be used with closed system. Any application
that uses water from system, causes the introduction of a frequent supply of fresh water into the boiler. This will cause damage to the boiler. Use of heat exchangers will prevent this damage.
PIPING FOR WATER UNITS
NOTE: On knock down boiler only, jacket may be installed after return pip­ing connection, but must be installed prior to adding trim & supply piping. I. CIRCULATING SYSTEM
A. FORCED CIRCULATION hot water heating system: Use the top
tapping as supply tapping, and use the rear bottom tappings for the return.
B. A FLOW CONTROL VALVE will prevent gravity circulation. II. AIR CONTROL SYSTEMS
A. DIAPHRAGM-TYPE COMPRESSION TANKS are used to control
system pressure in an AIR ELIMINATING SYSTEM: an automatic air vent is used to REMOVE air from the system water. See figure 3.
Figure 2. Typical Installation
4
1
3-31/32
7
-11/16
Relief valve 3/4
1/2” NPT Tapping for Feed Valve and E
xpansion Tank
1-1/4 NPT r
eturn tapping
Drain outlet
Panel Mounted
T
ridicator Temperature
Sensor Well
A
ir Eliminator
a
s per Manufacturer
Specifications
To Circ. (s) and Zones
1
-1/4”
NPT
Supply
Automatic Air Vent
S
uppy Pipe Mounted
Tridicator
Panel Mounted Tridicator Pressure Sensor Well
Figure 3. Air Eliminating System or Alternating Collecting System
EUTECTIC EC-10 DV
If system pressure needs further control, add an additional tank or install a larger capacity tank. The automatic air vent should be installed in the top of the boiler, as in figure 3.
B. CONVENTIONAL COMPRESSION TANKS (non-diaphragm type) are
used to control system pressure in an AIR COLLECTING SYSTEM. Within the system, after initial start-up and venting, air is collected in the tank and acts in contact with the water to control pressure. Air is not vented from this system. If system pressure needs further control, add another tank in parallel with the original tank or install a large capacity tank. Locate the tank at the inlet end of the pump near the boiler. (See figure 3)
C. HOT WATER RADIATION VENTING - Manual air vents should be installed
at the top of all "drops" (where piping goes downward). Air must be vented or purged from all zone lines to permit proper system heating.
D. PUMP LOCATION - Locating low-head pump(s) on return to boiler is
acceptable for smaller boiler sizes in residences of one or two stories. The pump location sho
wn in figure 3 is required in large
, m
y
ulti-stor
building installations, especially when high-head pumps are used.
IMPORTANT: Hot water heating systems containing high water volume, such
ould occur with cast iron r
as w
adiation, require special care with air elimina­tion. The circulator pump should be located on the boiler supply pipe and the expansion tank and air scoop should be located near the pump suction.
INSTALLING THE BURNER
ner Data, pages 8-9, and Bur
See Bur
ner Man
ual supplied with b
ur
ner. If burner is not mounted as received, mount to boiler, placing flange over mounting studs flange and nose of burner must be as shown on pages 8-9. Check to see
. Use gasket between flange and boiler. Distance between
that nozzle and settings are as given in burner data tables, pages 8-9.
VOLUME OF WATER IN STANDARD PIPE OR TUBE
Standard Steel Pipe Copper Pipe
4
2
2
Pipe
Schedule
40 0.622 0.0157 0.545 0.0121
40 0.824 0.0277 0.785 0.0251
40 1.380 40 1.610 0.106 1.505 0.0924 40 40 2.469 0.249 2.465 0.248
Nominal
pipe Dia.
3
8
1
2
5
8
3
4
1 40 1.049 0.0449 1.025 0.0429
1
1
1
1
2
1
2
Pipe ID
Inch
Gal. per
Lin.Ft.
Pipe ID
Inch
Gal. per
Lin. Ft.
0.430 0.0075
0.666 0.0181
1.265 0.0653
1.985 0.161
2.067
0.0779
0.174
3 40 3.068 0.384 2.945 0.354
WATER CONTENT OF BOILER (GALLONS)
EC-13 EC-14
5 6.5 8 8.5
EC-15 EC-16
Loading...
+ 7 hidden pages