20 Daily Operation and Maintenance ......................................................38
Page 4
1 Instruction to Users
Air-to-water Heat Pump Monoblock
1
Thank you for choosing our air to water heat pumps. Please read this manual carefully before
installation and use the unit correctly according to the following procedure.
◆
After receipt of the unit, check it for appearance, unit model compared with your desire and
attachments.
◆
For proper installation and future maintenance please read this Instruction and keep it carefully.
◆
Design and installation work of the unit must be performed by authorized personnel according to
applicable laws and regulations and this Instruction.
◆
After installation work, the unit cannot be energized unless there is not any problem in check.
◆
Ensure periodical clean and maintenance of the unit after normal operation of the unit for longer
life and reliable operation.
◆
For improvement of products, there should be not additional notice of amendment of the
contents.
Notice!
◆
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualied persons in order to avoid a hazard.
◆
The appliance shall be installed in accordance with national wiring regulations.
Correct Disposed of this product
This marking indicates that this product should not be disposed with
other household wastes throughout the EU.To prevent possible harm to
the environment or human health from uncontrolled waste disposal,recycle
it responsibly to promote the sustainable reuse of material resources. To
retuern your used device,please use the return and collection systems or
contact the retailer where the product was purchased. They can take this
product for environmental safe recycling.
R410A(R32/125:50/50):2087.5
This appliance can be used by children aged from 8 years and above
and persons with reduced physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards
involved.Children shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without supervision.
Page 5
2 Safety Considerations
Air-to-water Heat Pump Monoblock
2
Please read the following contents carefully before operating.
WARNING
■ Once abnormality like burning
smell occurs, please cut off
the power supply immediately
and then contact with service
center.
If the abnormality still exists, the
unit may be damaged and
electric shock or re may result.
■ Special circuit must be
adopted for power supply to
prevent re.
■ Don't operate the unit with wet
hand.
Otherwise, it may cause electric
shock.
■ Be sure to pull out the power
plug and drain the unit and
water tank when unit is not in
use for a long time.
■ Before installation,please
see if the voltage of local
place accords with that on
nameplate of unit and capacity
of power supply, power cord
or socket is suitable for input
power of this unit.
■ Never damage the electric
wire or use the one which is
not specied.
Do not use octopus multipurpose
plug or mobile terminal board for
wire connection.
■ Before cleaning please cut off
the power supply.
Otherwise, it may cause electric
shock or damage.
Otherwise, the accumulated dust
may cause overheating,fire or
freeze of water tank or coaxial
heater exchanger in winter.
■ The power supply must adopt
special circuit with leakage
switch and enough capacity.
Otherwise, it may cause
overheating or re.
■ User can not change power
cord socket without prior
consent. Wiring working must
be done by professionals.
Ensure good earthing and
don't change earthing mode
of unit.
Page 6
■ Earthing: the unit must be
Air-to-water Heat Pump Monoblock
3
earthed reliably ! The earthing
wire should connect with
special device of buildings.
If not, please ask the qualified
personnel to install.
Furthermore, don't connect
earth wire to gas pipe, water
pipe, drainage pipe or any
other improper places which
professional does not recognize.
■ Don't step on the top of the
unit or place anything on it.
■ Never insert any foreign
matter into uint to avoid
damage . And never insert
your hands into the air outlet
of the unit.
■ Never block the air inlet and
outlet of unit.
■ Don't attempt to repair the unit
by yourself.
Improper repair may cause electric
shock or fire, so you should
contact the service center to
repair.
■ Keep pressurized spray, gas
holder and so on away from
the unit above 1m .
There is the danger of fall of
It may reduce efficiency or cause
stop of the unit and even re.
things or people.
It may cause re or explosion.
■ Please note whether the
installation stand is firm
enough or not.
■ Unit should be installed at the
place with good ventilation to
save energy.
■ When there is not water in
water tank, never power the
unit on to run.
If damaged, it may cause fall of
the unit and injury of people.
Notice!
(1) Before installation, please check if the adopted power is accordance with that listed on
nameplate, and check the safety of power.
(2) Before using, please check and conrm if wires and water pipes are connected correctly to avid
water leakage, electric shock or re etc.
(3) Don’t operate the unit with wet hand, and don’t allow children to operate the unit.
Page 7
(4) The On/off in the instruction is for the operation to on and off button of PCB for users; cut off
Air-to-water Heat Pump Monoblock
4
power means to stop supplying power to the unit.
(5) Don’t directly expose the unit under the corrosive ambient with water or dampness.
(6) Don’t operate the unit without water in water tank .The air outlet/inlet of unit can not be blocked
by other objects.
(7) The water in unit and pipeline should be discharged if the unit is not in use, to prevent the water
tank, pipe line and water pump from frost-cracking.
(8) Never press the button with sharp objects to protect manual controller. Never use other wires
instead of special communication line of the unit to protect control elements. Never clean the
manual controller with benzene, thinner or chemical cloth to avoid fading of surface and failure
of elements. Clean the unit with the cloth soaked in neutral eradicator .Slightly clean the display
screen and connecting parts to avoid fading.
(9) The power cord must be separated with the communication line.
(10) maximum and minimum water operating temperatures.
Item
Cooling7°C25°C
Heating25°C60°C
Water heating40°C80°C
Minimum water operating
temperatures
Maximum water operating
temperatures
maximum and minimum water operating pressures.
Item
Cooling
Water heating
Minimum water operating
pressures
0.05MPa0.25MPaHeating
Maximum water operating
pressures
maximum and minimum entering water pressures.
ItemMinimum entering water pressures
Cooling
Maximum entering water
pressures
0.05MPa0.25MPa Heating
Water heating
the range of external static pressures at which the appliance was tested (add-on heat pumps, and
appliances with supplementary heaters,only);If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualied persons in order to avoid a hazard.
(11) The appliance is intended to be permanently connected to the water mains and not connected
by a hose-set.
If there is any question, please contact with local dealer, authorized service center, agencies
6Finned heat exchanger18Auxiliary electric heater30
7
8
9Filter21Main water pump33
10EXV 122Main ow switch34
11Flasher23Outlet pipe connector35Solar panel
12Pressure sensor24Inlet pipe connector36
sensor
Environment
temperature sensor
Defrosting temperature
sensor
14EXV 226
Suction temperature
sensor
Outlet water
temperature sensor
(plate heat exchanger)
19Expansion tank31Water tank43By-pass valve
Main outlet temperature
20
sensor
28Exhaust valve40Floor radiator
293-way valve 241Water collector
32
Inlet temperature
sensor (plate heat
exchanger)
Water tank
temperature sensor 1
Solar system outlet
temperature sensor
Solar system ow
switch
Solar system water
pump
Solar panel
temperature sensor
38Water separator
42FCU
44Vapor liquid separator
45Main plate heat exchanger
46
Solar system inlet
temperature sensor
Water tank temperature
sensor 2
Page 9
4 Operating Principle of the Unit
Air-to-water Heat Pump Monoblock
6
DC Inverter Air to Water Heat Pump is composed of the unit,FCU and water tank. Operation
functions:
(1) Cooling;
(2) Heating;
(3) Water heating;
(4) Cooling +water heating;
(5) Heating+ water heating;
(6) Emergency mode;
(7) Quick water heating;
(8) Holiday mode;
(9) Forced Operation Mode;
(10) Silent mode;
(11) Disinfection mode;
(12) Weather-dependent Operation;
(13) Floor debugging
(14) Air removal of the water system
(15) Solar water heater
(16) Backup heat source
Cooling: in cooling mode, the refrigerant is condensed in the aluminum fin-copper tube and
evaporated in the plate heat exchanger. Via the heat exchange with water in the plate heat
exchanger, the temperature of water decrease and it releases heat while the refrigerant absorbs
heat and evaporates. With the help of wired controller, the outow temperature can meet the user’s
requirement. Through the control of valve, the low-temperature water in the system is connected
with indoor fan coil and underground pipe, and exchanges heat with the indoor air so that the indoor
temperature decreases to the required range.
Heating: in heating mode, the refrigerant evaporates in the aluminum fin-copper tube and
is condensed in the plate heat exchanger. Via the heat exchange with water in the plate heat
exchanger, the water absorbs heat and its temperature increase while the refrigerant releases heat
and is condensed. With the help of wired controller, the outflow temperature can meet the user’s
requirement. Through the control of valve, the high-temperature water in the system is connected
with indoor fan coil and underground pipe, and exchanges heat with the indoor air so that the indoor
temperature increases to the required range.
Water heating: in water heating mode: the refrigerant evaporates in the aluminum n-copper tube
and is condensed in the plate heat exchanger. Via the heat exchange with water in the plate heat
exchanger, the water absorbs heat and its temperature increase while the refrigerant releases heat
and is condensed. With the help of wired controller, the outflow temperature can meet the user’s
requirement. Through the control of valve, the high-temperature water in the system is connected
with the coil pipe of bearing water tank, and exchanges heat with the water in the water tank so that
the temperature of water tank increases to the required range.
Cooling + water heating: when cooling mode exists together with the water heating mode, the
user can set the priority of these two modes based on the needs. The default priority is heat pump.
That is under the default setting, if cooling mode exists together with the water heating mode, the
heat pump gives priority to cooling. In that case, water heating can only realized with e-heater of
the water tank. Inversely, the heat pump gives priority to water heating and switches to cooling after
nishing water heating.
Heating+ water heating: when heating mode exists together with the water heating mode, the
Page 10
user can set the priority of these two modes based on the needs. The default priority is heat pump.
Air-to-water Heat Pump Monoblock
7
That is under the default setting, if heating mode exists together with the water heating mode, the
heat pump gives priority to heating. In that case, water heating can only realized with e-heater of
the water tank. Inversely, the heat pump gives priority to water heating and switches to heating after
nishing water heating.
Emergency mode: this mode is only available for heating and water heating. When the monobloc
unit stops due to malfunction, enter the corresponding emergency mode; as to heating mode, after
entering the emergency mode, heating can only be realized through e-heater .When the setting
outflow temperature or indoor temperature is reached, the e-heater will stop running; as to water
heating mode, the e-heater stops while the e-heater of water tank runs. When the setting temperature
or water tank is reached, the e-heater will stop running.
Quick water heating: in quick water heating mode, the unit runs according to the water heating
control of heat pump and the e-heater of water tank runs at the same time.
Forced Operation Mode: this mode is only used for refrigerant recovery and debugging for the
unit.
Holiday mode:this mode is only available for heating mode. This mode is set to keep indoor
temperature or leaving water temperature in a certain range, so as to prevent water system of the
unit from freezing or protect certain indoor articles from freezing damage. When the unit stops due to
malfunction, the two e-heaters of the unit will run.
Disinfection mode: in this mode, the water heating system can be disinfected. When starting up
the disinfection function and setting corresponding time to meet the requirement of disinfection mode,
the function will start. After the setting temperature is reached, this mode will terminate.
Weather-dependent Operation: this mode is only available for space heating or space cooling.
In Weather- dependent mode, the setting value (remote room air temperature or leaving water
temperature) is detected and controlled automatically when the outdoor air temperature is changed.
Quiet mode: Silent mode is available in cooling, heating and water heating mode. In silent mode,
the unit will reduce the running noise via automatic control.
Floor commissioning: this function is intended to preheat the oor periodically for the initial use.
Air removal of the water system: this function is intended to replenish water and remove air in
the water system to make the equipment run at the stabilized water pressure.
Solar water heater: when the condition for starting the solar water heater is satised, the solar
heater will start to heat the circulation water. Then the heated water will go to the water tank and
exchange heat with water in it. At any condition, the solar water heater will be given priority for startup
so as for energy conservation.
Backup heat source: when the outdoor temperature is lower than the set point for starting the
backup heat source and the unit is under the error condition and the compressor has stopped for
three minutes, then the backup heat source will start to supply heat or hot water to the room.
Page 11
5 Nomenclature
Air-to-water Heat Pump Monoblock
8
Model Line-Up
Model Name
SMH-100IRA
SMH-140IRA
Note:
1
Capacities and power inputs are based on the following conditions:
Heating
1
9.59.8
14.2
Indoor Water Temperature 30°C/35°C,Outdoor Air Temperature 7°C DB/6°C WB;
2
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 23°C/18°C,Outdoor Air Temperature 35°C DB/24°C WB.
Operation Range
Mode
Heating
Cooling
Water Heating
Heat Source Side Temperature (°C) User Side Temperature (°C)
,kW
Capacity
14.5
2
,kW
Cooling
-20~35
10~487~25
-20~4540~80
Power supply
220-240V,~,50Hz
380-415V,3N~,50Hz
25~60
Page 12
6 Installation Example
Air-to-water Heat Pump Monoblock
9
CASE 1: Connecting Heat Emitters for Heating and Cooling(Under floor loop,Fan Coil
Unit,and Radiator)
Note:
The two-way valve is very important to prevent dew condensation on the floor and Radiator
①
while cooling mode;
Type of thermostat and specication should be complied with installation of this manual;
②
The Bypass valve must be installed to secure enough water ow rate, and should be installed at
③
the collector;
CASE 2: Connecting Sanitary Water Tank
Page 13
Note:
Air-to-water Heat Pump Monoblock
10
In this case, three-way valve should be installed and should be complied with installation of this
①
manual;
Sanitary water tank should be equipped with internal electric heater to secure enough heat
②
energy in the very cold days;
CASE 3 : Connecting Solar thermal system
Two-way valve is very important to prevent dew condensation on the floor and Radiator while
cooling mode.
CASE 4 : Connecting Swimming pool system
Under Floor Coil
B
Radiator
FCU 1FCU 2
Hot water
City water
3-way valve 1
3-way valve 2
T
M
Sanitary water tank
Booster heater
Page 14
Notes:
Air-to-water Heat Pump Monoblock
11
1)Two-way valve is very important to prevent dew condensation on the oor and Radiator while
cooling mode.
2) 3-Way valve 1 is controlled by user,while the pool pump is actived, 3-Way valve 1 switches to
pool loop;while the pool pump is shuted down,3-Way valve 1 switches to under oor/FCU loop.
3) 3-Way valve 2 is automatic controlled by monobloc unit,while running water heating mode,3-
Way valve 2 switches to water tank loop;while running cooling/heating mode,3-Way valve 2 switches
to under oor/FCU loop.
7 Main Components
(1) SMH-100IRA
DC Fan Motor
Control Box
Electric Heater
Water Pump
Flow Switch
Expansion Tank
Compressor
Plate Heat Exchanger
Page 15
(2) SMH-140IRA
Air-to-water Heat Pump Monoblock
12
DC Fan Motor
Control Box
Safety Valve
Air Vent
Electric Heater
Flow Switch
Expansion Tank
Water Pump
Compressor
Plate Heat Exchanger
Flash Tank
Page 16
8 Installation Guideline of the Unit
Air-to-water Heat Pump Monoblock
13
8.1 Instruction to installation
(1) Installation of the unit must be in accordance with national and local safety codes.
(2) IInstallation quality will directly affect the normal use of the air conditioner unit. The user is
prohibited from installation. Please contact your dealer after buying this machine. Professional
installation workers will provide installation and test services according to installation manual.
(3) Do not connect to power until all installation work is completed.
8.2 Installation of the Monobloc Unit
8.2.1 Selection of the Installation Location of the Monobloc Unit
(1) The monobloc unit must be installed on a rm and solid support.
(2) Avoid placing the monobloc unit under window or between two constructions, hence to prevent
normal operating noise from entering the room.
(3) Air ow at inlet and outlet shall not be blocked.
(4) Install at a well-ventilated place, so that the machine can absorb and discharge sufcient air.
(5) Do not install at a place where ammable or explosive goods exist or a place subject to severe
dust, salty fog and polluted air.
8.2.2 Outline Dimensions of the Monobloc Unit
(1) SMH-100IRA
1390
890
361
412
388
Page 17
(2) SMH-140IRA
Air-to-water Heat Pump Monoblock
14
1430
367
340
8.2.3 Space requirements for installation
500
>
500
500
>
2000
>
>
1390
>
2000
1000
>
500
>
8.2.4 Precautions on installation of the Monobloc Unit
(1) When moving the monobloc unit, it is necessary to adopt 2 pieces of long enough rope to hand
the unit from 4 directions. Included angle between the rope when hanging and moving must be
40°below to prevent center of the unit from moving.
(2) The monobloc unit should be installed on concrete base that is 10cm height.
(3) Requirements on installation space dimension of unit’s bodies are shown in following drawing.
(4) The monobloc unit must be lifted by using designated lifting hole. Take care to protect the unit
during lift. To avoid rusting, do not knock the metal parts.
Page 18
8.3 Water Volume and Pump Capacity (with pump)
Air-to-water Heat Pump Monoblock
15
Note: during operation, the water pump will adjust its output based on the actual load.
1
/min
n/
max
n
min
n
Off
1U/V
0132
Page 19
8.4 Water Volume and Expansion Vessel Pressure
Air-to-water Heat Pump Monoblock
16
2.5
2.0
1.5
1.0
0.5
Pre-pressure in expension vessel(Bar)
0.0
050100150200250300350400
Maximum total water volume(liter)
Note:
The expansion vessel is 10 liter and 1bar pre-pressurized;
①
Total water volume of 280 liter is default; if total water is changed because of installation
②
condition, the pre-pressure should be adjusted to secure proper operation;
Minimum total water volume is 20 liter;
③
To adjust pre-pressure, use nitrogen gas by certicated installer.
④
8.5 Selection of Expansion Vessels
Formula:
V--- Volume of expansion vessel
C--- Total water volume
--- Pre-set pressure of expansion vessel
P
1
-- The highest pressure during running of the system (that is the action pressure of safety valve.)
P
2
e---The expansion factor of water (the difference between the expansion factor of the original water
temperature and that of highest water temperature.)
Distance between the monobloc unit and the remote air temperature senor should be less than
①
15 meter due to length of the connection cable of remote air temperature sensor;
Height from oor is approximately 1.5 meter;
②
Remote air temperature sensor can not be located where the area may be hidden when door is
③
open;
Remote air temperature sensor can not be located where external thermal inuence may be
④
2
Page 21
applied;
Air-to-water Heat Pump Monoblock
18
Remote air temperature sensor should be installed where space heating is mainly applied;
⑤
After the remote air temperature sensor is installed, it should be set to “With” through the wired
⑥
controller so as to set the remote air temperature to the control point.
10 Thermostat
Installation of the thermostat is very similar to that of the remote air temperature sensor.
XT3
212223242526
2220V GND
220V AC
Thermostat
OFF
HEAT
COOL
27282930
224V GND
COOL
HEAT
Thermostat
24V AC
OFF
How to Wire Thermostat
(1) Uncover the front cover of the monobloc unit and open the control box.
(2) Identify the power specification of the thermostat, if it is 230V , find terminal block XT3
asNO.21~25; Otherwise, if it is 24V, nd terminal block XT3 as NO.26~30;
(3) If it is the heating/cooling thermostat, please connect wire as per the gure above;
CAUTION!
Never use 230V AC and 24V AC thermostat at the same time, otherwise, it will cause short
①
circuit and power cut-off by the circuit breaker;
Setting temperature by the thermostat(heating or cooling) should be within the temperature
②
range of the product ;
For other constrains, please refer to previous pages about the remote air temperature sensor;
③
Do not connect external electric loads. Wire 220V AC(24V AC) and 220V GND(24V GND)
④
should be used only for the electric thermostat.
Never connect external electric loads such as valves, fan coil units, etc. If connected, the
⑤
mainboard of the unit can be seriously damaged.
Installation of the thermostat is very similar to that of the remote air temperature sensor.
⑥
11 2-Way Valve
There are two 2-way valve,the 2-way valve 1 is available and the 2-way vavle is reserved.The
2-way valve 1 is required to control water ow for cooling operation. The role of 2-way valve 1 is to
cut off water ow into the underoor loop when the fan coil unit is equipped for cooling operation.
General Information
TypePowerOperating ModeSupported
NO 2-wire230V 50Hz ~AC
NC 2-wire230V 50Hz ~AC
(1) Normal Open type. When electric power is NOT supplied, the valve is open. (When electric
power is supplied, the valve is closed.)
(2) Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric
power is supplied, the valve is open.)
Closing water owYes
Opening water owYes
Closing water owYes
Opening water owYes
Page 22
How to Wire 2-Way Valve:
Air-to-water Heat Pump Monoblock
19
Follow steps below to wire the 2-way valve.
Step 1. Uncover the front cover of the unit and open the control box.
Step 2. Find the terminal block and connect wires as below.
XT2
456101112
L2(ON)
L1(OFF)
N
2-Way Valve 22-Way Valve 1
L2(ON)
L1(OFF)
N
WARING!
Normal Open type should be connected to wire (ON) and wire (N)for valve closing in cooling
①
mode.
Normal Closed type should be connected to wire (OFF) and wire (N)for valve closing in cooling
②
mode.
(ON) : Line signal (for Normal Open type) from PCB to 2-way valve
(OFF) : Line signal (for Normal Closed type) from PCB to 2-way valve
(N) : Neutral signal from PCB to 2-way valve
The 2-way value 2 is reserved without any control program. At the eld installation, it should be
wired at the terminal board of the 2-way valve 1.
12 3-Way Valve
There are two 3-way valve, the 3-way valve 1 is reserved and the 3-way valve 2 is available.The
3-way valve 2 is required for the sanitary water tank. Its role is ow switching between the under oor
heating loop and the water tank heating loop.
General Information
TypePowerOperating ModeSupported
SPDT
3-wire
230V 50Hz ~AC
Selecting “Flow A” between “Flow A” and “Flow B”Ye s
Selecting “Flow B” between “Flow B” and “Flow A”Yes
(1) SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting (for selecting Flow
B), and Neutral (for common).
(2) Flow A means 'water ow from the monobloc unit to under oor water circuit'.
(3) Flow B means 'water ow from the monobloc unit to sanitary water tank'.
Follow steps below to wire the 3-way valve:
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the unit and open the control box.
Step 2. Find terminal block and connect wire as below.
XT2
123789
L2(ON)
L1(OFF)
N
L2(ON)
L1(OFF)
N
3-Way Valve 13-Way Valve 2
Page 23
WARING!
Air-to-water Heat Pump Monoblock
20
The 3-way valve should select water tank loop when electric power is supplied to wire (OFF)
①
and wire (N).
The 3-way valve should select under oor loop when electric power is supplied to wire (ON) and
②
wire (N).
(ON): Line signal (Water tank heating) from the main board to the 3-way valve
(OFF): Line signal (Under oor heating) from the main board to the 3-way valve
(N): Neutral signal from the main board to the 3-way valve
13 Wired Controller
Wired controller wiring guidance:
14 Other Auxiliary Heat Sources
Other auxiliary heat sources are allowed for the equipment and controlled in such a way that the
mainboard will output 230V when outdoor temperature is lower than the set point for startup of the
auxiliary heat source.
XT2
1314
N
Other Thermal
15 Gate-controller
If there is gate control function,installation guide follow as:
(1) SMH-100IRA
XT3
12
Gate-Controller
(2) SMH-140IRA
XT4
56
Gate-Controller
Page 24
16 Charging and Discharging of Refrigerant
Air-to-water Heat Pump Monoblock
21
The unit has been charged with refrigerant before delivery. Overcharging or undercharging will
cause the compressor to run improperly or be damaged. When refrigerant is required to be charged
or discharged for installation, maintenance and other reasons, please follow steps below and nominal
charged volume on the nameplate.
(1) Discharging: remove metal sheets of the outer casing, connect a hose to the charging valve and
then discharge refrigerant.
Charging
valve 1
Charging
valve 2
Notes:
Discharge is allowed unless the unit has been stopped. (Cut off the power and repower it 1
①
minutes later)
Protective measures should be taken during discharging to avoid frost bites.
②
When discharging is nished, if vacuuming cannot be done immediately, remove the hose to
③
avoid air or foreign matters entering the unit.
(2) Vacuuming: When discharging is nished, use hoses to connect the charging valve, manometer
and vacuum pump to vacuum the unit.
Pressure Meter
Note: when vacuuming is nished, pressure inside the unit should be kept lower than 80Pa for at
least 30 minutes to make sure there is no leak. Either charging valve 1 or charging valve 2 can be
used for vacuuming.
(3) Charging: when vacuuming is nished and it is certain that there is no leak, charging can be
done.
◆
Be sure to charge the specied amount of refrigerant in liquid state.
Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant
composition to change, preventing normal operation.
◆
Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not.
Connection Pipe
Vacuum pump
Page 25
Air-to-water Heat Pump Monoblock
22
With siphon tube No siphon tube
17 Installation of Insulated Water Tank
17.1 Installation measure
The water tank should keep a horizontal distance of 5 meters and a vertical distance of 3 meters
with the main unit. It allowed to be installed in the room.
The standing type water tank must be installed erectly on the ground/floor and never be
suspended. Installation place must be rm enough and the water tank should be xed on the wall with
bolts to avoid vibration, as shown in the following gure. During installation, weight of the water tank
should be taken into consideration.
Water Tank
Fix
With
Bolts
Installed on the ground
and never suspended
The minimum clearance between the water tank and any combustible object must be 500mm.
The water pipe, hot water joint and oor drain should be equipped for the water replenishment, hot
water supply and drainage of the water tank respectively.
Connection of the inlet/outlet waterway: connect the safety check valve attached with the unit
(with the arrow on it pointing at the water tank) to the water inlet of the water tank with the PPR pipe
according to the following figure and seal with seal tape. The other end of the safety check valve
should connect with the water tap. The hot water pipe should be connected to the water outlet of the
water tank also with the PPR pipe.
Safety check valve
Tap water
Note:
For safe use of water, water outlet/inlet of water tank must connect with a certain length of PPR
2
pipe ,L ≥70×R
(cm, R is inside radius of the pipe). Moreover, heat preservation should be conducted
and metal pipe can not be used. For the rst use, water tank must be full of water before the power is
on.
Page 26
17.2 Connection of waterway system
Air-to-water Heat Pump Monoblock
23
(1) If connection between the water tank and the monobloc unit should go through the wall, drill a
hole φ70 for pass of circulating water pipe.
(2) Preparation of pipelines: circulating water outlet/inlet pipe must be hot water pipe and PPR pipe
with nominal outer diameter of dn25 and S2.5 series (wall thickness of 4.2mm) are recommended.
Cooling water inlet pipe and hot water outlet pipe of water tank should also be hot water pipe
and PPR pipe with nominal outer diameter of dn20 and S2.5 series (wall thickness of 3.4mm)
are recommended. If other insulated pipes are adopted, refer to the above dimensions for outer
diameter and wall thickness.
(3) Installation of circulating water inlet/outlet pipes: connect the water inlet of the unit with
circulating outlet of water tank and water outlet of unit with circulating inlet of water tank.
(4) Installation of water inlet/outlet pipes of the water tank: safety check valve, lter and cut-off valve
must be installed for the water inlet pipe according to the installation sketch of the unit. At least a
cut-off valve is needed for the water outlet pipe.
(5) Installation of blow-off pipes at the bottom of water tank: connect a piece of PPR pipe with
drainage outlet to oor drain. A cut-off valve must be installed in the middle of the drainage pipe and
at the place where it is easy to be operated by the users.
(6) After connection of all waterway pipelines, perform the leakage test rstly. After that, bind up the
water pipes, water temp sensor and wires with wrapping tapes attached with the unit.
(7) Refer to Installation Sketch of the Unit for details.
CN29
CN12
Monobloc
Unit
AP1
XT3
CN11
1
Power cord of
booster heater
Hot Water Outlet
Tem.Sensor1
Cool Water Inlet
Safety Check
Valve
Cut- Off Valve
Other Thermal
Blow -O ff Outlet
DescriptionJoint pipe thread
Circulating water inlet/outlet of main unit1″Male BSP
Cooling water inlet of water tank1/2″Female BSP
Circulating water inlet/outlet of water tank3/4″Female BSP
Hot water outlet of water tank1/2″Female BSP
System
Tap Water
Filter
Note:
Distance between monobloc unit and water tank should not exceed 5m levelly and 3m vertically.
①
If higher, please contact with us. Water tank on lower and main unit on higher side is recommended.
Prepare the materials according to the above joints dimension. If cut-off valve is installed
②
outside the room, PPR pipe is recommended to avoid freeze damage.
Page 27
Waterway pipelines can’t be installed until water heater unit is xed. Do not let dust and other
Air-to-water Heat Pump Monoblock
24
③
sundries enter into pipeline system during installation of connection pipes.
After connection of all waterway pipelines, perform leakage test rstly. After that, perform heat
④
preservation of waterway system; meanwhile, pay more attention to valves and pipe joints. Ensure
enough thickness of insulated cotton. If necessary, install heating device for pipeline to prevent the
pipeline from freezing.
Hot water supplied from insulated water tank depends on pressure of water tap, so there must
⑤
be supply of tap water.
During using, the cut-off valve of cooling water inlet of water tank should be kept normally on.
⑥
17.4 Electric wiring work
17.4.1 Wiring principle
General principles
◆
Wires, equipment and connectors supplied for use on the site must be in compliance with
provisions of regulations and engineering requirements.
◆
Only certicated electricians are allowed to perform wire connection on the site.
◆
Before connection work is started, the power supply must be shut off.
◆
Installer shall be responsible for any damage due to incorrect connection of the external circuit
of the unit.
◆
Caution --- only copper wires are allowed to be used.
Connection of power cable to the electric cabinet of the unit
◆
Power cables should be laid out through cabling trough, conduit tube or cable channel.
◆
Power cables to be connected into the electric cabinet must be protected with rubber or plastic to
prevent scratch by edge of metal plate.
◆
Power cables close to the electric cabinet of the unit must be xed reliably to make the power
terminal in the cabinet free from an external force.
◆
Power cable must be grounded reliably.
17.4.2 Specication of Power Supply Wire and Leakage Switch
Power cable specications and Leakage switch types in the following list are recommended.
Minimum Sectional
Area of Earth Wire
2
)(mm2)
Model
SMH-100IRA
SMH-140IRA
Power Supply
V / Ph / Hz
220-240 / 1 / 50
380-400 / 3 / 50
Breakers
(A)(mm
63165×25
40105×10
Note:
The leakage switch is necessary for additional installation. If circuit breakers with leakage
①
protection are in use, action response time must be less than 0.1 second, leakage circuit must be
30mA.
The above selected power cable diameters are determined based on assumption of distance
②
from the distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to
150m, diameter of power cable must be increased to a further grade.
The power supply must be of rated voltage of the unit and special electrical line for air-
③
conditioning.
All electrical installation shall be carried out by professional technicians in accordance with the
④
Minimum Sectional
Area of Power
Supply Wire
Page 28
local laws and regulations.
Air-to-water Heat Pump Monoblock
25
Ensure safe grounding and the grounding wire shall be connected with the special grounding
⑤
equipment of the building and must be installed by professional technicians.
The specifications of the breaker and power cable listed in the table above are determined
⑥
based on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-
⑦
guarded multi-wire copper cable (like, YJV XLPE insulated power cable) used at 40°C and resistible
to 90°C(see IEC 60364-5-52). If the working condition changes, they should be modied according to
the related national standard.
The specications of the breaker listed in the table above are applied to the breaker with the
⑧
working temperature at 40°C. If the working condition changes, they should be modied according to
the related national standard.
Page 29
18 Wring Diagram
Air-to-water Heat Pump Monoblock
26
18.1 Control Board
(1) Main Board (AP2): SMH-100IRA; SMH-140IRA
PWR1
DC-MOTOR0
AC-NAC-L4VVA-1HEAT
ENTH
FBFA
ENTH-PRESS
L-PRESS
H-PRESS
CN8
COM-ESPE2
CN7
HPP
T-SENSOR3
T-SENSOR2CN5DC-MOTOR1
Silk ScreenSpecication
AC_NNeutral wire input of power supply
AC_LLive wire input of power supply
4V4-way valve
VA-1E-heater of chassis
HEATElectric heating tape
ENTHSolenoid valve
FBTo EXV2,pipe electric expansion valve,1-4 pin: driving impulse output; 5 pin: +12V;
FATo EXV1,pipe electric expansion valve,1-4 pin: driving impulse output; 5 pin: +12V;
ENTH-PRESSSignal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
L-PRESSSignal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
H-PRESSSignal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
CN8
To the wired controller, communication cable: 1 pin earthed, 2 pin B, 3 pin A, 4
pin+12power supply;
CN7Communication between AP1 and AP2;communication cable 2 pin B, 3 pinA
DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V; 5 pin: control signal;
6pin:feedback signal;
DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V; 5 pin: control signal;
6pin:feedback signal;
PWR1Supply 310V DC power to the drive.
Page 30
(2)Main Board (AP1): SMH-100IRA; SMH-140IRA
Air-to-water Heat Pump Monoblock
27
CN31
CN33
TR-IN
CN18
TR-OUT2
TR-OUT1
AC-LNERR RUNHEAT
HEAT1
HEAT2
BAN-HEAT
OTHER_HEAT_
220V
X5
X10X92V1_OFF
2V1_ON
2V2_OFF
2V2_ON
3V1_OFF 3V2_OFF
3V2_ON3V1_ON
OTHER_HEAT_DCOUT
OTHER_HEAT_DCIN
CN6
CN4
COM-OUT
INDOOR_PUMP
POOL_PUMP
SOLOR_PUMP
T-SEN13
T-SEN12
T-SEN11
T-SEN10
T-SEN9
T-SEN8
T-SEN7
T-SEN5
T-SEN1
T-SEN6
T-SEN2
T-SEN3
T-SEN4
Silk ScreenLocationIntroduction
AC-L-Live wire of power supply
N-Neutral wire of power supply
ERRX19Error indicator
RUNX15Running indicator
WT_HEATX16E-heater of water tank
HEAT1X17E-heater 1
HEAT2X18E-heater 2
BAN_HEATX3Antifreeze heater for the heat exchanger
SW_INDOOR
SW_SOLAR
SW_POOL
DOOR_INOVC_WT_HEATOVC_HEAT2OVC_HEAT1
OTHER_HEAT_220VX6Assistant heat by 220VAC
X5X5Reserved
X10X10Reserved
X9X9Reserved
2V1_OFFX8Electric magnetic 2-way valve1 is normally closed.
Page 31
2V1_ONX7Electric magnetic 2-way valve1 is normally open.
Air-to-water Heat Pump Monoblock
28
2V2_OFFX14Electric magnetic 2-way valve2 is normally closed.
2V2_ONX13Electric magnetic 2-way valve2 is normally open.
3V1_OFFX22Electric magnetic 3-way valve1 is normally closed.
3V1_ONX21Electric magnetic 3-way valve1 is normally open.
3V2_OFFX11Electric magnetic 3-way valve2 is normally closed.
3V2_ONX12Electric magnetic 3-way valve2 is normally open.
OTHER_HEAT_DCOUTX1The dc output of assistant heat
OTHER_HEAT_DCINX2The dc input of assistant heat
COM-OUTCN5Connect to AP2
CN6CN6Connect the wired controller
INDOR_PUMPCN4Control and feedback of the water pump for the main unit
CN8CN8Feedback of the water pump for the main unit
POOL_PUMPCN9Control and feedback of the water pump for the swimming pool
SOLAR_PUMPCN7Control and feedback of the water pump for the solar system
SW_INDOORCN25Detection input of water ow switch for indoor
SW_SOLARCN16Detection input of water ow switch for solar
SW_POOLCN17Detection input of water ow switch for pool
DOOR_INCN23Door detection input
OVC_WT_HEATCN28E-heater of water tank adhesion-proof protection detector
OVC-HEAT1CN26E-heater of indoor unit1 adhesion-proof protection detector
OVC-HEAT2CN27E-heater of indoor unit2 adhesion-proof protection detector
T-SEN4CN20Terminal of temperature sensor4
T-SEN3CN22Terminal of temperature sensor3
T-SEN2CN21Terminal of temperature sensor2
T-SEN1CN11Terminal of temperature sensor1
T-SEN6CN12Terminal of temperature sensor6
T-SEN5CN10Terminal of temperature sensor5
T-SEN7CN29Terminal of temperature sensor7
T-SEN8CN32Terminal of temperature sensor8
T-SEN9CN30Terminal of temperature sensor9
T-SEN10CN24Terminal of temperature sensor10
T-SEN11CN15Terminal of temperature sensor11
T-SEN12CN13Terminal of temperature sensor12
T-SEN13CN14Terminal of temperature sensor13
TR-OUT1CN2Transformer output 1 (12V)
TR-OUT2CN3Transformer output 2 (24V)
CN18CN18Power supply interface of the thermostat (220~240V)
TR-INCN1220V input of transformer
CN31CN31Power supply interface and control signal of the thermostat (24V))
CN33CN33Control signal of the thermostat
Page 32
(3) Drive Board (AP4): SMH-100IRA
Air-to-water Heat Pump Monoblock
29
U
V
W
G-OUT
P-OU
L1-2
L2-1DC-BUS1
T
PWR
L1-1
L2-2
Silk ScreenIntroduction
AC-LLive line input of the drive board
NNeutral line input of the drive board
L1-1To PFC inductor brown line
L1-2To PFC inductor white line
L2-1To PFC inductor white line
L2-2To PFC inductor blue line
UTo compressor phase U
VTo compressor phase V
WTo compressor phase W
DC-BUS1Pin for electric discharge of the high-voltage bar during test.
P-OUTReserved
G-OUTReserved
COMM
COMM1
PWRPower input of the drive board [1-GND,2-18V,3-15V]
12DC-BUSPin for electric discharge of the high-voltage bar during test.
13X501Connector to the compressor phase-U
14X502Connector to the compressor phase-V
15X503Connector to the compressor phase-W
Page 34
(5) Filter Board (AP3): SMH-100IRA
Air-to-water Heat Pump Monoblock
31
N-OUT1
N-OUT
L
-OUT
Silk ScreenIntroduction
AC-NNeutral line of the power supply for the main unit
AC-LLive line of the power supply for the main unit
AC-NAC-L
E1
E2
N-OUT
Neutral line output of the lter board (to the drive board)
Neutral line output of the lter board (to the main board )
N-OUT1Reserved
L-OUTLive line output of the lter board (to the drive and main boards)
E1To the grounding line of the main unit
E2Reserved
Page 35
(6) Filter Board (AP3): SMH-140IRA
Air-to-water Heat Pump Monoblock
32
1
2
3
4
1011
9
8
7
6
5
NoSilk ScreenIntroduction
1X1Connector to power supply output line AC-L1
2X2Connector to power supply output line AC-L2
3X3Connector to power supply output line AC-L3
4X4Connector to power supply neutral line AC-N
5X9Connector to the grounding line E , reserved
6X8Connector to power supply neutral line N-F (mainboard AC-N)
7X7Connector to power supply output line L3-F (drive board L3-F)
8X6Connector to power supply output line L2-F (drive board L2-F)
9X5Connector to power supply output line L1-F (drive board L1-F and AC-L)
10X11Connector to power supply output line L1-F (drive board L1-F and AC-L)
11X10Connector to the grounding line E
Page 36
18.2 Electric Wiring
Air-to-water Heat Pump Monoblock
33
18.2.1 Wiring principle
Refer to Section 16.4.
18.2.2 Electric wiring design
Wiring diagram: monobloc unit.
◆
SMH-100IRA
PEPE
XT1
Power
L
N
3
6
1
1
4
8
2
N
WatertankAuxiliary
electricheater
ConsumerConnection
PEPE
KM3
SpecificationX
1. The wires intheimaninalframes
areconnectedbythe consumer.
2. power supply forThermostat: If it is
220V AC,PleaseconnectTerminal
block(XT4) 21.22.23.24.25; If itis 24V
AC, pleaseconnectTerminal
block(XT4) 26.27.28.29.30.
L1(OFF)
L2(ON)
N
L1(OFF)
L2(ON)
N
L1(OFF)
L2(ON)
N
L1(OFF)
L2(ON)
HL1
HL2
EH3
220VAC
OFF
HEAT
COOL
HEAT
COOL
24VACGND
24VAC
SW1
SW2
L6
W1
W2
W3
W4
AC-L
N
XT2
W45
W43
1
X22
W44
2
X21
3
W46
4
X14
W47
W50
5
X13
6
W48
7
X11
W51
W49
8
X12
9
W52
10
X8
W53
W54
11
N
N
OFF
X7
12
W55
13
X6
W59
14
W57
X15
15
W60
16
W58
X19
17
W61
18
W56
19
X3
W62
20
XT3
W63
21
W64
CN18
22
W70
23
W71
CN33
24
W72
25
W65
26
W66
27
28
29
30
31
32
33
34
35
36
37
38
39
40
XT4
5
6
7
8
9
10
AP1
W67
W68
CN31
W69
W73
W74
W75
CN9
W76
W77
W78
W79
CN7
W80
W81
W82
CN8
W102
W103
CN23
W106
W107
CN16
W104
W105
CN17
CN1
1N
1L
TC
RT1
CN10
RT2
RT3
CN13
RT4
CN11
W41
W42
CN12
RT7
CN14
RT8
CN20
RT9
CN21
RT10
CN22
RT11
CN24
RT12
CN29
RT13
CN30
W85
W86
CN26
W88
CN27
W87
X17
W90
X18
A1
W91
W92
CN28
W93
X16
CN25
CN5
2
CN15
L14
CN4
CN3
CN2
2N
2L
3N
3L
L5
X1(AC-L1)
X2(AC-L2)
AP3
X3(AC-L3)
X4(AC-N)
20K
20K
20K
RT14
RT15
50K
RT16
RT5
50K
RT17
15K
HP
20K
20K
20K
20K
20K
50K
KM1-2
KM2-2
EH5
W89
A2A1
KM1
EH4
W94
W95
A2
KM2
HT3
1
KM3-2
2
W96
XT5
W97
2
A2A1
KM3
SW3
RT6
15K
CN1
AP
M3
L15
BN
M
BU
YEGN
L15
PE
X9(E)
W112
PE
20K
15K
T-SENSOR2
50K
20K
T-SENSOR3
p
SP1
SP2
SP3
YV1
4YV
COM-ESPE2
W37
W38
HPP
H-PRESS
AP2
L-PRESS
ENT-PRESS
DC-MOTOR0
ENTH
4V
DC-MOTOR1
VA-1
HEAT
CN7
W98
2
XT5
W113
XT1-L1
1
W114
XT1-N
2
W19
X5(L1-F)
W20
X6(L2-F)
W21
X7(L3-F)
X11(L1)
RD
X8(N-F)
W22
L4
L1L2L3
BK
L13
X2(AC-N)
X1(AC-L)
PWR1PWR
5
4
EKV1
FA
3
2
1
5
4
EKV2
FB
3
2
1
31456
CN8
M
M1
L16
4
Display
board
X1(L1-F)
X2(L2-F)
X3(L3-F)
L7
W25
X4(L1-1)
W26
X5(L2-1)
W27
X6(L3-1)
L8
W30
X9(L3-2)
W29
X8(L2-2)
W28
X7(L1-2)
L9
W31
W32
L10
W108
W109
W110
W111
L11
W33 W34 W35
L12
31456
M
M2
COMM
X501(U)
CODENAME
4YV 4-wayvalvecoil
AP MainBoardOnlyFor RT6
AP1 IndoorunitMainBoard
AP2 OutdoorunitMainBoard
AP3 FilterBoard
AP4 DriveBoard
COMP Compressor
EH1,2 Auxiliaryelectricheater
EH3 Plateheat exchangerelectricheater
AP4
EH4 Compressorbandheater
EH5 Bottonband heater
EH6 Expandjarelectricheater
EKV1 Electric expansion valvecoil1
EKV2 Electric expansion valvecoil2
HL1 Running indicatinglamp
HL2 Errorindicatinglamp
HP Highpressure switch
HT1,2 Thermostat (WP95A-R)
HT3 Thermostat(WP75A-R)
L1~L3 Inductor
X502(V)
L4 Electrical Inductance
X503(W)
L5~L16 Magneticring
M1 DownDC Motor
M2 UPDC Motor
M3 Indoorunitpump
RT1 Water-outtemp sensor ofthewholeunit
RT2 Water-intemp sensor ofthewholeunit
RT3 Auxiliaryheaterwater-outtemp sensor
RT4 Water-tanktemp sensor 1
WVU
RT5 Water-tanktemp sensor 2
COMP
3~
RT6 RemoteAirtempsensor1
W36
RT7 RemoteAirtempsensor2
PE
RT8 Poolwatertempsensor
RT9 poolwater-intempsensor
RT10 Pool water-outtemp sensor
RT11 Solarwater-out tempsensor
RT12 Solarwater-intempsensor
RT13 Solarboard tempsensor
RT14 Defrosting tempsensor
RT15 Outdoortempsensor
RT16 Dischargedtempsensor
RT17 Suctiontempsensor
SP1 Highpressure sensor
SP2 Low pressure sensor
SP3 Increaseenthalpypressuresensor
SW1 Solarwaterflow switch
SW2 Pool waterflowswitch
SW3 Indoor unitswaterflowswitch
TC Transformer
YV1 Increaseenthalpysolenoidvalve
Page 37
18.2.3 Terminal Board
Air-to-water Heat Pump Monoblock
34
◆
SMH-100IRA
◆
SMH-140IRA
Page 38
19 Commissioning
Air-to-water Heat Pump Monoblock
35
19.1 Check before startup
For safety of users and unit, the unit must be started up for check before debugging. The
procedures are as below:
The following items shall be performed by qualied repair persons.
Conrm together with the sales engineer, dealer, installing contractor and customers for the following items
nished or to be nished.
No.Conrmation of Installation
If the contents of Application for Installation of this Unit by Installer are real. If not, debugging
1
will be refused.
Is there written notice in which amendment items are shown in respect of unqualified
2
installation?
√
□
□
3Are Application for Installation and Debugging list led together?
No.Pre-check
Is appearance of the unit and internal pipeline system ok during conveying, carrying or
1
installation?
2Check the accessories attached with the unit for quantity, package and so on.
3Make sure there is drawings in terms of electricity, control, design of pipeline and so on.
Check if installation of the unit is stable enough and there is enough space for operation and
4
repair.
5Completely test refrigerant pressure of each unit and perform leakage detection of the unit.
6Is the water tank installed stably and are supports secure when the water tank is full?
Are heat insulating measures for the water tank, outlet/inlet pipes and water replenishing pipe
7
proper?
Are the nilometer of water tank, water temperature indicator, controller, manometer, pressure
8
relief valve and automatic discharge valve etc. installed and operated properly?
Does power supply accord with the nameplate? Do power cords conform to applicable
9
requirements?
Is power supply and control wiring connected properly according to wiring diagram? Is
10
earthing safe? Is each terminal stable?
11Are connection pipe, water pump, manometer, thermometer, valve etc. are installed properly?
12Is each valve in the system open or closed according to requirements?
13Conrm that the customers and inspection personnel of Part A are at site.
14Is Installation Check-up Table completed and signed by the installation contractor?
□
√
□
□
□
□
□
□
□
□
□
□
□
□
□
□
Attention: If there is any item marked with ×, please notify the contractor. Items listed above are just for
reference.
General Evaluation: Debugging □ Amendment □
Conrmed Items after pre-checking
Judge the following items (if there is not any lling, qualication will be regarded.)
a: Power supply and electric control system b: Loading calculation
c: Heating problems of Unit d: Noise problem
e: Pipeline problem f: Others
Normal debugging work can’t be performed unless all installation items are qualied. If there is any
problem, it must be solved rstly. The installer will be responsible for all costs for delay of debugging
and re-debugging incurred by any problem which is not solved immediately.
Submit schedule of amending reports to installer.
Is the written amending report which should be signed after communication provided to installer?
Yes ( ) No ( )
Page 39
19.2 Test run
Air-to-water Heat Pump Monoblock
36
Test run is testing whether the unit can run normally via preoperation. If the unit cannot run
normally, find and solve problems until the test run is satisfactory. All inspections must meet the
requirements before performing the test run. Test run should follow the content and steps of the table
below:
The following procedure should be executed by experience and qualied maintenance men.
No.Start up the pretest procedure
Notice: before test, ensure that all power must be cut off, including the far- end power switch, otherwise, it
may cause casualty.
1Ensure that the compressor of the unit is preheated for 8h.
Caution: heat the lubricating oil at least 8h in advance to prevent refrigerant from mixing with the
lubricating oil, which may cause damage to the compressor when starting up the unit.
Check whether the oil temperature of the compressor is obviously higher than the outdoor ambient
2
temperature.
Caution: if the oil temperature of the compressor is obviously higher than the outdoor ambient
temperature, it means that the heating tape of compressor is damaged. In that case, the compressor will be
damaged easily. Therefore, repair the heating tape before using the unit.
Check whether the phase sequence of the main power supply is correct. If not, correct the phase
3
sequence rstly.
Recheck the phase sequence before start-up to avoid reverse rotation of the compressor which may
damage the unit.
Apply the universal electric meter to measure the insulation resistance between each outdoor
4
phase and earth as well as between phases.
Caution: defective earthing may cause electric shock.
No.Ready to start
Cut off all temporary power supply, resume all the insurance and check the electricity for the last
time.
1
Check the power supply and voltage of the control circuit; _____V must be ±10% within the range
of rated operating power.
No.Start up the unit
1Check all the conditions needed to start up the unit: oil temperature, mode, required load etc.
Start up the unit, and observe the operation of compressor, electric expanding valve, fan motor and
water pump etc.
2
Note: the unit will be damaged under abnormal running state. Do not operate the unit in states of
high pressure and high current.
Others:
Estimation or suggestion on the general running situation: good, modify
Identify the potential problem (nothing means the installation and debugging are in
accordance with the requirements.)
a. problem of power supply and electric control system:
b. problem of load calculation:
Items for
acceptance
after debugging
c. outdoor refrigerant system:
d. noise problem:
e. problem of indoor and piping system:
h. other problems:
During operation, it is needed to charge for the maintenance due to non-quality problems
such as incorrect installation and maintenance.
Acceptance
Is the user trained as required? Please sign. Yes( ) No( )
Page 40
20 Daily Operation and Maintenance
Air-to-water Heat Pump Monoblock
37
In order to avoid damage of the unit, all protecting devices in the unit had been set before delivery,
so please do not adjust or remove them.
For the rst startup of the unit or next startup of unit after long-period stop (above 1 day) by cutting
off the power, please electrify the unit in advance to preheat the unit for more than 8 hours.
Never put sundries on the unit and accessories. Keep dry, clean and ventilated around the unit.
Remove the dust accumulated on the condenser n timely to ensure performance of the unit and to
avoid stop of the unit for protection.
In order to avoid protection or damage of the unit caused by blockage of the water system, clean
the lter in water system periodically and frequently check water replenishing device.
In order to ensure anti-freezing protection, never cut off the power if ambient temperature is below
zero in winter.
In order to avoid frost crack of the unit, water in the unit and pipeline system not used for a long
period should be drained. In addition, open the end cap of the water tank for drainage.
Never frequently make the unit on/off and close the manual valve of the water system during
operation of the unit by users.
Ensure frequent check to the working condition of each part to see if there is oil stain at pipeline
joint and charge valve to avoid leakage of refrigerant.
If malfunction of the unit is out of control of users, please timely contact with authorized service
center.
Notes:
The water pressure gage is installed in the returning water line in the unit. Please adjust the
hydraulics system pressure according to next item:
If the pressure is less than 0.5 bar, please recharge the water immediately;
①
When recharging, the hydraulics system pressure should be not more than 2.5Bar.
②
Troubleshooting
Malfunctions ReasonsTroubleshooting
Compressor does
not start up
Heavy noise of fan
Heavy noise of
compressor
Water pump does
not run or runs
abnormally
Compressor starts or
stops frequently
The unit does not
heat although
compressor is
running
Poor efciency of hot
water heating
①
Power supply has problem.
②
Connection wire is loose.
③
Malfunction of mainboard.
④
Malfunction of compressor.
①
Fixing bolt of fan is loose.
②
Fan blade touches shell or grill.
③
Operation of fan is unreliable.
①
Liquid slugging happens when liquid
refrigerant enters into compressor.
②
Internal parts in compressor are broken.
①
Malfunction of power supply or terminal.
②
Malfunction of relay.
③
There is air in water pipe.
①
Poor or excess refrigerant.
②
Poor circulation of water system.
③
Low load.
①
Leakage of refrigerant.
②
Malfunction of compressor.
①
Poor heat insulation of water system.
②
Poor heat exchange of evaporator.
③
Poor refrigerant of unit.
④
Blockage of heat exchanger at water side.
①
Phase sequence is reverse.
②
Check out and re-x.
③
Find out the reasons and repair.
④
Replace compressor.
①
Re-x xing bolt of fan.
②
Find out the reasons and adjust.
③
Replace fan.
①
Check if expansion valve is failure and
temp. sensor is loose .If that, repair it.
②
Replace compressor.
①
Find out the reasons and repair.
②
Replace relay.
③
Evacuate.
①
Discharge or add part of refrigerant.
②
Water system is blocked or there is air in
it.Check water pump, valve and pipeline.
Clean water lter or evacuate.
③
Adjust the load or add accumulating
devices.
①
Repair by leakage detection and add
refrigerant.
②
Replace compressor.
①
Enhance heat insulation efficiency of the
system.
②
Check if air in or out of unit is normal and
clean evaporator of the unit.
③
Check if refrigerant of unit leaks.
④
Clean or replace heat exchanger.
Page 41
Page 42
NOTE CONCERNING PROTECTION OF
ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be
taken to a collection station for the recycling of electrical and electronic devices. The symbol on the
product, the operating instructions or the packaging indicate such disposal procedures. The materials
are recyclable in accordance with their respective symbols. By means of re-use, material recycling or
any other form of recycling old appliances you are making an important contribution to the protection
of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT
MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The maintanance and the liquidation must
be carried out by qualified personel.
Type of refrigerant: R410A
The composition of the cooling medium R410A: (50% HFC-32, 50% HFC-125)
The quantity of the refrigerant: please see the unit label.
The value GWP: 2088
GWP = Global Warming Potential
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd.
1-4 Argyll St.
London W1F 7LD
Great Britain
www.sinclair-world.com
This product was manufactured in China (Made in China).
REPRESENTATIVE, TECHNICAL SUPPORT
NEPA spol. s r.o.
Purkyňova 45
612 00 Brno
Czech republic