The input rate for the Concept boiler, on Direct Vent or
Category IV installations, may be set up to a maximum of
15% above to 25% below the nominal specified rating plate
input of each model. See Chart 1. This allowance is useful in
better sizing the boiler’s input rate to each installation site's
heat load.
The input rate for the Concept boiler, on Category I
installations, must only be set to one specified input rate for
each model. See Chart 2. This rate, which is typically higher
than the nominal specified rating plate input for each model
(except the CB-180), will ensure that a high enough flue
temperature is obtained to safeguard against condensation
forming in the flue piping and chimney stack. On all Category
I installations, the air pressure switch provided on the boiler
must be replaced with the switch provided in vent kit 665194.
This switch is set to prevent the boiler from operating below
the approved Category I input rate.
Input Rate Adjustment Specifications
To set the input rate of the Concept boiler perform the
following adjustment procedure:
A. Refer to the Operation Procedures on pages 18 and 19
which specify the methods of calibrating the boiler’
components for proper input rate and air/gas ratio.
B. Note that Step A and Step C are followed to set rate only
depending on whether a differential pressure gauge or a
gas meter is available. Either method is adequate to se
input, or both can be performed as a verification of inpu
rate. Use these procedures, in conjunction with the
appropriate chart below, to adjust the input rate a
specified for that venting application.
C. Note that Step B is followed to set the air/gas ratio only
not to set input rate. Follow Step B precisely as specified
in the instruction manual.
20
CB-45 CB-90 CB-135 CB-180
w BTUH w BTUH w BTUH w BTUH
mm w.c. in.w.c.
9 890 33,750 19 780 67,500 29 670 101,250 39 560 135,000 10.67 .42 Reduced by 25%
10 550 36,000 21 100 72,000 31 650 108,000 42 200 144,000 12.19 .48 Reduced by 20%
11 210 38,250 22 420 76,500 33 630 114,750 44 840 153,000 13.72 .54 Reduced by 15%
11 870 40,500 23 740 81,000 35 610 121,500 47 480 162,000 15.49 .61 Reduced by 10%
12 530 42,750 25 060 85,500 37 590 128,250 50 120 171,000 17.27 .68 Reduced by 5%
13 190 45,000 26 380 90,000 39 570 135,000 52 760 180,000 19.05 .75 Nominal 0%
13 850 47,250 27 700 94,500 41 550 141,750 55 400 189,000 21.08 .83 Increased by 5%
14 510 49,500 29 020 99,000 43 530 148,500 58 040 198,000 23.11 .91 Increased by 10%
15 170 51,750 30 340 103,500 45 510 155,250 60 680 207,000 25.15 .99 Increased by 15%
Boiler Model and Allowable Input *
Air Flow
Differential
Pressure †
Percent of change
to nominal boiler
input rate
* Follow instruction manual operation procedures, Step C, to set with meter. Ability to attain input rates over the nominal rating plate specifications
may be constrained by installation variables such as vent length, altitude, and calorific value of the gas, particularly on the larger models of boilers.
† Follow instruction manual operation procedures, Step A, to set with gauge.
w BTUH mm w.c. in. w.c.
CB-45 16 120 55,000 25.40 1.00 22%
CB-90 30 480 104,000 21.59 .85 15%
CB-135 42 500 145,000 19.05 .75 7%
CB-180 52 760 180,000 16.51 .65 0%
Boiler
Model
Category I Input Rate * Air Flow
Differential Pressure †
Percent of increase
over nominal boiler
input rate
Chart 2:
This chart must be used for Input Rate Adjustment for Category I Installations
* Follow instruction manual operation procedures, Step C, to set with meter.
† Follow instruction manual operation procedures, Step A, to set with gauge.
Provisions for combustion and ventilation air must be made in accordance with Section 5.3, air for combustion and ventilation, CSA 149.1-00 for
natural gas and propane..
Chart 1:
Input Rate Adjustment Specifications for Direct Vent and Category IV Installations