Clearing a Lockout – Any of the following methods
can be used to clear a Lockout:
1. Display - Clear the lockout from the display Home
Screen; press “OK” button on the keypad (see
Figure 1-2).
2. Controller - Clear the lockout by pressing the
RESET button situated on the boiler controller near
the indicator lights (see Figure 1-1).
3. Switch - Cycle power to the boiler using the power
on/off switch situated on the display console.
Reset Button
CHS Series Controller and Display │Slant Fin Corp.
1.0 INTRODUCTION
The Controller and Display, together, form the control system of the Slant/Fin CHS boiler. All control
configuration parameters are stored in non-volatile memory in the CHS controller. Access to controller status
and configuration is achieved with the display. Interaction with the display is performed by physically touching
the buttons on the display keypad. Communication between the CHS controller and display is via EIA-485
interface using the Modbus RTU protocol.
When the appliance is powered there is a brief interval while the display retrieves data from the boiler control.
The display then shows the Home Screen (Summary screen) similar to the one depicted in Figure 1-2. The Home
Screen provides a summary of the overall operational status of the boiler. A series of menus, entered by pressing
the “i-Information” button, provide access to all boiler configuration parameters, information and diagnostics.
1.1 Clearing a Lockout
Figure 1-1 Clearing a Lockout
1.2 Keypad
See Figure 1-2 and Table 1-1 for a complete description of the functions of each keypad button.
Directional Arrow Buttons – are used to quickly navigate through the menu structures and within each
individual screen.
OK Button – Confirms/enters an item selection.
BackButton – returns the user to the previous screen.
i-Information Button – accesses the Main Menu where all control settings, diagnostics, etc are accessed
Home Button – immediately returns the display to the Home Screen.
via a series of sub-menus.
2
Analog Sensors I/O
Digital I/O
Outlet temp
Inlet temp
Delta T
DHW temp
Stack temp
Outdoor temp
Fan speed
Flame signal
Firing rate
4-20mA input
System sensor
70 oF
70 oF
1 oF
OPEN
71 oF
OPEN
LOW
0.00 A
0 RPM
OPEN
Outlet
Boiler pump (B)
CH pump (C)
DHW pump (A)
Blower/HSI
Eternal ignition
Pilot valve
Main valve
Alarm
Interlock (ILK)
Pre-ignit interlock (PTI)
Load control input (LCI)
STAT (Demand)
Time Of Day
Safety relay
off
off
off
off
off
off
off
off
on
off
off
off
off
off
7
1 2 3
6
4
5 9 8
10
11
12
13
Slant Fin Corp.│Controller and Display CHS Series
1.3 Home Screen
The Home Screen is displayed following initial power-up and can be displayed at anytime by simply pressing the
“Home” button. The Home Screen provides a summary of the current boiler status, most recent Alert or Lockout,
and readings from chosen boiler sensors. Figure 1-2 below, identifies each Home Screen and keypad item; Table
1-1 describes them.
Figure 1-2 Home Screen & Key Pad Identification
From the Home Screen the display offers easy access to diagnostic screens through the use of the horizontal
directional buttons (◄ ►) on the display keypad. Pressing either of the horizontal buttons advances you through
the Analog Sensor I/O (inputs/outputs), Digital I/O, and then back to the Home Screen.
Figure 1-3 Diagnostic Screens
3
Item
Name
Description
1
Back button
Returns the display to the previous screen in the menu structure.
2
i-Information button
Displays the Main Menu screen, where all control settings, diagnostics, etc are accessed
via a series of sub-menus.
3
Home button
Returns the display to the Home Screen (screen illustrated in Figure 1-2).
4
Directional buttons
(horizontal)
Left and right buttons (◄ ►) allow navigation within some display screens. Also
provide access, via the Home Screen, to controller input and output diagnostic screens.
5
OK button
Used to select highlighted display items, necessary for confirming settings.
6
Direction buttons
(vertical)
Up and down buttons (▲ ▼) allow navigation within display screens.
7
Boiler summary
Provides the status of five (5) boiler readings (i.e. sensor inputs or boiler operating
conditions). From a list of 15 readings, the user can select which 5 will be displayed
/summarized on the Home Screen, see Section 2.6 Display Setup
8
Boiler name
Provides the name of the boiler, i.e. 110MBH; user can choose to change the name, see
Section 2.4.4.1 System ID & Access.
9
State
Indicates the current state of burner operation:
Initiate
Standby delay
Standby
Safe startup
Prepurge - Measured purge time
Prepurge - Drive to lightoff rate
Pre ignition test
Direct Burner ignition
Run
Postpurge
Lockout
10
Demand
Indicates the current heat demand source:
OFF (no heat demand)
CH (Central Heat demand – CH1)
LL [ Lead Lag heat demand – CH2 (LL)
DHW (Domestic Hot Water demand)
CH frost protection
DHW frost protection
LL frost protection
11
Access Status
Indicates the present level of access:
User (indicates that no password has been entered – adjustment of certain settings
will be blocked.
Installer (indicates that the installer password, “sola” has been entered, allowing
adjustment of all field adjustable parameters).
12
Lockout/alert/hold
Indicates the most recent Alert, or a current Hold or Lockout.
13
Clear
When selected, clears the most recent Alert from the Home Screen; also resets and clears
a current Lockout.
CHS Series Controller and Display │Slant Fin Corp.
Table 1-1 Home Screen & Key Pad Description (Reference Figure 1-2)
4
i-Information – Main Menu screen, accessed
by pressing the “i” button, lists the major submenus. Use the arrow buttons to navigate the
menu options; when the desired option is
highlighted it will appear at the top of the
screen (i.e. Quick Start in the example right);
select by pressing the “OK” button.
Menu Item
Description
Reference
Quick Start
Provides a summary of the most common settings for installer adjustment.
Section 2.1
Login
Provides access to a keypad for entry of the installer password – many
parameters are installer level password protected.
Section 2.2
Test
Allows the installer to test specific firing rates and pump operation manually.
Section 2.3
Advanced Setup
Provides access to all parameter settings (including those in Quick Start), for
more advanced settings.
Section 2.4
Diagnostics
Lists the status of all controller inputs and outputs (i.e. sensors and switches);
also provides access to a history of Alerts and Lockouts.
Section 2.5
Display Setup
Allows the installer to set what information (i.e. sensor status) is displayed on the
Home Screen.
Section 2.6
Quick
Start
Test
Diagnostics
Login
Advanced
Setup
Display
Setup
QuickStart
Slant Fin Corp.│Controller and Display CHS Series
2.0 i-Information Screen (Main Menu)
Figure 2-1 i-Information Screen
Table 2-1 i-Information Screen Menu Options
5
Quick Start – screen, accessed by selecting
“Quick Start” from the “i-Information” screen,
provides a summary of the most common settings
that will need to be adjusted (or considered) when
initially setting up the boiler. Use the up and down
(▲▼) buttons to navigate the menu options; when
the desired option is highlighted select by pressing
the “OK” button.
Each of the parameters under Quick Start are also
listed under separate setting groups under
“Advanced Setup”; where more advanced settings
can be accessed..
Parameter
Description
Factory Setting
CH setpoint
Setpoint value for CH modulation. If “Outdoor reset” is set to “Disable”, this is
the target temperature at the “Modulation sensor”. If “Outdoor reset” is set to
“Enable”, this is the maximum target temperature at the “Modulation sensor”
(Setpoint for CHI heat input).
180ºF
DHW setpoint
Boiler setpoint for DHW modulation. Range 60°F to 190°F
180ºF
Outdoor reset
Enables or disables CH outdoor reset function for CH1 heat inputs.
Enable
Low water temp
Minimum boiler setpoint; occurs when the outdoor temperature is equal to or
greater than the “Max outdoor temp”. Range 60°F to 140°F
95ºF
Max outdoor temp
Outdoor temperature that corresponds to the “Low water temp” setting.
Example:If the “Low water temp” setting is 95°F, and the “Max outdoor
temp” setting is 70°F, the boiler setpoint will be 95°F when the outdoor
temperature is 70°F or higher. Range 50°F to 95°F
70ºF
Min outdoor temp
Design Temperature - Outdoor temperature that corresponds to the “CH
setpoint” setting. Example: If the “CH setpoint” is 180°F, and the “Min
outdoor temp” setting is 0°F, the boiler setpoint will be 180°F when the
outdoor temperature is 0°F or lower. Range -40°F to 40°F
0ºF
Adjustable high
limit
Outlet water temperature high limit. Controller will not permit burner
operation above this setting. Recommend leaving configured as 200ºF. Range
100°F to 200°F
200ºF
Adjustable stack
limit
Stack exhaust gas high limit. Controller will lockout if exhaust gas
temperature exceeds this setting. Range 145°F to 220°F
220ºF
CH setpoint
DHW setpoint
Outdoor reset
Low water temp
Max outdoor temp
Min outdoor temp
Adjustable high limit
Adjustable stack limit
180 oF
180 oF
Enable
95
o
F
70
o
F
0
o
F
200
o
F
220
o
F
QuickStart
CHS Series Controller and Display │Slant Fin Corp.
2.1 Quick Start
Figure 2-2 Quick Start Screen
Table 2-2 Quick Start Configuration Parameters
6
Login - Parameters that are password protected
require an installer to enter the password before they
can be changed. A message indicating this may
appear when a password protected parameter is
selected. To enter the password, touch the “iInformation” button and select Login to access the
keyboard screen.
Use the horizontal and vertical directional buttons
(▼▲◄►) on the keypad to navigate the keyboard
screen. Once the desired letter or number is
selected/highlighted, press the round “OK” button on
the keypad to confirm selection.
Once the password is filled in, select/highlight “OK”
on the keyboard, and press the round OK button on
the keypad to confirm selection.
Figure 2-4 Test Screen Menu
Test – menu screen, accessed by selecting “Test”
from the “i-Information” screen, lists the three test
screen options. Use the up and down (▲▼) buttons
to navigate the menu options; when the desired option
is highlighted select by pressing the “OK” button.
Password - Many of the configuration parameters are password protected. The required case-sensitive password is "sola" and must be entered in lower-case letters.
2.3 Test
7
Figure 2-5 Forced Rate Test Screen
Forced Rate – test screen, permits the installer to
force the burner to operate at “high fire” or “low fire”
for the purpose of combustion setup and diagnoses.
Set the “Manual firing rate” to high or low fire by
using the up and down (▲▼) buttons to highlight
either “Set high fire” or “Set low fire”; then select it
by pressing the “OK” button.
When the test is complete, select “Stop test” to return
firing rate control to automatic.
The burner MUST be firing
to initiate “Start test”.
Parameter
Description
Set high fire *
When selected, sets “Manual firing rate” setting equal to the maximum modulation rate of the boiler.
Set low fire *
When selected, sets “Manual firing rate” setting equal to the minimum modulation rate of the boiler.
Start test *
When selected, initiates the forced rate test, burner will operate at the “Manual firing rate” setting
indicated on the screen. To stop test select “Stop test”; which will be displayed in place of “Start test”
once the test is initiated.
* = Password protected
State
Firing rate
Fan speed
Outlet temp
Manual firing rate
Test State: Idle
Test Timer: 0 sec
Set high fire
Set low fire
Start test
Standby
0 RPM
Low
71 oF
1625 RPM
ForcedRate
Burner must be in run state
CHS Series Controller and Display │Slant Fin Corp.
2.3.1 Forced Rate
Table 2-3 Forced Rate Parameters
8
Figure 2-6 Manual Burner and Pump Operation Test Screens
Parameter
Description
Default
Burner
Switch *
Allows the installer to manually switch the burner off and on.
On
Manual
firing rate *
Establishes the burner firing rate (blower RPM) when “Firing rate control” is set to
“Manual in Run” or “Manual in Run & Standby”. Feature may be useful as a diagnostic
tool; i.e. to test burner operating characteristic at a specific firing rate.
N/A
Firing rate
control *
Establishes the firing rate control of the boiler:
Auto (firing rate – blower RPM is controlled by the boiler control)
Manual in Run (blower RPM is set to the “Manual firing rate” setting; only when
burner is running).
Manual in Run & Standby (blower RPM is set to the “Manual firing rate” setting).
Auto
* = Password protected
Burner switch
Manual firing rate
Firing rate control
Off
1625 RPM
Auto
ManualBurnerOperation
CH Pump Control
DHW Pump Control
Boiler Pump Control
Auto
Auto
Auto
ManualPumpOperation
Slant Fin Corp.│Controller and Display CHS Series
2.3.2 Manual Burner and Pump Operation
Manual Burner Operation – test screen, allows the installer to manually control the firing rate of the burner.
Using the up and down (▲▼)buttons to highlight the menu options, and the “OK” button to select them, set “Firing rate control” to “Manual”, then adjust “Manual firing rate” to the desired value.
Manual Pump Operation – test screen, allows the installer to manually turn the individual pumps on. Using the
up and down (▲▼) buttons to highlight the menu options, and the “OK” button to select them, set the desired “Pump Control” to “On”.
Table 2-4 Manual Burner Operation Parameters
The burner MUST be firing to initiate Manual Burner Operation.
Setting “Burner switch” to “Off” will inhibit burner operation, regardless of the operating
conditions.
When the test is complete, return the settings to “Auto” to allow the control to
automatically turn the circulators off and on and modulate the burner firing rate as needed.
9
Figure 2-7 Advanced Setup (Menu) Screen
Advanced Setup – menu screen, accessed by
selecting “Advanced Setup” from the “i-Information”
screen, lists all of the configuration parameter groups.
Use the up and down (▲▼) buttons to navigate the
menu options; when the desired option is highlighted
select by pressing the “OK” button.
Login – adjustment of many of the advanced settings
will prompt the user to login.
Name
Description
Reference:
CH Config
Edit Central Heat settings; CH1 heat input.
Section 2.4.1
DHW Config
Edit Domestic Hot Water settings.
Section 2.4.2
Lead Lag Config
Edit Lead-Lag Master and Slave settings; CH2 (LL) heat input.
Section 2.4.3
System Config
Edit temperature units, anti-short-cycle time, alarm silence time.
Section 2.4.4
Modulation Config
Edit burner modulation settings.
Section 2.4.5
Delta T Limits
Edit delay time for delta-t limit.
Section 2.4.6
T-rise Limits
Edit delay time for T-rise limit.
Section 2.4.6
Frost Protection Config
Enable/disable CH, DHW and LL frost protection
Section 2.4.7
Burner Timings & Rates
Read only, for information only.
Section 2.4.8
Burner Control Ignition
Read only, for information only.
Section 2.4.9
CH Config
DHW Config
Lead Lag Config
System Config
Modulation Config
Delta T Limits
T-rise Limits
Frost Protection Config
Burner Control Timings & Rates
Burner Control Ignition
AdvancedSetup
CHS Series Controller and Display │Slant Fin Corp.
2.4 Advanced Setup
Table 2-5 Advanced Setup Menu Options
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.