Slant/Fin CHS-399 User Manual

Page 1
This manual must be left
®
C US
hung on or adjacent to the
boiler for reference.
HIGH EFFICIENCY FIRETUBE
CONDENSING GAS BOILER
MODELS CHS-85 through CHS-399
– APPENDIX A –
CONTROLLER AND DISPLAY INSTRUCTIONS
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS AND STATEMENT
SYMBOLS AND DEFINITIONS BEFORE READING THE
INSTALLATION INSTRUCTIONS
DANGER
!
Danger Sign: Indicates a hazardous situation which,
if not avoided, will result in serious injury or death.
WARNING
!
Warning Sign: Indicates a hazardous situation which, if not avoided, could result in serious injury or death.
CAUTION
!
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situa-
tion which, if not avoided, could result in minor or moderate injury.
CAUTION
Caution Sign without Safety Alert Symbol: Indicates a hazardous
situation which, if not avoided, could result in property damage.
NOTICE
Notice Sign: Indicates a hazardous situation which, if
not avoided, could result in property damage.
WARNING
!
This Boiler must be installed by a licensed and trained Heating Techni­cian or the Warranty is Void. Failure to properly install thisunit may re-
sult in property damage, serious injury to occupants, or possibly death.
©Slant/Fin Corp. 2013 • 813 • PUBLICATION CHS-CD-40
Page 2
Table of Contents
1.0 INTRODUCTION ........................................................................................................................... 1
1.1 Clearing a Lockout .................................................................................................................... 1
1.2 Keypad ....................................................................................................................................... 1
1.3 Home Screen ............................................................................................................................. 2
2.0 I-INFORMATION SCREEN (MAIN MENU) ................................................................................ 4
2.1 Quick Start ................................................................................................................................. 5
2.2 Login ......................................................................................................................................... 6
2.3 Test ............................................................................................................................................ 6
2.3.1 Forced Rate ................................................................................................................... 7
2.3.2 Manual Burner and Pump Operation ............................................................................ 8
2.4 Advanced Setup ......................................................................................................................... 9
2.4.1 CH Config .................................................................................................................. 10
2.4.1.1 CH Config – CH Config ............................................................................. 10
2.4.1.2 CH Config - Outdoor Reset Config ............................................................ 12
2.4.1.3 CH Config - Warm Weather Shutdown ...................................................... 13
2.4.2 DHW Config .............................................................................................................. 14
2.4.3 Lead Lag Config ......................................................................................................... 15
2.4.3.1 Lead Lag Master Config ............................................................................. 16
2.4.3.2 Use of 4-20mA Input .................................................................................. 17
2.4.3.3 Lead Lag Slave Config ............................................................................... 18
2.4.3.4 Lead Lag Outdoor Reset ............................................................................. 19
2.4.4 System Config ............................................................................................................ 20
2.4.4.1 System ID & Access ................................................................................... 20
2.4.4.2 Pump Config ............................................................................................... 22
2.4.4.3 Statistics Config .......................................................................................... 23
2.4.4.4 High & Stack Limits ................................................................................... 24
2.4.4.5 System Config ............................................................................................. 25
2.4.5 Modulation Config ..................................................................................................... 26
2.4.6 Delta T & T-rise Limits .............................................................................................. 27
2.4.7 Frost Protection Config .............................................................................................. 28
2.4.8 Burner Control Ignition and Timings & Rates ........................................................... 29
2.5 Diagnostics .............................................................................................................................. 30
2.5.1 History ........................................................................................................................ 31
2.6 Display Setup .......................................................................................................................... 32
Page 3
1
Clearing a Lockout Any of the following methods can be used to clear a Lockout:
1. Display - Clear the lockout from the display Home
Screen; press “OK” button on the keypad (see Figure 1-2).
2. Controller - Clear the lockout by pressing the
RESET button situated on the boiler controller near the indicator lights (see Figure 1-1).
3. Switch - Cycle power to the boiler using the power
on/off switch situated on the display console.
Reset Button
CHS Series Controller and Display Slant Fin Corp.
1.0 INTRODUCTION
The Controller and Display, together, form the control system of the Slant/Fin CHS boiler. All control configuration parameters are stored in non-volatile memory in the CHS controller. Access to controller status and configuration is achieved with the display. Interaction with the display is performed by physically touching the buttons on the display keypad. Communication between the CHS controller and display is via EIA-485 interface using the Modbus RTU protocol.
When the appliance is powered there is a brief interval while the display retrieves data from the boiler control. The display then shows the Home Screen (Summary screen) similar to the one depicted in Figure 1-2. The Home Screen provides a summary of the overall operational status of the boiler. A series of menus, entered by pressing the “i-Information” button, provide access to all boiler configuration parameters, information and diagnostics.
1.1 Clearing a Lockout
Figure 1-1 Clearing a Lockout
1.2 Keypad
See Figure 1-2 and Table 1-1 for a complete description of the functions of each keypad button. Directional Arrow Buttons are used to quickly navigate through the menu structures and within each
individual screen. OK Button Confirms/enters an item selection.
Back Button – returns the user to the previous screen.
i-Information Button – accesses the Main Menu where all control settings, diagnostics, etc are accessed
Home Button – immediately returns the display to the Home Screen.
via a series of sub-menus.
Page 4
2
Analog Sensors I/O
Digital I/O
Outlet temp Inlet temp Delta T DHW temp Stack temp Outdoor temp Fan speed Flame signal Firing rate 4-20mA input System sensor
70 oF 70 oF
1 oF
OPEN
71 oF
OPEN
LOW
0.00 A 0 RPM
OPEN
Outlet
Boiler pump (B) CH pump (C) DHW pump (A)
Blower/HSI Eternal ignition Pilot valve Main valve Alarm Interlock (ILK) Pre-ignit interlock (PTI) Load control input (LCI) STAT (Demand) Time Of Day Safety relay
off off off
off off off off off
on off off off off off
7
1 2 3
6
4
5 9 8
10
11
12
13
Slant Fin Corp. Controller and Display CHS Series
1.3 Home Screen
The Home Screen is displayed following initial power-up and can be displayed at anytime by simply pressing the “Home” button. The Home Screen provides a summary of the current boiler status, most recent Alert or Lockout, and readings from chosen boiler sensors. Figure 1-2 below, identifies each Home Screen and keypad item; Table 1-1 describes them.
Figure 1-2 Home Screen & Key Pad Identification
From the Home Screen the display offers easy access to diagnostic screens through the use of the horizontal directional buttons (◄ ►) on the display keypad. Pressing either of the horizontal buttons advances you through the Analog Sensor I/O (inputs/outputs), Digital I/O, and then back to the Home Screen.
Figure 1-3 Diagnostic Screens
Page 5
3
Item
Name
Description
1
Back button
Returns the display to the previous screen in the menu structure.
2
i-Information button
Displays the Main Menu screen, where all control settings, diagnostics, etc are accessed via a series of sub-menus.
3
Home button
Returns the display to the Home Screen (screen illustrated in Figure 1-2).
4
Directional buttons (horizontal)
Left and right buttons (◄ ►) allow navigation within some display screens. Also provide access, via the Home Screen, to controller input and output diagnostic screens.
5
OK button
Used to select highlighted display items, necessary for confirming settings.
6
Direction buttons (vertical)
Up and down buttons (▲ ▼) allow navigation within display screens.
7
Boiler summary
Provides the status of five (5) boiler readings (i.e. sensor inputs or boiler operating conditions). From a list of 15 readings, the user can select which 5 will be displayed /summarized on the Home Screen, see Section 2.6 Display Setup
8
Boiler name
Provides the name of the boiler, i.e. 110MBH; user can choose to change the name, see Section 2.4.4.1 System ID & Access.
9
State
Indicates the current state of burner operation:
Initiate Standby delay Standby Safe startup Prepurge - Measured purge time Prepurge - Drive to lightoff rate Pre ignition test Direct Burner ignition Run Postpurge Lockout
10
Demand
Indicates the current heat demand source:
OFF (no heat demand) CH (Central Heat demand – CH1) LL [ Lead Lag heat demand – CH2 (LL) DHW (Domestic Hot Water demand) CH frost protection DHW frost protection LL frost protection
11
Access Status
Indicates the present level of access: User (indicates that no password has been entered – adjustment of certain settings
will be blocked.
Installer (indicates that the installer password, “sola” has been entered, allowing
adjustment of all field adjustable parameters).
12
Lockout/alert/hold
Indicates the most recent Alert, or a current Hold or Lockout.
13
Clear
When selected, clears the most recent Alert from the Home Screen; also resets and clears a current Lockout.
CHS Series Controller and Display Slant Fin Corp.
Table 1-1 Home Screen & Key Pad Description (Reference Figure 1-2)
Page 6
4
i-Information – Main Menu screen, accessed
by pressing the “i” button, lists the major sub­menus. Use the arrow buttons to navigate the menu options; when the desired option is highlighted it will appear at the top of the screen (i.e. Quick Start in the example right); select by pressing the “OK” button.
Menu Item
Description
Reference
Quick Start
Provides a summary of the most common settings for installer adjustment.
Section 2.1
Login
Provides access to a keypad for entry of the installer password – many parameters are installer level password protected.
Section 2.2
Test
Allows the installer to test specific firing rates and pump operation manually.
Section 2.3
Advanced Setup
Provides access to all parameter settings (including those in Quick Start), for more advanced settings.
Section 2.4
Diagnostics
Lists the status of all controller inputs and outputs (i.e. sensors and switches); also provides access to a history of Alerts and Lockouts.
Section 2.5
Display Setup
Allows the installer to set what information (i.e. sensor status) is displayed on the Home Screen.
Section 2.6
Quick
Start
Test
Diagnostics
Login
Advanced
Setup
Display
Setup
Quick Start
Slant Fin Corp. Controller and Display CHS Series
2.0 i-Information Screen (Main Menu)
Figure 2-1 i-Information Screen
Table 2-1 i-Information Screen Menu Options
Page 7
5
Quick Start screen, accessed by selecting “Quick Start” from the “i-Information” screen,
provides a summary of the most common settings that will need to be adjusted (or considered) when initially setting up the boiler. Use the up and down
(▲▼) buttons to navigate the menu options; when
the desired option is highlighted select by pressing the “OK” button.
Each of the parameters under Quick Start are also listed under separate setting groups under
“Advanced Setup”; where more advanced settings
can be accessed..
Parameter
Description
Factory Setting
CH setpoint
Setpoint value for CH modulation. If “Outdoor reset is set to “Disable, this is the target temperature at the “Modulation sensor”. If “Outdoor reset is set to “Enable, this is the maximum target temperature at the “Modulation sensor” (Setpoint for CHI heat input).
180ºF
DHW setpoint
Boiler setpoint for DHW modulation. Range 60°F to 190°F
180ºF
Outdoor reset
Enables or disables CH outdoor reset function for CH1 heat inputs.
Enable
Low water temp
Minimum boiler setpoint; occurs when the outdoor temperature is equal to or greater than the “Max outdoor temp”. Range 60°F to 140°F
95ºF
Max outdoor temp
Outdoor temperature that corresponds to the “Low water temp” setting.
Example: If the “Low water temp” setting is 95°F, and the “Max outdoor temp” setting is 70°F, the boiler setpoint will be 95°F when the outdoor temperature is 70°F or higher. Range 50°F to 95°F
70ºF
Min outdoor temp
Design Temperature - Outdoor temperature that corresponds to the “CH setpoint” setting. Example: If the “CH setpoint” is 180°F, and the “Min
outdoor temp” setting is 0°F, the boiler setpoint will be 180°F when the
outdoor temperature is 0°F or lower. Range -40°F to 40°F
0ºF
Adjustable high limit
Outlet water temperature high limit. Controller will not permit burner operation above this setting. Recommend leaving configured as 200ºF. Range 100°F to 200°F
200ºF
Adjustable stack limit
Stack exhaust gas high limit. Controller will lockout if exhaust gas temperature exceeds this setting. Range 145°F to 220°F
220ºF
CH setpoint DHW setpoint Outdoor reset Low water temp Max outdoor temp Min outdoor temp Adjustable high limit Adjustable stack limit
180 oF 180 oF
Enable
95
o
F
70
o
F
0
o
F
200
o
F
220
o
F
Quick Start
CHS Series Controller and Display Slant Fin Corp.
2.1 Quick Start
Figure 2-2 Quick Start Screen
Table 2-2 Quick Start Configuration Parameters
Page 8
6
Login - Parameters that are password protected require an installer to enter the password before they can be changed. A message indicating this may appear when a password protected parameter is selected. To enter the password, touch the Information” button and select Login to access the keyboard screen.
Use the horizontal and vertical directional buttons (▼▲◄►) on the keypad to navigate the keyboard screen. Once the desired letter or number is selected/highlighted, press the round OK button on the keypad to confirm selection.
Once the password is filled in, select/highlight “OK” on the keyboard, and press the round OK button on the keypad to confirm selection.
Figure 2-4 Test Screen Menu
Test – menu screen, accessed by selecting “Test” from the “i-Information” screen, lists the three test
screen options. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
1 2 3 4 5 6 7 8 9 0 -
=
q w e r t y u i o
p
[
]
a s d f g h j k l
;
'
z x c v b n m , .
/
Shift
BS
OK
Password
sola
Forced Rate Manual Burner Operation Manual Pump Operation
Test
Slant Fin Corp. Controller and Display CHS Series
2.2 Login
Figure 2-3 Login Screen
Password - Many of the configuration parameters are password protected. The required case-sensitive password is "sola" and must be entered in lower-case letters.
2.3 Test
Page 9
7
Figure 2-5 Forced Rate Test Screen
Forced Rate test screen, permits the installer to force the burner to operate at “high fire” or “low fire”
for the purpose of combustion setup and diagnoses.
Set the “Manual firing rate” to high or low fire by using the up and down (▲▼) buttons to highlight either “Set high fire” or “Set low fire”; then select it
by pressing the “OK” button.
When the test is complete, select “Stop test” to return
firing rate control to automatic.
The burner MUST be firing to initiate “Start test”.
Parameter
Description
Set high fire *
When selected, sets “Manual firing rate” setting equal to the maximum modulation rate of the boiler.
Set low fire *
When selected, sets “Manual firing rate” setting equal to the minimum modulation rate of the boiler.
Start test *
When selected, initiates the forced rate test, burner will operate at the “Manual firing rate” setting indicated on the screen. To stop test select “Stop test”; which will be displayed in place of “Start test”
once the test is initiated.
* = Password protected
State Firing rate Fan speed Outlet temp
Manual firing rate Test State: Idle Test Timer: 0 sec
Set high fire Set low fire Start test
Standby
0 RPM
Low
71 oF
1625 RPM
Forced Rate
Burner must be in run state
CHS Series Controller and Display Slant Fin Corp.
2.3.1 Forced Rate
Table 2-3 Forced Rate Parameters
Page 10
8
Figure 2-6 Manual Burner and Pump Operation Test Screens
Parameter
Description
Default
Burner Switch *
Allows the installer to manually switch the burner off and on.
On
Manual firing rate *
Establishes the burner firing rate (blower RPM) when “Firing rate control” is set to “Manual in Run” or “Manual in Run & Standby”. Feature may be useful as a diagnostic tool; i.e. to test burner operating characteristic at a specific firing rate.
N/A
Firing rate control *
Establishes the firing rate control of the boiler:
Auto (firing rate – blower RPM is controlled by the boiler control) Manual in Run (blower RPM is set to the “Manual firing rate” setting; only when
burner is running).
Manual in Run & Standby (blower RPM is set to the “Manual firing rate” setting).
Auto
* = Password protected
Burner switch Manual firing rate Firing rate control
Off
1625 RPM
Auto
Manual Burner Operation
CH Pump Control DHW Pump Control Boiler Pump Control
Auto Auto Auto
Manual Pump Operation
Slant Fin Corp. Controller and Display CHS Series
2.3.2 Manual Burner and Pump Operation
Manual Burner Operation test screen, allows the installer to manually control the firing rate of the burner. Using the up and down (▲▼) buttons to highlight the menu options, and the “OK” button to select them, set “Firing rate control” to “Manual”, then adjust “Manual firing rate” to the desired value.
Manual Pump Operation test screen, allows the installer to manually turn the individual pumps on. Using the up and down (▲▼) buttons to highlight the menu options, and the “OK” button to select them, set the desired “Pump Control” to “On”.
Table 2-4 Manual Burner Operation Parameters
The burner MUST be firing to initiate Manual Burner Operation.
Setting “Burner switch” to “Off” will inhibit burner operation, regardless of the operating
conditions. When the test is complete, return the settings to “Auto” to allow the control to
automatically turn the circulators off and on and modulate the burner firing rate as needed.
Page 11
9
Figure 2-7 Advanced Setup (Menu) Screen
Advanced Setup menu screen, accessed by selecting “Advanced Setup” from the “i-Information”
screen, lists all of the configuration parameter groups. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Login adjustment of many of the advanced settings will prompt the user to login.
Name
Description
Reference:
CH Config
Edit Central Heat settings; CH1 heat input.
Section 2.4.1
DHW Config
Edit Domestic Hot Water settings.
Section 2.4.2
Lead Lag Config
Edit Lead-Lag Master and Slave settings; CH2 (LL) heat input.
Section 2.4.3
System Config
Edit temperature units, anti-short-cycle time, alarm silence time.
Section 2.4.4
Modulation Config
Edit burner modulation settings.
Section 2.4.5
Delta T Limits
Edit delay time for delta-t limit.
Section 2.4.6
T-rise Limits
Edit delay time for T-rise limit.
Section 2.4.6
Frost Protection Config
Enable/disable CH, DHW and LL frost protection
Section 2.4.7
Burner Timings & Rates
Read only, for information only.
Section 2.4.8
Burner Control Ignition
Read only, for information only.
Section 2.4.9
CH Config DHW Config Lead Lag Config System Config Modulation Config Delta T Limits T-rise Limits Frost Protection Config Burner Control Timings & Rates Burner Control Ignition
Advanced Setup
CHS Series Controller and Display Slant Fin Corp.
2.4 Advanced Setup
Table 2-5 Advanced Setup Menu Options
Page 12
10
Figure 2-8 Central Heat Configuration Main Menu Screen
CH Config main menu screen, accessed by
selecting “CH Config” from the “Advanced Setup”
screen, lists the sub-menus specific to the Central Heat Configuration. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is
highlighted select by pressing the “OK” button.
The settings under “CH Config” are specific to boiler
operation given a local central heat demand, i.e. CH1 heat input.
Figure 2-9 Central Heat Configuration Sub-menu Screen
CH Config sub-menu screen, allows the installer to set parameters specific to the boiler response and operation for local (i.e. non Lead Lag) Central Heat demands. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Demand switch - Central heat demand can be initiated by a contact closure to CH1, “LCI”, or by boiler temperature, “Sensor only”.
Setpoint source – The boiler setpoint can be “Local”, i.e. the “CH setpoint” set from the display, or “4­20mA” set from an external source.
Modulation sensor – With the “Setpoint source” set
to “Local”, the control can be set to use either the “Outlet”, “Inlet” or “S10” (pipe) sensor for regulation
of burner modulation.
Mod rate source The burner modulation can either
be controlled by the boiler control, “Local”, or by an
external source, “4-20mA”.
Demand switch Setpoint source CH setpoint Off hystersis On hysteresis Modulation sensor Mod rate source
CH Config
LCI
Local
180 oF
10 oF 20 oF Outlet
Local
CH Config Outdoor Reset Config
Warm weather shutdown
CH Config
Slant Fin Corp. Controller and Display CHS Series
2.4.1 CH Config
2.4.1.1 CH Config – CH Config
Page 13
11
Parameter
Description
Factory Settings
Demand switch *
Source of CH demand:
Sensor only (modulation sensor – no contact closure required) LCI (contact closure of CH1” to “R”, i.e. via a thermostat)
LCI
Setpoint source *
Select the Central Heat setpoint source:
Local (control references CH setpoint setting) 4-20mA with sensor on/off [remote source]
Local
CH setpoint
Setpoint value for CH modulation. If “Outdoor reset is set to “Disable, this is the target temperature at the “Modulation sensor”. If “Outdoor reset is set to “Enable, this is the maximum target temperature at the “Modulation sensor” (see Section
2.4.1.2 Outdoor Reset Config). Range 60°F to 190°F
180°F
Off hysteresis
Value added to CH setpoint to determine water temperature at which the burner will shut off e.g. if CH setpoint is 180°F, and CH off hysteresis is 10°F, the burner will be shut off at 190°F. Range 2°F to 20°F
10°F
On hysteresis
Value subtracted from CH setpoint to determine water temperature at which the burner will fire e.g. if CH setpoint is 180°F, and CH on hysteresis is 20°F, the burner will fire at 160°F. Range 2 °F to 40°F
20°F
Modulation sensor *
Select which sensor Central Heat will modulate to:
Outlet Inlet S10 [System (pipe) temperature sensor]
Outlet sensor
Mod rate source *
Select which source controls the modulation rate:
Local [PID control] 4-20mA with sensor on/off [remote source]
Local
* = Password protected
CHS Series Controller and Display Slant Fin Corp.
Use of 4-20mA Input Setpoint source – If “Local” is selected as the “Setpoint source, the CH setpoint value entered on the screen,
depicted in Figure 2-10, is used for control. If 4-20mA is selected as the Setpoint source, the boiler determines its setpoint from the 4-20mA signal. The setpoint is calculated from a factory-set scale between 60°F corresponding to 4mA, and 190°F corresponding to 20mA. If the 4-20mA input signal is invalid, out of range, or absent, the CH setpoint is used until the signal is valid again. Regardless of the “Setpoint source”, “Local” or “4-20mA”, the controller’s internal PID algorithm modulates the burner.
Mod rate source The Slant/Fin CHS controller supports two methods of burner modulation for CH, selected by the “Mod rate source” parameter, depicted on Figure 2-10; the factory set method is by internal PID
algorithm. The installer has the option to use a 4-20mA signal from an external control to directly modulate the burner. Rates vary (see Section 2.4.5 Modulation Config) from minimum at 4mA to CH maximum at 20mA.
The 4-20mA signal does not create burner demand; a call for heat must be present; i.e. CHI input made when
“Demand Switch” = LCI..
Table 2-6 Central Heat Configuration Parameters
Page 14
12
Figure 2-10 Outdoor Reset Configuration Screen
(CH Config) Outdoor Reset Config sub-menu screen, allows the installer to set parameters specific to the effect the outdoor temperature has on the operation of the boiler during local (i.e. non Lead Lag) Central Heat demands. Use the up and down
(▲▼) buttons to navigate the menu options; when
the desired option is highlighted select by pressing the “OK” button.
Outdoor Reset is in effect only if the following two conditions are met: Outdoor reset is set to "Enable", and an outdoor temperature sensor is connected to the boiler. The Outdoor Reset Config parameters, together with the CH Config parameters, define the relationship of boiler temperature setpoint to outdoor temperature. Refer to Figure 2-12 for an example of the relationship between outdoor temperature and boiler temperature, with a given set of settings.
Parameter
Description
Factory Settings
Outdoor reset enable
Enables or disables Outdoor reset
Enabled
Max outdoor temp
Outdoor temperature that corresponds to the “Low water temp” setting. Example:
If the “Low water temp” setting is 95°F, and the “Max outdoor temp” setting is
70°F, the boiler setpoint will be 95°F when the outdoor temperature is 70°F or higher. Range 50°F to 95°F
70ºF
Min outdoor temp
Design Temperature - Outdoor temperature that corresponds to the “CH setpoint” setting. Example: If the “CH setpoint” is 180°F, and the “Min outdoor temp” setting is 0°F, the boiler setpoint will be 180°F when the outdoor
temperature is 0°F or lower. Range -40°F to 40°F
0ºF
Low water temp
Minimum boiler setpoint; occurs when the outdoor temperature is equal to or greater than the “Max outdoor temp”. Range 60°F to 140°F
95ºF
Outdoor boost max off point
Read only – functional in future revisions.
130ºF
Figure 2-11 Outdoor Reset Graph
Outdoor reset Max outdoor temp Min outdoor temp Low water temp Outdoor boost max off point
Enable
70 oF
0 oF
95 oF
130 oF
Outdoor Reset Config
Point defined by: Min outdoor temp= 0ºF
Point defined by: Max outdoor temp= 70ºF
Slant Fin Corp. Controller and Display CHS Series
2.4.1.2 CH Config - Outdoor Reset Config
Table 2-7 Outdoor Reset Configuration Parameters
Page 15
13
Figure 2-12 WWSD Configuration Screen
(CH Config) Warm Weather Shutdown (WWSD) – sub-menu screen, allows the installer to
enable the WWSD function for local (i.e. non Lead Lag) Central Heat demands, and define at what outdoor temperature it is initiated. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by pressing the “OK” button.
When “Warm weather shutdown” is set to one of the
“Shutdown” options, and the outdoor temperature is above the “Warm weather shdn setpoint”, CH
operation is inhibited.
CH operation is restored when the outdoor temperature drops below the WWSD setpoint by a fixed value of 4ºF.
Parameter
Description
Factory Settings
Warm weather shutdown
Enable or Disable Warm Weather Shutdown and select shutdown options
Shutdown after demand ends Shutdown immediately Disable
Disable Warm weather
shdn setpoint
Temperature at which local Central Heat operation is inhibited. Not applicable when “Warm weather shutdown” is set to “Disable”. Range 50°F to120°F
60°F
Warm weather shutdown Warm weather shdn setpoint
Disable
60 oF
Warm Weather Shutdown
CHS Series Controller and Display Slant Fin Corp.
2.4.1.3 CH Config - Warm Weather Shutdown
Table 2-8 Warm Weather Shutdown Configuration Parameters
Page 16
14
Figure 2-13 Domestic Hot Water Configuration Screen
DHW Config menu screen, accessed by selecting
“DHW Config” from the “Advanced Setup” screen, lists
the configuration parameters specific to boiler operation for a DHW demand. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Demand switch - DHW demand can be initiated by a contact closure, “DHW switch”, or by a tank temperature sensor, “DHW Sensor with On/Off Temp”.
Mod sensor – The control can be set to use the “Outlet” or “Inlet” sensor for regulation of burner modulation.
When “Demand switch” is set to
DHW Sensor with On/Off
Temp”, demand is determined by
the Demand ON and OFF temp settings.
Parameter
Description
Factory Settings
Demand switch *
Select which sensor is the DHW demand source:
DHW switch DHW Sensor with On/Off Temp
(If “DHW Sensor with On/Off Temp is selected, a tank sensor must be used to generate a demand.)
DHW switch Mod
sensor *
Select the DHW modulation sensor:
Outlet Inlet
Outlet
DHW setpoint
Setpoint for DHW modulation. If “Mod sensor” is set to “DHW” or “Inlet”, reduce setting accordingly. Range 60°F to 190°F
180°F
Off hysteresis *
Value added to DHW setpoint to determine water temperature at which the burner will shut off e.g. if DHW setpoint is 180°F, and Off hysteresis is 10°F, the burner will be shut off at 190°F. Range 5°F to 70°F
10°F
On hysteresis *
Value subtracted from DHW setpoint to determine water temperature at which the burner will fire e.g. if DHW setpoint is 180°F, and On hysteresis is 10°F, burner ignition occurs at 170°F. Range 2°F to 40°F
10°F
Priority time *
Time period during which a DHW demand has priority. If override time has elapsed, the boiler and CH pump (Pump C) will service a CH demand regardless of DHW demand. Value=0 inhibits DHW priority. Range 0 to 18 hours.
2 hour
Demand ON temp *
DHW demand is switched ON when DHW tank temperature is < this setting. Applied when Demand switch is set to “DHW Sensor with on/off temperatures”. Range 60°F to 165°F.
135 oF
Demand OFF temp *
DHW demand is switched OFF when DHW tank temperature is this setting. Applied when Demand switch is set to “DHW Sensor with on/off temperatures”. Range 65°F to 170°F.
140 oF
* = Password protected
= If “Demand switch” is set to “DHW Sensor with On/Off Temp”, demand is determined by the Demand ON and OFF temp settings.
DHW tank sensor MUST be used in conjunction with a DHW temperature safety shutoff switch. Failure to provide such a switch may result in property damage, serious injury to occupants, or possibly death.
Demand switch Mod sensor DHW setpoint Off hystersis On hysteresis Demand ON temp Demand OFF temp
DHW switch
Outlet
180 oF
10 oF
10 oF 135 oF 140 oF
DHW Config
Slant Fin Corp. Controller and Display CHS Series
2.4.2 DHW Config
Table 2-9 DHW-Domestic Hot Water Configuration Parameters
Page 17
15
CHS Series Controller and Display Slant Fin Corp.
2.4.3 Lead Lag Config
The CHS boiler can be used as a stand-alone unit or as part of a cascaded arrangement with as many as 8 CHS boilers. The Lead Lag Configuration parameters determine the boiler’s (or group of boilers) behavior during a Lead Lag heat demand [i.e. CH2 (LL) heat input]. Only a demand on CH2 (LL) will initiate Lead-Lag, or “staging”, of cascaded boilers. For stand-alone boilers, the CH2 (LL) demand simply behaves as a second heat input (CH1 being the first). Note: a demand for central heat from CH1, takes priority over a demand for central heat from CH2 (LL).
To enable, or allow the use of Lead-Lag function and the CH2 (LL) input, the “Lead Lag Master Config” parameter “Master enable”, must be set to “Enable”; see Section 2.4.3.1 Lead Lag Master Config. In Lead Lag cascade boiler arrangements, only one boiler has “Master enable” set to “Enable”, the others are set to “Disable” (factory default).
Check List for Lead Lag Installation:
1. All Boilers in Cascade a. Wire boilers together – Daisy-chain Data Communication wiring between boilers. See Installation and
Operating Instructions (Not applicable for stand-alone boiler applications).
b. Lead Lag Slave Configuration Settings (Optional) – Adjust the “Lead Lag Slave Config” setting “Slave
mode”, as desired. See Section 2.4.3.2.
c. MB2 Modbus address – set a unique “MB2 Modbus address for each boiler. See Section 2.4.4.1 System
ID & Access.
2. Master Boiler in Cascade a. Set “Master enable” to “Enable” – Select one boiler in the cascade to be Master; set its “Master enable”
setting to “Enable”. Other boilers are left as “Disable” (factory default). For stand-alone boilers the lone boiler must have “Master enable” configured as “Enable”. See Section 2.4.3.1 Lead Lag Master Config.
b. Lead Lag Master Configuration Settings – Adjusted the “Lead Lag Master Config” and “Outdoor Reset”
settings to the desired values on the boiler with “Master enable” configured as “Enable”. No need to adjust these settings on other boilers.
c. Heat Demand Input [CH2 (LL)] – Wire the head demand input to CH2 (LL) of the boiler with “Master
enable” configured as “Enable”.
d. System Sensor (Optional) – Wire the system (pipe) sensor to the boiler with “Master enable” configured
as “Enable”.
3. Any Boiler in Cascade a. Outdoor Sensor (Optional) – Wire the outdoor sensor to any boiler within the cascade. Note: only one
outdoor sensor is required for a multiple boiler application.
b. System Pump Control (Optional) – With “CH pump use for LL master” set to “On”. The respective boiler
will operate the CH pump (Pump C) anytime there is a Lead Lag heat demand. See Section 2.4.4.2 Pump Config.
Page 18
16
Figure 2-14 Lead Lag Configuration Main Menu Screen
Lead Lag Config main menu screen, accessed by
selecting “Lead Lag Config” from the “Advanced
Setup” screen, lists the sub-menus specific to the Lead
Lag Configuration. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Figure 2-15 LL Master Configuration Screen
Lead Lag Master Config sub-menu screen, allows the installer to set parameters specific to the boiler response and operation for Lead Lag CH2 (LL)
demands. Use the up and down (▲▼) buttons to
navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Master enable – must be set to “enable” in order for
the boiler to respond to a CH2 (LL) demand (only one
boiler in the cascade can have “Master enable” set to
“Enable”. Setpoint source The boiler LL setpoint can be
“Local”, i.e. the “Setpoint” set from the display, or “4­20mA” set from an external source.
System Sensor When using the optional system (pipe) sensor; the controller automatically uses it as the modulation sensor – reduce the “Setpoint” accordingly.
Master enable Setpoint source Setpoint Off hysteresis On hysteresis P gain I gain Base load common rate
Disable
Local
150 oF
15 oF 15 oF
30 15
70%
Lead Lag Master Config
Lead Lag Master Config Lead Lag Slave Config Lead Lag Outdoor Reset
Lead Lag Config
Slant Fin Corp. Controller and Display CHS Series
2.4.3.1 Lead Lag Master Config
Page 19
17
Parameter
Description
Factory Settings
Master enable *
Enable or Disable Lead Lag Master. One (and only one) unit must be set to “Enable” for Lead Lag operation to function.
Disable
Setpoint source *
Select the Lead Lag setpoint source:
Local (control references “Setpoint” setting) 4-20mA (control references 4-20mA signal from an external control). “Outdoor
reset enable” must be set to “Disable when using a 4-20mA signal; see Section
2.4.3.3 Lead Lag Outdoor Reset.
Local Setpoint
Setpoint value for Lead Lag modulation. Range 60°F to 190°F.
150°F
Off Hysteresis *
Value added to the “Setpoint” to determine water temperature at which the burner
will shut off. Example: If “Setpoint” is 150°F, and “Off hysteresis” is 15°F, the burner will be shut off at 165°F. Range 5 °F to 70°F.
15°F
On Hysteresis *
Value subtracted from “Setpoint” to determine water temperature at which the
burner will fire. Example: If “Setpoint” is 150°F, and “On hysteresis” is 10°F, burner ignition occurs at 140°F. Range 2°F to 40°F.
10°F P Gain *
Gain applied to the proportional term of the LL PID control algorithm. Range 5 to 50 (no units). Decrease to slow rate of control response.
30
I Gain *
Gain applied to the integral term of the LL PID control algorithm. Range 5 to 50 (no units). Decrease to slow rate of control response.
15
Base load common *
Maximum modulation rate of all firing units when other units are still available and idle. Range 25 - 100%.
70%
* Password protected
CHS Series Controller and Display Slant Fin Corp.
Table 2-10 Lead Lag Master Configuration Parameters
Use of 4-20mA Input
Setpoint source – If “Local” is selected as the “Setpoint source, the “Setpoint value entered on the screen, depicted in Figure 2-16, is used for control. If 4-20mA is selected as the Setpoint source, the boiler determines its setpoint from the 4-20mA signal. The setpoint is calculated from a factory-set scale between 60°F corresponding to 4mA, and 190°F corresponding to 20mA. If the 4-20mA input signal is invalid, out of range, or absent, the “Setpoint is used until the signal is valid again. Regardless of the “Setpoint source”, “Local” or “4-
20mA”, the controller’s internal PID algorithm modulates the burner. The 4-20mA signal does not create burner demand; a call for heat must be present at the CH2 (LL) input.
Page 20
18
Figure 2-16 LL Slave Configuration Screen
Lead Lag Slave Config sub-menu screen, allows
the installer to set the “Slave mode” which establishes
the order in which the boiler is chosen during the staging sequence of a Lead Lag demand.
Use First This mode has priority over all others. A unit with its “Slave mode set to "Use First", will
always fire first before any other slave in the cascade and it will be the last one dropped.
Equal run time – This mode stages the units based on run time equalization where the unit with the least burner hours fires first and the most burner hours fires last. Only "Use First" has higher priority.
Use Last – This mode has the lowest priority. A unit with its “Slave mode set to "Use Last", will always fire last after every other slave in the cascade is running. It will be the last slave to fire and the first one dropped.
Parameter
Description
Factory Settings
Slave mode *
Select slave mode from drop down list:
Use First Equal run time Use Last
Equal run time
* Password protected
Slave mode
Equal run time
Lead Lag Slave Config
Slant Fin Corp. Controller and Display CHS Series
2.4.3.2 Lead Lag Slave Config
Table 2-11 Lead Lag Slave Configuration Parameters
Page 21
19
Figure 2-17 LL Outdoor Reset Screen
(LL Config) Outdoor Reset Config sub-menu screen, allows the installer to set parameters specific to the effect the outdoor temperature has on the operation of the boiler during a CH2 (LL) demand.
Use the up and down (▲▼) buttons to navigate the
menu options; when the desired option is highlighted select by pressing the “OK” button.
Outdoor Reset is in effect only if the following two conditions are met: “Outdoor reset enable” is set to "Enable", and an outdoor temperature sensor is connected to the boiler. The “Lead Lag Outdoor Reset” parameters, together with the “Lead Lag Master Config parameters, define the relationship of boiler temperature setpoint to outdoor temperature. Refer to Figure 2-12 for an example of the relationship between outdoor temperature and boiler temperature, with a given set of settings.
Parameter
Description
Factory Settings
Outdoor reset enable *
Enables or disables Outdoor reset
Enabled
Max outdoor temp *
Outdoor temperature that corresponds to the “Low water temp” setting. Example:
If the “Low water temp” setting is 85°F, and the “Max outdoor temp” setting is
70°F, the boiler setpoint will be 85°F when the outdoor temperature is 70°F or higher. Range 50°F to 95°F
70ºF
Min outdoor temp *
Design Temperature - Outdoor temperature that corresponds to the “Setpoint” setting. Example: If the “Setpoint” is 150°F, and the “Min outdoor temp” setting is 0°F, the boiler setpoint will be 150°F when the outdoor temperature is 0°F or lower. Range -40°F to 40°F
0ºF
Low water temp *
Minimum boiler setpoint; occurs when the outdoor temperature is equal to or greater than the “Max outdoor temp”. Range 60°F to 140°F
85ºF
Outdoor boost max off point *
Read only – functional in a future revision.
130ºF
* = Password protected
Outdoor reset enable Max outdoor temp Min outdoor temp Low water temp Outdoor boost max off point
Enable
70 oF
0 oF
85 oF
130 oF
Lead Lag Outdoor Reset
CHS Series Controller and Display Slant Fin Corp.
2.4.3.3 Lead Lag Outdoor Reset
Table 2-12 Lead Lag Outdoor Reset Config Parameters
Page 22
20
Figure 2-18 System Configuration Main Menu Screen
System Config main menu screen, accessed by
selecting “System Config” from the “Advanced
Setup” screen, lists the sub-menus specific to the
System Configuration. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Figure 2-19 System Identification & Access Screen
System ID & Access sub-menu screen contains information about the CHS controller; it also provides the installer with the ability to change the “Boiler
name” as it appears on the display, and the “Modbus address”, which is necessary for configurating Lead
Lag multiple boiler installations. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by pressing the “OK” button.
MB2 Modbus address each boiler in a Lead Lag multiple boiler installation, must have a unique MB2 Modbus address.
Boiler name OEM ID MB1 Modbus address MB2 Modbus address Modbus address
Modbus port used
Product ID Product family OS number Model name Software version Date code Application revision Safety revision
110MBH
F/T110v06-18-12
1 1 1
MB1
IResidential
Hydronic boiler
R7910B1015
R7910B1015s1m
4104.2901 1117
19 13
System ID & Access
System ID & Access Pump Config
Statistics Config High Limits System Config
System Config
Slant Fin Corp. Controller and Display CHS Series
2.4.4 System Config
2.4.4.1 System ID & Access
Page 23
21
Parameter
Description
Factory Settings
Boiler name *
Name describing the specific boiler. Limited to 20 characters.
e.g.: 110MBH
OEM ID
Name identifying factory configuration settings; field is read only.
N/A
MB1 Modbus address *
Modbus communication address used by the display to identify the attached controller. No need to change this setting. Range: 1 – 8.
1
MB2 Modbus address *
Unique controller I.D. needed when multiple boilers are connected together in a Lead Lag cascade configuration. Each boiler in a Lead Lag cascade configuration must have a unique setting. Range: 1 – 8.
1
Modbus address
Displays the “MB1 Modbus address” setting – do not adjust this setting.
1
Modbus port used
Identifies the Modbus port used by the display to controller; field is read only.
MB1
Product ID
Controller type identification; field is read only. Residential
Product family
Hydronic boiler
OS number
Controller model identification; field is read only.
R7910B1015
Model name
Software version
Controller software version identification; field is read only.
N/A
Date code
Controller date code; field is read only.
N/A
Application revision
Controller application revision; field is read only.
N/A
Safety revision
Controller safety revision; field is read only.
N/A
CHS Series Controller and Display Slant Fin Corp.
Table 2-13 System Identification & Access Parameters
* = Password protected
Page 24
22
Figure 2-20 Pump Configuration
Pump Config sub-menu screen allows adjustment of the individual pump overrun times; also allows the individual pumps to be manually turned on for testing purposes. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
CH pump use for LL Master for Lead Lag multiple boiler configurations; set this parameter to
“On” on the boiler that is controlling the System
pump with the Pump C output.
pump control – This may be
used to manually override automatic control of the pumps for testing purposes. If used in this manner, ensure that it is set back to “Auto”; otherwise, the selected pump(s) will remain powered on indefinitely.
Parameter
Description
Factory Settings
CH pump control *
Switches CH pump (Pump C) control from Automatic to ON.
Auto
CH overrun time *
Amount of time the CH pump (Pump C) will continue to run after a CH [CH1 or CH2 (LL)] demand ends. Range 0 to 1080 minutes.
0 sec
CH pump use for LL master *
Check box used to allocate Pump C output as the system pump operator for Lead Lag applications.
off
Boiler pump control *
Switches Boiler pump (Pump B) control from Automatic to ON.
Auto
Boiler pump overrun time *
Amount of time the Boiler pump (Pump B) will continue to run after burner shutdown. Range 0 to 1080 minutes.
30 sec
DHW pump control *
Switches DHW pump (Pump A) control from Automatic to ON.
Auto
DHW pump overrun time *
Amount of time the DHW pump (Pump A) will continue to run after a DHW demand ends. Range 0 to 1080 minutes.
10 sec
* = Password protected
CH pump control CH pump overrun time CH pump use for LL Master Boiler pump control Boiler pump overrun time DHW pump control DHW pump overrun time
Auto
0 sec
off
Auto
30 sec
Auto
10 sec
Pump Config
Slant Fin Corp. Controller and Display CHS Series
2.4.4.2 Pump Config
Table 2-14 Pump Configuration Parameters
Page 25
23
Figure 2-21 Statistics Configuration Screen
Statistics Config sub-menu screen displays the number of burner and pump cycles, as well as burner
run time. Use the up and down (▲▼) buttons to
navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Pump cycle counts can be reset by the installer, for example when a circulator is replaced.
Burner cycles and Burner run time counters cannot be reset.
Parameter
Description
Factory Settings
Burner cycle count
Number of burner cycles on controller. Not resettable by the installer. Range 0 to 999,999.
0 Burner run time
Total number of hours of burner operation. Range 0 to 999,999 hours.
0 hour
Boiler pump cycle count *
Number of Boiler pump (Pump B) cycles since last reset. Range 0 to 999,999.
0
CH pump cycle count *
Number of CH pump (Pump C) cycles since last reset. Range 0 to 999,999.
0
DHW pump cycle count *
Number of DHW pump (Pump A) cycles since last reset. Range 0 to 999,999.
0
Burner cycle count Burner run time Boiler pump cycle count CH pump cycle count DHW pump cycle count
29
7 hour
75 56 74
Statistics Config
CHS Series Controller and Display Slant Fin Corp.
2.4.4.3 Statistics Config
Table 2-15 Statistics Configuration Parameters
* = Password protected
Page 26
24
Figure 2-22 High Limit Screen
Parameter
Description
Factory
Outlet high limit response
Indicates controller response to an outlet temperature exceeding the “Outlet high
limit setpoint”. Parameter is read only.
Recycle & Hold
Outlet high limit response
Recycle & hold
High Limit
Slant Fin Corp. Controller and Display CHS Series
2.4.4.4 High Limit
High Limit sub-menu screen displays the outlet limit response. This value is “read only” and cannot be adjusted.
Table 2-16 High & Stack Limit Parameters
Page 27
25
Figure 2-23 System Configuration Screen
System Config sub-menu screen allows the operator to set the temperature units (ºF/ºC) and the burner “Anti short-cycle time”. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Anti short-cycle time - This feature does not apply to
Domestic Hot Water demand or recycle events.
The Anti short-cycle feature is designed to prevent excessive burner on/off cycling due to short or rapid thermostat cycles, low heating load, etc.
Parameter
Description
Factory Settings
Temperature units
Select which temperature units to display:
Fahrenheit Celsius
Fahrenheit
Anti short­cycle time *
Whenever the burner is turned off due to no demand the anti-short-cycle timer is started and the burner remains in a Standby Delay condition waiting for this time to expire. Range 0 to 60 minutes (1 hour).
5 min
Burner off inhibit time *
If demand changes from a high-temperature setpoint to a lower setpoint (e.g. from DHW to CH), water temperature may exceed the burner off point for the new demand. This value determines how long the control will ignore the burner off hysteresis or threshold before shutting down the burner, in order to reduce burner cycling. Range 0 to 30 minutes.
10 sec General
Config
Allows for advanced parameter configuration modifications – only use when instructed by Slant/Fin technical support.
N/A
* Password protected
Temperature units Anti short-cycle time Burner off inhibit time General Config
Fahrenheit
5 min
10 sec
System Config
CHS Series Controller and Display Slant Fin Corp.
2.4.4.5 System Config
Table 2-17 System Configuration Parameters
Page 28
26
Figure 2-24 Modulation Configuration Screen
Modulation Config menu screen, accessed by
selecting “Modulation Config” from the “Advanced
Setup” screen, allows for adjustment of the min. and
max. modulation rates of the boiler. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by pressing the “OK” button.
Modulation rates are listed by model number:
CH and DWH
Max Modulation Rate
Min Modulation
Rate
CHS-85 = 6300 CHS-110 = 7000 CHS-155 = 3700 CHS-175 = 4100 CHS-200 = 4650 CHS-250 = 5900 CHS-300 = 5000 (4800 on LP) CHS-399 = 6900 (6600 on LP)
85 = 1525 110 = 1625 155 = 900 175 = 900 200 = 900 250 = 900 300 = 1500 399 = 1500
Parameter
Description
Factory Settings
CH max modulation rate *
Maximum permissible blower speed during CH demand [CH1 or CH2 (LL)]. Range is model dependent.
Model dependent
DHW max modulation rate *
Maximum permissible blower speed during DHW demand. Range is model dependent.
Model dependent
Min modulation rate *
Minimum permissible blower speed. Range is model dependent.
Model dependent
* = Password protected
CH max modulation rate DHW max modulation rate Min modulation rate
7000 RPM 7000 RPM 1625 RPM
Modulation Config
Slant Fin Corp. Controller and Display CHS Series
2.4.5 Modulation Config
Table 2-18 Modulation Configuration Parameters
Page 29
27
Figure 2-25 Delta T & T-rise Limits Screens
Parameter
Description
Factory Settings
Delta T delay *
Delay time between burner cycles when Delta T limit is exceeded. Range 1 to 60 minutes.
5 min
Outlet T-rise delay *
Delay time between burner cycles when T-rise limit is exceeded. Range 1 to 60 minutes.
5 min *=Password Protected
Outlet T-rise delay
5 min
T-rise Limits
Delta T delay
5 min
Delta T Limits
CHS Series Controller and Display Slant Fin Corp.
2.4.6 Delta T & T-rise Limits
Delta T Limits accessed by selecting “Delta T Limits” from the “Advanced Setup” screen; Delta T is the difference in water temperature between Inlet and Outlet of the boiler. If the temperature difference (Delta T) is greater than 60oF the burner is shut off for the time specified before firing again. An initial cycle and two recycles are allowed before Lockout occurs.
T-rise Limits – accessed by selecting “T-rise Limits” from the “Advanced Setup” screen; T-rise is the rate of increase of the boiler Outlet temperature. If the boiler outlet temperature increases by a rate greater than 4oF/second the burner will recycle with a delay equal to the “Outlet T-rise delay setting. An initial cycle and two recycles are allowed before Lockout occurs.
Table 2-19 Delta T & T-rise Limits Parameters
Page 30
28
Figure 2-26 Frost Protection Screen
Frost Protection Config accessed by selecting “Frost Protection Config” from the “Advanced
Setup” screen. Provides optional freeze protection for the boiler system. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the
“OK” button.
When set to “Enable”, causes the respective
circulators to operate when the inlet temperature drops below 45°F; and the burner to fire (at the min. modulation rate) when the outlet temperature drops below 38°F.
Parameter
Description
Factory Settings
CH frost protection *
Enable or Disable frost protection for central heat (i.e. Pumps B and C).
Enabled
DHW frost protection *
Enable or Disable frost protection for DHW (i.e. Pumps A and B).
Disabled
Lead Lag frost protection *
Enable or Disable frost protection for lead lag (i.e. Pumps B and C). Each slave detects frost protection and notifies the Master.
Disabled
* Password protected
CH frost protection DHW frost protection Lead Lag frost protection
Enable Disable Disable
Frost Protection Config
Slant Fin Corp. Controller and Display CHS Series
2.4.7 Frost Protection Config
Table 2-20 Frost Protection Configuration Parameters
Page 31
29
Figure 2-27 Burner Control Ignition and Timings & Rates Screens
Parameter
Description
Factory Settings
Postpurge rate *
Rate the blower will operate following the shutdown of the burner. Parameter is read only.
4500 RPM
Postpurge time *
Time the blower will operate following the shutdown of the burner. Parameter is read only.
25 sec
Adjustable lightoff rate *
Rate the blower will operate during burner ignition. Range 2500 rpm to 5000 rpm.
4000 RPM
Postpurge rate Postpurge time
4500 RPM
20 sec
Burner Timings & Rates
Adjustable lightoff rate
4000 RPM
Burner Control Ignition
CHS Series Controller and Display Slant Fin Corp.
2.4.8 Burner Control Ignition and Timings & Rates
Burner Timings & Rates – accessed by selecting “Burner Timings & Rates” from the “Advanced Setup” screen. Displays the Postpurge rate and time settings; values are “read only” and cannot be adjusted.
Burner Control Ignition – accessed by selecting “Burner Control Ignition” from the “Advanced Setup” screen. Displays the “Adjustable lightoff rate” setting.
Table 2-21 Burner Control Ignition and Timings & Rate Parameters
* Password protected
Page 32
30
Figure 2-28 Diagnostic Input/Output Screens
Diagnostics menu screen, accessed by selecting “Diagnostics” from the “i-Information” screen, allows
the user to view the operational status of the boiler.
Use the up and down (▲▼) buttons to navigate the
menu options; when the desired option is highlighted select by pressing the “OK” button.
Analog Sensors indicates the status of all temperature sensors, flame sensor, blower speed (both demanded and actual), and optional 4-20mA input signal; see Figure 2-31.
Digital IO indicates the status of each on/off input and output, i.e. pump outputs and thermostat inputs; see Figure 2-31.
Analog Sensors
Digital IO
Analog Sensors Digital IO History
Diagnostics
Outlet temp Inlet temp Delta T DHW temp Stack temp Outdoor temp Fan speed Flame signal Firing rate 4-20mA input System sensor
70 oF 70 oF
1 oF
OPEN
71 oF
OPEN
LOW
0.00 A 0 RPM
OPEN
Outlet
Boiler pump (B) CH pump (C) DHW pump (A)
Blower/HSI Eternal ignition Pilot valve Main valve Alarm Interlock (ILK) Pre-ignit interlock (PTI) Load control input (LCI) STAT (Demand) Time Of Day Safety relay
off off off
off off off off off
on off off off off off
Slant Fin Corp. Controller and Display CHS Series
2.5 Diagnostics
Figure 2-29 Diagnostic Screens
Page 33
31
Figure 2-30 History Screen
History sub-menu screen provides access to a log of past Lockouts and Alerts. Use the up and down (▲▼) buttons to navigate the menu options; when the desired option is highlighted select by pressing the “OK” button.
Figure 2-31 Example Lockout History Record Screen
Lockout/Alert Record by selecting a Lockout or Alert event from the list of Lockouts/Alerts, the display provides specific information about the operating condition of the boiler during the Lockout/Alert (see example left). This information can be helpful for troubleshooting.
Lockout History Alert Log
History
Lockout 67 ILK OFF
Cycle: 8 Hours: 3 Time: 0 sec State: Run
First out: None Outlet: 77ºF Inlet: 76ºF DHW: 110ºF
Lockout History Record 1
CHS Series Controller and Display Slant Fin Corp.
2.5.1 History
The CHS controller identifies and records two kinds of events and categorizes them as either Lockouts or Alerts. The bulleted lists below indicate the significance of each type of fault:
Lockouts:
Cause the burner to shutdown and require manual intervention to reset the controller from Lockout Always cause the Alarm contacts to close Are logged in the Lockout History
Alerts:
Events reported by the controller For informational purposes only
Page 34
32
Figure 2-32 Display Setup User Customizable Screen
Display Setup menu screen, accessed by selecting “Display Setup” from the “i-Information” screen,
allows the user to select which value (operating parameter or sensor reading) is displayed on each of the first 5 lines of the Home Screen. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by pressing the “OK” button.
The comprehensive list of sensor I/O is identified in Table 2-22 below.
Value
Description
System setpoint
Indicates the actual local CH setpoint (i.e. for a CH1 demand); adjusts for outdoor reset.
Operating temp
Indicates the temperature at the sensor used for burner modulation during a local CH or DHW demand, i.e. boiler inlet, boiler outlet or system/pipe sensor.
Outlet temp
Indicates the temperature reading from the boiler outlet sensor.
Inlet temp
Indicates the temperature reading from the boiler inlet sensor.
Outdoor temp
Indicates the temperature reading from the outdoor sensor.
Delta T
Indicates the temperature difference between the boiler inlet and outlet sensors.
LL Operating temp
Indicates the temperature at the sensor used for burner modulation during a Lead Lag demand, i.e. boiler outlet or system/pipe sensor.
LL System setpoint
Indicates the actual Lead Lag setpoint [i.e. for a CH2 (LL) demand]; adjusts for outdoor reset.
Fan speed
Indicates the speed that the combustion blower is running at – tachometer reading.
Flame signal
Indicates the flame current sensed from the flame probe.
Firing rate
Indicates the speed that the combustion blower is being commanded to operate at.
DHW temp
Indicates the dhw tank temperature (if used) or OPEN/CLOSED for Aquastat switch status.
Stack temp
Indicates the temperature reading from the boiler stack sensor.
4-20mA input
Indicates the input signal from an external 4-20mA source (used for direct burner modulation or establishing temperature setpoint).
Lead Lag temp
Indicates the temperature reading from an optional system/pipe sensor.
LCD contrast 270 Home screen l ine 1: System setpo 180oF Home screen l ine 2: Operating tem 71oF Home screen l ine 3: Outlet temp 71oF Home screen l ine 4: Inlet temp 71oF
Home screen l ine 5: Outdoor temp OPEN
OS number DSP49G2094 Software version 0.14
Display Setup
Slant Fin Corp. Controller and Display CHS Series
2.6 Display Setup
Table 2-22 List of Optional Values for Display on Home/Summary Screen
Page 35
33
CHS Series Controller and Display Slant Fin Corp.
NOTES
Page 36
©Slant/Fin Corp. 2013
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Loading...