Danger Sign: Indicates a hazardous situation which,
if not avoided, will result in serious injury or death.
Warning Sign: Indicates a hazardous situation which,
if not avoided, could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situa-
tion which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous
situation which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if
not avoided, could result in property damage.
This Boiler must be installed by a licensed and trained Heating Technician or the Warranty is Void. Failure to properly install thisunit may re-
sult in property damage, serious injury to occupants, or possibly death.
!
WARNING
!
CAUTION
CAUTION
NOTICE
!
WARNING
Page 2
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
2
Read Before Proceeding
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to turn the gas “shutoff” valve. Never use tools. If the handle will not turn by hand,
don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the boiler and to replace any part of the control system and any gas control which has been
under water.
OPERATING INSTRUCTIONS_
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service
technician or gas supplier.
TO TURN OFF GAS TO THE BOILER_
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler.
3. Turn the manual gas valve to the OFF position.
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Section 14.0 for information on handling instructions and recommended personal protective equipment.
Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must
read and follow the supplied instructions before installing, servicing, or removing this boiler. This boiler
contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Void Warranty - This Boiler must have water flowing through it whenever the burner is
on or it will damage the unit and void the warranty. Failure to follow these instructions
may result in serious injury or death.
Page 3
CHS Series Installation and Operation Instructions │Slant Fin Corp.
3
1.0 INTRODUCTION
General Installation Requirements
The installation of your Slant/Fin CHS gas boiler must conform to the requirements of this manual, your local
authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where
required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for
Automatically Fired Boilers ANSI/ASME CSD-1.
This document pertains to the correct installation and operation of Slant/Fin boiler model CHS. The instructions
detailed in this document supersede any and all previous instructions provided by Slant/Fin, written or
otherwise. Each unit is provided with the following:
1. Installation and Operating Instructions,
2. Appendix A – Controller and Display Instructions,
3. CHS User Manual, and
4. Natural Gas to LP Conversion Kit*
* The conversion kit is required to convert the boiler so it will safely operate with Propane Gas.
Read and understand this entire document prior to proceeding with the installation of the
CHS boiler. Failure to follow the instructions outlined in this document will result in
property damage, serious injury or death.
User Responsibilities
This boiler must be installed and serviced by a qualified installer or service technician. This boiler must be
serviced and inspected annually when operating in normal residential applications. Demanding applications or
extreme conditions (i.e. commercial) may require more frequent service and inspection. As the User/Owner of
this equipment, you are responsible for ensuring the maintenance is performed at the required intervals (see
Section 14 – Annual Maintenance and Inspection).
Installer Responsibilities
As the installing technician it is your responsibility to ensure the installation is performed in accordance with this
instruction manual as well as any applicable local or National installation codes. It is also your responsibility to
inform the User/Owner of their obligation with respect to the above description under “User Responsibilities”.
Failure to follow this warning could result in fire, serious injury, or death.
property damage, serious injury or death. Refer to section titled ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE for applicable conversion kit and LP orifice numbers.
Failure to have the boiler properly serviced and inspected on a regular basis by a qualified
service technician may result in property damage, serious injury or death.
Failure to keep the Vent and Combustion Air Intake clear of ice, snow, and other debris
may result in property damage, serious injury, or death.
Failure to use the appropriate Natural to LP Conversion Kit and Orifice when operating
the CHS with Propane will result in extremely dangerous burner operation leading to
Page 4
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
4
IN THE STATE OF MASSACHUSETTS ONLY
(a) For all horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not
limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas
equipment is to be installed and on each additional level of the dwelling, building or structure served by the
equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of 30 days to comply with the above requirements; provided,
however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall
be installed.
2. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating boiler or equipment. The sign shall read, in print size no less than one-
half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”
(plate included with boiler).
4. INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
…..Continued on Next Page
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
The CHS boiler is factory set to operate with Natural Gas. BEFORE OPERATING WITH PROPANE, the
specified LP Conversion Kit and Orifice must be installed to convert the boiler so it will operate safely with
LP Propane. The correct kit and LP orifice is listed below (Each kit comes with conversion instructions).
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your CHS boiler is not
installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require
boilers fueled with LP gas be provided with an approved means of removing unburned gases from the room.
Check your local codes for this requirement.
The CHS boiler is certified as a “Category IV” boiler, and requires a “Special Venting
System” designed for pressurized venting. The exhaust gases must be piped directly to
the outdoors using the vent materials and rules outlined in these instructions. Failure to follow these instructions
will result in serious injury or death.
Page 5
CHS Series Installation and Operation Instructions │Slant Fin Corp.
5
…..Continued.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for residential purposes.
(c)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED: When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED:
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment
installation instructions; and
2. The “special venting system” shall be Product Approved by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts list for venting instructions, and/or all venting design instructions shall remain with
the appliance or equipment at the completion of the installation.
Page 6
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
6
DESCRIPTION
CHS-85
CHS-110
CHS-155
CHS-175
CHS-200
CHS-250
CHS-300
CHS-399
CSA Input Modulation
1,4
[MBH]
17-85
21.6-108
31-155
31-175
31-200
31-250
79.8-299
79.8-399
DOE Heating Capacity
1,2
[MBH]
78
99
144
163
185
230
278
380
Net I=B=R Rating
1,2
[MBH]
68
86
125
141
160
199
239
330
DOE AFUE2 [%]
95
95
95
94.8
94.7
94.5
94
95.4
Water Connections – NPT
[in.]
1
1-1/4
1-1/2
Gas Connection - NPT, in.
1/2
3/4
Vent/Air-inlet Pipe
Diameter
[in.] 3
2 or 3
3
4
Dimensions H x W x D [in.]
33-3/8 x 19-3/4 x 14-1/2
33-3/8 x 19-3/4 x 18-1/2
36-3/8 x 25-1/4 x 20
Approx. Boiler Weight
with Water [lbs]
110
180
250
Approx. Boiler Water
Content [Gallons]
3.2
4.9
6.4
Electrical Rating
120V/1Ph/60Hz/less than 12A
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at an altitude of 0-2000ft. Numbers will be lower with
longer venting and/or altitudes greater then 2000ft.
2
Ratings based on standard test procedures prescribed by the U.S. Department of Energy; certified by AHRI. CHS-399
efficiency represents Thermal Efficiency (AFUE is not applicable).
3
The CHS requires a special venting system, use only vent materials and methods detailed in these instructions.
4
When operating with Propane models CHS-85 and CHS-110 have min/max Input Modulation rates of 17.6/88 and
22.6/113 MBH respectfully.
Elevations
2001 ft [610 m]
3000 ft [914 m]
4000 ft [1219 m]
4500 ft [1372 m]
5000 ft [1524 m]
In Canada1
de-rate by 10%
de-rate by 10%
de-rate by 10%
de-rate by 10%
de-rate % may vary
In USA2
-
de-rate by 4%
de-rate by 8%
de-rate by 8%
de-rate by 12%
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 10%. Consult local authorities for de-rating
capacities for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m] over 2000 ft [610 m].
2.0 SPECIFICATIONS
Table 2-1 CHS Specifications
Wall mounting of unit requires two people to lift the boiler into place. Failure to follow
these instructions may result in property damage or personal injury.
High Altitude Operation
The CHS boiler is designed to operate at its maximum listed capacity in installations located at 0-2000ft above
Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity should be derated for elevations above 2000 ft [610 m] in accordance with Table 2-2.
Table 2-2 De-rate % for High Altitudes
Combustion – At elevations above 2000 feet, the combustion of the boiler must be checked with a calibrated combustion analyzer to ensure safe and reliable operation. It is
the Installers responsibility to check the combustion and to adjust the combustion in accordance with
Section 9.0. Failure to follow these instructions may result in property damage, serious injury, or death.
Page 7
CHS Series Installation and Operation Instructions │Slant Fin Corp.
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
8
Model No.
Clearances
Dimensions - inches [mm]
Front
Top
Sides
Back
Bottom
Flue Pipe
CHS 85-399
Minimum
24 [610]1
12 [305]
4 [102]
0
9 [229]
1 [25]
Recommended
36 [914]
24 [610]
12 [305]
0
24 [610]
1 [25]
Notes:
1
6” if surface is removable allowing a minimum of 24” [610 mm] clearance (i.e. closet installation). See Ventilation Air
Opening dimensions in Figure 3-1.
3.0 BOILER LOCATION
In all cases, the CHS boiler must be installed indoors in a dry location where the ambient temperature must be
maintained above freezing and below 100F [38C]. All boiler components must be protected from dripping,
spraying water, or rain during operation and servicing. Consider the proximity of system piping, gas and
electrical supply, condensate disposal drain, and proximity to vent termination when determining the best boiler
location.
Water or flood damaged components must be replaced immediately with new factoryapproved components as failure to do so may result in fire, serious injury, or death.
Boiler Area Ventilation Air Openings
If boiler area clearances are less than the recommended clearances specified in Table 3-1, the boiler area must be
ventilated (Exception: if the boiler area/room has a volume of 150 ft3 or greater, ventilation of the boiler room is
not required). Each ventilation air opening must meet the minimum requirements of 1 in2 per 1000 Btu/hr, but
not less then 100 in2. The lower ventilation opening must be located within 6” of the floor while the upper
opening must be located 6” from the top of the space.
If the "Boiler Area" does not meet the recommended clearances listed in Table 3-1, and if
the boiler area has a volume less than 150 ft3, it is considered a Closet or Alcove. In US/
Canada, PVC vent pipe and fittings shall not be used within the closet or alcove; only
approved CPVC, Polypropylene or Stainless Steel vent pipe and fittings can be used. See Table 4-4 for a list of
approved materials. Under all circumstances, the minimum clearances listed in Table 3-1 must be provided.
Closet Installations
For closet installations it is necessary to provide two ventilation air openings as shown in Figure 3-1, each
providing a minimum area equal to 1 in2 per 1000 Btu/hr, but not less then 100 in2 and within 6” of the top and
bottom of the closet door. See Table 3-1 for minimum clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be
completely open to the room at a distance no greater then 18” [457 mm] from the front of the boiler and the
room is at least three (3) times the size of the alcove. Provided these conditions are met, the boiler requires no
extra ventilation air openings to the space. See Table 3-1for minimum clearances.
Residential Garage Installations
When installed in a residential garage, mount the boiler a minimum of 18” [457 mm] above the floor. Locate or
protect the boiler so it cannot be damaged by a moving vehicle. Check with your local authorities for other
possible regulations pertaining to the installation of a boiler in a garage.
Wall Mounting Installations
The CHS is provided with integrated wall mounting brackets. Refer to Figure 3-2 for instructions and
illustrations on wall mounting.
Table 3-1 Minimum Clearances for Installation and Service
Closet/alcove installations in US and Canada require approved CPVC, Polypropylene or Stainless Steel vent and air-inlet pipe and fittings (see Table 4-4); PVC is not permitted.
Failure to follow these instructions may result in damage or serious injury.
Page 9
CHS Series Installation and Operation Instructions │Slant Fin Corp.
Top ventilation opening
Max. 6” below ceiling / top
Sides = 4”
Removable surface /
closet door
Ventilation air opening
1in2 per 1000 Btu/hr,
min. 100in
2
Ventilation air opening
1in2 per 1000 Btu/hr,
min. 100in
2
Min. 1” clearance for hot
water and vent pipes
Bottom = 9”
Top = 12”
Page 10
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
10
Figure 3-2 Wall Mounting Instructions
While leaving the Upper bracket (A) intact,
remove the Wall-mount bracket (B) attached
to the bottom-back of the appliance. Save the
mounting hardware for Step 4.
Secure the Wall-mount bracket (B), removed
from the bottom of the boiler in Step 1, to a
solid wall using field supplied lag screws
(anchors when mounting to a concrete wall)
that are adequate to support the weight of the
appliance (refer to Table 2-1 Specifications).
Ensure the Wall-mount bracket is mounted
level and flush to the wall with mounting holes
on the bottom, flange pointed upward and
angled away from the wall.
Mount the appliance to the wall by aligning the
Upper bracket (A) with the Wall-mount
bracket (B). Slide the Upper bracket down
over the wall mount bracket until it hooks.
Once the appliance is resting securely on the
Upper bracket, secure the Bottom bracket (C)
to the underside of the appliance using the
mounting hardware removed in Step 1; then,
anchor the bottom bracket to the wall as shown
using field supplied hardware.
Failure to follow instructions may
result in fire, serious injury, or death.
This unit requires two people to lift it
or damage and injury may result.
Upper bracket (A)
Wall-mount
bracket (B)
Wall-mount
bracket (B)
Wall
Boiler
Ensure bracket
(A) fully inserts
into bracket (B)
(B)
(A)
Bottom bracket (C) shipped
with boiler package
Page 11
CHS Series Installation and Operation Instructions │Slant Fin Corp.
11
4.0 GENERAL VENTING
The CHS boiler is certified as a “Category IV” boiler requiring a “Special Venting System” designed for
pressurized venting. The Exhaust Vent must be piped to the outdoors, using the vent materials and rules outlined
in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and
utilizes the approved venting material and rules described in this section.
Direct Vent Installation (Best Practice)
When installed as a Direct Vent boiler the combustion air-inlet must also be piped directly to the outdoors using
the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
Installation Using Indoor Combustion Air
When the installation uses Indoor Combustion Air (i.e. piping is not directly connecting the appliance air-inlet
fitting to the outdoors), the combustion air-inlet is drawn from Indoors or Outdoors via the appliance area using
the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
appliances may result in personal injury or death.
Indoor Combustion Air - Opening Size and Location: The methods detailed below for determining Opening
Size and Location for accessing indoor combustion air, shall be used when the air infiltration rate is adequate, i.e.
greater than 0.4 ACH (air changes per hour) and when the boiler area and communicating spaces have a
minimum volume of 50 cubic ft per 1000 Btu/hr. If the air infiltration rate is known to be less that 0.4 ACH,
refer to the National Fuel Gas Code for further guidance.
1. Combined spaces on the same story – Each opening shall have a minimum free area of 1 in.2/1000 Btu/hr
of the total input rating of all appliances in the space, but not less than 100 in.2. One opening shall
commence within 12 in. of the top, and one opening shall commence within 12 in. of the bottom, of the
enclosure, see Figure 4-1a. The minimum dimension of air openings shall be not less than 3in.
2. Combined spaces in different stories – The volumes of spaces in different stories shall be considered as
communicating spaces where such spaces are connected by one or more openings in doors or floors having a
total minimum free area of 2 in.2/1000 Btu/hr of total input rating of all appliances.
Outdoor Combustion Air – Opening Size and Location: Outdoor combustion air shall be provided through
opening(s) to the outdoors in accordance with the methods detailed below. The minimum dimension of air
openings shall not be less than 3in.
1. Two Permanent Openings Method – Two permanent openings, one commencing within 12in. of the top,
and one commencing within 12in. of the bottom of the enclosure, shall be provided. The openings shall
communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as
follows:
a. Where communicating with the outdoors or where communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1 in.2/4000 Btu/hr of total input rating of all appliances
in the enclosure; see Figures 4-1b and 4-1c.
b. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum
free area of 1 in.2/2000 Btu/hr of total input rating of all appliances in the enclosure; see Figure 4-1d.
2. One Permanent Opening Method – One permanent opening, commencing within 12 in. of the top of the
enclosure, shall be provided. The appliance shall have clearances of at least 1 in. from the sides and back
Vent and Air-inlet are to be piped separately. The CHS cannot share a common vent or
air-inlet with multiple boilers.Failure to comply will result in serious injury or death.
The boiler shall be located so as not to interfere with proper circulation of combustion,
ventilation, and dilution air.
Make up air requirements for the operation of exhaust fans, kitchen ventilation systems,
clothes dryers, and fireplaces shall be considered in determining the adequacy of a space
to provide combustion air requirements. Failure to ensure adequate make up air to all
Page 12
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
12
Figure 4-1(a) Indoor Air
Figure 4-1(b) Two Vertical Ducts
Figure 4-1(c) Two Vertical Duct
Figure 4-1(d) Two Horizontal Ducts
Figure 4-1(e) One Duct Options
Opening (within
1ft of ceiling)
Opening (within
1ft of floor)
Exhaust Vent
Opening
Opening
Exhaust Vent
Ventilation Louvers
(each end of attic)
Ventilated & unheated
crawl space
Exhaust Vent
Ventilation Louvers
(each end of attic)
Opening
Opening (duct
extended to within
1ft of floor)
Exhaust Vent
Opening (within
1ft of ceiling)
Opening (within
1ft of floor)
Exhaust Vent
Ventilation Louvers
(each end of attic)
Opening Option B
(within 1ft of ceiling)
Opening Option A
and 6 in. from the front of the appliance. The opening shall directly communicate with the outdoors or shall
communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the
outdoors (see Figure 4-1e) and shall have a minimum free area of the following:
a. 1 in.2/3000 Btu/hr of the total input rating of all appliances located in the enclosure, and
b. Not less than the sum of the areas of all appliance vent connectors in the space.
3. Combination Indoor and Outdoor Combustion Air – The use of a combination of indoor and outdoor
combustion air shall be in accordance with the following:
a. Indoor Openings – where used, openings connecting the interior spaces shall comply with “Indoor
Combustion Air – Opening and Size and Location” described above.
b. Outdoor Openings – Outdoor opening(s) shall be located in accordance with “Outdoor Combustion Air
– Opening Size and Location” described above.
c. Outdoor Opening(s) Size – The outdoor opening(s) size shall be calculated in accordance with the
following:
i. The ratio of interior spaces shall be the available volume of all communicating spaces divided by the
required volume (i.e. 50 cubic ft per 1000 Btu/hr if 0.4 ACH or greater).
ii. The outdoor size reduction factor shall be 1 minus the ratio of interior spaces.
iii. The minimum size of outdoor opening(s) shall be the full size of outdoor opening(s) calculated in
accordance with “Outdoor Combustion Air – Opening Size and Location” described above, multiplied
by the reduction factor. The minimum dimension of air openings shall not be less than 3 in.
Page 13
CHS Series Installation and Operation Instructions │Slant Fin Corp.
Cement powder, crack fill dust, cellulose, fiber based insulation
Concrete plant or construction site
Combustion Air-inlet Contamination
Be careful not to locate the air-inlet termination in an area where contaminants can be drawn in and used for
combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the
required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature
failure, fire, serious injury, or death. See Table 4-1 for a list of areas to avoid when terminating air-inlet piping:
Table 4-1 Corrosive Products and Contaminant Sources
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other boiler. Failure to follow instructions may result in serious injury or death.
It is BEST PRACTICE to pipe the combustion air-inlet directly to the outdoors (Direct
Vent installation) to avoid contamination often contained in indoor air.
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process
of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-inlet
prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly
assembled piping assembly should be allowed to cure for a minimum of 8 hours before applying power to the gas
fired boiler. Refer to Mandatory Pre-commissioning Procedure for Plastic Ventingin this section.
to reduce these risks. Failure to follow these instructions can cause explosions, property damage, injury or death.
Near Boiler Vent/Air-inlet Piping
Each CHS boiler is equipped with a short piece of approved CPVC vent pipe which is to be used when venting
with PVC. Insert one end into the boiler flue outlet adapter and cement the other to the field venting (see Table 44 for approved venting material). The CPVC vent pipe should extend fully into the boiler flue outlet adapter (see
Table 4-2). DO NOT insert PVC pipe directly into the flue outlet connection as it can deform from the clamping
force of the gear clamp. Ensure that the venting system does not apply a load or strain on the boiler flue outlet
adapter. The manufacturer recommends using two elbows to create a “swing joint” to reduce potential strain on
vent piping and cemented joints. See Figures 4-2 through 4-4 for illustrations.
adapter. Failure to follow these instructions may result in serious injury or death.
Flammable Cements and Primers – It is the installers’ responsibility to familiarize
themselves with the hazards associated with explosive solvents and to take all precautions
Gasket Seating - Improper seating can cause leakage and eventual failure of the sealing
gasket. Ensure the vent pipe is adequately beveled prior to inserting into the boiler flue
Page 14
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
14
Figure 4-2(a) CHS 85-110 & 300-399
Figure 4-2(b) CHS 85-110 & 300-399
Near Boiler Venting (CPVC)
Near Boiler Venting (PVC)
Figure 4-2(c) CHS 155-250
Figure 4-2(d) CHS 155-250
Near Boiler Venting (CPVC)
Near Boiler Venting (PVC)
PVC Coupling
Air Inlet
Adapter
(factory
supplied)
Swing Joint to attain
slope in horizontal runs
PVC Exhaust Vent (check local codes
and Table 4-3)
Mandatory Vent Pipe
Transition Pipe
See Table 4-2.
Air-inlet
Pipe *
CPVC Transition
Pipe - minimum 5”
long (factory supplied)
Flue Outlet
Adapter (factory
supplied)
Flue Outlet
Adapter (factory
supplied)
CPVC Exhaust
Vent
Swing Joint
to attain slope in
horizontal runs
Air-inlet
Pipe *
Air Inlet
Adapter
(factory
supplied)
PVC Coupling
Air Inlet
Adapter
(factory
supplied)
Swing Joint
to attain slope in
horizontal runs
PVC Exhaust Vent -
(check local codes
and Table 4-3)
Mandatory Vent Pipe
Transition Pipe
See Table 4-2.
Air-inlet
Pipe *
CPVC Transition
Pipe - minimum 5”
long (factory supplied)
Flue Outlet
Adapter (factory
supplied)
Flue Outlet
Adapter (factory
supplied)
CPVC Exhaust
Vent
Swing Joint
to attain slope in
horizontal runs
Air-inlet Pipe *
Air Inlet Adapter
(factory supplied)
Air-inlet - check with applicable local codes for acceptable pipe material.
Exhaust venting must be supported to reduce strain on piping joints. Failure to follow
these instructions may result in result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
Page 15
CHS Series Installation and Operation Instructions │Slant Fin Corp.
15
Figure 4-2(e) CHS 85-110 & 300-399
Figure 4-2(f) CHS 85-110 & 300-399
Near Boiler Venting (Stainless Steel)
Near Boiler Venting (Polypropylene)
Figure 4-2(g) CHS 155-250
Figure 4-2(h) CHS 155-250
Near Boiler Venting (Stainless Steel)
Near Boiler Venting (Polypropylene)
Flue Outlet
Adapter (factory
supplied)
SS Exhaust
Vent
Swing Joint
to attain slope in
horizontal runs
SS Air-inlet Pipe
FasNSeal Appliance
Adapter (see Table 4-3)
Air Inlet Adapter
(factory supplied)
Flue Outlet
Adapter (factory
supplied)
SS Exhaust
Vent
Swing Joint
to attain slope in
horizontal runs
SS Air-inlet Pipe
SS Appliance Adapter
(see Table 4-3)
Air Inlet Adapter
(factory supplied)
Air-inlet Adapter
(factory supplied)
PPS Elbow
w/ offset angle to
account for slope
PPS Exhaust Vent
PPS Air-inlet Pipe*
PPS Appliance Adapter
(see Table 4-3)
Flue OutletAdapter
(factory supplied)
PPS Appliance Adapter
(see Table 4-3)
Air Inlet Adapter
(factory supplied)
PPS Elbow
w/offset angle to
account for slope
PPS Exhaust Vent
PPS Air-inlet Pipe*
Flue Outlet Adapter
(factory supplied)
Air-Inlet - check with applicable local codes for acceptable pipe material.
Exhaust venting must be supported to reduce strain on piping joints. Failure to follow
these instructions may result in result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
Page 16
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
16
Model No.
Vent Pipe Size
CPVC Transition Vent Pipe Length
Full Insertion Depth
CHS 85-110
3”
Minimum 5” [127 mm]
2-7/8” [73 mm]
CHS 155-250
3”
Minimum 5” [127 mm]
2-5/8” [67 mm]
CHS 300-399
4”
Minimum 5” [127 mm]
2-5/8” [67 mm]
Model No.
Vent Material
Venting Brand
Adapter Part No.
1,2
CHS 85-250
Polypropylene
DuraVent – PolyPro
300150
Centrotherm - InnoFlue
ISAA0303
Stainless Steel
DuraVent – FasNSeal
300715
CHS 300-399
Polypropylene
DuraVent – PolyPro
300151
Centrotherm - InnoFlue
ISAA0404
Stainless Steel
DuraVent – FasNSeal
303631
Notes:
1
Listed appliance adapters are only approved for use with the respective venting brand; i.e. a PolyPro appliance adapter
shall not be used with InnoFlue venting.
2
PolyPro and FasNSeal appliance adapters are available from DuraVent (1-800-835-4429 or www.duravent.com);
InnoFlue appliance adapters are available from Centrotherm Eco Systems (1-877-434-3432 or www.centrotherm.us.com).
Items 1
Materials
2, 3
Venting System Standards
All Vent and Air-Inlet
materials installed on gas
fired appliances in CAN/US
must meet the Standards
listed in this Table. Failure
to comply could result in
fire, serious injury or death.
United States
Canada 4
Vent Piping
and Fittings
PVC - DWV
ANSI/ASTM D2265
All venting material in
Canada must be
ULC S636 approved.
See Note 4 below for
appropriate temperature
applications.
PVC Schedule 40
ANSI/ASTM D1785
CPVC Schedule 40
ANSI/ASTM F441
Stainless Steel (SS)
UL-1738
Polypropylene (PP)
-
Pipe Cement
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Primers
PVC / CPVC
ANSI/ASTM F656
Notes:
1
Refer to Table 4-5 for Allowable Vent and Air-Inlet Pipe Sizes and Lengths.
2
PVC venting (exhaust and air-inlet) is not permitted within the Closet/alcove of a Closet/alcove installation.
3
The Air-inlet does not require high temperature pipe material. Check applicable local codes for acceptable materials.
4
ULC S636 PVC is approved for flue gas temperatures up to 149oF (65oC) and must only be used for low temperature
applications. High temperature applications requiring boiler supply water temperatures greater than 140oF (60oC) must
use ULC S636 CPVC, PP or SS.
Table 4-2 CPVC Vent Pipe Transition Piece (used when venting with PVC)
Table 4-3 Appliance Adapters for Polypropylene and Stainless Steel Venting
Vent/Air-inlet Pipe Material
Table 4-4 Acceptable Vent and Air-Inlet Pipe Material
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
(polyphenolsulfone) in the exhaust venting system is prohibited. Failure to follow these
instructions may result in property damage, personal injury or death.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Failure
to follow these instructions may result in property damage, personal injury or death.
Page 17
CHS Series Installation and Operation Instructions │Slant Fin Corp.
17
Model No.
Pipe
Size
Gas
Length
(ft)
Number of Elbows (90’s or 45’s) and Equivalent Feet
1 2 3 4 5 6 7 8 9
CHS 85-110
2”
1
NG
100
95
90
85
80
75
70
65
60
55
CHS-85
LP
35
30
25
20
15
10 5 - - -
CHS-110
25
20
15
10 5 - - - - -
CHS 85-110
3”
NG/LP
150
145
140
135
130
125
120
115
110
105
CHS 155-250
100
95
90
85
80
75
70
65
60
55
CHS 300-399
4”
100
95
90
85
80
75
70
65
60
55
Note:
1
See WARNING below.
Mandatory Pre-commissioning Procedure for Plastic Venting (PVC or CPVC)
1) Working with the power turned off to the boiler, completely install the vent and air intake system, securely
cementing joints together. If possible, allow primers/cements to cure for 8 hours before firing the burner. If
curing time is less than 8 hours, proceed with Steps 2 through 6.
2) Maintain the boiler gas supply shut-off valve in the off position.
3) Remove the cable from the Spark Ignition Transformer.
4) Turn power on to the boiler and apply a heat demand.
5) Allow for 3 complete trials for ignition, consisting of pre and post purge of the combustion blower, until an
ignition lockout occurs. Repeat the process two more times (i.e. 9 complete ignition sequences in total).
6) Turn power off and reconnect the cable to the Spark Ignition Transformer.
Vent/Air-inlet Pipe Length Determination
Use Table 4-5 to determine the maximum pipe length that can be used. The table calculates 90º elbows, and 45º
elbows at 5 equivalent feet each.
Example: When using 3” pipe, a CHS 85-110 can be installed with 150 equivalent feet of air-inlet piping and
150 equivalent feet of exhaust-vent piping. See Table 4-5 for more details.
11’ for 2” and 3” venting respectfully.
Table 4-5 Allowable Vent and Air-inlet Pipe Size and Lengths
Do not apply power to the boiler prior to Step 4 in the Mandatory Pre-commissioning
Procedure for Plastic Venting.
Spark Ignition Circuit - Maintain a safe distance (2 inches minimum) from the spark
ignition circuit to avoid injury from electrical shock.
Models CHS 85-110 require a minimum equivalent exhaust vent length of 15’. When
operating on Propane, models CHS 85-110 require a minimum air-inlet length of 6’ and
PVC Exhaust Venting – When using 2” PVC venting with models CHS 85-110, the first
seven (7) equivalent feet of exhaust venting must be approved 2” CPVC or 3” PVC; see
exceptions in Table 4-4 and Figures 4-2b and 4-2d.
Page 18
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
18
Description
Vent
Size
Vent Material
Slant/Fin
P/N
Supplier
P/N
Boiler Models
Vent Option
Roof
Wall
IPEX Low Profile
(Flush Mount)
7
2”
PVC/CPVC
7
196984
CHS 85-110
3”
81 8171 000
196985
CHS 85-250
4”
81 8174 000
196986
CHS 300-399
IPEX Concentric
(Wall/Roof)
5,6,7
2”
PVC
196005
CHS 85-110
3”
81 8173 000
196116
CHS 85-250
CPVC
197009
4”
PVC
81 8175 000
196021
CHS 300-399
DuraVent - PolyPro
Concentric (Wall)
2”
PVC/CPVC/PP
2PPS-HK
CHS 85-110
3” 3PPS-HK
CHS 85-250
4” 4PPS-HK
CHS 300-399
DuraVent - PolyPro
Concentric (Roof)
2”
2PPS-VK
CHS 85-110
3”
3PPS-VK
CHS 85-250
4” 4PPS-VK
CHS 300-399
Notes:
1
Instructions included with termination kits contain detailed assembly and installation instructions.
2
All factory termination kits are ULC S636 approved.
3
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
4
Piping MUST be secured to the vent terminal during installation.
5
IPEX Concentric Terminal MUST be cemented together and to the vent pipes during installation.
6
Vent Screens provided with boiler may be used with the IPEX Concentric Vent Kits; otherwise use IPEX vent screens
(2” vent screen P/N 196050; 3" vent screen P/N 196051; 4" vent screen P/N 196052 – each sold separately).
7
IPEX Low Profile and Concentric kits (excluding p/n 197009) are constructed out of ULC S636 approved PVC; check
with your local authority for the acceptance of PVC as a venting material prior to use.
Termination Options – Direct Vent Installation
The venting system of the CHS may be terminated using field supplied piping to construct a “Two-Pipe”
termination, see Figures 4-3a, 4-4a, 4-4d, 4-5a, 4-6a and 4-6d; alternatively the venting may be terminated using
a factory kit selected from Table 4-6. The “IPEX Low Profile” kit (see Figures 4-3b and 4-5c) and “M&G
DuraVent Concentric (Wall)” kit (see Figures 4-3d and 4-5d) can be used for Sidewall terminations, while the
“M&G DuraVent Concentric (Roof)” kit (see Figures 4-4c and 4-6c) can be used for Rooftop terminations; the
“IPEX Concentric” kit (see Figures 4-3c, 4-4b, 4-5b and 4-6b) can be used for either Sidewall or Rooftop
terminations.
Optional Termination Kits – Direct Vent Installation
Kits certified with the CHS boiler are listed in Table 4-6 and available from IPEX, DuraVent and/or Slant/Fin.
For more information on System 636 Vent Kits or wholesaler locations contact IPEX directly USA: 1-800-4639572 or www.IPEXamerica.com │CAN: 1-866-473-9462 or www.ipexinc.com. For more information on
PolyPro Vent Kits or wholesaler locations contact DuraVent directly 1-800-835-4429 or www.duravent.com.
Table 4-6 Optional Vent Termination Kits
Venting Options - Due to potential moisture loading (build-up) along the exterior wall,
sidewall venting may not be the preferred venting option (see Figures 4-4 and 4-6).
Page 19
CHS Series Installation and Operation Instructions │Slant Fin Corp.
19
Figure 4-3(a)
Figure 4-3(b)
Two-pipe Termination (Sidewall)
IPEX Low Profile Termination (Sidewall)
Figure 4-3(c)
Figure 4-3(d)
IPEX Concentric Termination (Sidewall)
DuraVent Concentric Termination (Sidewall)
Location of exhaust and air-inlet
connections vary between
models, see Figure 4-2.
(model CHS 85-110 shown)
Exhaust
Inlet
Location of exhaustandair-inlet
connections varybetween
models, see Figure4-2.
(model CHS 85-110shown)
Exhaust
Inlet
Location of exhaust and air-inlet
connections vary between
models, see Figure 4-2.
(model CHS 85-110 shown)
Exhaust
Inlet
Location of exhaust and air-inlet
connections vary between
models, see Figure 4-2.
(model CHS 85-110 shown)
Exhaust
Inlet
Page 20
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
Location of exhaust and air-inlet
connections vary between
models, see Figure 4-2.
(model CHS 85-110 shown)
Exhaust
Inlet
Location of exhaust and air-inlet
connections vary between
models, see Figure 4-2.
(model CHS 85-110 shown)
Exhaust
Inlet
Location of exhaust and air-inlet
connections vary between
models, see Figure 4-2.
(model CHS 85-110 shown)
Exhaust
Inlet
Location of exhaustandair-inlet
connections varybetween
models, see Figure4-2.
(model CHS 85-110shown)
Exhaust
Inlet
Page 21
CHS Series Installation and Operation Instructions │Slant Fin Corp.
21
Sidewall Termination Details – Direct Vent Installation
Figure 4-5(a)
Figure 4-5(b)
Two-Pipe Termination (Sidewall)
IPEX Concentric Termination (Sidewall)
Figure 4-5(c)
Figure 4-5(d)
IPEX Low Profile Termination
DuraVent PolyPro Wall Termination
Exhaust
Air-inlet
Min. 12”
above grade
or snow level
Vertical
Min. 18”
Horizontal
4-12” or greater
than 36”
Exhaust
Air-inlet
Vent Screen
Vent pipe piece to
retain vent screen
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust
Air-inlet
Min. 12”
above grade
or snow level
Air-inlet around
perimeter (1-2”
from wall)
Exhaust through
center
Vent Screen
Vent pipe piece to
retain vent screen
Refer to documentation included with termination kit for
complete installation instructions.
Refer to documentation included with termination kit for
complete installation instructions.
Refer to documentation included with termination kit for
complete installation instructions.
Min. 12”
above grade
or snow level
Exhaust
Air-inlet
Exhaust
Air-inlet around
perimeter
Min. 12”
above grade
or snow level
Exhaust center
Air-inlet bottom
Exhaust
Air-inlet
Gas Vent Directly Below
Keep Free of Obstructions
Page 22
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
22
Roof Termination Details – Direct Vent Installation
Figure 4-6(a)
Figure 4-6(b)
Two-Pipe Termination (Roof)
IPEX Concentric Termination (Roof)
Figure 4-6(c)
Figure 4-6(d)
DuraVent PolyPro Roof Termination
Exhaust only Roof Termination
Min. 12”
above grade
or snow level
Vent Screen
Vent pipe piece to
retain vent screen
Exhaust
Air-inlet
Vertical
Min. 18”
Horizontal
4-12” or greater
than 36”
Flashing
Min. 12”
above grade
or snow level
Vent Screen
Vent pipe piece to
retain vent screen
Exhaust center
Air-inlet around
perimeter
Flashing
Refer to documentation included with termination kit for
complete installation instructions.
Refer to documentation included with termination kit for
complete installation instructions.
Min. 12”
above grade
or snow level
Flashing
Exhaust
Air-inlet
Figure illustrates two options for exhaust termination only;
neither vent pipe illustrated is for combustion air-inlet.
Min. 12”
above grade
or snow level
Flashing
Vent pipe piece to
retain vent screen
Vent Screen
Exhaust
Option 1
Exhaust
Option 2
Page 23
CHS Series Installation and Operation Instructions │Slant Fin Corp.
23
Venting Rules and Guidelines
1. Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
2. Combustion Air-inlet Contamination: Air for combustion must be drawn from an area free of dust and
contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust
and debris will cause corrosion damage of the heat exchanger voiding your Slant/Fin warranty. Refer to
Table 4-1 for a list of corrosive products and contaminants sources to avoid.
3.Vertical Separation: The exhaust must be a minimum of 18” [457 mm] above the air inlet, and the air inlet
must always be a minimum of 12” [305 mm] plus snow allowance above any surface that will support snow.
(Two feet plus snow allowance is highly recommended). Consult your weather office for the maximum
typical snowfall for your region.
Example: New Brunswick Canada - typical maximum snowfall is 19”, thus the inlet must be (12”+19”) =
31” above grade and exhaust must be (31”+18”) = 49” above grade.
4.Horizontal Separation: The horizontal distance between the inlet and exhaust must be a minimum of 4”
[102 mm] center to center.
5.Wall Flashing: Under normal operating conditions this boiler will produce a plume of white gases, and
should be taken into consideration when selecting an adequate location. A 36” [915 mm] diameter stainless,
plastic, or vinyl shield can be used to flash the exterior of the residence.
6.Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people
and pets or damage nearby shrubs and plants.
7. Elbow Extensions: Elbows on outside of wall must be no more than ½” [13 mm] away from the wall.
8. Vent Sloping: All indoor exhaust piping must be on a slope back to the boiler a minimum of ¼” per linear
foot of vent [6.25 mm per linear 305 mm]. For applications where excessive condensation is possible ½” per
linear foot [13 mm per linear 305 mm] is recommended.
9.Vent Supports: Where required Vent and Air-inlet piping shall be secured to the wall for more rigidity. All
interior vent pipe shall be supported a minimum of every 36” [915 mm].
10. Roof Exhaust: In all roof applications the discharge must point away from the pitch of the roof.
11. Roof Flashing: Install adequate flashing where the pipe enters the roof, to prevent water leakage.
12. Rain Cap: Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
13. Venting Below Grade: For installations that exit the wall below grade refer to Figure 4-7.
14. Vent Screens: Install factory supplied vent screens on the outside of the last elbow for both the inlet and
exhaust vent terminal elbows. Install the screen into the female opening of the elbow, and then cut a small
piece of pipe to sandwich the screen into the elbow. NOTE: ensure the small piece of pipe cut, does not
extend past the end of the elbow. Two screens are provided in the package. See Figures 4-5 and 4-6.
15.Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate
could drip and freeze resulting in a slip hazard or damage to vehicles and machinery.
16.Warning Plate: For Sidewall Venting, install the warning plate “Gas Vent Directly Below”, directly above
(within 4 ft [1.22 m] vertically) the location of the air-inlet pipe, so it is visible from at least 8 ft [2.4 m]
away. See Figure 4-5.
17.Wall Thickness: Direct vent terminations are designed to work with any standard wall thickness.
Installation guidelines for min/max wall thickness are as follows: Min.= 1” [25mm], Max.= 60” [1.52 m].
18.Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting
may not be the preferred venting option. Refer to Figures 4-4 and 4-6 for roof top venting options.
Page 24
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
24
Figure 4-7 Venting Below Grade
For installations that exit the wall below grade:
1. Excavate site to a point below where the pipes
are to exit as shown.
2. Ensure the wall is fully sealed where the pipes
penetrate.
3. The Vent/Air-inlet piping MUST be secured to
the side of the building above grade, as shown,
to provide rigidity.
4. Optional mounting bracket PN. 82075 for
securing the exhaust pipes (only applicable for
3” PVC/CPVC venting).
5. Ensure that the Vent/Air-inlet clearances are
maintained, see Section 5.0 for details.
Figure 4-8 Outdoor Horizontal Venting
Vent piping outside the Building is permitted under
the following conditions:
1. The maximum length outside the building is 20
feet [6.1 m]. Note that outdoor length must be
included in the overall vent length calculation.
2. All normal termination clearances are maintained.
3. The pipe is supported every 24” [610 mm].
4. The exhaust and air-inlet are sloped back to the
boiler ½” elevation for every linear foot [13 mm
for every linear 305 mm].
Figure 4-9 Existing Chimney Chase Way
It is permissible to use an existing chimney as a chase
way to run the Vent/Air-inlet piping as long as:
1. The chimney is not being used by any other
boiler.
2. Flue gases don’t enter the vacant chimney.
3. Only CHS certified venting materials are used,
see Section 4.0.
4. Vent lengths are within the maximums specified.
5. The top of the chimney is capped and the
Vent/Air-inlet pipes are flashed to prevent
leakage into the vacant chimney.
Air-Inlet
Existing
Chimney
(used as a
chase way)
Chimney
Cap
Exhaust Vent
Exhaust Vent Min.
18” [457 mm]
above air-inlet
Air-Inlet
Min. 12” [305 mm]
above roof and
snow level
Supports every
24” [610 mm]
12” [305 mm] plus snow
allowance above grade
Air-Inlet
Maximum of 20 ft
[6.1 m] is permitted
for piping outside a
building.
Exhaust
Vent
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust
Air-inlet
Wall Brackets
Page 25
CHS Series Installation and Operation Instructions │Slant Fin Corp.
25
Clearances to Air-Inlet Termination
Canada 1
USA 2
Min. Distance
Min. Distance
A
Above grade/roofline and snow level 8
12 in.
305 mm
12 in.
305 mm
B
Above roof line - Concentric Vent
6, 11, 13
24 in.
610 mm
24 in.
610 mm
C
To exhaust vent from any other boiler
36 in.
915 mm
12 in.
305 mm
Clearances to Exhaust Vent Termination
Min. Distance
Min. Distance
D
Minimum vertical separation above air inlet 9
18 in.
457 mm
18 in.
457 mm
E
Minimum horizontal separation from air inlet 3
4 in.
102 mm
4 in.
102 mm
F
Window, door or building opening
36 in.
915 mm
12 in.
305 mm
G
To combustion air inlet from any other boiler
36 in.
915 mm
12 in.
305 mm
H
Non-mechanical air supply inlet to building
36 in.
915 mm
12 in.
305 mm
I
Mechanical air supply inlet to building 4
6 ft.
1.83 m
3 ft.
915 mm
J
Soffit, overhang, eave or parapet
24 in.
610 mm
24 in.
610 mm
K
Soffit vent or vent opening in an overhang, eave or parapet
6 ft.
1.83 m
6 ft.
1.83 m
L
Outside corner 10
- - -
-
M
Inside corner of an L-shaped structure (including walls and fences)
36 in.
915 mm
36 in.
915 mm
N
Electric meters, gas meters, regulators and relief equipment
6 ft.
1.83 m
4 ft.
1.22 m
P
Each side of center line above or below meters, regulators and relief devices 5
36 in.
915 mm
36 in.
915 mm
Q
Above a paved sidewalk, driveway, or parking lot on public property if adjacent12
7 ft.
2.13 m
7 ft.
2.13 m
R
Above a sidewalk, driveway, or parking lot on public property
X X X
X
S
Above a sidewalk, driveway on private property between / serving both dwellings
X X X
X
T
Under a concrete veranda, porch, deck, or balcony 7
24 in.
610 mm
24 in.
610 mm
U
Above, under or near exterior stairs
X X X
X
V
Into a canopy or carport
X X X
X
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local
building codes.
2 - US installations must comply with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code and local building codes.
3 - Horizontal separation center-to-center (c.c.) 4”-12” (102-305 mm).
4 - For US installations, an exhaust vent may be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally.
5 -Horizontal clearance must be observed up to a height of 15 ft. [4.6 m] above/below the meter, regulator, or relief devices.
6 - Concentric Vent must protrude from the roof precisely 24” [610 mm] measuring from the terminal end-cap vanes.
7 - Permitted if veranda, porch, deck, or balcony is made of concrete and a minimum of two sides are fully open beneath.
8 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice
(i.e. for roof venting clearances - roofline and snow level). If living in a snowfall region, consult your local weather
office for the maximum typical snowfall for your area.
9 - Note that the vent must maintain a minimum vertical distance above the air-inlet. Example: Vent height = 18” (457
mm) above air inlet + 12” (305 mm) for air inlet above grade/roof line and snow level = 30” (762 mm) above grade and
snow level.
10-Clearances to an outside corner to be in accordance with local installation codes.
11-In Canada, concentric vent materials are subject to approval by local inspectors. See Termination Kits in Section 4.0.
12-Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard.
13-Contact the manufacturer for special exemptions relating to multiple boiler installations using concentric vents.
5.0 VENT/AIR-INLET TERMINATION CLEARANCES
The quick reference table below is to be read in conjunction with the numbered notes as
indicated, Figures 5-1 and 5-2, and the Venting Rules and Guidelines in Section 4.0. The
instructions detailed in this section are a combination of CHS specific and National Gas Code restrictions.
Compliance alone doesn’t insure a satisfactory installation as good common sense must also be applied. Failure
to follow these instructions may result in fire, property damage, serious injury or death.
Table 5-1 Termination Clearances Quick Reference Table (See Figures 5-1 and 5-2)
Page 26
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
26
G – Letter represents a specific Termination Position. Refer to Table 5-1 for corresponding termination clearances.
Concentric Vent
Termination
Q
Two-Pipe
Termination
F
Clearance “Q”
Adjacent to Public
Walkway or Driveway
Minimum 7ft [2.13 m]
G
Clearances “F” and “G”
Canada – Minimum 3 ft [915 mm]
The US– Minimum 1 ft [305 mm]
Figure 5-1 Termination Clearance Quick Reference Diagram (See Table 5-1)
Illustrations of Termination Clearances
Figure 5-2 Sidewall Termination (See Table 5-1)
Page 27
CHS Series Installation and Operation Instructions │Slant Fin Corp.
27
Extra precaution must be taken to adequately support the weight of the Vent/Air-inlet
piping in applications using roof-top terminations. Failure to follow these instructions
may result in venting or boiler component failure resulting in flue gas spillage leading to property damage,
serious injury or death.
result in fire, property damage, serious injury or death.
Removing an Existing Boiler from Common Venting System
emissions into the surrounding air resulting in serious injury or death.
connected to it. Instructions have been provided on how to remove the existing boiler and how to resize the
remaining venting system. Failure to follow these instructions may result in property damage, serious injury or
death.
Upon removal of an existing boiler, the following steps shall be followed for each boiler remaining in the
common venting system; prior to commencing this procedure, shutdown all boilers remaining in the common
venting system.
Steps to Removing an Existing Boiler:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Verify that there is no blockage,
restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close fireplace dampers, all building doors and windows and all doors between the
space in which the boilers remaining connected to the common venting system are located and other spaces
of the building. Turn on clothes dryers and any boiler not connected to the common venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do
not operate a summer exhaust fan.
4. Place in operation the boiler being inspected. Follow the applicable lighting instructions. Adjust thermostat
so boiler will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each boiler remaining connected to the common venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other
gas burning boiler to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms to
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code. When resizing any portion of the common venting system, the common venting system
should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code.
Under no circumstances may an existing chimney or chase-way be used to vent or
provide combustion inlet air to a CHS boiler. Failure to follow these instructions will
Do not install the CHS into a common venting system with any other boiler. Failure to
comply with this warning will cause flue gas spillage and leech carbon monoxide
When an existing boiler is removed from a common venting system, the common
venting system is likely to be too large for proper venting of the remaining boilers
Page 28
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
28
6.0 CONDENSATE DRAIN
This unit produces liquid condensate in the heat exchanger and venting system as a product of combustion.
Steps must be taken to ensure condensate does not collect in the venting system; therefore, all exhaust piping
must slope back to the boiler a minimum 1/4” per linear foot of vent. Condensate must be drained from the unit
into a household drain.
condensate must be neutralized prior to entering a drain).
The following are important notes that must be taken into consideration when constructing the condensate drain
system (See Condensate Trap Installation Instructions for further details):
DO NOT install condensate lines outside. A frozen or blocked drain will cause the condensate to back-up
and leak. This may result in damage to boiler components resulting in a no heat condition; property damage
may also occur.
NEVER use copper, steel, or galvanized piping in the construction of the condensate system (condensate is
very corrosive and will corrode most metals).
When a condensate pump is used or required, select a pump that is designed for residential furnaces.
Condensate Trap Installation Instructions (see Figure 6-1)
(Note: the Condensate Trap is factory supplied with the boiler and must be field installed)
1. Remove Hose-barb Adapter – Remove the Inlet Retaining Nut to access the Hose-barb Adapter (the
Hose-barb Adapter is not used and can be discarded).
2. Attach Corrugated Outlet Tube – Remove the Outlet Retaining Nut and Outlet Gasket and slide
components onto the Corrugated Outlet Tube – note orientation (gasket should be positioned
approximately 1/8” from the edge of the outlet tube – see Figure 6-1). Press the Corrugated Outlet Tube
into the Condensate Trap Outlet and firmly hand-tighten the Outlet Retaining Nut.
3. Attach to Boiler Condensate Drain (A) – Place the Inlet Retaining Nut and Inlet Gasket on the Boiler
Condensate Drain (gasket should be positioned approximately 5/8” from the edge of the Condensate
Drain Fitting – see Figure 6-1)
4. Attach to Boiler Condensate Drain (B) – Slide the Condensate Trap into place over the boiler
Condensate Drain Fitting – push-up until it bottoms out (ensure the Ball-float is placed inside the trap –
see Figure 6-1). Firmly hand-tighten the Inlet Retaining Nut.
5. Outlet to Drain – Route the condensate from the Corrugated Outlet Tube to a household drain, condensate
pump or neutralizer (check with your local authority regarding the disposal of condensate).
Failure to install the condensate trap properly will result in flue gas spillage and leeching of carbon monoxide
emissions into the surroundings resulting in serious injury or death.
Check with your municipality, or local gas company to determine if the disposal of
combustion condensate is permitted in your area (e.g. in the State of Massachusetts the
Carefully follow the above instructions and the accompanying figure – check to ensure
the condensate trap is secure to the bottom of the boiler and that no strain is placed on it.
Page 29
CHS Series Installation and Operation Instructions │Slant Fin Corp.
29
Figure 6-1 Condensate Drain Piping
Outlet Retaining Nut
firmly tightened
Condensate Trap
pushed up until it
bottoms-out on Boiler
Condensate Drain
Boiler Condensate Drain
Outlet Nut and Gasket
Ball -float
Outlet
Corrugated Outlet Tube
Outlet Retaining Nut
Outlet Gasket
Ball-float
Inlet Gasket
Inlet Retaining Nut
Hose-barb Adapter
Inlet
Condensate Trap
Cleanout Cap
Corrugated Outlet Tube routed to household
drain, condensate pump or neutralizer (no strain
applied on tubing or condensate drain assembly)
Page 30
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
30
Model
Kit Number
Orifice Number
CHS-85
81 8124 000
415 (4.15mm)
CHS-110
81 8124 000
52 (5.2mm)
CHS 155-250
81 8124 000
62 (6.2mm)
CHS 300-399
81 8125 000
74 (7.4mm)
7.0 INSTALLING GAS PIPING
Conversion Kit (see Table 7-1) must be installed prior to installing the gas piping to the boiler. Failure to
properly convert the unit to operate with Propane may result in property damage, serious injury or death.
Codes as they may require boilers fueled with LP gas to be provided with an approved means of removing
unburned gases from the room. Failure to follow these instructions may result in serious injury or death.
Table 7-1Natural to LP Propane Conversion Kit
Installation
Refer to the current National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation codes,
and local codes for gas piping requirements and sizing. Pipe size running to the unit depends on:
Length of pipe.
Number of fittings.
Type of gas.
Maximum input requirement of all gas boilers in the residence.
Ensure that:
The gas line connection to the boiler does not apply any weight to the gas valve. Slant/Fin recommends
using approved flexible gas piping (if acceptable by local codes) to connect the boiler to the gas supply (See
Figure 7-1 for details).
You plan the installation so the piping does not interfere with the vent pipe, or the removal of the valve,
burner, and serviceable components.
The Boiler is installed such that the gas ignition system components are protected from water (dripping,
spraying, rain etc.) during installation and servicing.
The gas piping is large enough for all the gas appliances in the home. No appreciable drop in line pressure
should occur when any unit (or combination of units) lights or runs. Use common gas-line sizing practices.
Always use a pipe-threading compound that is resistant to Propane (LP) gas solvent action. Apply sparingly
to all male threads, starting at two threads from the end. Over doping or applying dope to the female end,
can result in a blocked gas line.
DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the valve or
blower motor can occur.
Install a manual “Equipment Shut-Off Valve” as shown in Figure 7-1. Valve must be listed by a nationally
recognized testing laboratory.
The gas line piping can safely be removed from the boiler for servicing, by strategically placing the gas line
shutoff and union; see example in Figure 7-1.
All gas piping, including gas components in the boiler, are checked for leaks using a “Bubble Test”, prior to
operating the boiler.
gas valve could occur resulting in fire, property damage, serious injury or death.
The CHS boiler is factory equipped to operate with Natural Gas, the installation of a
conversion kit is required prior to operating with Propane Gas. The Natural to LP
Liquefied Petroleum (LP) propane gas is heavier than air. Do not install the boiler in a pit
or similar location that will permit heavier than air gas to collect. Check with Local
Strain on the gas valve and fittings may result in vibration, premature component failure
and leakage and may result in a fire, explosion, property damage, serious injury or death.
Do not use an open flame to test for gas leaks. Failure to follow these instructions may
result in fire, property damage, serious injury or death.
When performing a pressure test on the gas line piping, be sure the boiler is disconnected
or isolated if the test pressure is expected to exceed 1/2 PSI (14” w.c.), as damage to the
Page 31
CHS Series Installation and Operation Instructions │Slant Fin Corp.
31
Figure 7-1 Gas Line Connection (Typical)
Test all gas piping, internal and external to the boiler, for leaks. Failure to follow
these instructions may result in fire, property damage, serious injury or death.
Manual Gas Shutoff Valve
Should overheating occur or the
gas supply fail to shutoff, close the
Manual Gas Shutoff Valve to the
boiler.
Union
Flexible Gas Line Piping
Recommended to eliminate
strain on the boiler gas
components (only use if
acceptable by local codes).
DripLeg / Optional Gas Supply Location
When used as the Gas Supply Location,
remove cap and install on the top fitting;
drip leg must be field constructed external
to the boiler.
Page 32
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
32
8.0 LIGHTING THE BOILER
manual, including the Vent/Air-Inlet, Condensate Drain, and System Water Piping. Failure to precisely follow
these instructions will cause a fire or explosion resulting in property damage, serious injury or death.
damage, serious injury or death.
property damage, serious injury or death.
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to turn the gas “shutoff” valve. Never use tools. If the handle will not turn by hand,
don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the boiler and to replace any part of the control system and any gas control which has been
under water.
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service
technician or gas supplier.
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler
3. Turn the manual gas valve to the OFF position
Before Start-up refer to Mandatory Pre-commissioning Procedure for Plastic Venting
in Section 4.0.Failure to follow these instructions can result in explosions, injury or death.
Prior to turning the gas supply on and lighting the boiler, ensure all aspects of the
installation are complete and in conformance with the instructions provided in this
Do not store or use gasoline or other flammable vapors & liquids in the vicinity of this or
any other boiler. Failure to follow instructions could result in explosion causing property
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, serious injury or death.
Should overheating occur or the gas supply fail to shutoff, close the Manual Gas Shutoff
Valve to the boiler. Failure to follow instructions could result in explosion causing
FOR YOUR SAFETY, READ BEFORE OPERATING_
OPERATING INSTRUCTIONS_
TO TURN OFF GAS TO THE BOILER_
Page 33
CHS Series Installation and Operation Instructions │Slant Fin Corp.
33
The initial lighting of the boiler must be performed by a licensed Gas Technician.
Ensure the boiler is wired in accordance with this manual.
Ensure the gas shutoff valve is turned on, and that the gas system has been fully tested for leaks.
Ensure the system is completely filled with water, and that ALL the air is purged out.
Plastic Venting in Section 4.0.Failure to follow these instructions can result in explosion, serious injury or death.
Initial Start-Up
1. Turn on power to the CHS boiler and turn-up the Thermostat(s). The boiler should run through a purge, and
combustion should occur. (The control system has a built-in ignition retry, allowing the system to try at least
three times, before locking-out.)
2. With the unit operating at full capacity, verify that the gas line pressure is 4-10.5 inches w.c. for Natural gas,
and 9-13 inches w.c. for Propane (See Section 9.0 for details).
3. Using an appropriate Oxygen (O2) or Carbon Dioxide (CO2) analyzer, take a sample of the flue gas. The
sample must fall within the acceptable ranges for CO2, which is 8.7% - 9.7% for Natural Gas, and 10.5%-
11.5% for Propane (See Section 9.0 for details).
4. Perform at least three lights in succession to ensure proper operation.
5. After the three successive lights, unplug the flame probe, and allow the unit to cycle again. The flame safety
system will allow the unit to go through 4 ignition cycles before going to “Hold 110 – Ignition failure
occurred”. Once you have confirmed this behavior, replace the wire on the flame sensor, recycle power and
reconfirm proper lighting.
(also located in the burner plate); this device is used for spark ignition and produces 14,000 volts potential which
would result in an EXTREME ELECTRICAL SHOCK possibly causing serious injury or death.
operation of the burner is rough or erratic. Failure to follow these instructions may result in serious injury or
death.
Re-lighting Unit
1. Stop and read these instructions very carefully.
2. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device that automatically lights the burner.
Do not try to light the burner by hand.
4. Turn the gas shutoff valve to the off position, and then remove the front cover.
5. Wait five (5) minutes to clear out any gas. Then check for gas, including near the floor. If you smell gas
“Stop” and follow “B” above (see FOR YOUR SAFETY, READ BEFORE OPERATING). If you don’t
detect any gas proceed to the next step.
6. Turn the gas shutoff valve to the on position, wait an addition five (5) minutes and check for gas.
7. Replace the front cover.
8. Set the thermostat to the highest setting, and then turn on all power to the boiler.
9. Ignition sequence is automatic, combustion will occur after a brief fan purge. Ignition will retry 3 times.
10. If ignition does not occur, “Turn off the gas and electricity to the boiler” and contact a qualified service
technician, or gas supplier.
Turning Off the Boiler
1. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
2. Turn the gas shutoff valve to the off position.
Failure to follow instructions may result in property damage, serious injury or death.
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8
hours,first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for
The flame probe is located in the burner plate; it has a single white/semi-transparent wire
connected to it. DO NOT remove the orange spark cable from the ignition electrode
If the unit fails to light consistently and smoothly, contact Slant/Fin for technical
assistance at (516) 484-2600. Never allow the boiler to operate if the ignition or
Page 34
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
34
Gas
Line Pressure (inches wc)
CO2 (%)*
CO (ppm)
Max.*
Nominal/Desired
Min.
Max.
Min.
Max.
Natural
7
4
10.5
8.7
9.7
175
Propane
11 8 13
10.5
11.5
175
Model
Min. Modulation Rate (RPM)
Max. Modulation Rate (RPM)
CHS-85
1525 (1700 on LP)
6300
CHS-110
1625 (2150 on LP)
7000
CHS-155
900
3700
CHS-175
900
4100
CHS-200
900
4650
CHS-250
900
5900
CHS-300
1500
5000 (4800 on LP)
CHS-399
1500
6900 (6600 on LP)
9.0 GAS VALVE AND BURNER SET-UP
property damage, serious injury or death.
Gas Line Pressure
The boiler gas valve is equipped with a line pressure test port; see Figures 9-1 and 9-2. Use the following
procedure to measure the gas line pressure to the boiler to ensure if falls within the range given in Table 9-1:
1. Turn the supply of gas to the boiler off.
2. Open the bleed screw of the line pressure test port approximately 1-1/2 turns. This port is directly
connected to the gas line feeding the boiler. See Figures 9-1 and 9-2.
3. Force 1/4 ID tubing over the housing of the line pressure test port; install the other end of the tubing to an
appropriate line pressure test gauge or manometer. Ensure both ends of the tubing make a tight connection.
4. Open the supply of gas to the boiler and check for gas leaks.
5. Observe the line pressure under static conditions and compare it to Table 9-1. The pressure will be greatest
under static conditions.
6. With all other gas appliances in the application running, operate the burner to the maximum firing rate (See
Table 9-2) and compare the observed line pressure with Table 9-1. The pressure will be lowest during the
maximum flow of gas.
7. Adjust the gas line pressure to ensure the parameters in Table 9-1 are attained under all conditions. If
possible adjust the line pressure to the "Nominal/Desired" value listed in Table 9-1, while the unit is
operating at the maximum modulation rate, see Table 9-2.
8. Continue observing the gas line pressure until the completion of the combustion analyses, in case
adjustments need to be made.
9. Complete pressure testing, and then return the bleed screw of the Line Pressure Test Port to the closed
position.
Table 9-1 Line Pressure and Combustion Parameters
Set-up of the CHS gas valve must be performed by a licensed Gas Technician. Failure to
perform the set-up correctly may result in incorrect operation, component failure,
The line pressure is a function of the gas supply and is affected solely by field provided
parameters such as line size and regulator settings. Under no circumstances can the boiler
gas valve influence or be used to adjust the gas line pressure.
Failure to close the bleed screw of the Line Pressure Test Port will cause a severe leakage
of gas, resulting in a fire or explosion causing property damage, serious injury or death.
*Note: Observe the combustion products with the burner operating at the maximum modulation rate.
Table 9-2 Minimum and Maximum Modulation Rates
Carbon Monoxide - Never leave the unit operating while producing Carbon Monoxide
(CO) concentrations in excess of 175ppm. Failure to follow this warning may result in
serious injury or death.
Page 35
CHS Series Installation and Operation Instructions │Slant Fin Corp.
35
Throttle/Input Adjustment Screw
Increase gas
Turn Counter Clockwise
Decrease gas
Turn Clockwise
Manifold Pressure - DO NOT adjust or measure the Manifold Pressure of the boiler.
Correct manifold pressure is factory set. Field adjustment could result in improper burner
operation resulting in fire, explosion, property damage or death.
CO. Adjustments may only be performed if the gas line pressure is maintained above minimum levels
throughout the duration of the test, see Table 9-1. Failure to follow these instructions may result in serious
injury or death.
Adjustment
Throttle / Input Screw Adjustments - The boiler is equipped with a Throttle/Input Adjustment Screw, located
on the Gas Valve and Venturi Assembly. It is used to adjust the flow of gas leaving the gas valve entering the
Venturi and then the combustion air stream. Turn the adjustment screw in (clockwise) to reduce the flow of gas,
make combustion leaner, and reduce the concentration of CO2 in the flue gases. To increase the CO2 level and
flow of gas in the combustion air stream, adjust the Throttle screw out (counterclockwise).
CHS 85-250 Adjustments - The throttle screw for models CHS 85-250 is a multiple turn valve. Typical
adjustment required for Natural Gas is 0-1 full turns in or out from the factory setting. Typical adjustment for LP
Gas is 0-3 full turns in or out from the factory setting upon inserting the LP orifice as per the applicable Propane
conversion instructions. See Figure 9-1 for throttle screw location.
CHS 300-399 Adjustments - The throttle screw for the CHS 300-399 is a geared valve with a 4:1 ratio.
Adjusting the throttle screw 4 complete turns will return the valve to the original location, 2 turns from fully
open will completely close the valve. Typical adjustment required is 0-1/4 turn in or out from the factory setting.
See Figure 9-2 for throttle screw location.
Combustion Calibration - To calibrate burner operation, perform the following procedure using a calibrated
combustion analyzer capable of measuring CO2 and CO from Natural and Propane Gas burning boilers:
1. Operate the unit at the maximum modulation rate, see Table 9-2.
2. Ensure the gas line pressure is maintained within tolerance, see Table 9-1.
3. While at the maximum modulation rate, measure the CO2 and CO; adjust as necessary, using the Throttle
Screw, to be within the limits listed in Table 9-1.
4. Operate the unit at the minimum modulation rate (Table 9-2). Ensure the combustion remains smooth and
CO2 and CO remain within the limits (Table 9-1). If not, do not adjust further, contact Slant/Fin for
assistance.
Flue Gas Analysis and Adjustment
Each CHS boiler is factory set to operate with Natural Gas, for boilers field converted to operate with Propane
Gas, a flue gas analysis and adjustment is mandatory. See Table 7-1 and Propane conversion instructions.
consumption, reduced component life, heat exchanger combustion deposits, and general unsafe operation.
Failure to follow these instructions may result in serious injury or death.
Analysis – Perform flue gas analysis, and adjust throttle/input screw as required until CO2 and CO levels are
within acceptable limits.
Adjustments to the Throttle / Input Screw may only be made by a qualified gas
technician, while using a calibrated combustion analyzer capable of measuring CO2 and
Failure to perform the flue gas analysis and adjustment detailed in this section may result
in erratic and unreliable burner operation, leading to reduced efficiency, increased fuel
Page 36
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
36
Figure 9-1 CHS 85-250 Gas Valve and Venturi Assembly
(model CHS 85-110 shown)
Figure 9-2 CHS 300-399 Gas Valve and Venturi Assembly
Gas Valve
Venturi
Throttle / Input
Adjustment Screw
Line Pressure
Test Port
Manifold Pressure
Test Port
DO NOT Remove
Cap
Gas Valve
Venturi
Throttle / Input
Adjustment Screw
Line Pressure
Test Port
Manifold Pressure
Test Port
DO NOT
Remove Cap
Page 37
CHS Series Installation and Operation Instructions │Slant Fin Corp.
37
Table 10-1 Boiler System Cleansers and Corrosion Inhibitors
Application
Fernox Product
Slant/Fin Part #
Description
Boiler Water Treatment
F1 Protector
81 8180 000
Corrosion inhibitor.
Cleanser for new and old systems
F3 Cleaner
81 8181 000
Removes flux, grease and carbon residue.
Cleanser for Retrofits
DS-40 Cleaner
81 8182 000
Removes heavy limescale and sludge deposits.
10.0 BOILER AND HEATING SYSTEM PIPING
The fire tube design of the CHS heat exchanger results in minimal head loss, however it must be considered
when sizing system piping and circulators. Furthermore, the low mass of the CHS heat exchanger requires a
minimum flow rate anytime the burner is operating. To maintain the efficient and reliable operation of the heat
exchanger, and to avoid heat exchanger failure, it is critical to ensure the rules and guidelines in this section are
followed.
Failure to follow the instructions provided in this section will void the Slant/Fin warranty
and may result in property damage, fire, serious injury or death.
Boiler System Preparation
Prior to connecting plumbing to the boiler, flush the entire system to ensure it is free of sediment, flux, solder,
scale, debris or other impurities that may be harmful to the system and boiler. During the assembly of the
heating system, it is important to keep the inside of the piping free of any debris including construction and
copper dust, sand and dirt.
For retrofits, all system piping, including radiators, must be cleansed of build-up including sludge and scale. All
systems, old and new, must be cleansed to remove flux, grease and carbon residue; Slant/Fin recommends
cleaning the boiler system with “Fernox F3 Cleaner”. For retrofit applications with heavy limescale and sludge
deposits, a heavier duty cleaner may be required; Slant/Fin recommends the use of “Fernox DS-40 System
Cleaner”. For information on performing the cleaning, follow the instructions included with the applicable
Fernox Cleaner. See Table 10-1 for a list of recommended boiler system cleaning and treatment products.
Failure to rid the heating system of the contaminants listed above will void your
Slant/Fin warranty and may result in premature heat exchanger failure and property
damage.
Boiler Water
Pressure - CHS boilers are intended solely for use in pressurized closed-loop heating systems operating with a
minimum pressure of 15 PSI at the boiler outlet. To obtain the minimum system design pressure, follow the
piping diagrams illustrated in this section.
Oxygen Elimination - This boiler may only be installed in a pressurized closed-loop heating system, free of air
and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the system during
commissioning via strategically placed, adequately sized air-removal devices; located throughout the heating
system. See figures in this section detailing the location of the primary air-removal device required for the
boiler. Immediately repair any leaks in the system plumbing to avoid the addition of make-up water; make-up
water provides a source of oxygen and minerals that may lead to heat exchanger failure. Failure to follow these
instructions will result in poor performance, unnecessary wear of system components and premature failure.
The CHS boiler is not approved for operation in an “open system”, thus it cannot be used
for direct potable water heating or process heating of any kind.
Water Chemistry – The installer of the CHS boiler must consider the condition of the water in the heating
system. Ensure the condition of the boiler water falls within the following parameters:
Conductivity – less than 400µS/cm (at 25ºC); [TDS < 200ppm or Total Hardness < 11.6grains/USgal.]
PH – between 6.6 and 8.5.
Chloride – less than 125mg/l.
Iron – less than 0.5mg/l.
Copper – less than 0.1mg/l.
Page 38
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
38
Treatment - Boiler water that falls outside of the conditions listed above must be treated with a corrosion
inhibitor. For information on performing the treatment, follow the instructions included with the corrosion
inhibitor. See Table 10-1 for a list of recommended boiler system cleaners and corrosion inhibitors.
To maintain protection, the level of corrosion inhibitor must be monitored periodically
for the correct concentration.
Anti-freeze - For systems requiring freeze protection, use only inhibited propylene glycol, specially formulated
for hydronic heating systems; use of other types of antifreeze may be harmful to the system and will void the
warranty. Note: the use of glycol may reduce the usable output capacity of the boiler, thus requiring the unit to
be “down-fired” by limiting the maximum operating capacity and/or the maximum water temperature. Slant/Fin
recommends against exceeding 35% concentration of glycol.
DO NOT use inhibited glycol with non-compatible boiler inhibitors. Non-compatible
inhibitors may counteract each other rendering them ineffective.
Near Boiler Plumbing
Pressure Relief Valve - A Pressure Relief Valve is factory supplied with each unit. CHS boilers have a
maximum allowable operating pressure of 30PSI (80PSI for models CHS 300-399).
The pressure relief valve must be installed at the boiler outlet and in the vertical position, as shown in Figures
10-1 through 10-3, with the drain pipe outlet exiting the side of the pressure relief valve horizontally and
elbowing downward.
If installed in the incorrect orientation (horizontally with drain pipe out the bottom) the
relief valve may not function properly resulting in property damage or personal injury.
Ensure the discharge of the pressure relief is piped to a location where the steam or water
will not cause property damage or serious injury.
Pressure Gauge – CHS units come with a factory supplied Pressure Gauge. The pressure gauge must be
installed at the boiler outlet prior to any circulators. See Figures 10-1 through 10-3.
Auto Air Vent – Install the factory supplied auto air vent directly above the outlet fitting on the top of the unit;
see Figures 10-1 through 10-3 illustrating the correct location. Failure to install the auto air vent as illustrated
may result in occasional malfunctioning of the incorporated LWCO.
Low Water Cutoff (LWCO) – CHS boilers are provided with a factory installed LWCO switch which
incorporates a Test Button and Power and Low Water indicator lights. Perform the following Operational Test
Procedure before placing the boiler in service, and ensure Maintenance is carried out with the following
schedule.
Do not run the boiler unattended until the following procedure is completed. Failure to
follow procedure may lead to unsafe boiler operation resulting in fire, property damage
and loss of life.
Operational Test Procedure (LWCO)
1. Before introducing water to the boiler, turn the power on; both the green “POWER” LED and amber “LOW
WATER” LED should illuminate. Generate a burner demand; the burner should not fire and “Lockout 67
ILK OFF” should appear on the screen. Contact Slant/Fin for assistance if this does not happen.
2. Fill the boiler with water; the “LOW WATER” LED should turn off. Clear the Lockout from the display
board; burner should fire.
3. With the burner firing, press the TEST button to simulate a low water condition; the amber “LOW WATER”
LED should illuminate and the burner should turn off – resulting in “Lockout 67 ILK OFF”.
Maintenance (LWCO)
Every Year – perform Step 3 from the Operational Test Procedure.
Every 5-years – Remove the LWCO and clean all surfaces in contact with water.
Page 39
CHS Series Installation and Operation Instructions │Slant Fin Corp.
39
Figure 10-1(a)
Figure 10-1(b)
Supply/Return Bottom (CHS 85-110)
Supply/Return Top (CHS 85-110)
Figure 10-1(c)
Figure 10-1(d)
Supply Top / Return Bottom (CHS 85-110)
Supply Bottom / Return Top (CHS 85-110)
Inlet
Outlet
Pressure Relief
Valve (alternate
location)
Pressure Relief
Valve
Pressure Gauge
AutoAir-Vent
Auto Air-Vent
Pressure Relief
Valve
Pressure Relief
Valve(alternate
location)
Inlet
Pressure Gauge
Outlet
Auto Air-Vent
Pressure Relief
Valve
Pressure Gauge
Pressure Relief
Valve(alternate
location)
Outlet
Inlet
Auto Air-Vent
Pressure Relief
Valve
Pressure Relief
Valve (alternate
location)
PressureGauge
Inlet
Outlet
Page 40
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
40
Figure 10-2(a)
Figure 10-2(b)
Supply/Return Bottom (CHS 155-250)
Supply/Return Top (CHS 155-250)
Figure 10-2(c)
Figure 10-2(d)
Supply Top / Return Bottom (CHS 155-250)
Supply Bottom / Return Top (CHS 155-250)
AutoAir-Vent
Pressure Relief
Valve
Pressure Relief
Valve(alternate
location)
Pressure Gauge
Outlet
Inlet
AutoAir-Vent
PressureRelief
Valve
Pressure Gauge
PressureRelief
Valve(alternate
location)
Outlet
Inlet
AutoAir-Vent
PressureRelief Valve
Pressure Gauge
PressureRelief Valve(alternate
location)
Inlet
Outlet
AutoAir-Vent
Pressure Relief Valve
(alternate location)
Pressure Gauge
Outlet
Inlet
Pressure Relief Valve
Page 41
CHS Series Installation and Operation Instructions │Slant Fin Corp.
41
Figure 10-3(a)
Figure 10-3(b)
Supply/Return Bottom (CHS 300-399)
Supply/Return Top (CHS 300-399)
Figure 10-3(c)
Figure 10-3(d)
Supply Top / Return Bottom (CHS 300-399)
Supply Bottom / Return Top (CHS 300-399)
AutoAir-Vent
Pressure Relief
Pressure Gauge
Pressure Relief
Valve(alternate location)
Inlet
Outlet
AutoAir-Vent
PressureRelief
Pressure Gauge
PressureRelief
Valve(alternate
location)
Outlet
Inlet
AutoAir-Vent
Pressure Relief Valve
Pressure Gauge
PressureRelief
Valve(alternate
location)
Inlet
Outlet
AutoAir-Vent
Pressure Relief
Pressure Gauge
Pressure Relief
Valve(alternate
location)
Inlet
Outlet
Page 42
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
42
Table 10-2 Minimum Flow Rate Requirements
Model
Flow (US gpm)
CHS 85-110
3.5
CHS 155-250
7.5
CHS 300-399
12
Factory Supplied
Field Supplied Components
Pressure Relief Valve
Boiler Loop Circulator (Pump B in Figure 10-5 or Pump C in Figure 10-6)
Pressure Gauge
DHW Loop Circulator (Pump A in Figure 10-5 and Figure 10-6, for applications
utilizing and Indirect Fired Water Heater)
Auto Air Vent
Central Heat (CH) Loop Circulator(s)
(CH Circulator - Pump C in Figure 10-5; Zone Circulators in Figure 10-6)
Central Air Removal Devices (i.e. Micro Bubbler or Air-Scoop)
Pressure Regulating “Fill Valve”
Backflow Preventer
Expansion Tank
Boiler System Plumbing
The CHS boiler uses a low mass heat exchanger that requires a minimum rate of forced water circulation any
time the burner is operating (See Table 10-2 for minimum flow rate requirements). To ensure the minimum flow
rate is attained, Slant/Fin strongly recommends installing the boiler in a “Primary/Secondary” plumbing
configuration utilizing “Closely Spaced Tees” or a “Low Loss Header” to de-couple the Boiler-Primary loop
from the System-Secondary loop(s). See the examples of Primary/Secondary Loop configurations in Figures 105 and 10-6.
System Components – As a minimum, a properly installed system will include the following major components
identified in Table 10-3.
Table 10-3 System Major Component Checklist
Circulating Pumps – CHS boilers are equipped with three 120VAC pump outputs:
1. PUMP A “DHW Pump” - operates during a Domestic Hot Water demand (DHW).
2. PUMP B “Boiler Pump” - operates during any demand.
3. PUMP C “CH Pump” - operates during a Central Heat/Thermostat demand (THERMOSTAT).
Ensure pumps are oriented as per the manufacturers’ instructions. Wiring of these circulators will depend on the
system configuration selected; see Figures 10-5 and 10-6. For further wiring details see Section 11.0.
Circulators responsible for forcing the water flow through the boiler must be sized
according to Table 10-4. Pump recommendations are based on a Primary/Secondary
plumbing configuration (see Figures 10-5 and 10-6) using the listed pipe size in the Boiler-Primary Loop, with
up to 50 equivalent feet of pipe length. The installer is responsible for sizing the boiler circulator(s) and piping
for applications using non Primary/Secondary plumbing; Figure 10-4 provides Head Loss curves for this
purpose.
Failure to ensure the minimum water flow rate through the boiler when the burner is
operating will result in “short-cycling”, reduced performance and operating efficiency,
and may also cause overheating and premature failure which will void the warranty. Failure to follow
instructions may result in fire, property damage, serious injury or death.
Page 43
CHS Series Installation and Operation Instructions │Slant Fin Corp.
43
Model
Temp.
Rise (ºF)
Boiler Flow
Rate (GPM)
Boiler Head
Loss (ft)
Minimum
Pipe Size
Minimum Primary Loop Pump Size
(1)
B&G
Grundfos
Taco
Armstrong
CHS-
85
20 8 3.4
1”
NRF-22
UPS15-58 (2)
007
Astro 30 (3)
25 6 2.7
1”
NRF-22
UPS15-58 (2)
005
Astro 30 (2)
35 4 1.6
¾”
NRF-22
UPS15-58 (1)
005
Astro 30 (2)
CHS-
110
20
10
3.9
1”
2
NRF-22
(2)
UPS15-58 (3)
007
2
Astro 30 (3)
(2)
25 8 3.4
1”
NRF-22
UPS15-58 (2)
007
Astro 30 (3)
35 6 2.7
1”
NRF-22
UPS15-58 (2)
005
Astro 30 (2)
CHS-
155
20
14
5.3
1-1/4”
NRF-25 (3)
UPS26-99 (2)
0011
E7
25
11
3.9
1-1/4”
NRF-22
UPS15-58 (3)
007
Astro 30 (3)
35 8 3.1
1”
NRF-22
UPS15-58 (2)
007
Astro 30 (3)
CHS-
175
20
16
6.6
1-1/2”
NRF-36 (2)
UPS26-99 (2)
0011
E7
25
13
4.7
1-1/4”
NRF-25 (3)
UPS26-99 (2)
0010
E7
35 9 3.4
1”
NRF-22
UPS15-58 (3)
007
Astro 30 (3)
CHS-
200
20
18
7.5
1-1/2”
NRF-36 (2)
UPS26-99 (2)
0011
E7
25
15
5.8
1-1/4”
NRF-36 (2)
UPS26-99 (2)
0011
E7
35
11
3.9
1-1/4”
NRF-22
UPS15-58 (3)
007
Astro 30 (3)
CHS-
250
20
23
11.3
1-1/2”
NRF-36 (3)
UPS26-99 (3)
0013
E8
25
18
7.5
1-1/2”
NRF-36 (2)
UPS26-99 (2)
0011
E7
35
13
4.7
1-1/4”
NRF-25 (3)
UPS26-99 (2)
0010
E7
CHS-
300
20
28
5.4
2”
NRF-36 (3)
UP26-116
0012
E8
25
22
4
1-1/2”
NRF-36 (2)
UPS26-99 (3)
0011
E7
35
16
3.1
1-1/2”
NRF-25 (3)
UPS26-99 (2)
0010
E7
CHS-
399
20
37
8.2
2”
PL55
UPS32-80 (2)
2400-30
E11
25
29
5.7
2”
NRF-36 (3)
UP26-116
0012
E8
35
21
3.9
1-1/2”
NRF-36 (2)
UP26-99 (2)
0011
E7
Notes:
1
Pump sizing based on Primary/Secondary plumbing configuration with specified minimum pipe diameter with up to 50’
equivalent length.
2
Upsize piping to 1-1/4” if using Taco 007, Armstrong Astro 30 or B&G NRF-22; alternatively upsize circulator to 0010,
Astro 50 or NRF-25.
Table 10-4 Circulator and Pipe Size Requirements
Page 44
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
44
Figure 10-4(a) CHS 85-110 Head Loss Curve
0
1
2
3
4
5
6
24681012
Flow Rate (US gpm)
Head Loss (ft)
Figure 10-4(b) CHS 155-250 Head Loss Curve
0
2
4
6
8
10
12
14
681012141618202224
Flow Rate (US gpm)
Head Loss (ft)
Figure 10-4(c) CHS 300-399 Head Loss Curve
0
2
4
6
8
10
101214161820222426283032343638
Flow Rate (US gpm)
Head Loss (ft)
Page 45
CHS Series Installation and Operation Instructions │Slant Fin Corp.
45
Air Removal – The boiler and system plumbing layout must be configured to promote the removal of air from
the water. Air vents and bleeders must be strategically placed throughout the system to aid in purging the air
from the system during commissioning of the boiler. The system must also employ the use of a strategically
located air removal device, such as an air scoop or micro-bubbler, designed to remove the air from the water as it
flows through the system.
system. Always locate air removal devices in areas of the system that have a guaranteed positive pressure, e.g.,
in close proximity to the water fill and expansion tank.
10-1 through 10-3.
Expansion Tank – The expansion tank must be sized in accordance with the water volume of the system as well
as the firing rate of the appliance. It is important to locate the expansion tank, and make-up water fill, on the
inlet side of any circulator in the system, as doing so will guarantee the lowest pressure in the system will be at
least equal to the tank and make-up water pressure. See examples in Figures 10-5 and 10-6.
Relief Valve may result in property damage or personal injury.
Tees" and the expansion tank; see Figures 10-5 and 10-6.
Follow the installation instructions included with the air removal device when placing it
in the system; air removal devices generally work better when placed higher in the
CHS boilers are supplied with an automatic air removal device to aid in the purging of air
from the boiler during the initial fill. Place this devise in the location indicated in Figures
Ensure the expansion tank cannot become isolated from the boiler anytime the system is
operating. Failure to follow these instructions may result in discharge of the Pressure
The installation of flow checks, motorized valves or other shutoff devices (other than for
the purpose of servicing) are not permitted between the location of the "Closely Spaced
Page 46
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
46
Indirect Fired Water Heater – When installed as per Figure 10-6, the indirect fired water heater is in series
with the boiler during a demand for DHW. Therefore, its head loss, along with the head loss of the boiler and
associated piping, must be considered when sizing the circulator.
Figures 10-5 and 10-6 are examples of plumbing configurations using a single system circulator and multiple
system circulators, respectively.
Figure 10-5: Single System Circulator Configuration - Often used in applications zoned with “Zone Valves”.
During a demand for central heat, the boiler energizes the System Circulator via the Central Heating (CH) pump
output (PUMP C). The System Circulator must be sized to provide adequate circulation throughout the heating
system. During a Domestic Hot Water (DHW) demand, the boiler de-energizes the System Circulator (PUMP
C) and energizes the DHW Circulator (Pump A). With this configuration the Boiler Circulator is the only pump
that causes flow through the boiler and it is powered during any demand via the boiler pump output (PUMP B).
This circulator must be sized according to Table 10-4.
The piping configuration described above requires the Central Heating system and DHW
system to be de-coupled from the “Primary Loop” via closely spaced tees (Figure 10-5).
Figure 10-6: Multiple System Circulator Configuration - Often used in applications with “Zone Circulators”.
This configuration requires the installation of a check valve located at each circulator. During a central heating
demand the boiler energizes the Central Heat Circulator via the Central Heat pump output (PUMP C). During a
Domestic Hot Water (DHW) demand, the boiler de-energizes PUMP C and energizes the DHW Circulator
(Pump A). Both Pump A and C, used in this configuration, are responsible for water flow through the boiler and
must be sized according to Table 10-4. Pump output, PUMP B is not used in this configuration.
Figures 10-5 and 10-6 illustrate typical piping systems. These piping schematics do not
illustrate all of the required concepts and components required to have a proper
installation. Concepts not shown include: prevention of thermal-siphoning (heat traps), isolation valves, drain
and purge valves, etc. It is the responsibility of the installing contractor and system designer to determine which
system best meets the need of the installation and to consider all aspects of a proper system design. Contractor
modifications to these instructions may be required, based upon existing piping and system design.
Page 47
CHS Series Installation and Operation Instructions │Slant Fin Corp.
47
Water connection locations will
vary between boiler models;
refer to Figures 10-1 to 10-3.
Figure 10-5 Primary/Secondary Plumbing
(Single System Circulator Configuration)
Page 48
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
48
Water connection locations will
vary between boiler models;
refer to Figures 10-1 to 10-3.
Figure 10-6 Primary/Secondary Plumbing
(Multiple System Circulator Configuration)
Page 49
CHS Series Installation and Operation Instructions │Slant Fin Corp.
49
# of
Units
CHS-85
CHS-110
CHS-155
CHS-175
CHS-200
CHS-250
CHS-300
CHS-399
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
2
1-1/4”
1-1/2”
1-1/2”
2”
2”
2”
2-1/2”
2-1/2”
3
1-1/2”
2”
2”
2”
2-1/2”
2-1/2”
3”
3” 4 2”
2”
2-1/2”
2-1/2”
2-1/2”
3”
3”
4” 5 2”
2-1/2”
2-1/2”
3”
3”
4”
4”
4”
6
2”
2-1/2”
3”
3”
4”
4”
4”
5”
7
2-1/2”
2-1/2”
3”
4”
4”
4”
4”
5”
8
2-1/2”
3”
3”
4”
4”
4”
5”
5”
Note: Minimum pipe size based on assumed temperature rise of 25ºF at maximum firing rate.
Multiple Boiler Applications
The CHS controller has the internal capacity to stage or Lead-Lag up to 8 boilers configured in a cascade. This
Lead-Lag capability allows a designated “Master” boiler to communicate with and effectively control each
boiler in a multiple boiler system. This function is accomplished by “Daisy Chaining” a 3-wire cable between
each of the boilers and enabling the Master parameter in the boiler of your choice. The boiler with the Master
parameter enabled becomes the single point of contact for Central Heating and Outdoor Reset set-points as well
as system control wiring such as the Thermostat demand and Outdoor and System Water Temperature. See
section on Low Voltage Connections for wiring and control set-up details. Figures 10-7 and 10-8 are examples
of multiple boiler plumbing configurations illustrating small and large DHW applications.
Modbus Address – Each boiler in a cascade arrangment (lead-lag) must have a unique
modbus address between 1 and 8, inclusive. For detailed instructions on how to set the
modbus address for each CHS controller, refer to "System ID & Access" in Appendix A.
Figure 10-7: Multiple Boiler Applications with Small DHW Requirements – Used in applications where the
DHW load can be satisfied by a single boiler. In this example, Boiler 1 provides DHW priority over Central
Heating, while Boilers 2 and 3 provide Central Heating only; furthermore, the DHW demand to Boiler 1 comes
directly from the Aquastat of the Indirect Fired Water Heater.
Figure 10-8: Multiple Boiler Applications with Large DHW Requirements – Used in applications where the
DHW load is too large to be satisfied by a single boiler. In this example, Boilers 1 and 2 provide DHW priority
over Central Heating, while Boiler 3 provides Central Heating only. In contrast to small DHW requirements, the
Aquastat(s) of the Indirect Water Heater(s) is used to activate the main DHW pump and a relay is used to trigger
individual contacts for the DHW inputs of Boilers 1 and 2. Refer to Figure 11-3 for relay wiring details.
During a Lead-Lag Central Heat demand [CH2 (LL)], the Master communicates the call to the applicable
boiler(s); boilers attempting to satisfy the Central Heat demand will energize their local pump contacts B
(Boiler) and C (Central Heat). Boilers not responsible for heating DHW use pump contact B for controlling their
local Central Heat Pump (see Boilers 2 and 3 in Figure 10-7). Boilers responsible for heating DHW use pump
contact C for controlling the local Central Heat Pump (see Boilers 1 and 2 in Figure 10-8). A boiler receiving a
local DHW demand will turn off pump contact C for Central Heat and will activate pump contact A for DHW,
thus providing DHW priority.
With the exception of the Main System circulator in Figures 10-7 and 10-8 and the Main
DHW circulator in Figure 10-8, all circulators must be sized to support adequate water
flow through the boiler.
System Circulator - The installer can designate one of the boilers, preferably one not responsible for DHW
heating, to control the operation of the System Circulator. Via the user interface, under “Pump Configuration”
and “Central Heat Pump”, check the box labeled “Use for Lead Lag Master demand”. This forces the local
pump output C to activate when the Master gets a Lead-Lag Central Heat demand [(CH2 (LL)]. Pump output C
can then be used to power the System Circulator. Due to the large load of a typical system circulator, it is
recommended that a 120VAC isolation relay be used instead of powering the system circulator directly from
pump output C (i.e. pump output C is limited to 3 Amps or 1/6hp).
Table 10-5Minimum Pipe Sizes for Multiple Boiler Applications
Page 50
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
52
11.0 FIELD WIRING
All wiring must be in accordance with the Canadian Electrical code, CSA C22.2 and any applicable local codes.
Ensure that the wiring complies with this manual. The boiler must be electrically grounded in accordance with
the National Electrical Code ANSI/NFPA 70, local codes, and/or the Canadian Electrical Code CSA C22.1.
wiring connections are being made. Failure to follow these instructions may result in component failure, serious
injury or death.
Line Voltage Connections
Electrical rating for the CHS boiler is 120V/1 Phase/60 Hz/12A. All line voltage wiring connections to the CHS
are made at the junction box in the control panel located at the bottom of the boiler cabinet. The connections are
accessed by removing the front door of the boiler, followed by the removal of the control panel cover. Field
connections are to be installed in accordance with Figure 11-1 and Table 11-1. Holes are located on the bottom
(underside) of the control panel junction box.
Fuses (120VAC) – The CHS boiler is equipped with two 7 Amp fuses to protect 120VAC system components.
The fast-acting fuses are located on the left side of the control panel and are easily accessed upon removal of the
front cover of the boiler cabinet.
Fuse A: Protects the blower, spark generator and PUMP B output circuits.
Fuse B: Protects PUMP A and PUMP C output circuits.
Failure to follow instructions may result in component failure, serious injury or death.
maximum of 15 Amps. Failure to follow instructions may result in component failure, serious injury or death.
blow a fuse or damage electrical components. Also check the polarity of the line and neutral wires. Line must
measure 120VAC to ground; neutral must measure zero. Failure to follow instructions may damage the unit.
Table 11-1.
Avoid Shocks - To Avoid Electrical Shock, turn off electrical power to the boiler prior to
opening any electrical box within the unit. Ensure the power remains off while any
Field Wiring - Wire grommets must be used to secure wiring and prevent chafing when
passing wiring through the cabinet wall. Failure to follow instructions may damage unit.
Wire Protection - When passing any wiring through the cabinet of the boiler, the
installer must use wire grommets suitable for securing the wiring and preventing chafing.
Power Supply - The CHS boiler is designed to be powered using a single phase
120VAC power supply that is fused (or protected via a circuit breaker) to allow a
Labeling - Label all wires prior to disconnecting them when servicing controls. Wiring
errors can cause improper and dangerous operation. Failure to follow instructions may
result in property damage or personal injury.
Continuity - Before connecting the line voltage wiring, perform a continuity check
between all wires and ground to make sure that there are no electrical leaks that could
Max Load - Circulator outputs (PUMP A, B, C) are each limited to operating a
circulator with a maximum current load of 3 Amps or a maximum 1/6 hp motor. See
Page 53
CHS Series Installation and Operation Instructions │Slant Fin Corp.
53
Table 11-1 Line Voltage Field Connections
Connection
Location
Description
L1
(120VAC)
1
Location for connecting line voltage of the power supply. Note; most installation codes
require the installation of a service switch to break line voltage to the appliance.
PUMP A
2
120VAC output to the DHW circulator; powered during a demand for DHW.
PUMP B
3
120VAC output to the Boiler circulator; powered during all demands; DHW, local Central
Heat (CH1) and Lead-Lag Central Heat [CH2 (LL)]. This output is not used for all
plumbing configurations, see Section 10.0.
PUMP C
4
120VAC output to the Central Heating circulator; powered during a demand for local
Central Heat (CH1) or Lead-Lag Central Heat [CH2 (LL)].
L2
(Neutral)
5
Location for connecting neutral of the power supply and all circulators.
6
Ground
7
Location for connecting earth ground and for grounding all of the circulators.
8
Figure 11-1 Line Voltage Field Wiring
Page 54
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
54
Connection
Location
Description
COMM.
DATA +
1
Lead-Lag –Terminals 1, 2 and 3 can be "daisy-chained" to multiple boilers (up to 8
total) for the purpose of staging.
For lone boiler applications, these terminals can be alternatively used for communication
to an external device (i.e. Building Automation System, BAS)
DATA -
2
DATA COM
3
4-20mA (+)
4
External Modulation Control – Using a 4-20mA signal connected to terminals 4 and 5,
an external control can be used to directly modulate the burner firing rate or adjust the
active set point. This can be useful for applications using external staging controls or
Building Automation Systems.
4-20mA (-)
5
SENSOR
COM
6
Sensor Common –Common port for field inputs SYSTEM, OUTDOOR and DHW.
SYSTEM
7
System Water Temperature –An optional strap-on System Sensor is available from
Slant/Fin (P/N 81 8146 000). When connected to terminals 6 and 7, the control will
indicate a “CH” or “Lead-Lag” temperature. Sensor can be used for direct modulation of
system temperature.
OUTDOOR
8
Outdoor Temperature Sensor –A wall mountable OD Sensor is included with each
boiler. When connected to terminals 6 and 8, the control will indicate the outdoor
temperature and Outdoor Reset function will be operable.
DHW
9
DHW Tank Demand –Input requiring closure of terminals 6 and 9 to initiate a demand
for DHW. Switch made via isolated end switch (dry contact) from a thermostat
(aquastat) located in an Indirect Fired Water Heater. Optional DHW Tank Sensor see
Appendix A for details.
Connection
Location
Description
COM
(24VAC)
1
24VAC Common – Neutral for the 24VAC power supply from the boiler. COM can be
used in conjunction with terminal R to provide a power source for a digital thermostat.
R
(24VAC)
2
24VAC Hot - Power supply for inputs LIM, CH1 and CH2 (LL).
3
LIM
4
External Limit – Input requiring 24VAC from terminal R to permit the burner to operate.
Comes factory equipped with a jumper to the R terminal. For installations requiring the
use of an additional safety switch, such as a Flow Switch, or auxiliary temperature limit,
remove the factory installed jumper and install the normally open isolated contacts of the
additional limit in its place.
CH1
5
Local Central Heat Demand – Input requiring 24VAC from terminal R to initiate a
“local” CH call. Switch is made using an isolated end switch (dry contact) via thermostat,
zone controller or other device. Typically used as the lone heat input or as the high
temperature input in dual CH temperature systems.
CH2 (LL)
6
Lead-Lag Central Heat Demand –Input requiring 24VAC from terminal R to initiate a
“lead-lag” CH call. Switch is made using an isolated end switch (dry contact) via
thermostat, zone controller or other device. Typically used as a lead-lag input for cascaded
boilers or as the low temperature input in dual CH temperature systems.
ALARM
7
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm
condition. May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
8
Low Voltage Connections
Like the line voltage, the low voltage wiring connections to the CHS boiler are made at the junction box in the
control panel located at the bottom of the boiler cabinet. The connections are accessed by removing the front
door of the boiler, followed by the removal of the control panel cover. Field connections are to be installed in
accordance with Figure 11-2 and Tables 11-2a and 11-2b. Holes are located on the bottom (underside) of the
control panel junction box.
The low voltage connections are divided into two separate barrier strips: Communication
and Sensor I/O (Input/Output) and 24VAC I/O. DO NOT connect 24VAC (or other
power supply) to the Communication and Sensor I/O connections; doing so will cause control failure.
Table 11-2a Low Voltage Field Connections (Communication and Sensor I/O)
Table 11-2b Low Voltage Field Connections (24VAC I/O)
Page 55
CHS Series Installation and Operation Instructions │Slant Fin Corp.
55
24VAC I/O
Communication and Sensor I/O
Low Voltage Terminals –“R” terminals 2 and 3 of the 24VAC I/O barrier has 24VAC
potential from the internal transformer. Do not connect power from this terminal to any
other terminal other than terminals 4, 5 and 6 (LIM, CH1 and CH2 (LL)). Failure to follow these instructions
may damage the unit.
Fuse (24VAC) - CHS models are equipped with a “blade style” 2 Amp fuse to protect
the internal transformer located within the control panel box.
Figure 11-2 Low Voltage Field Wiring
Page 56
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
56
Figure 11-3 DHW Input Contacts (Multiple Boilers)
Page 57
CHS Series Installation and Operation Instructions │Slant Fin Corp.
57
Figure 12-1 CHS Connection Diagram
12.0 WIRING SCHEMATICS
Page 58
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
58
Figure 12-2 CHS Ladder/Logic Diagram
Page 59
CHS Series Installation and Operation Instructions │Slant Fin Corp.
59
13.0 INSTALLATION CHECKLIST
Installation
1. If operating on Propane Gas, convert boiler using appropriate Kit number. See Table 7-1.
2. Locate the boiler in accordance with Section 3.0 of this manual.
3. Install the Vent/Air-inlet piping in accordance with Sections 4.0 and 5.0 of this manual. Ensure all
joints are secured and cemented properly. Both the Vent and Air-inlet pipes must terminate outdoors.
Perform the Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.
4. Connect the condensate trap and drain in accordance with Section 6.0 of this manual.
5. Connect the gas supply in accordance with Section 7.0 of this manual.
6. Install the plumbing in accordance with this manual, Flush/cleanse the internals of the heating system.
Treat system water with Fernox F1 Protector when needed.
7. Connect field wiring in accordance with Section 11.0 of this manual.
8. Advise home/building owner of their responsibilities with respect to maintaining the boiler.
The building owner is responsible for keeping the Vent/Air-inlet termination free of snow,
ice, or other potential blockages and for scheduling boiler routine maintenance as
described in the next section. Failure to properly maintain the boiler may result in serious injury or death.
Start-up
Plastic Venting in Section 4.0.Failure to follow these instructions can result in explosion, serious injury or death.
1. Turn gas shut-off valve to the ON position.
2. Turn Power on to the boiler.
3. Set Controller to the desired settings.
4. Turn thermostat up, Ignition will occur.
Operational Checklist
1. System is free of gas leaks.
2. System is free of water leaks.
3. Water pressure is maintained above 15 PSI.
4. All air is purged from the heating system piping.
5. Ensure proper water flow rate; unit must not kettle, bang, hiss or flash the water to steam.
6. Ensure gas line pressure is in accordance with Section 9.0.
7. System is free of combustion leaks.
8. Unit must operate smoothly.
9. Ensure the flue gas combustion readings are within the tolerances listed in Table 9-1.
10. Each ignition must be smooth.
11. Verify that all condensate lines are clean and drain freely.
Before Leaving
1. Remove line pressure gauge from gas valve, tighten bleed screw, test screw for leaks. See Section 9.0.
2. Install plug into the flue gas test port and test for leaks, see Section 9.0.
3. Allow the boiler to complete at least one heating cycle, or to operate for at least 15 minutes.
4. Always verify proper operation after servicing.
Instructions to Installing Contractor
1. Ensure that the customer receives the Warranty Documentation included with the installation manual.
2. Leave the manual with the customer so they know when to call for annual maintenance and inspection.
matches the need of the application may result in fire, property damage, or death.
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8
hours,first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for
This boiler must have water flowing through it whenever the burner is firing. Failure to
comply may damage the unit, void the warranty, and cause serious injury or death.
Allowing the boiler to operate with a dirty combustion chamber will adversely affect its
operation and void the warranty. Failure to clean the heat exchanger on a frequency that
Page 60
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
60
14.0 ANNUAL MAINTENANCE AND INSPECTION
This unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
1. Lighting is smooth and consistent, and the combustion fan is noise & vibration free.
2. The condensate drain freely flows, and is cleaned of sediment.
3. Relief Valve and air vents are not weeping.
4. Low water cut off is tested (remove and clean a minimum of once every 5 years, see Section 10.0)
5. Examine all venting for evidence of leaks. Ensure vent screens are cleaned and clear of debris.
6. Check the burner plate for signs of leaking.
7. The combustion chamber must be inspected and if necessary cleaned.
8. Keep boiler area clear and free from combustible materials, gasoline, and other flammable vapors and
liquids.
9. Ensure there is nothing obstructing the flow of combustion and ventilation air.
10. Listen for water flow noises indicating a drop in boiler water flow rate.
Important - The hydronic system may need to be flushed to eliminate hard water scale
(Use Fernox DS-40 Descaler, Slant/Fin PN: 81 8182 000).
11. Verify proper operation after servicing.
Combustion Chamber Cleaning Procedure
Slant/Fin recommends having the combustion chamber cleaned after the first year of operation, with subsequent
cleanings scheduled based on the condition of the combustion chamber at the time. Units operating with LP Gas
or in an industrial environment may require more frequent cleanings.
chamber. Take all necessary precautions and use recommended personal protective equipment as required.
Cleaning Checklist
1. Remove the demand for heat, allow the post-purge cycle to finish, turn gas and power supply off.
2. Working inside the cabinet, disconnect the cabling to the combustion blower, gas valve, spark igniter
and flame sensor, then remove the air-inlet piping and Gas Valve/Venturi assembly (gas line is
disconnected at the factory supplied union fitting).
3. Once the combustion chamber has cooled, remove the combustion blower followed by the burner plate –
be careful not to damage the insulation disc located underneath the burner plate.
4. Use a vacuum with a high efficiency filter to remove any loose debris or dust.
5. Remove the condensate trap from the bottom of the boiler and place a drain under the boiler condensate
drain.
6. Wet the inside of the combustion chamber with warm water (do not use any chemicals). Use a garden
hose with a trigger nozzle to direct pressurized water through the heat exchanger tubes; the water will
exit via the condensate drain on the bottom. Continue process until the tubes are clear and the water
runs clean. Use dry rags or plastic to protect electrical components from being damaged by dripping or
spraying water.
7. Disassemble the condensate trap and thoroughly clean it; then reassemble and securely connect it to the
boiler condensate drain, see Section 6.0.
8. Remove the burner from the burner plate; clean if necessary using compressed air. Reattach the burner;
ensure the gasket is in perfect condition and is reinstalled (replace if necessary).
9. Inspect the insulation disc located on the under-side of the burner plate. Replace if damaged.
10. Re-install the burner plate; be sure the insulation disc is properly aligned. Reinstall remaining
components in the opposite order they were removed.
11. Perform the Start-up and Operational Checklist detailed in the previous section.
Wiring Labels - Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
Cleansers and Potable Water - Boiler system cleansers and corrosion inhibitors must not
be used to flush contaminants from water heaters or potable water systems.
Crystalline Silica - Read carefully the warnings and handling instructions pertaining to
Refractory Ceramic Fibers before commencing any service work in the combustion
Replace any gaskets or insulation discs that show any signs of damage and do not re-use.
Failure to follow these instructions may result in fire, property damage or death.
Page 61
CHS Series Installation and Operation Instructions │Slant Fin Corp.
61
Reduce the Risk of Exposure
Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes
Wear long-sleeved clothing, gloves, and safety goggles or glasses.
Avoid breathing in silica dust
Wear a respirator with an N95-rated filter efficiency or better. 1
Use water to reduce airborne dust levels when cleaning the combustion chamber.
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
Avoid transferring contamination
When installing or removing RFCs, place the material in a sealable plastic bag.
Remove contaminated clothing after use. Store in sealable container until cleaned.
Wash contaminated clothing separately from other laundry.
First Aid Measures
If irritation persists after implementing first aid measures consult a physician.
Skin - Wash with soap and water.
Eyes - Do not rub eyes; flush with water immediately.
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated
passage ways.
Notes:
1
Respirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult
your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling,
and disposal of RCFs.
For more information on Refractory Ceramic Fibers, the risks, recommended handling procedures and
acceptable disposal practices contact the organization(s) listed below:
Canada (CCOHS): Telephone directory listing
under Government Blue Pages Canada—Health and
Safety—Canadian Centre for Occupational Health
and Safety; or website http://www.ccohs.ca.
United States (OSHA): Telephone directory listing
under United States Government—Department of
Labor—Occupational Safety and Health
Administration; or website http://www.osha.gov.
Refractory Ceramic Fibers (RFC)
chamber. The insulating material on the inside of the burner plate contains Refractory Ceramic Fibers and
should not be handled without personal protective equipment.
(cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic
lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational
carcinogen by the following regulatory organizations: International Agency for Research on Cancer (IARC),
Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration
(OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling
instructions in Table 14-1 may result in serious injury or death.
maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Table 14-1 for handling instruction and recommended personal protective equipment. Installation and service
must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the
supplied instructions before installing, servicing, or removing this boiler. This boiler contains materials that have
been identified as carcinogenic, or possibly carcinogenic, to humans).
Table 14-1 Handling Instructions for Refractory Ceramic Fibers (RCF)
Personal Protective Equipment Recommended - Read the following warnings and
handling instructions carefully before commencing any service work in the combustion
Potential Carcinogen - Use of Refractory Ceramic Fibers in high temperature
applications (above 1000oC/1800ºF) can result in the formation of Crystalline Silica
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
Page 62
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
62
15.0 TROUBLESHOOTING
Servicing the Boiler
Disconnect or shutoff all energy sources to the boiler: 120VAC power, water and gas.
Identify and mark wires before disconnecting or removing them.
Never bypass electrical fuses or limit devices except temporarily for testing.
Use proper personal protective equipment (PPE) i.e. eye protection, safety footwear.
These procedures should only be performed by qualified service personnel, when abnormal operation of the
boiler is suspected. The boiler incorporates a sophisticated microprocessor based control which normally
responds appropriately to varying conditions. If the boiler operation appears to be incorrect, or it is not
responding at all to a demand for heat, the following is suggested to determine and correct the problem.
Resistance (Ohms) and Continuity.
Check 120VAC and 24VAC at the Boiler
First, verify the following:
There is 120V being supplied to the boiler:
o The circuit breaker in the electrical panel supplying power to the boiler is not tripped.
o The service switch (if applicable) is in the ON position.
o The boiler service switch located on the front of the boiler is in the ON (1) position
There is a heat call from the thermostat:
o Verify 24VAC to thermostat.
o The thermostat is placed at a sufficiently high setting to create a call for heat to the boiler.
To check for the presence of 120VAC and 24VAC at the boiler follow this procedure:
Remove the boiler front cover (remove screw from bottom, undo side latches, then lift cover up and off0.
120VAC
oRemove the control panel cover. Loosen the three #8 hex-head sheet metal screws securing the cover to
the control panel (one on the bottom, and one on each side). Lift the cover off and remove it from the
unit; this will expose the field wiring barrier strips.
oWith an AC voltmeter set on the appropriate scale, measure the voltage across the L1 and L2 terminals
(terminals 1 and 5).
oIf 120VAC is not detected, check the electrical service as suggested above. If the service is verified,
inspect the circuit wiring from the panel to the boiler for broken or disconnected conductors.
oIf 120VAC is detected, turn power off to the boiler at the service switch and check the 120VAC fuse
located on the right side of the control panel; refer to Figure 15-1 – replace if necessary.
24VAC (only check if 120VAC supply is verified).
oRemove the control panel cover. Loosen the three #8 hex-head sheet metal screws securing the cover to
the control panel (one on the bottom, and one on each side). Lift the cover off and remove it from the
unit; this will expose the field wiring barrier strips.
oWith an AC voltmeter set on the appropriate scale, measure the voltage between the R and COM
terminals (terminals 1 and 2).
oIf 24VAC is not detected, check the 24VAC fuse located at the transformer in the control panel; refer to
Figure 15-1 – replace if necessary.
Observe the following precautions when servicing the boiler. Failure to comply with
these may result in fire, property damage, serious injury or death.
Before undertaking any troubleshooting procedures it is highly recommended to have
available a digital multimeter(s) capable of measuring AC and DC volts, Amperes,
Only replace fuses with identical parts, see Figure 15-1. Failure to follow this warning
may result in component failure, fire, property damage, serious injury or death.
Page 63
CHS Series Installation and Operation Instructions │Slant Fin Corp.
63
Figure 15-1 CHS Control Panel
Fuse “C” ATO 2A
32V Auto Blade Type
Fuses “A” and “B” 3AG
7A 250 Fast-Acting
Control Panel Cover
Control Panel
Fuses
The CHS boiler is equipped with three (3) fuses. Check these fuses before replacing the controller or any other
electrical component; if the fuse is blown, it will prevent the protected device(s) from functioning.
To check, and if necessary replace, the fuses:
Remove all 120VAC power from the appliance. Be careful to check that the unit is not powered from more
than one source e.g. a UPS (uninterruptible power supply).
Remove the front cover.
Fuses "A" and "B" are accessible by removing the spring-loaded knurled knob of their respective holders.
Push the knob toward the panel, and twist approximately 1/4 turn counter-clockwise.
Fuse "C" is an auto blade type and is installed in an “inline” fuse holder; gain access by removing the
control panel cover.
After inspecting and if necessary replacing fuses, replace the panel cover and front cover. Restore power to the
appliance and confirm proper operation.
Only replace fuses with identical parts, see Figure 15-1. Failure to follow this warning
may result in component failure, fire, property damage, serious injury or death.
User Interface (LCD Dot-Matrix Display)
The User Interface (display) provides the communication between the boiler controller and the user. If the
communication fails, the User Interface will display, “Boiler Search, Modbus address: 1,2,3…” indefinitely,
if the display loses power (or fails completely) the screen will appear blank. To troubleshoot these issues
perform the following procedures:
Blank Screen
1. Confirm that 120VAC is being supplied to the boiler and that the service switch located below the display is
turned ON (1).
2. Remove the front cover from the boiler; confirm that the green “power” light is illuminated on the boiler
controller (Sola). If the light is NOT illuminated check the 24VAC fuse (Step 3); if the light is illuminated,
proceed to Step 4.
3. Remove the control panel cover and check Fuse “C” (Auto Blade Type); if faulty check for shorts in the
thermostat wiring, correct, then replace fuse (see Figure 15-1).
4. Ensure the Molex connector, located behind the display at the top, is connected and that the wires are fully
inserted (see Figures 15-2 and 15-3). Verify that 5VDC is present between the Red and Black wires; if not
trace wiring back to the boiler controller (see Figure 12-1); check for 5VDC at boiler controller (Sola).
5. Remove the display assembly from the control panel and check the wiring connections (see Figure 15-3).
Page 64
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
Electrical Disconnect Located
Behind Display at Top
Access the electrical connections in
the back of the display by removing
the screws securing the display
assembly to the control panel.
White
Green
Green (data +)
Black (Common)
White (data -)
Red (5VDC)
Red
Black
Loss of Communication
If the Display is not blank, but is displaying “Boiler Search, Modbus address: 1,2,3…” indefinitely, ensure
the Molex connector, located behind the display at the top, is connected and that the wires are fully inserted (see
Figures 15-2 and 15-3). If the connector appears to be fine, check the wiring connections on the back of the
display (remove display assembly - Figure 15-3); trace wiring back to boiler controller (Sola).
Page 65
CHS Series Installation and Operation Instructions │Slant Fin Corp.
If wiring and connections are correct, replace
display, then Sola controller.
Burner not operating
Heat demand satisfied; no call for
heat
Check Demand and Setpoints via user interface.
Check thermostat and DHW aquastat settings (as
applicable).
Appliance outlet temperature
exceeds “Setpoint - On Hysteresis”
Check outlet temperature, setpoint and hysteresis
settings via user interface.
Hold, Delay or Lockout
Check Home page on user interface for code.
Burner switch off
Check Home page, if Demand indicates “Burner
switch off” go to Manual burner operation Test
page and switch on (see Appendix A).
Lockout 2 – Waiting for
safety data verification
Faulty Sola controller
Replace Sola controller
Lockout 9 – Flame bias out of
range
4-20mA input being overdriven.
If using 4-20mA input, check to ensure current is
not greater than 21mA.
Control malfunction
Cycle power, if problem returns replace Sola
controller.
Hold 27 – Flame sensor
shorted to ground detected
A flame circuit shorted to ground
may show up as a flame circuit
timeout. Zero-Ohm shorts can
display as Hold 27.
Check to ensure condensate drain is not blocked.
Check to ensure no external voltage is applied to
R & CH terminals. If using 4-20mA input, check
to ensure current is not greater than 21mA.
Hold 61 – Anti short-cycle
Normal operation
Allow timer to expire, or reduce Anti short-cycle
setting as needed (See Appendix A)
Hold 62 – Fan speed not
proved
Normal Operation (Drive to
Lightoff)
Hold 62 is momentarily displayed prior to burner
ignition during the Drive to Lightoff.
Blown fuse
Check Fuse "A", blown fuse prevents blower
from operating.
Wiring defect
Inspect blower wiring, ensure connectors at Sola
controller and blower are securely attached.
- Blower problem
- Faulty Sola controller
If Hold 62 persists for 15 seconds or more, check
"Fan speed" on user interface. If "LOW RPM",
"HIGH RPM" or rapidly changing RPM value is
displayed, try connecting another blower. If
problem remains, replace Sola controller.
Hold 63 – LCI OFF (Limit
control input)
Incorrect Sola controller.
Replace control with correct model .
Hold 65 – Interrupted Air
Switch OFF
Hold 66 – Interrupted air
switch ON
Hold 67 – ILK OFF
Low Water Condition
Check operation of internal LWCO.
Display Diagnostics – The CHS controller and user interface provide detailed operational and diagnostic
information for aid in troubleshooting. When power is applied to the boiler the initial screen displayed is the
Home page. Information presented on the Home page includes Demand, State, status of sensors, and so forth.
Any current Alert or Lockout condition is also displayed. Refer to Appendix A - Controller and Display Instructions for more information.
Lockout and Alert History – The controller maintains a record of the fifteen (15) most recent events for both
Lockouts and Alerts (refer to Appendix A - Controller and Display Instructions). In any situation where a
malfunction is suspected, always check the Alerts and Lockouts history. Entries recorded in the history provide
useful information for determining the cause of the malfunction.
Page 66
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
66
Table 15-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
External Limit Tripped
Indication that an external limit (wired to “LIM”)
is open. Not a problem with boiler, check
external limit.
Lockout or Hold 79 – Outlet
High Limit
CH or DHW settings
Check if CH and/or DHW setpoint temperature
plus off hysteresis exceed “High limit” setpoint –
factory setting = 200°F (93°C).
CH or DHW pump problem
See "Inoperative CH or DHW pump" below.
Incorrect “Outlet high limit” setting
Increase “Outlet high limit” setting; maximum
setting = 200°F (93°C).
Incorrect “Outlet high limit
response” setting
Unless deemed unacceptable by local installation
codes, the “Outlet high limit response” should be
set to “recycle and hold” to prevent lockout.
Lockout or Hold 81 – Delta T
limit
OR
Appliance making banging or
hissing sounds
Insufficient water flow
Check Fuse "B"
Check appliance pump.
Ensure plumbing is correct. Refer to Section
10.0 System Piping. Check that water pressure
is at least 15PSI.
Boiler heat transfer surfaces may be fouled
with scale or magnetite. Clean with Fernox
DS-40 Descaler and Cleanser. See Table 10-1.
Lockout 82 – Stack limit
Dirty heat exchanger
Inspect and if required clean the combustion
chamber and/or heat exchanger. Refer to Section
14.0 Annual Maintenance and Inspection and
Section 10.0 Boiler and Heating System Piping.
Incorrect “Stack limit setpoint”
Unless installed in Canada with PVC exhaust
venting, set “Stack limit setpoint” to maximum
setting of 220ºF (104ºC). In Canada PVC exhaust
venting is limited to 149ºF (65ºC).
Lockout 85 – Inlet/Outlet
Inversion Limit
Pump flowing in the wrong
direction
Ensure water circulation through the boiler is in
the correct direction, see Figure 10-1.
Lockout or Hold 88 – Outlet
T Rise limit
Insufficient water flow
See Lockout 81.
Hold 91– Inlet sensor fault
Sensor disconnected
Check sensor connection located on the bottom of
the heat exchanger. Check connection on control
board.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 15-2.
Hold 92 – Outlet sensor fault
Sensor disconnected
Check sensor connection located on the top of the
heat exchanger. Check connection on control
board.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 15-2. (Note
the Outlet sensor incorporates two sensors, check
resistance individually.)
Hold 95 – Stack sensor fault
Sensor disconnected
Check sensor connection located at the bottom of
the flue pipe inside the boiler cabinet. Check
connection on control board.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 15-2. (Note
the Outlet sensor incorporates two sensors, check
resistance individually.)
Hold 110 – Ignition failure
occurred (failure to prove
flame after 3 ignition
attempts)
Spark cable disconnected
Ensure that the high voltage spark cable is
securely connected to the spark generator and the
igniter electrode. Check that the green ground
wire is securely attached to the ¼” quick connect
tab on the igniter electrode.
Page 67
CHS Series Installation and Operation Instructions │Slant Fin Corp.
67
Table 15-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Blocked venting
Check for blockage of the exhaust-vent, Air-inlet,
combustion blower, gas valve venturi, heat
exchanger etc.
Insufficient gas line pressure
Ensure the manual gas shutoff valve is open.
Refer to Section 9.0 GAS VALVE AND
BURNER SETUP.
Flame rod disconnected
Verify that the flame rod signal wire is securely
attached to the flame rod and the Sola controller.
No 120VAC to Spark Generator
Check wiring from Sola controller to spark
generator. With an AC voltmeter measure voltage
across J5-6 and ground (the Sola controller
chassis is connected to the 120VAC supply
ground) during trial for ignition.
Faulty Spark Generator
During trial for ignition check for arc on spark
electrode via the observation port located next to
the spark electrode in the burner door. If the spark
generator is receiving 120VAC and no spark is
observed, replace the spark generator.
No 24VAC to Gas Valve
Check the wiring harness for loose or interrupted
connections of the gas valve wiring. With an AC
voltmeter, measure the voltage between Sola
controller terminals J5-2 to J4-10. There should be
24VAC present during trial for ignition, if not
replace Sola controller.
Faulty Gas Valve
The gas valve emits an audible click when it
switches on or off. If the Sola controller is
providing 24VAC to the gas valve, and the wiring
is intact, it should be possible to detect if the valve
is responding.
Lockout 113 – Flame circuit
timeout
A flame circuit shorted to ground
may show up as a flame circuit
timeout. High resistance shorts can
display as Lockout 113.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage is applied to R & CH
terminals. If using 4-20mA input, check to ensure
current is not greater than 21mA.
Alert 128 - Modulation rate
was limited due to IAS open
Incorrect Sola controller.
Replace control with correct model.
Lockout 138 – Flame too low
Blocked venting
Check for blockage of the exhaust-vent, Air-inlet,
combustion blower, gas valve venturi, heat
exchanger etc.
Fowled or faulty flame sensor
Inspect flame sensor for cracks of fowling, clean
or replace as necessary.
Lockout 174 – Safety relay
feedback incorrect
External Electrical Noise
Look for sources of electrical noise, i.e. a large
motor or multiple pieces of equipment starting at
the same time.
Failing Limit Switch in ILK circuit
Check operation of internal LWCO, and/or
external limit (i.e. devise connected between “R”
and “LIM”); replace as necessary
Hardware failure of Sola controller
Reset power, If problem persists replace Sola
controller.
Alert 206 – Lead Lag header
temperature was invalid
System Sensor not connected
If desired, install System Sensor and wire to
SENSOR input connections “SYSTEM” and
“COM”. Otherwise ignore Alert 206
Alert 233 – Lead Lag outdoor
temperature was invalid
See Alert 248
Alert 248 – CH outdoor
temperature was invalid
Outdoor sensor not connected
The CHS is factory set with Outdoor Reset
enabled. Connect outdoor sensor or disable
Outdoor Reset.
Page 68
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
68
Table 15-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Outdoor sensor wiring
Check wiring of outdoor sensor. Wires should
connect to SENSOR inputs “OUTDOOR” and
“COM”.
Faulty sensor
Check sensor. Should be free of ice and snow.
Check resistance of sensor and compare to
thermistor resistance chart, see Table 15-2.
Alert 448 – Flame too low
See Lockout 138
Alert 449 – Modulation rate
was limited due to flame
strength
Normal operation
Indicates that the minimum permissible
modulation rate was temporarily increased due to
low flame signal strength. If Alert persists, refer
to Lockout 138.
Inoperative CH and/or DHW
pump
Blown fuse
Check Fuse "B".
Faulty Sola controller
If Fuse “B” not blown, and Sola controller is
operating, navigate to pump diagnostic on display.
Manually switch pump on, check for 120VAC at
pump connection terminal on line voltage barrier
strip. If 120VAC not detected, replace Sola
controller.
Faulty pump
If 120VAC supplied to pump, and pump does not
operate, replace pump.
Blower operating at high
speed while burner off
Blower signal cable disconnected
Verify that the 5-position Molex connector on
the wiring harness is securely connected to its
mating connector on the blower.
Check that the 4-position Molex connector on
wiring harness is securely connected to its
mating connector on the Sola controller.
No 24VAC to Sola controller
Check Power LED on Sola controller.
Check Fuse "C".
With an AC voltmeter measure voltage at
terminals J8 1 & 2, 24VAC should be present.
Blower not operating
Blower signal cable disconnected
Verify that the 5-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.
Blower power disconnected
Verify that the 3-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.
Blown fuse
Check Fuse "A" using the procedure described
above. Fuse "A" protects the blower as well as the
ignition spark generator and appliance pump.
Faulty blower
Measure voltage across pins 1 & 2 (black and
white wires) of 3-position connector on wiring
harness. If 120VAC detected, replace power
connector and remove 5-position signal connector.
Blower should rotate at high speed. If blower does
not rotate, replace blower.
Page 69
CHS Series Installation and Operation Instructions │Slant Fin Corp.
69
Table 15-2 Thermistor Resistance vs. Temperature
Temp °F (°C)
Resistance Ohms (Ω)
Temp °F (°C)
Resistance Ohms (Ω)
-22 (-30)
176,133
122 (50)
3,603
-4 (-20)
96,761
131 (55)
2,986
14 (-10)
55,218
140 (60)
2,488
32 (0)
32,650
149 (65)
2,083
41 (5)
25,390
158 (70)
1,752
50 (10)
19,900
167 (75)
1,481
59 (15)
15,710
176 (80)
1,258
68 (20)
12,490
185 (85)
1,072
77 (25)
10,000
194 (90)
918
86 (30)
8,057
203 (95)
789
95 (35)
6,531
212 (100)
680
104 (40)
5,327
230 (110)
506
113 (45)
4,369 - -
Table 15-3 Hold and Lockout Codes
Code
Description
Note
0
None
Hold / No lockout
1
Unconfigured safety data
Lockout
2
Waiting for safety data verification
Lockout
3
Internal fault: Hardware fault
Hold
4
Internal fault: Safety Relay key feedback error
Hold
5
Internal fault: Unstable power (DCDC) output
Hold
6
Internal fault: Invalid processor clock
Hold
7
Internal fault: Safety relay drive error
Hold
8
Internal fault: Zero crossing not detected
Hold
9
Internal fault: Flame bias out of range
Hold
10
Internal fault: Invalid Burner control state
Lockout
11
Internal fault: Invalid Burner control state flag
Lockout
12
Internal fault: Safety relay drive cap short
Hold
13
Internal fault: PII shorted to ILK
Hold / Lockout
14
Internal fault: HFS shorted to LCI
Hold / Lockout
15
Internal fault: Safety relay test failed due to feedback ON
Lockout
16
Internal fault: Safety relay test failed due to safety relay OFF
Lockout
17
Internal fault: Safety relay test failed due to safety relay not OFF
Lockout
18
Internal fault: Safety relay test failed due to feedback not ON
Lockout
19
Internal fault: Safety RAM write
Lockout
20
Internal fault: Flame ripple and overflow
Hold
21
Internal fault: Flame number of sample mismatch
Hold
22
Internal fault: Flame bias out of range
Hold
23
Internal fault: Bias changed since heating cycle starts
Hold
24
Internal fault: Spark voltage stuck low or high
Hold
25
Internal fault: Spark voltage changed too much during flame sensing time
Hold
26
Internal fault: Static flame ripple
Hold
27
Internal fault: Flame rod shorted to ground detected
Hold
28
Internal fault: A/D linearity test fails
Hold
29
Internal fault: Flame bias cannot be set in range
Hold
Page 70
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
70
Table 15-3 Hold and Lockout Codes
Code
Description
Note
30
Internal fault: Flame bias shorted to adjacent pin
Hold
31
Internal fault: SLO electronics unknown error
Hold
32
Internal fault: Safety Key 0
Lockout
33
Internal fault: Safety Key 1
Lockout
34
Internal fault: Safety Key 2
Lockout
35
Internal fault: Safety Key 3
Lockout
36
Internal fault: Safety Key 4
Lockout
37
Internal fault: Safety Key 5
Lockout
38
Internal fault: Safety Key 6
Lockout
39
Internal fault: Safety Key 7
Lockout
40
Internal fault: Safety Key 8
Lockout
41
Internal fault: Safety Key 9
Lockout
42
Internal fault: Safety Key 10
Lockout
43
Internal fault: Safety Key 11
Lockout
44
Internal fault: Safety Key 12
Lockout
45
Internal fault: Safety Key 13
Lockout
46
Internal fault: Safety Key 14
Lockout
47
Flame rod to ground leakage
Hold
48
Static flame (not flickering)
Hold
49
24VAC voltage low/high
Hold
50
Modulation fault
Hold
51
Pump fault
Hold
52
Motor tachometer fault
Hold
53
AC inputs phase reversed
Lockout
54-57
RESERVED
58
Internal fault: HFS shorted to IAS
Lockout
59
Internal fault: Mux pin shorted
Lockout
60
Internal fault: HFS shorted to LFS
Lockout
61
Anti short cycle
Hold
62
Fan speed not proved
Hold
63
LCI OFF
Hold
64
PII OFF
N/A
65
Interrupted Airflow Switch OFF
Hold
66
Interrupted Airflow Switch ON
Hold
67
ILK OFF
Hold
68
ILK ON
N/A
69
Pilot test hold
Hold
70
Wait for leakage test completion
Hold
71-77
RESERVED
78
Demand lost in run
Hold
79
Outlet high limit
Hold
80
DHW high limit
Disabled
81
Delta T limit
Hold / Lockout
82
Stack limit
Lockout
83-84
RESERVED
85
Inlet/Outlet inversion limit (See Table 16-1)
Hold
86-87
RESERVED
88
Outlet T-Rise limit (See Table 16-1)
Lockout
89-90
RESERVED
Page 71
CHS Series Installation and Operation Instructions │Slant Fin Corp.
71
Table 15-3 Hold and Lockout Codes
Code
Description
Note
91
Inlet sensor fault
Hold
92
Outlet sensor fault
Hold
93
DHW sensor fault
Hold
94
Header sensor fault
Hold
95
Stack sensor fault
Hold
96
Outdoor sensor fault
Hold
97
Internal fault: A2D mismatch
Lockout
98
Internal fault: Exceeded VSNSR voltage tolerance
Lockout
99
Internal fault: Exceeded 28V voltage tolerance
Lockout
100
Pressure sensor fault
Hold
101-104
RESERVED
105
Flame detected out of sequence
Hold / Lockout
106
Flame lost in MFEP
Lockout
107
Flame lost early in run
Lockout
108
Flame lost in run
Lockout
109
Ignition failed
Lockout
110
Ignition failure occurred
Hold
111
Flame current lower than WEAK threshold
Hold
112
Pilot test flame timeout
Lockout
113
Flame circuit timeout
Lockout
114-121
RESERVED
122
Light off rate proving failed
Lockout
123
Purge rate proving failed
Lockout
124
High fire switch OFF
Hold
125
High fire switch stuck ON
Hold
126
Low fire switch OFF
Hold
127
Low fire switch stuck ON
Hold
128
Fan speed failed during pre-purge
Hold / Lockout
129
Fan speed failed during pre-ignition
Hold / Lockout
130
Fan speed failed during ignition
Hold / Lockout
131
Fan movement detected during standby
Hold
132
Fan speed failed during run
Hold
133-135
RESERVED
136
Interrupted Airflow Switch failed to close
Hold
137
ILK failed to close
Hold
138-148
RESERVED
149
Flame detected
Hold / Lockout
150
Flame not detected
Hold
151
High fire switch ON
Hold / Lockout
152
Combustion pressure ON
Hold / Lockout
153
Combustion pressure OFF
Hold / Lockout
154
Purge fan switch ON
Hold / Lockout
155
Purge fan switch OFF
Hold / Lockout
156
Combustion pressure and Flame ON
Hold / Lockout
157
Combustion pressure and Flame OFF
Lockout
158
Main valve ON
Lockout
159
Main valve OFF
Lockout
160
Ignition ON
Lockout
161
Ignition OFF
Lockout
Page 72
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
72
Table 15-3 Hold and Lockout Codes
Code
Description
Note
162
Pilot valve ON
Lockout
163
Pilot valve OFF
Lockout
164
Block intake ON
Lockout
165
Block intake OFF
Lockout
166-171
RESERVED
172
Main relay feedback incorrect
Lockout
173
Pilot relay feedback incorrect
Lockout
174
Safety relay feedback incorrect
Lockout
175
Safety relay open
Lockout
176
Main relay ON at safe start check
Lockout
177
Pilot relay ON at safe start check
Lockout
178
Safety relay ON at safe start check
Lockout
179-183
RESERVED
184
Invalid BLOWER/HSI output setting
Lockout
185
Invalid Delta T limit enable setting
Lockout
186
Invalid Delta T limit response setting
Lockout
187
Invalid DHW high limit enable setting
Lockout
188
Invalid DHW high limit response setting
Lockout
189
Invalid Flame sensor type setting
Lockout
190
Invalid interrupted air switch enable setting
Lockout
191
Invalid interrupted air switch start check enable setting
Lockout
192
Invalid Igniter on during setting
Lockout
193
Invalid Ignite failure delay setting
Lockout
194
Invalid Ignite failure response setting
Lockout
195
Invalid Ignite failure retries setting
Lockout
196
Invalid Ignition source setting
Lockout
197
Invalid Interlock open response setting
Lockout
198
Invalid Interlock start check setting
Lockout
199
Invalid LCI enable setting
Lockout
200
Invalid light off rate setting
Lockout
201
Invalid Light off rate proving setting
Lockout
202
Invalid Main Flame Establishing Period time setting
Lockout
203
Invalid MFEP flame failure response setting
Lockout
204
Invalid NTC sensor type setting
Lockout
205
Invalid Outlet high limit response setting
Lockout
206
Invalid Pilot Flame Establishing Period setting
Lockout
207
Invalid PII enable setting
Lockout
208
Invalid pilot test hold setting
Lockout
209
Invalid Pilot type setting
Lockout
210
Invalid Post-purge time setting
Lockout
211
Invalid Power up with lockout setting
Lockout
212
Invalid Pre-ignition time setting
Lockout
213
Invalid Pre-purge rate setting
Lockout
214
Invalid Pre-purge time setting
Lockout
215
Invalid Purge rate proving setting
Lockout
216
Invalid Run flame failure response setting
Lockout
217
Invalid Run stabilization time setting
Lockout
218
Invalid Stack limit enable setting
Lockout
219
Invalid Stack limit response setting
Lockout
Page 73
CHS Series Installation and Operation Instructions │Slant Fin Corp.
73
Table 15-3 Hold and Lockout Codes
Code
Description
Note
220
Unconfigured Delta T limit set point setting
Lockout
221
Unconfigured DHW high limit set point setting
Lockout
222
Unconfigured Outlet high limit set point setting
Lockout
223
Unconfigured Stack limit set point setting
Lockout
224
Invalid DHW demand source setting
Lockout
225
Invalid Flame threshold setting
Lockout
226
Invalid Outlet high limit set point setting
Lockout
227
Invalid DHW high limit set point setting
Lockout
228
Invalid Stack limit set point setting
Lockout
229
Invalid Modulation output setting
Lockout
230
Invalid CH demand source setting
Lockout
231
Invalid Delta T limit delay setting
Lockout
232
Invalid Pressure sensor type setting
Lockout
233
Invalid IAS closed response setting
Lockout
234
Invalid Outlet high limit enable setting
Lockout
235
Invalid Outlet connector type setting
Lockout
236
Invalid Inlet connector type setting
Lockout
237
Invalid DHW connector type setting
Lockout
238
Invalid Stack connector type setting
Lockout
239
Invalid Header connector type setting
Lockout
240
Invalid Outdoor connector type setting
Lockout
241-255
RESERVED
Page 74
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
74
Table 15-4 Alert Codes
Code
Description
Action/Response
0
None (No alert)
1 Alert PCB was restored from factory defaults
2
Safety configuration parameters were restored from factory defaults
3
Configuration parameters were restored from factory defaults
4 Invalid Factory Invisibility PCB was detected
5 Invalid Factory Range PCB was detected
6 Invalid range PCB record has been dropped
7 EEPROM lockout history was initialized
8
Switched application annunciation data blocks
9
Switched application configuration data blocks
10
Configuration was restored from factory defaults
11
Backup configuration settings was restored from active configuration
12
Annunciation configuration was restored from factory defaults
13
Annunciation configuration was restored from backup
14
Safety group verification table was restored from factory defaults
15
Safety group verification table was updated
16
Invalid Parameter PCB was detected
17
Invalid Range PCB was detected
18
Alarm silence time exceeded maximum
19
Invalid safety group verification table was detected
20-26
RESERVED
27
Safety processor was reset
28
Application processor was reset
29
Burner switch was turned OFF
30
Burner switch was turned ON
31
Program Module (PM) was inserted into socket
32
Program Module (PM) was removed from socket
33
Alert PCB was configured
34
Parameter PCB was configured
35
Range PCB was configured
36
Program Module (PM) incompatible with product was inserted into socket
37
Program Module application parameter revision differs from application processor
38
Program Module safety parameter revision differs from safety processor
39
PCB incompatible with product contained in Program Module
40
Parameter PCB in Program Module is too large for product
41
Range PCB in Program Module was too large for product
42
Alert PCB in Program Module was too large for product
43
IAS start check was forced on due to IAS enabled
44
Low voltage was detected in safety processor
45
High line frequency occurred
46
Low line frequency occurred
47
Invalid subsystem reset request occurred
48
Write large enumerated Modbus register value was not allowed
49
Maximum cycle count was reached
50
Maximum hours count was reached
51
Illegal Modbus write was attempted
52
Modbus write attempt was rejected (NOT ALLOWED)
53
Illegal Modbus read was attempted
Page 75
CHS Series Installation and Operation Instructions │Slant Fin Corp.
75
Table 15-4 Alert Codes
Code
Description
Action/Response
54
Safety processor brown-out reset occurred
55
Application processor watchdog reset occurred
56
Application processor brown-out reset occurred
57
Safety processor watchdog reset occurred
58
Alarm was reset by the user at the control
59
Burner control firing rate was > absolute max rate
60
Burner control firing rate was < absolute min rate
61
Burner control firing rate was invalid, % vs. RPM
62
Burner control was firing with no fan request
63
Burner control rate (non-firing) was > absolute max rate
64
Burner control rate (non-firing) was < absolute min rate
65
Burner control rate (non-firing) was absent
66
Burner control rate (non-firing) was invalid, % vs. RPM
67
Fan off cycle rate was invalid, % vs. RPM
68
Set point was over ridden due to sensor fault
69
Modulation was over ridden due to sensor fault
70
No demand source was set due to demand priority conflicts
71
CH 4-20mA signal was invalid.
72-73
RESERVED
74
Periodic forced recycle
75
Absolute max fan speed was out of range
76
Absolute min fan speed was out of range
77
Fan gain down was invalid
78
Fan gain up was invalid
79
Fan minimum duty cycle was invalid
80
Fan pulses per revolution was invalid
81
Fan PWM frequency was invalid
82-89
RESERVED
90
Modulation output type was invalid
91
Firing rate control parameter was invalid
92
Forced rate was out of range vs. min/max modulation
93
Forced rate was invalid, % vs. RPM
94
Slow start ramp value was invalid
95
Slow start degrees value was invalid
96
Slow start was ended due to outlet sensor fault
97
Slow start was end due to reference set point fault
98
CH max modulation rate was invalid, % vs. RPM
99
CH max modulation rate was > absolute max rate
100
CH modulation range (max minus min) was too small (< 4% or 40 RPM)
101
DHW max modulation rate was invalid, % vs. RPM
102
DHW max modulation rate was > absolute max rate
103
DHW modulation range (max minus min) was too small (< 4% or 40 RPM)
104
Min modulation rate was < absolute min rate
105
Min modulation rate was invalid, % vs. RPM
106
Manual rate was invalid, % vs. RPM
107
Slow start enabled, but forced rate was invalid
108
Analog output hysteresis was invalid
109
Analog modulation output type was invalid
110
IAS open rate differential was invalid
Page 76
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
76
Table 15-4 Alert Codes
Code
Description
Action/Response
111
IAS open step rate was invalid
112-114
RESERVED
115
Fan was limited to its minimum duty cycle
116
Manual rate was > CH max modulation rate
117
Manual rate was > DHW max modulation rate
118
Manual rate was < min modulation rate
119
Manual rate in Standby was > absolute max rate
120
Modulation commanded rate was > CH max modulation rate
121
Modulation commanded rate was > DHW max modulation rate
122
Modulation commanded rate was < min modulation rate
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
125
Modulation rate was limited due to stack limit
126
Modulation rate was limited due to anti-condensation
127
Fan Speed out of range in RUN
128
Modulation rate was limited due to IAS was open
129
Slow start ramp setting of zero will result in no modulation rate change
130
No forced rate was configured for slow start ramp
131
CH demand source was invalid
132
CH P-gain was invalid
133
CH I-gain was invalid
134
CH D-gain was invalid
135
CH OFF hysteresis was invalid
136
CH ON hysteresis was invalid
137
CH sensor type was invalid
138
CH hysteresis step time was invalid
139
CH remote control parameter was invalid
140
CH ODR not allowed with remote control
141-145
RESERVED
146
CH control was suspended due to fault
147
CH header temperature was invalid
148
CH outlet temperature was invalid
149
CH steam pressure was invalid
150-156
RESERVED
157
DHW demand source was invalid
158
DHW P-gain was invalid
159
DHW I-gain was invalid
160
DHW D-gain was invalid
161
DHW OFF hysteresis was invalid
162
DHW ON hysteresis was invalid
163
DHW hysteresis step time was invalid
164
DHW sensor type was invalid
165
Inlet sensor type was invalid for DHW
166
Outlet sensor type was invalid for DHW
167-170
RESERVED
171
DHW control was suspended due to fault
172
DHW temperature was invalid
173
DHW inlet temperature was invalid
174
DHW outlet temperature was invalid
Page 77
CHS Series Installation and Operation Instructions │Slant Fin Corp.
77
Table 15-4 Alert Codes
Code
Description
Action/Response
175-182
RESERVED
183
Lead Lag P-gain was invalid
184
Lead Lag I-gain was invalid
185
Lead Lag D-gain was invalid
186
Lead Lag OFF hysteresis was invalid
187
Lead Lag ON hysteresis was invalid
188
Lead Lag slave enable was invalid
189
Lead Lag hysteresis step time was invalid
190-203
RESERVED
204
Lead Lag master was suspended due to fault
205
Lead Lag slave was suspended due to fault
206
Lead Lag header temperature was invalid
207
Lead Lag was suspended due to no enabled Program Module installed
208
Lead Lag slave session has timed out
209-221
RESERVED
222
CH frost protection temperature was invalid
223
CH frost protection inlet temperature was invalid
224
DHW frost protection temperature was invalid
225-230
RESERVED
231
LL set point was invalid
232
LL time of day set point was invalid
233
LL outdoor temperature was invalid
234
LL ODR time of day set point was invalid
235
LL ODR time of day set point exceeded normal set point
236
LL max outdoor set point was invalid
237
LL min outdoor set point was invalid
238
LL min water set point was invalid
239
LL outdoor temperature range was too small (minimum 12 C / 22 F)
240
LL water temperature range was too small (minimum 12 C / 22 F)
241-245
RESERVED
246
CH set point was invalid
247
CH time of day set point was invalid
248
CH outdoor temperature was invalid
249
CH ODR time of day setpoint was invalid
250
CH ODR time of day set point exceeds normal set point
251
CH max outdoor set point was invalid
252
CH min outdoor setp oint was invalid
253
CH min water set point was invalid
254
CH outdoor temperature range was too small (minimum 12 C / 22 F)
255
CH water temperature range was too small (minimum 12 C / 22 F)
256-260
RESERVED
261
DHW set point was invalid
262
DHW time of day set point was invalid
263-271
RESERVED
272
Abnormal Recycle: Pressure sensor fault
273
Abnormal Recycle: Safety relay drive test failed
274
Abnormal Recycle: Demand off during Pilot Flame Establishing Period
275
Abnormal Recycle: LCI off during Drive to Purge Rate
276
Abnormal Recycle: LCI off during Measured Purge Time
Page 78
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
78
Table 15-4 Alert Codes
Code
Description
Action/Response
277
Abnormal Recycle: LCI off during Drive to Light off Rate
278
Abnormal Recycle: LCI off during Pre-Ignition test
279
Abnormal Recycle: LCI off during Pre-Ignition time
280
Abnormal Recycle: LCI off during Main Flame Establishing Period
281
Abnormal Recycle: LCI off during Ignition period
282
Abnormal Recycle: Demand off during Drive to Purge Rate
283
Abnormal Recycle: Demand off during Measured Purge Time
284
Abnormal Recycle: Demand off during Drive to Light off Rate
285
Abnormal Recycle: Demand off during Pre-Ignition test
286
Abnormal Recycle: Demand off during Pre-Ignition time
287
Abnormal Recycle: Flame was on during Safe Start check
288
Abnormal Recycle: Flame was on during Drive to Purge Rate
289
Abnormal Recycle: Flame was on during Measured Purge Time
290
Abnormal Recycle: Flame was on during Drive to Light off Rate
291
Abnormal Recycle: Flame was not on at end of Ignition period
292
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
295
Abnormal Recycle: Leakage test failed
296
Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate
297
Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time
298
Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate
299
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
300
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time
301
Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing
302
Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
303
Abnormal Recycle: ILK off during Drive to Purge Rate
304
Abnormal Recycle: ILK off during Measured Purge Time
305
Abnormal Recycle: ILK off during Drive to Light off Rate
306
Abnormal Recycle: ILK off during Pre-Ignition test
307
Abnormal Recycle: ILK off during Pre-Ignition time
308
Abnormal Recycle: ILK off during Main Flame Establishing Period
309
Abnormal Recycle: ILK off during Ignition period
310
Run was terminated due to ILK was off
311
Run was terminated due to interrupted air flow switch was off
312
Stuck reset switch
313
Run was terminated due to fan failure
314
Abnormal Recycle: Fan failed during Drive to Purge Rate
315
Abnormal Recycle: Fan failed during Measured Purge Time
316
Abnormal Recycle: Fan failed during Drive to Light off Rate
317
Abnormal Recycle: Fan failed during Pre-Ignition test
318
Abnormal Recycle: Fan failed during Pre-Ignition time
319
Abnormal Recycle: Fan failed during Ignition period
320
Abnormal Recycle: Fan failed during Main Flame Establishing Period
321
Abnormal Recycle: Main Valve off after 10 seconds of RUN
322
Abnormal Recycle: Pilot Valve off after 10 seconds of RUN
323
Abnormal Recycle: Safety Relay off after 10 seconds of RUN
324
Abnormal Recycle: Hardware flame bias
325
Abnormal Recycle: Hardware static flame
Page 79
CHS Series Installation and Operation Instructions │Slant Fin Corp.
79
Table 15-4 Alert Codes
Code
Description
Action/Response
326
Abnormal Recycle: Hardware flame current invalid
327
Abnormal Recycle: Hardware flame rod short
328
Abnormal Recycle: Hardware invalid power
329
Abnormal Recycle: Hardware invalid AC line
330
Abnormal Recycle: Hardware SLO flame ripple
331
Abnormal Recycle: Hardware SLO flame sample
332
Abnormal Recycle: Hardware SLO flame bias range
333
Abnormal Recycle: Hardware SLO flame bias heat
334
Abnormal Recycle: Hardware SLO spark stuck
335
Abnormal Recycle: Hardware SLO spark changed
336
Abnormal Recycle: Hardware SLO static flame
337
Abnormal Recycle: Hardware SLO rod shorted
338
Abnormal Recycle: Hardware SLO AD linearity
339
Abnormal Recycle: Hardware SLO bias not set
340
Abnormal Recycle: Hardware SLO bias shorted
341
Abnormal Recycle: Hardware SLO electronics
342
Abnormal Recycle: Hardware processor clock
343
Abnormal Recycle: Hardware AC phase
344
Abnormal Recycle: Hardware A2D mismatch
345
Abnormal Recycle: Hardware VSNSR A2D
346
Abnormal Recycle: Hardware 28V A2D
347
Abnormal Recycle: Hardware HFS IAS shorted
348
Abnormal Recycle: Hardware PII INTLK shorted
349
Abnormal Recycle: Hardware HFS LCI shorted
350
Abnormal Recycle: Hardware HFS LFS shorted
351
Abnormal Recycle: Invalid zero crossing
352
Abnormal Recycle: fault stack sensor
353
Abnormal Recycle: stack limit
354
Abnormal Recycle: delta T limit
355
Abnormal Recycle: fault outlet sensor
356
Abnormal Recycle: outlet high limit
357
Abnormal Recycle: fault DHW sensor
358
Abnormal Recycle: DHW high limit
359
Abnormal Recycle: fault inlet sensor
360
Abnormal Recycle: Check Parameters Failed
361
Internal error: No factory parameters were detected in control
362
Internal error: PID iteration frequency was invalid
363
Internal error: Demand-Rate interval time was invalid
364
Internal error: Factory calibration parameter for modulation was invalid
365
Internal error: CH PID P-scaler was invalid
366
Internal error: CH PID I-scaler was invalid
367
Internal error: CH PID D-scaler was invalid
368
Internal error: DHW PID P-scaler was invalid
369
Internal error: DHW PID I-scaler was invalid
370
Internal error: DHW PID D-scaler was invalid
371
Internal error: Lead Lag master PID P-scaler was invalid
372
Internal error: Lead Lag master PID I-scaler was invalid
373
Internal error: Lead Lag master PID D-scaler was invalid
374-459
RESERVED
Page 80
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
80
Table 15-4 Alert Codes
Code
Description
Action/Response
460
LCI demand lost in run
461
Demand lost in run
462
STAT demand lost in run
463
Demand lost in run due to no flame
464-
RESERVED
467
Internal error: EEPROM write was attempted before EEPROM was initialized
468
Internal error: EEPROM cycle count address was invalid
469
Internal error: EEPROM days count address was invalid
470
Internal error: EEPROM hours count address was invalid
471
Internal error: Lockout record EEPROM index was invalid
472
Internal error: Request to write PM status was invalid
473
Internal error: PM parameter address was invalid
474
Internal error: PM safety parameter address was invalid
475
Internal error: Invalid record in lockout history was removed
476
Internal error: EEPROM write buffer was full
477
Internal error: Data too large was not written to EEPROM
478
Internal error: Safety key bit 0 was incorrect
479
Internal error: Safety key bit 1 was incorrect
480
Internal error: Safety key bit 2 was incorrect
481
Internal error: Safety key bit 3 was incorrect
482
Internal error: Safety key bit 4 was incorrect
483
Internal error: Safety key bit 5 was incorrect
484
Internal error: Safety key bit 6 was incorrect
485
Internal error: Safety key bit 7 was incorrect
486
Internal error: Safety key bit 8 was incorrect
487
Internal error: Safety key bit 9 was incorrect
488
Internal error: Safety key bit 10 was incorrect
489
Internal error: Safety key bit 11 was incorrect
490
Internal error: Safety key bit 12 was incorrect
491
Internal error: Safety key bit 13 was incorrect
492
Internal error: Safety key bit 14 was incorrect
493
Internal error: Safety key bit 15 was incorrect
494
Internal error: Safety relay timeout
495
Internal error: Safety relay commanded off
496
Internal error: Unknown safety error occurred
497
Internal error: Safety timer was corrupt
498
Internal error: Safety timer was expired
499
Internal error: Safety timings
500
Internal error: Safety shutdown
Page 81
CHS Series Installation and Operation Instructions │Slant Fin Corp.
81
Figure 16-1(a) CHS Heat Engine and Gas Train
Heat Exchanger, Gas Valve, Blower and Burner Assembly
20
23
19
21
15
12
18
16
26
22
11
1
13
10
14 9 8
7
6 4 5 3 2
16
24
17
25
17
16.0 PARTS LIST
For a list of parts that corresponds to the item numbers in the callouts, refer to Table 16-1. Note that some item
numbers may appear more than once in the parts list depending on which model number is being referenced.
Building Owners - Replacement parts are available from your stocking wholesaler. Contact your local Installer
or Wholesaler for assistance with parts.
Wholesalers - Contact Slant/Fin inside sales department when ordering replacement parts at 1-516-484-2600.
Installers - Contact Slant/Fin tech support department if technical assistance required at 1-516-484-2600.
Page 82
Slant Fin Corp.│ Installation and Operation Instructions CHS Series
82
Figure 16-1(b) CHS Cabinet
Cabinet, Vent and Air-Inlet Parts
Figure 16-1(c) CHS Controls
Electrical Housing, Controller, and Display Module
85
84
86
87
42
41
52
39
43
40
44
50
46
45
49
48
40
49
50
46
47
80
82
34
30
27
35
33
32
36
38
37
33
28
31
29
29
29
31
74
73
75
75
76
77
78
79
83
81
Page 83
CHS Series Installation and Operation Instructions │Slant Fin Corp.
83
Figure 16-1(d) CHS Installation Kit
Item
Model
Part Number
Description
1
CHS 85-110
81 8010 000
Premix Burner CHS 85-110
1
CHS 155-250
81 8011 000
Premix Burner CHS 155-250
1
CHS 300-399
81 8012 000
Premix burner CHS 300-399
2
CHS 85-110
81 8013 000
Premix Burner Gasket CHS 85-110
2
CHS 155-250
81 8014 000
Premix Burner Gasket CHS 155-250
2
CHS 300-399
81 8015 000
Premix Burner Gasket CHS 300-399
3
CHS 85-110
81 8064 000
Burner Plate Gasket CHS 85-110
3
CHS 155-250
81 8065 000
Burner Plate Gasket CHS 155-250
3
CHS 300-399
81 8066 000
Burner Plate Gasket CHS 300-399
4
CHS 85-399
81 8016 000
Blower Gasket CHS 85-399
5
CHS 85-110
81 8017 000
Combustion Blower RG130, CHS 85-110
5
CHS 155-250
81 8018 000
Combustion Blower RG148, CHS 155-250
5
CHS 300-399
81 8019 000
Combustion Blower RG148 Enhanced, CHS 300-399
6
CHS 85-250
81 8021 000
Venturi Gasket, Cork CHS 85-250
6
CHS 300-399
81 8020 000
Venturi to Blower O-ring CHS 300-399
7
CHS 85
81 8022 000
Venturi 051, CHS 85
7
CHS 110
81 8023 000
Venturi 45900450-010, CHS 110
7
CHS 155-250
81 8024 000
Venturi 003, CHS 155-250
7
CHS 300-399
81 8025 000
Venturi 002, CHS 300-399
53
54
55
56
57
58
59
60
61
62
63
65
66
67
68
69
64
70
71
72
61
60
Natural to LP Conversion Kit
Table 16-1 Parts List:
Page 84
Slant Fin Corp.│ Installation and Operation Instructions CHS Series