Slant/Fin EC-10 Installation

EUTECTIC EC-10
OIL-FIRED WATER BOILERS/NO. 2 OIL
INSTALLATION AND OPERATING INSTRUCTIONS
SAFETY WARNING:
KEEP BOILER AREA CLEAR AND FREE FROM COM­BUSTIBLE MATERIALS, GASOLINE AND OTHER FLAM­MABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO ABOVE SAFETY WARNING, MAY RESULT IN PERSONAL INJURY OR DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 & 4
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Baffle Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Air Supply and Venting . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Controls and Accessories . . . . . . . . . . . . . . . . . . . . . . . . .7
Piping for Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Vent Piping and Draft Regulator . . . . . . . . . . . . . . . . . . . .8
Operating Instructions:
Precautions Before Starting . . . . . . . . . . . . . . . . . . . . . . .8
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Cleaning and Filling New Water Boiler . . . . . . . . . . . . . . .8
Care and Maintenance:
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-16
Burner Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-21
IMPORTANT: The installation of this equipment must con­form to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the Installation of Oil Burning Equipment, ANSI/NFPA 31, latest edition, and to the National Electrical Code ANSI/NFPA 70, latest edition. The installation must also conform to the additional require­ments in this Slant/Fin Instruction Manual. Where there is any difference, the more stringent requirement shall govern.
In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1, latest edition.
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJACENT TO THE BOILER
FOR REFERENCE.
IMPORTANT: This boiler must be installed, serviced and repaired by a trained, experienced, service technician, licensed for the installation and servicing of oil burning hot water heating system equipment or otherwise qualified by the authorities having jurisdiction over the installation.
Printed in U.S.A. 1214 Publication No. EC-10-40 Rev.B Part No. 470900000
SERVICE COMPANY
Name ______________________________ Address_____________________________
___________________________________ Telephone ___________________________ Model # _____________________________ Serial # _____________________________
EUTECTIC EC-10
2
Maximum operating pressure 60 psi. All boilers hydrostatically tested — A.S.M.E. * For forced hot water heating systems where the boiler and all piping are
located within the area to be heated, the boiler may be selected on the basis of D.O.E. capacity output. The net AHRI output ratings shown are based on an allowance for piping and pickup of 1.15 (water). D.O.E. capacity output is divided by the allowance to obtain net rating. The Slant/Fin Technical Service department should be consulted before selecting a boiler for unusual piping and pickup requirements such as intermittent system operation, extensive piping, etc.
† Ratings apply to the use of light oil at 140,000 Btu per gallon and apply only
when burner models listed on pages 13 and 17 of this manual are used, and
are properly adjusted to produce 13% CO2.
§ Boiler models have two firing rates. The boiler is factory shipped at the lower firing rate. To obtain the higher firing rate, refer to the boiler installation instructions for the appropriate field adjustments.
# All dimensions subject to normal manufacturing tolerance. NOTE: All boilers under 300,000 Btuh (87.9 kw) input are tested and rated for capacity under the U.S. Department of Energy (D.O.E.) Test Procedures for Boilers.
TABLE 1: Ratings and Dimensions
EC-13P 0.65 91,000 79 69 6 x 15 87 36 22-1/4 27 5 11-13/16 2 EC-13-0.7 0.70 98,000 85 74 6 x 15 86 36 22-1/4 27 5 11-13/16 2 EC-14P 0.80 112,000 98 85 6 x 15 87 41 27-1/4 32 5 16-13/16 2 EC-14-0.9 0.90 126,000 109 95 6 x 15 86 41 27-1/4 32 5 16-13/16 2 EC-15P 1.00 140,000 123 107 6 x 15 87 46 32-1/4 37 5 21-13/16 2 EC-15-1.1 1.10 154,000 134 117 6 x 15 86 46 32-1/4 37 5 21-13/16 2 EC-16P 1.15 161,000 141 123 6 x 15 87 51 37-1/4 42 6 26-13/16 4 EC-16-1.25 1.25 175,000 152 132 6 x 15 86 51 37-1/4 42 6 26-13/16 4
BOILER MODEL
NO.
GPH BTUH
AHRI
BURNER
CAPACITY
OIL INPUT † §
D.O.E.
HEATING
CAPACITY
MBH *
WATER
APPROX.
OVERALL
LENGTH
“A”
AHRI
WATER
NET
RATING
MBH *
AHRI
CHIMNEY SIZE
DIMENSIONS (inches) #
I.D. ROUND
X HEIGHT
(in x ft)
AFUE %
BOILER
LENGTH
“B”
BOILER
LENGTH
“C”
FLUE
DIA.
“D”
DISTANCE BETWEEN
LEGS
“E”
FLUE OUTLET LENGTH
“F”
Figure 1: Dimensions
Supply Pipe Mounted
Tridicator
A
Panel Mounted Tridicator Temperature Sensor Well
Panel Mounted Tridicator Pressure Sensor Well
1-1/4 threaded
supply
Relief valve 3/4’’
Flue outlet øD
1-1/4 threaded return pipe
Drain outlet
EUTECTIC EC-10
3
THE INSTALLATION INSTRUCTIONS IN THIS MANUAL ARE ABBREVIATED. SEE THE FRONT COVER OF THIS MANUAL FOR REFERENCES TO CODES AND STAN­DARDS.
BOILER LOCATION
CAUTION: NEVER BURN GARBAGE OR PAPER IN THE
UNIT, AND NEVER LEAVE COMBUSTIBLE MATERIAL AROUND IT.
Provide a level, solid foundation for the boiler. Location should be near the chimney so that the Flue Pipe Connector or Breeching to the chimney is short and direct.
A. The foundation must be capable of supporting the weight
of the boiler when filled with water:
* Includes burner, circulator and controls
B. The EC-10 Boiler has full wet base sections which sur-
round fire-box for maximum heat absorption of burning fuel, and low floor temperature.
C. The boiler can be installed on both combustible and non-
combustible floors, but must NOT be installed on or above carpeting.
D. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific require­ments.
MINIMUM CLEARANCE
Provide accessibility clearance of 24" from surfaces requiring servicing (top and front) and 20" on any side requiring pas­sage. The boiler shall be installed with the following MINIMUM clearances from combustible materials: A. CHIMNEY CONNECTOR-18" B. BACK- 6" EXCEPT as limited by 18" clearance from chim-
ney connector
C. SIDES- 2" EXCEPT as limited by 18" clearance from chim-
ney connector
NOTE: Except in closets and alcoves, clearances above in (A) and (B) may be reduced by providing forms of protection as specified in NFPA 31, latest edition.
See bottom of page 4 for clearance diagrams.
CHIMNEY REQUIREMENTS (see NFPA 211, latest edition)
A. The chimney must be constructed in accordance with all
local applicable codes and the National Board of Fire Underwriters. See boiler models and rating table shown on page 2 for chimney sizes.
B. Check chimney condition.
Existing chimneys and stacks may have deteriorated; with­out repairs their use would be hazardous. Before connect­ing to an old chimney or stack:
1. Clean it.
2. Inspect it thoroughly.
3. Remove obstructions.
4. Replace worn sections of metal stacks.
5. Seal bad masonry joints.
6. Repair damaged lining.
C. Breeching area must not be reduced at connection into
chimney. Breeching must be inserted into, but not beyond, inside of chimney liner.
D. Chimney height shall extend at least 3 feet above where it
passes through the roof of the building, and at least 2 feet above any ridge within 10 feet of the chimney.
E. The use of a vent cap, where permitted by code, gives
additional protection against adverse wind conditions and precipitation.
F. Flue Connection: Connect flue pipe between top of boiler
and chimney. Horizontal sections of flue pipe must be pitched upward to the chimney at least 1/4" per foot. Flue must be inserted into, but not extend beyond, the inside wall of the chimney flue. Draft regulator is not required but may be installed if conditions warrant it. Install draft regula­tor in flue pipe, as shown in figure 2.
CAUTION: AN OIL-FIRED UNIT SHALL BE CONNECTED TO A VENT HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF THE UNIT.
AIR SUPPLY AND VENTILATION (see NFPA 31, latest edition) Sufficient air for combustion and ventilation in the boiler room must be provided. Failure to do this will result in poor combus­tion, heavy sooting and health hazards. Any oil-fired boiler must have a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney draft* is
Boiler Approximate Total Weight of Boiler
Size Assembly*, filled with water
EC-13 353 EC-14 426 EC-15 501 EC-16 575
EC-13
EC-14 & 15
EC-16
(3) Baffle Plates
(2) Baffle Plates
center & right side
when viewing from
front
(0)
EC-10 SERIES BAFFLE PLACEMENT:
EUTECTIC EC-10
4
Sufficient space shall be left clear around the boiler.
the minimum recommended dimensions for providing easy access around the boiler.
8578N016
20
A
40
22
7/
16
20
20
33
7/8
Boiler A (in)
EC-13 22
1
/4
1
/4
EC-14 27 EC-15 32
1
/4
EC-16 37
1
/4
EC-10
Do not stack items on or box in the appliance within the required clearances to combustibles.
The figures stated in inches in the drawing below are
CHIMNEY
BOILERBOILER
PITCH UP 1/4" PER LINEAR FOOT
DO NOT INSTALL DRAFT REGULATOR HERE
BAROMETRIC DRAFT CONTROL INSTALLED ON VERTICAL RISE
18"
MINIMUM
9"
PITCH UP 1/4" PER LINEAR FOOT
DOUBLE SWING BAROMETRIC DRAFT CONTROL INSTALLED ON HORIZONTAL CONNECTOR
DRILL 1/4" HOLE TO MEASURE DRAFT,SMOKE,CO % AND STACK TEMPERATURE
DO NOT INSTALL DRAFT REGULATOR HERE
9"
18"
MINIMUM
2
DRILL 1/4" HOLE TO MEASURE DRAFT,SMOKE,CO % AND STACK TEMPERATURE
2
CHIMNEY
Figure 2. Barometric Draft Regulator Location
unreliable, CO2and overfire draft* will change unpredictably. DO NOT vent this boiler to the same chimney flue used by a
fireplace or coal or wood burning furnace or boiler. The draft* produced by solid fueled devices varies tremendously between high fire and low fire:
In modern, weather stripped, energy-saving buildings or older buildings which have been modified similarly, natural infiltra­tion may not supply enough air for combustion, particularly if other fuel burning appliances, exhaust fans or draft inducers are competing for the same air supply. Fireplaces, other solid fuel burning appliances and exhaust fans consume great quantities of air; if air supply is not ample, such an appliance will create a downdraft in the oil-fired boiler flue. This can cre­ate a hazardous condition. Flue gases can be sucked out of
the chimney through the vent regulator into the living space. DO NOT operate this boiler and a solid fuel burning appliance at the same time, unless the solid fuel burner is provided with its own outside air supply.
See Table 2, “Provisions for Combustion and Ventilation Air Supply” for determining need and method of providing air for combustion and ventilation.
If fly screen must be used over air supply openings, areas cal­culated should be doubled; the screen should be inspected and cleaned frequently to maintain free air flow.
Protect air openings against closure by snow, debris, etc. Openings such as doors or windows, if used, must be locked open.
TABLE 2: Provisions for Combustion and Ventilation Air Supply. See NFPA 31, latest edition for more detailed information.
Boiler Location Air Supply
2.1 Unconfined space Is there sufficient air for combus­tion by natural infiltration (see NOTE (1), “Test...” below)?
2.2 Unconfined space If there is NOT sufficient air for combustion by natural infiltration due to tight construction or other conditions, then it REQUIRES AIR FROM OUTDOORS. SEE “ACTION REQUIRED” column at right. See Notes (1) and (2) below.
2.3 Confined space If there is sufficient air for combus­tion from within building but it comes from outside of the confined space, see “ACTION REQUIRED” column at right. See Note (1) below.
2.4 Confined space If there is NOT sufficient air for combustion due to tight construc­tion or other conditions it REQUIRES AIR FROM OUT­DOORS. SEE “ACTION REQUIRED” column at right. See NOTE (2) below.
Action Required
NONE
Provide air from outdoors directly through a permanent out­side wall opening or openings with a free open area of not less than 1 sq. in. per 4000 Btu/hr of TOTAL input of ALL fuel burning appliances in the building. See Note (1) and (3).
The confined space shall be provided with two permanent air openings, one near the top of the enclosure and one near the bottom. EACH opening shall have a free air opening of not less than 1 sq. in. per 1000 Btu/hr. of TOTAL input of ALL fuel burning appliances within the enclosure. The two openings shall freely communicate with the interior areas of the building which in turn would have to have adequate infiltration of air from outdoors. See Notes (1, 3) and Figure 3a.
(a) Air from the outdoors shall be provided to the confined
space by two permanent openings, one in or near the top of the enclosure space and one in or near the bottom. The openings shall communicate directly, or by means of ducts, with outdoors or to such spaces (crawl or attic) that freely communicate with outdoors (See figures 3b, 3c and 3d).
(b) Where directly communicating with outdoors or by means
of vertical ducts, each opening shall have a free area of not less than 1 sq. in. per 4,000 Btu/hr. (35 sq. in. per gal. per hr.) of total input rating of all appliances in the enclo­sure. If horizontal ducts are used, each opening shall have a free area of not less than 1 sq. in. per 2,000 Btu/hr. (70 sq. in. per gal. per hr.) of total input of all appliances in the confined space. See Figures 3b, 3c and 3d.
(1) Test for sufficient air for combustion by infiltration by running this boiler for 30 minutes under all of the following conditions and at the same time: a) all doors, win-
dows and other like openings must be closed, b) all fuel burning appliances should be FIRING, c) all exhaust fans and clothes dryers turned ON. At the above conditions the CO2, smoke and draft readings must be normal. (CO2between 11% and 13%, smoke between ZERO and a TRACE, draft between .02” W.C. and
.04” W.C. negative pressure in the breeching.) (2) Aside from tight construction, some of the conditions that steal air for combustion from a boiler are other fuel burning appliances, exhaust fans and clothes dryers. (3) Generally, louvers made of wood have a free open area of 20% and those made of metal have a 60% to 70% free open area. Screens also reduce the open area
of the louvers. Fly screen can reduce air opening by 50%.
* Draft is negative or suction pressure
EUTECTIC EC-10
5
EUTECTIC EC-10
6
6 IN. MAX.
12 IN MAX
CHIMNEY
6 IN. MAX.
12 IN MAX
CHIMNEY
CHIMNEY
CHIMNEY
Figure 3a.
Appliances located in confined spaces. Air from inside the building. See Table 2 (2.3).
Figure 3b.
Appliances located in confined spaces. Air from out­doors. See Table 2 (2.4).
Figure 3c.
Appliances located in confined spaces. Air from out­doors through ventilated attic. See Table 2 (2.4).
Figure 3d.
Appliances located in confined spaces. All air from outdoors through ventilated crawl space and outlet air to ventilated attic. See Table 2 (2.4).
The opening size recommendation just given is for guidance only. It is the installer’s responsibility to provide air for combus­tion and ventilation to all appliances, under all operating con­ditions, for each installation. See NFPA 31, latest edition for more specific details.
INSTALLING CONTROLS AND ACCESSORIES ON BOILER UNITS Notes:Jacket must be installed on boiler units prior to
installation of trim. WATER BOILER TRIM, see page 2, figures 1 and 2 for tap­ping locations.
WATER PIPING FOR HOT WATER HEATING BOILERS
NOTE: On knocked-down boiler only, jacket may be installed after return piping connection, but must be installed prior to adding trim, supply piping and drain valve. I. CIRCULATING SYSTEM
A. FORCED CIRCULATION hot water heating system: Use
the top tapping as supply tapping, and use the rear bot­tom tapping for the return.
B. A FLOW CONTROL VALVE will prevent gravity circula-
tion and is required when an external tankless heater, an indirect water heater or multiple circulators are installed.
II. AIR CONTROL SYSTEMS
A. DIAPHRAGM-TYPE COMPRESSION TANKS are used
to control system pressure in an AIR ELIMINATING SYSTEM: an automatic air vent is used to REMOVE air from the system water. (See figure 4) If system pressure needs further control, add an addi­tional tank or install a larger capacity tank. The automatic air vent should be installed in the top of the boiler, as in figure 4 and at radiation high points.
B. CONVENTIONAL COMPRESSION TANKS (non-
diaphragm type) are used to control system pressure in an AIR COLLECTING SYSTEM. Within the system, after initial start-up and venting, air is collected in the tank and acts in contact with the water to control pres­sure. Air is not vented from this system except at radia­tion high points.
If system pressure needs further control, add another tank in parallel with the original tank or install a large capacity tank. Locate the tank at the inlet end of the pump near the boiler.
C. HOT WATER RADIATION VENTING - Manual air vents
should be installed at the top of all "drops" (where pip­ing goes downward). Air must be vented or purged from all zone lines to permit proper system heating.
D. PUMP LOCATION - Locating low-head pump(s) on
return to boiler is only acceptable in residences of one or two stories. The pump location shown in figure 4 is required in large, multi-story building installations, espe­cially when high-head pumps are used and is also rec-
ommended for all applications. IMPORTANT: Hot water heating systems containing high water volume, such as would occur with cast iron radiation, require special care with air elimination.
The circulator pump should be located on the boiler supply pipe and the expansion tank and air scoop should be located near the pump suction. For alternate circulator pump location on return for low-head pumps and one or two story buildings ONLY.
DOMESTIC HOT WATER
For Indirect-fired storage water heater application, see Slant/Fin publication WH-10, Sizing Guide WH-SG and Installation manual WH-40. The installation manual includes several control systems and relay centers for space and domestic water heating in addition to plumbing.
INSTALLING THE BURNER
See Burner Data, pages 13-17, and Burner Manual supplied with burner. If burner is not mounted as received, mount to boiler, placing flange over mounting studs. Use gasket between flange and boiler. Distance between flange and nose of burner must be as shown on pages 13-17. Check to see that nozzle and settings are as given in burner data tables, pages 13-17.
CAUTION: Do Not use gasoline, crankcase drainings, or any oil containing gasoline.
Figure 4. Air Eliminating System or Alternating Collecting System. Pipe off to a safe place the relief valve and drain outlet.
EUTECTIC EC-10
7
Air Eliminator as per Manufacturer Specifications
To Circ. (s) and Zones
Tridicator
Relief valve 3/4
Panel Mounted
Tridicator Temperature
Sensor Well
13-31/32
7-11/16
1-1/4 NPT return tapping
Drain outlet
Panel Mounted Tridicator Pressure Sensor Well
1/2” NPT Tapping for Feed Valve and Expansion Tank
1-1/4”
NPT
Supply
Automatic Air Vent
Suppy Pipe Mounted
EUTECTIC EC-10
8
OIL SUPPLY PIPING
Install the oil tank or tanks and piping from tank to burner. Follow local codes and practices, INSTALLATION OF OIL BURNING EQUIPMENT, NFPA 31, latest edition, and the instruction sheet attached to the oil burner pump. A one-pipe system should be used for gravity-fed fuel systems and for lift systems, where the total lift is less than 8 feet. Where the total lift is greater than 8 feet, a two-pipe system must be used. In some instances, local codes may require a two-pipe system for below grade fuel oil tanks. Be sure to set up the fuel oil pump for the piping system used; follow the instructions attached to the pump. Be sure to include a good quality, low pressure drop fuel oil filter in the supply line from the tank. This is necessary, especially at low fuel oil flow rates (small nozzle sizes), to prevent nozzle plugging. Fuel oil shutoff valves should be installed at the burner on the supply (and return if two-pipe) to facilitate servicing. See Slant/Fin publica­tion on one-pipe and two-pipe fuel oil systems.
WIRING THE BOILER
(see National Electric Code ANSI/NFPA 70-latest edition) A. The wiring diagrams for the burner and boiler may be found
on pages 11 through 15.
B. 24 volt control wiring should be approved Safety Circuit
wire, protected as needed.
C. Power supply wiring to the burner must be 14 gauge, as
required, and should have a properly fused disconnect switch. 120 volt wiring to pumps and safety controls must also be 14 gauge. Wire must be enclosed in approved conduit.
D. The wires supplying power to the burner MUST go through
the quick disconnect plugs provided with the boiler.
E. All wiring must be installed in compliance with the National
Electric Code, or any local or insurance codes having
jurisdiction. Wiring to the boiler must come through an emergency power isolation switch with a clearly marked red switch plate. This switch should be located so that it is apparent to the home­owner when entering the basement or other boiler area. The homeowner should be made familiar with operating the toggle to provide or stop the power to the boiler.
VENT PIPING AND DRAFT REGULATOR
(see NFPA 31, latest edition) A. Vent connectors must be the same diameter as the boiler
flue collar. (See page 2) B. Vent pipes and breeching must be pitched upward a mini-
mum of 1/4" per foot. C. Connect vent pipe to the chimney using as few elbows as
possible and as short as possible within NFPA 31 or
authority. D. Horizontal vent connector into the chimney should not be
inserted beyond the inside wall of the chimney. E. Install barometric draft regulator on horizontal breeching,
near chimney, with hinge horizontal and face vertical condi-
tions permitting as in Figure 3a. See Figure 3b as a second
choice. See manufacturer's instructions packed in carton
with barometric draft regulator. F. If two or more appliances are used on the same chimney,
see CHIMNEY, page 3. G. Make up all joints with minimum air leaks, secure with
sheet metal screws.
PRECAUTIONS BEFORE STARTING OIL BURNER
Make a positive check of A through F before starting burner: A. Boiler and system are full of water. All air is vented from
system. See below. B. All wiring is completed. See page 11 through 15. C. Oil supply is connected to the burner; nozzle is installed
correctly; oil valve is open at tank. D. Main cast iron door on which burner is mounted is bolted
shut and fiberglass rope seal is making good contact. E. Smokepipe is connected to chimney. F. All combustible materials are cleared away. G. Combustion air supply is provided. See page 3. H. Burner settings are adjusted as per pages 8, 9, 17-21 and
as shown on boiler jacket.
START-UP (COMBUSTION TEST INSTRUMENTS MUST
BE USED) THIS BOILER IS A POSITIVE PRESSURE BOILER.
A. Make sure the boiler is installed and wired properly and is full
of water. B. The observation port cover is mounted on the hinged burner
mounting door (see figure 2 on page 2). NEVER touch the
port cover or any surrounding surfaces with hands. They may
be HOT. Use tools. Loosen the 2 screws and swing cover
until window is directly below pivot (and tighten 2 screws) to
observe through window. Loosen the 2 screws and swing
cover until slot is directly below pivot (and tighten 2 screws)
to be able to insert probe through slot. See the burner
instructions for bleeding air, etc. Step away from the boiler
and start the oil burner. C. IMMEDIATELY, set burner air bands to obtain a bright fire
without smoke or oil stain. Set the DRAFT REGULATOR to
obtain .02" – .04" draft at the breeching. D. Tighten the observation door screw. Allow the burner to fire
for at least one hour total firing time, to bake out the volatile
binders in the combustion chamber before taking final com-
bustion readings. E. By alternate adjustment of the barometric draft regulator, the
burner air regulation and head regulation devices (whichever
apply), set for a zero to a trace of smoke and 12% CO
2
.
Then open the air bands or shutter (whichever apply) an
additional 1/8". This should result in zero smoke with NO raw
oil on the smoke paper and a smooth light-off. DO NOT
ATTEMPT TO SET FIRE BY EYE. Flame retention burners
may appear efficient and smoke free from an inefficient 7%
up to an overly high 14% CO
2
. However, a very low CO2can
also result in poor ignition and raw (unburned) oil entering the
fire box. At very high CO
2
, any slight decrease in air flow for
any reason will cause incomplete combustion, with high
smoke and dry soot formation in the fire box. F. Once burner and draft have been set up, then smoke, CO
2
and stack temperature should be checked and recorded. If
smoke is greater than trace, review the burner instructions
and replace the nozzle if necessary. Normal smoke to be
expected is zero to a trace. G. Make sure that the observation port cover is closed and
the screw is tightened.
CLEANING AND FILLING A NEW WATER BOILER
I. There are a number of commercial preparations available
from your distributor for cleaning and for corrosion protection
conditioning the internal (waterside) surfaces of boilers.
Follow the preparation manufacturer’s instructions.
DANGER:
Use CAUTION when handling chemicals and draining hot water from a boiler. Scalding water and/or chemicals can cause permanent injury to the skin, eyes and respiratory system.
Loading...
+ 16 hidden pages