Sinclair SMH-100IRA? SMH-140IRA Original Instructions Manual

Page 1
SMH-100IRA
SMH-140IRA
MONOBLOCK INVERTER
Page 2
“Originalinstructions”
Page 3
Contents
1 Instruction to Users..................................................................................1
2 Safety Considerations .............................................................................2
3 Diagram of the Operating Principle .........................................................5
4 Operating Principle of the Unit.................................................................6
5 Nomenclature ..........................................................................................8
6 Installation Example .............................................................................9
7 Main Components ................................................................................ 11
8 Installation Guideline of the Unit ............................................................ 13
9 Remote Air Temperature Sensor ...........................................................17
10 Thermostat ..........................................................................................18
11 2-Way Valve ......................................................................................... 18
12 3-Way Valve.........................................................................................19
13 Wired Controller .................................................................................20
14 Other Auxiliary Heat Sources .............................................................20
15 Gate-controller ................................................................................... 20
16 Charging and Discharging of Refrigerant ............................................21
17 Installation of Insulated Water Tank ....................................................22
18 Wring Diagram .....................................................................................27
19 Commissioning .................................................................................... 36
20 Daily Operation and Maintenance ......................................................38
Page 4

1 Instruction to Users

Air-to-water Heat Pump Monoblock
1
Thank you for choosing our air to water heat pumps. Please read this manual carefully before
installation and use the unit correctly according to the following procedure.
After receipt of the unit, check it for appearance, unit model compared with your desire and attachments.
For proper installation and future maintenance please read this Instruction and keep it carefully.
Design and installation work of the unit must be performed by authorized personnel according to applicable laws and regulations and this Instruction.
After installation work, the unit cannot be energized unless there is not any problem in check.
Ensure periodical clean and maintenance of the unit after normal operation of the unit for longer life and reliable operation.
For improvement of products, there should be not additional notice of amendment of the contents.
Notice!
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualied persons in order to avoid a hazard.
The appliance shall be installed in accordance with national wiring regulations.
Correct Disposed of this product
This marking indicates that this product should not be disposed with other household wastes throughout the EU.To prevent possible harm to the environment or human health from uncontrolled waste disposal,recycle it responsibly to promote the sustainable reuse of material resources. To retuern your used device,please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
R410A(R32/125:50/50):2087.5
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Page 5

2 Safety Considerations

Air-to-water Heat Pump Monoblock
2
Please read the following contents carefully before operating.
WARNING
■ Once abnormality like burning
smell occurs, please cut off the power supply immediately and then contact with service center.
If the abnormality still exists, the unit may be damaged and
electric shock or re may result.
■ Special circuit must be
adopted for power supply to
prevent re.
■ Don't operate the unit with wet
hand.
Otherwise, it may cause electric shock.
■ Be sure to pull out the power
plug and drain the unit and water tank when unit is not in use for a long time.
■ Before installation,please
see if the voltage of local place accords with that on nameplate of unit and capacity of power supply, power cord or socket is suitable for input power of this unit.
■ Never damage the electric
wire or use the one which is
not specied.
Do not use octopus multipurpose plug or mobile terminal board for wire connection.
■ Before cleaning please cut off
the power supply.
Otherwise, it may cause electric shock or damage.
Otherwise, the accumulated dust may cause overheating,fire or freeze of water tank or coaxial heater exchanger in winter.
■ The power supply must adopt
special circuit with leakage switch and enough capacity.
Otherwise, it may cause
overheating or re.
■ User can not change power
cord socket without prior consent. Wiring working must be done by professionals. Ensure good earthing and don't change earthing mode of unit.
Page 6
■ Earthing: the unit must be
Air-to-water Heat Pump Monoblock
3
earthed reliably ! The earthing wire should connect with special device of buildings.
If not, please ask the qualified personnel to install. Furthermore, don't connect earth wire to gas pipe, water pipe, drainage pipe or any other improper places which professional does not recognize.
■ Don't step on the top of the
unit or place anything on it.
■ Never insert any foreign
matter into uint to avoid damage . And never insert your hands into the air outlet of the unit.
■ Never block the air inlet and
outlet of unit.
■ Don't attempt to repair the unit
by yourself.
Improper repair may cause electric shock or fire, so you should contact the service center to repair.
■ Keep pressurized spray, gas
holder and so on away from the unit above 1m .
There is the danger of fall of
It may reduce efficiency or cause
stop of the unit and even re.
things or people.
It may cause re or explosion.
■ Please note whether the
installation stand is firm enough or not.
■ Unit should be installed at the
place with good ventilation to save energy.
■ When there is not water in
water tank, never power the unit on to run.
If damaged, it may cause fall of the unit and injury of people.
Notice!
(1) Before installation, please check if the adopted power is accordance with that listed on nameplate, and check the safety of power. (2) Before using, please check and conrm if wires and water pipes are connected correctly to avid
water leakage, electric shock or re etc.
(3) Don’t operate the unit with wet hand, and don’t allow children to operate the unit.
Page 7
(4) The On/off in the instruction is for the operation to on and off button of PCB for users; cut off
Air-to-water Heat Pump Monoblock
4
power means to stop supplying power to the unit. (5) Don’t directly expose the unit under the corrosive ambient with water or dampness. (6) Don’t operate the unit without water in water tank .The air outlet/inlet of unit can not be blocked by other objects. (7) The water in unit and pipeline should be discharged if the unit is not in use, to prevent the water tank, pipe line and water pump from frost-cracking. (8) Never press the button with sharp objects to protect manual controller. Never use other wires instead of special communication line of the unit to protect control elements. Never clean the manual controller with benzene, thinner or chemical cloth to avoid fading of surface and failure of elements. Clean the unit with the cloth soaked in neutral eradicator .Slightly clean the display screen and connecting parts to avoid fading. (9) The power cord must be separated with the communication line. (10) maximum and minimum water operating temperatures.
Item
Cooling 7°C 25°C
Heating 25°C 60°C
Water heating 40°C 80°C
Minimum water operating
temperatures
Maximum water operating
temperatures
maximum and minimum water operating pressures.
Item
Cooling
Water heating
Minimum water operating
pressures
0.05MPa 0.25MPaHeating
Maximum water operating
pressures
maximum and minimum entering water pressures.
Item Minimum entering water pressures
Cooling
Maximum entering water
pressures
0.05MPa 0.25MPa Heating
Water heating
the range of external static pressures at which the appliance was tested (add-on heat pumps, and
appliances with supplementary heaters,only);If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualied persons in order to avoid a hazard.
(11) The appliance is intended to be permanently connected to the water mains and not connected by a hose-set.
If there is any question, please contact with local dealer, authorized service center, agencies
or our company directly.
Page 8

3 Diagram of the Operating Principle

Air-to-water Heat Pump Monoblock
5
No. Name No. Name No. Name No. Name
1 Inverter compressor 13 Solenoid valve 25 Water lter 37
Discharge temperature
2
3 High-pressure switch 15 Low pressure sensor 27 Safety valve 39 2-way Valve 1
4 High pressure sensor 16
5 4-way Valve 17
6 Finned heat exchanger 18 Auxiliary electric heater 30
7
8
9 Filter 21 Main water pump 33
10 EXV 1 22 Main ow switch 34
11 Flasher 23 Outlet pipe connector 35 Solar panel
12 Pressure sensor 24 Inlet pipe connector 36
sensor
Environment
temperature sensor
Defrosting temperature
sensor
14 EXV 2 26
Suction temperature
sensor
Outlet water
temperature sensor
(plate heat exchanger)
19 Expansion tank 31 Water tank 43 By-pass valve
Main outlet temperature
20
sensor
28 Exhaust valve 40 Floor radiator
29 3-way valve 2 41 Water collector
32
Inlet temperature
sensor (plate heat
exchanger)
Water tank
temperature sensor 1
Solar system outlet
temperature sensor
Solar system ow
switch
Solar system water
pump
Solar panel
temperature sensor
38 Water separator
42 FCU
44 Vapor liquid separator
45 Main plate heat exchanger
46
Solar system inlet
temperature sensor
Water tank temperature
sensor 2
Page 9

4 Operating Principle of the Unit

Air-to-water Heat Pump Monoblock
6
DC Inverter Air to Water Heat Pump is composed of the unit,FCU and water tank. Operation
functions:
(1) Cooling; (2) Heating; (3) Water heating; (4) Cooling +water heating; (5) Heating+ water heating; (6) Emergency mode; (7) Quick water heating; (8) Holiday mode; (9) Forced Operation Mode; (10) Silent mode; (11) Disinfection mode; (12) Weather-dependent Operation; (13) Floor debugging (14) Air removal of the water system (15) Solar water heater (16) Backup heat source
Cooling: in cooling mode, the refrigerant is condensed in the aluminum fin-copper tube and evaporated in the plate heat exchanger. Via the heat exchange with water in the plate heat exchanger, the temperature of water decrease and it releases heat while the refrigerant absorbs
heat and evaporates. With the help of wired controller, the outow temperature can meet the user’s
requirement. Through the control of valve, the low-temperature water in the system is connected with indoor fan coil and underground pipe, and exchanges heat with the indoor air so that the indoor temperature decreases to the required range.
Heating: in heating mode, the refrigerant evaporates in the aluminum fin-copper tube and is condensed in the plate heat exchanger. Via the heat exchange with water in the plate heat exchanger, the water absorbs heat and its temperature increase while the refrigerant releases heat and is condensed. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve, the high-temperature water in the system is connected with indoor fan coil and underground pipe, and exchanges heat with the indoor air so that the indoor temperature increases to the required range.
Water heating: in water heating mode: the refrigerant evaporates in the aluminum n-copper tube
and is condensed in the plate heat exchanger. Via the heat exchange with water in the plate heat exchanger, the water absorbs heat and its temperature increase while the refrigerant releases heat and is condensed. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve, the high-temperature water in the system is connected with the coil pipe of bearing water tank, and exchanges heat with the water in the water tank so that the temperature of water tank increases to the required range.
Cooling + water heating: when cooling mode exists together with the water heating mode, the user can set the priority of these two modes based on the needs. The default priority is heat pump. That is under the default setting, if cooling mode exists together with the water heating mode, the heat pump gives priority to cooling. In that case, water heating can only realized with e-heater of the water tank. Inversely, the heat pump gives priority to water heating and switches to cooling after
nishing water heating.
Heating+ water heating: when heating mode exists together with the water heating mode, the
Page 10
user can set the priority of these two modes based on the needs. The default priority is heat pump.
Air-to-water Heat Pump Monoblock
7
That is under the default setting, if heating mode exists together with the water heating mode, the heat pump gives priority to heating. In that case, water heating can only realized with e-heater of the water tank. Inversely, the heat pump gives priority to water heating and switches to heating after
nishing water heating.
Emergency mode: this mode is only available for heating and water heating. When the monobloc unit stops due to malfunction, enter the corresponding emergency mode; as to heating mode, after entering the emergency mode, heating can only be realized through e-heater .When the setting outflow temperature or indoor temperature is reached, the e-heater will stop running; as to water heating mode, the e-heater stops while the e-heater of water tank runs. When the setting temperature or water tank is reached, the e-heater will stop running.
Quick water heating: in quick water heating mode, the unit runs according to the water heating control of heat pump and the e-heater of water tank runs at the same time.
Forced Operation Mode: this mode is only used for refrigerant recovery and debugging for the unit.
Holiday mode:this mode is only available for heating mode. This mode is set to keep indoor temperature or leaving water temperature in a certain range, so as to prevent water system of the unit from freezing or protect certain indoor articles from freezing damage. When the unit stops due to malfunction, the two e-heaters of the unit will run.
Disinfection mode: in this mode, the water heating system can be disinfected. When starting up the disinfection function and setting corresponding time to meet the requirement of disinfection mode, the function will start. After the setting temperature is reached, this mode will terminate.
Weather-dependent Operation: this mode is only available for space heating or space cooling. In Weather- dependent mode, the setting value (remote room air temperature or leaving water temperature) is detected and controlled automatically when the outdoor air temperature is changed.
Quiet mode: Silent mode is available in cooling, heating and water heating mode. In silent mode, the unit will reduce the running noise via automatic control.
Floor commissioning: this function is intended to preheat the oor periodically for the initial use.
Air removal of the water system: this function is intended to replenish water and remove air in
the water system to make the equipment run at the stabilized water pressure.
Solar water heater: when the condition for starting the solar water heater is satised, the solar
heater will start to heat the circulation water. Then the heated water will go to the water tank and exchange heat with water in it. At any condition, the solar water heater will be given priority for startup so as for energy conservation.
Backup heat source: when the outdoor temperature is lower than the set point for starting the backup heat source and the unit is under the error condition and the compressor has stopped for three minutes, then the backup heat source will start to supply heat or hot water to the room.
Page 11

5 Nomenclature

Air-to-water Heat Pump Monoblock
8
Model Line-Up
Model Name
SMH-100IRA
SMH-140IRA
Note:
1
Capacities and power inputs are based on the following conditions:
Heating
1
9.5 9.8
14.2
Indoor Water Temperature 30°C/35°C,Outdoor Air Temperature 7°C DB/6°C WB;
2
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 23°C/18°C,Outdoor Air Temperature 35°C DB/24°C WB.
Operation Range
Mode
Heating
Cooling
Water Heating
Heat Source Side Temperature (°C) User Side Temperature (°C)
,kW
Capacity
14.5
2
,kW
Cooling
-20~35
10~48 7~25
-20~45 40~80
Power supply
220-240V,~,50Hz
380-415V,3N~,50Hz
25~60
Page 12

6 Installation Example

Air-to-water Heat Pump Monoblock
9
CASE 1: Connecting Heat Emitters for Heating and Cooling(Under floor loop,Fan Coil Unit,and Radiator)
Note:
The two-way valve is very important to prevent dew condensation on the floor and Radiator
while cooling mode;
Type of thermostat and specication should be complied with installation of this manual;
The Bypass valve must be installed to secure enough water ow rate, and should be installed at
the collector;
CASE 2: Connecting Sanitary Water Tank
Page 13
Note:
Air-to-water Heat Pump Monoblock
10
In this case, three-way valve should be installed and should be complied with installation of this
manual;
Sanitary water tank should be equipped with internal electric heater to secure enough heat
energy in the very cold days;
CASE 3 : Connecting Solar thermal system
Two-way valve is very important to prevent dew condensation on the floor and Radiator while cooling mode.
CASE 4 : Connecting Swimming pool system
Under Floor Coil
B
Radiator
FCU 1F CU 2
Hot water
City water
3-way valve 1
3-way valve 2
T
M
Sanitary water tank
Booster heater
Page 14
Notes:
Air-to-water Heat Pump Monoblock
11
1)Two-way valve is very important to prevent dew condensation on the oor and Radiator while
cooling mode.
2) 3-Way valve 1 is controlled by user,while the pool pump is actived, 3-Way valve 1 switches to
pool loop;while the pool pump is shuted down,3-Way valve 1 switches to under oor/FCU loop.
3) 3-Way valve 2 is automatic controlled by monobloc unit,while running water heating mode,3-
Way valve 2 switches to water tank loop;while running cooling/heating mode,3-Way valve 2 switches
to under oor/FCU loop.

7 Main Components

(1) SMH-100IRA
DC Fan Motor
Control Box
Electric Heater
Water Pump
Flow Switch
Expansion Tank
Compressor
Plate Heat Exchanger
Page 15
(2) SMH-140IRA
Air-to-water Heat Pump Monoblock
12
DC Fan Motor
Control Box
Safety Valve
Air Vent
Electric Heater
Flow Switch
Expansion Tank
Water Pump
Compressor
Plate Heat Exchanger
Flash Tank
Page 16

8 Installation Guideline of the Unit

Air-to-water Heat Pump Monoblock
13
8.1 Instruction to installation
(1) Installation of the unit must be in accordance with national and local safety codes. (2) IInstallation quality will directly affect the normal use of the air conditioner unit. The user is prohibited from installation. Please contact your dealer after buying this machine. Professional installation workers will provide installation and test services according to installation manual. (3) Do not connect to power until all installation work is completed.
8.2 Installation of the Monobloc Unit
8.2.1 Selection of the Installation Location of the Monobloc Unit
(1) The monobloc unit must be installed on a rm and solid support. (2) Avoid placing the monobloc unit under window or between two constructions, hence to prevent normal operating noise from entering the room. (3) Air ow at inlet and outlet shall not be blocked. (4) Install at a well-ventilated place, so that the machine can absorb and discharge sufcient air. (5) Do not install at a place where ammable or explosive goods exist or a place subject to severe dust, salty fog and polluted air.
8.2.2 Outline Dimensions of the Monobloc Unit
(1) SMH-100IRA
1390
890
361
412
388
Page 17
(2) SMH-140IRA
Air-to-water Heat Pump Monoblock
14
1430
367
340
8.2.3 Space requirements for installation
500
500
500
2000
1390
2000
1000
500
8.2.4 Precautions on installation of the Monobloc Unit
(1) When moving the monobloc unit, it is necessary to adopt 2 pieces of long enough rope to hand the unit from 4 directions. Included angle between the rope when hanging and moving must be 40°below to prevent center of the unit from moving. (2) The monobloc unit should be installed on concrete base that is 10cm height. (3) Requirements on installation space dimension of unit’s bodies are shown in following drawing. (4) The monobloc unit must be lifted by using designated lifting hole. Take care to protect the unit during lift. To avoid rusting, do not knock the metal parts.
Page 18
8.3 Water Volume and Pump Capacity (with pump)
Air-to-water Heat Pump Monoblock
15
Note: during operation, the water pump will adjust its output based on the actual load.
1
/min
n/
max
n
min
n
Off
1U/V
0132
Page 19
8.4 Water Volume and Expansion Vessel Pressure
Air-to-water Heat Pump Monoblock
16
2.5
2.0
1.5
1.0
0.5
Pre-pressure in expension vessel(Bar)
0.0 0 50 100 150 200 250 300 350 400
Maximum total water volume(liter)
Note:
The expansion vessel is 10 liter and 1bar pre-pressurized;
Total water volume of 280 liter is default; if total water is changed because of installation
condition, the pre-pressure should be adjusted to secure proper operation;
Minimum total water volume is 20 liter;
To adjust pre-pressure, use nitrogen gas by certicated installer.
8.5 Selection of Expansion Vessels
Formula:
V--- Volume of expansion vessel C--- Total water volume
--- Pre-set pressure of expansion vessel
P
1
-- The highest pressure during running of the system (that is the action pressure of safety valve.)
P
2
e---The expansion factor of water (the difference between the expansion factor of the original water
temperature and that of highest water temperature.)
Water expansion factor in different temperature
Temperature
0 0.00013
4 0 10 0.00027 20 0.00177 30 0.00435 40 0.00782 45 0.0099 50 0.0121 55 0.0145 60 0.0171 65 0.0198 70 0.0227 75 0.0258 80 0.029
(℃)
Expansion factor e
Page 20
85 0.0324
t
Air-to-water Heat Pump Monoblock
17
90 0.0359 95 0.0396
100 0.0434

9 Remote Air Temperature Sensor

Front side Back side
Remote Air Temperature Sensor
CN15
NO
YES
1.5 Meters
CN1
NO
NONO
Remote Air Environmen Temp sensor
15K
Doors
Electric box
Note:
Distance between the monobloc unit and the remote air temperature senor should be less than
15 meter due to length of the connection cable of remote air temperature sensor;
Height from oor is approximately 1.5 meter;
Remote air temperature sensor can not be located where the area may be hidden when door is
open;
Remote air temperature sensor can not be located where external thermal inuence may be
2
Page 21
applied;
Air-to-water Heat Pump Monoblock
18
Remote air temperature sensor should be installed where space heating is mainly applied;
After the remote air temperature sensor is installed, it should be set to “With” through the wired
controller so as to set the remote air temperature to the control point.

10 Thermostat

Installation of the thermostat is very similar to that of the remote air temperature sensor.
XT3
21 22 23 24 25 26
2220V GND
220V AC
Thermostat
OFF
HEAT
COOL
27 28 29 30
224V GND
COOL
HEAT
Thermostat
24V AC
OFF
How to Wire Thermostat
(1) Uncover the front cover of the monobloc unit and open the control box. (2) Identify the power specification of the thermostat, if it is 230V , find terminal block XT3
asNO.21~25; Otherwise, if it is 24V, nd terminal block XT3 as NO.26~30; (3) If it is the heating/cooling thermostat, please connect wire as per the gure above;
CAUTION!
Never use 230V AC and 24V AC thermostat at the same time, otherwise, it will cause short
circuit and power cut-off by the circuit breaker;
Setting temperature by the thermostat(heating or cooling) should be within the temperature
range of the product ;
For other constrains, please refer to previous pages about the remote air temperature sensor;
Do not connect external electric loads. Wire 220V AC(24V AC) and 220V GND(24V GND)
should be used only for the electric thermostat.
Never connect external electric loads such as valves, fan coil units, etc. If connected, the
mainboard of the unit can be seriously damaged.
Installation of the thermostat is very similar to that of the remote air temperature sensor.

11 2-Way Valve

There are two 2-way valve,the 2-way valve 1 is available and the 2-way vavle is reserved.The
2-way valve 1 is required to control water ow for cooling operation. The role of 2-way valve 1 is to cut off water ow into the underoor loop when the fan coil unit is equipped for cooling operation.
General Information
Type Power Operating Mode Supported
NO 2-wire 230V 50Hz ~AC
NC 2-wire 230V 50Hz ~AC
(1) Normal Open type. When electric power is NOT supplied, the valve is open. (When electric power is supplied, the valve is closed.) (2) Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric power is supplied, the valve is open.)
Closing water ow Yes
Opening water ow Yes
Closing water ow Yes
Opening water ow Yes
Page 22
How to Wire 2-Way Valve:
Air-to-water Heat Pump Monoblock
19
Follow steps below to wire the 2-way valve. Step 1. Uncover the front cover of the unit and open the control box. Step 2. Find the terminal block and connect wires as below.
XT2
4 5 6 10 11 12
L2(ON)
L1(OFF)
N
2-Way Valve 2 2-Way Valve 1
L2(ON)
L1(OFF)
N
WARING!
Normal Open type should be connected to wire (ON) and wire (N)for valve closing in cooling
mode.
Normal Closed type should be connected to wire (OFF) and wire (N)for valve closing in cooling
mode.
(ON) : Line signal (for Normal Open type) from PCB to 2-way valve (OFF) : Line signal (for Normal Closed type) from PCB to 2-way valve (N) : Neutral signal from PCB to 2-way valve
The 2-way value 2 is reserved without any control program. At the eld installation, it should be
wired at the terminal board of the 2-way valve 1.

12 3-Way Valve

There are two 3-way valve, the 3-way valve 1 is reserved and the 3-way valve 2 is available.The
3-way valve 2 is required for the sanitary water tank. Its role is ow switching between the under oor
heating loop and the water tank heating loop.
General Information
Type Power Operating Mode Supported
SPDT 3-wire
230V 50Hz ~AC
Selecting “Flow A” between “Flow A” and “Flow B” Ye s Selecting “Flow B” between “Flow B” and “Flow A” Yes
(1) SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting (for selecting Flow B), and Neutral (for common). (2) Flow A means 'water ow from the monobloc unit to under oor water circuit'. (3) Flow B means 'water ow from the monobloc unit to sanitary water tank'.
Follow steps below to wire the 3-way valve: Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the unit and open the control box. Step 2. Find terminal block and connect wire as below.
XT2
1 2 3 7 8 9
L2(ON)
L1(OFF)
N
L2(ON)
L1(OFF)
N
3-Way Valve 1 3-Way Valve 2
Page 23
WARING!
Air-to-water Heat Pump Monoblock
20
The 3-way valve should select water tank loop when electric power is supplied to wire (OFF)
and wire (N).
The 3-way valve should select under oor loop when electric power is supplied to wire (ON) and
wire (N).
(ON): Line signal (Water tank heating) from the main board to the 3-way valve
(OFF): Line signal (Under oor heating) from the main board to the 3-way valve
(N): Neutral signal from the main board to the 3-way valve

13 Wired Controller

Wired controller wiring guidance:

14 Other Auxiliary Heat Sources

Other auxiliary heat sources are allowed for the equipment and controlled in such a way that the mainboard will output 230V when outdoor temperature is lower than the set point for startup of the auxiliary heat source.
XT2
13 14
N
Other Thermal

15 Gate-controller

If there is gate control function,installation guide follow as:
(1) SMH-100IRA
XT3
1 2
Gate-Controller
(2) SMH-140IRA
XT4
5 6
Gate-Controller
Page 24

16 Charging and Discharging of Refrigerant

Air-to-water Heat Pump Monoblock
21
The unit has been charged with refrigerant before delivery. Overcharging or undercharging will cause the compressor to run improperly or be damaged. When refrigerant is required to be charged or discharged for installation, maintenance and other reasons, please follow steps below and nominal charged volume on the nameplate.
(1) Discharging: remove metal sheets of the outer casing, connect a hose to the charging valve and then discharge refrigerant.
Charging
valve 1
Charging
valve 2
Notes:
Discharge is allowed unless the unit has been stopped. (Cut off the power and repower it 1
minutes later)
Protective measures should be taken during discharging to avoid frost bites.
When discharging is nished, if vacuuming cannot be done immediately, remove the hose to
avoid air or foreign matters entering the unit.
(2) Vacuuming: When discharging is nished, use hoses to connect the charging valve, manometer and vacuum pump to vacuum the unit.
Pressure Meter
Note: when vacuuming is nished, pressure inside the unit should be kept lower than 80Pa for at
least 30 minutes to make sure there is no leak. Either charging valve 1 or charging valve 2 can be used for vacuuming.
(3) Charging: when vacuuming is nished and it is certain that there is no leak, charging can be done.
Be sure to charge the specied amount of refrigerant in liquid state.
Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not.
Connection Pipe
Vacuum pump
Page 25
Air-to-water Heat Pump Monoblock
22
With siphon tube No siphon tube

17 Installation of Insulated Water Tank

17.1 Installation measure
The water tank should keep a horizontal distance of 5 meters and a vertical distance of 3 meters with the main unit. It allowed to be installed in the room.
The standing type water tank must be installed erectly on the ground/floor and never be
suspended. Installation place must be rm enough and the water tank should be xed on the wall with bolts to avoid vibration, as shown in the following gure. During installation, weight of the water tank
should be taken into consideration.
Water Tank
Fix
With
Bolts
Installed on the ground
and never suspended
The minimum clearance between the water tank and any combustible object must be 500mm.
The water pipe, hot water joint and oor drain should be equipped for the water replenishment, hot
water supply and drainage of the water tank respectively.
Connection of the inlet/outlet waterway: connect the safety check valve attached with the unit (with the arrow on it pointing at the water tank) to the water inlet of the water tank with the PPR pipe according to the following figure and seal with seal tape. The other end of the safety check valve should connect with the water tap. The hot water pipe should be connected to the water outlet of the water tank also with the PPR pipe.
Safety check valve
Tap water
Note:
For safe use of water, water outlet/inlet of water tank must connect with a certain length of PPR
2
pipe ,L ≥70×R
(cm, R is inside radius of the pipe). Moreover, heat preservation should be conducted
and metal pipe can not be used. For the rst use, water tank must be full of water before the power is
on.
Page 26
17.2 Connection of waterway system
Air-to-water Heat Pump Monoblock
23
(1) If connection between the water tank and the monobloc unit should go through the wall, drill a
hole φ70 for pass of circulating water pipe.
(2) Preparation of pipelines: circulating water outlet/inlet pipe must be hot water pipe and PPR pipe with nominal outer diameter of dn25 and S2.5 series (wall thickness of 4.2mm) are recommended. Cooling water inlet pipe and hot water outlet pipe of water tank should also be hot water pipe and PPR pipe with nominal outer diameter of dn20 and S2.5 series (wall thickness of 3.4mm) are recommended. If other insulated pipes are adopted, refer to the above dimensions for outer diameter and wall thickness. (3) Installation of circulating water inlet/outlet pipes: connect the water inlet of the unit with circulating outlet of water tank and water outlet of unit with circulating inlet of water tank. (4) Installation of water inlet/outlet pipes of the water tank: safety check valve, lter and cut-off valve must be installed for the water inlet pipe according to the installation sketch of the unit. At least a cut-off valve is needed for the water outlet pipe. (5) Installation of blow-off pipes at the bottom of water tank: connect a piece of PPR pipe with
drainage outlet to oor drain. A cut-off valve must be installed in the middle of the drainage pipe and
at the place where it is easy to be operated by the users. (6) After connection of all waterway pipelines, perform the leakage test rstly. After that, bind up the water pipes, water temp sensor and wires with wrapping tapes attached with the unit. (7) Refer to Installation Sketch of the Unit for details.
CN29 CN12
Monobloc
Unit
AP1
XT3
CN11
1
Power cord of
booster heater
Hot Water Outlet
Tem.Sensor1
Cool Water Inlet
Safety Check
Valve
Cut- Off Valve
Other Thermal
Blow -O ff Outlet
Description Joint pipe thread
Circulating water inlet/outlet of main unit 1″Male BSP
Cooling water inlet of water tank 1/2″Female BSP
Circulating water inlet/outlet of water tank 3/4″Female BSP
Hot water outlet of water tank 1/2″Female BSP
System
Tap Water
Filter
Note:
Distance between monobloc unit and water tank should not exceed 5m levelly and 3m vertically.
If higher, please contact with us. Water tank on lower and main unit on higher side is recommended.
Prepare the materials according to the above joints dimension. If cut-off valve is installed
outside the room, PPR pipe is recommended to avoid freeze damage.
Page 27
Waterway pipelines can’t be installed until water heater unit is xed. Do not let dust and other
Air-to-water Heat Pump Monoblock
24
sundries enter into pipeline system during installation of connection pipes.
After connection of all waterway pipelines, perform leakage test rstly. After that, perform heat
preservation of waterway system; meanwhile, pay more attention to valves and pipe joints. Ensure enough thickness of insulated cotton. If necessary, install heating device for pipeline to prevent the pipeline from freezing.
Hot water supplied from insulated water tank depends on pressure of water tap, so there must
be supply of tap water.
During using, the cut-off valve of cooling water inlet of water tank should be kept normally on.
17.4 Electric wiring work
17.4.1 Wiring principle
General principles
Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of regulations and engineering requirements.
Only certicated electricians are allowed to perform wire connection on the site.
Before connection work is started, the power supply must be shut off.
Installer shall be responsible for any damage due to incorrect connection of the external circuit of the unit.
Caution --- only copper wires are allowed to be used.
Connection of power cable to the electric cabinet of the unit
Power cables should be laid out through cabling trough, conduit tube or cable channel.
Power cables to be connected into the electric cabinet must be protected with rubber or plastic to prevent scratch by edge of metal plate.
Power cables close to the electric cabinet of the unit must be xed reliably to make the power
terminal in the cabinet free from an external force.
Power cable must be grounded reliably.
17.4.2 Specication of Power Supply Wire and Leakage Switch
Power cable specications and Leakage switch types in the following list are recommended.
Minimum Sectional
Area of Earth Wire
2
) (mm2)
Model
SMH-100IRA
SMH-140IRA
Power Supply
V / Ph / Hz
220-240 / 1 / 50
380-400 / 3 / 50
Breakers
(A) (mm
63 16 5×25
40 10 5×10
Note:
The leakage switch is necessary for additional installation. If circuit breakers with leakage
protection are in use, action response time must be less than 0.1 second, leakage circuit must be 30mA.
The above selected power cable diameters are determined based on assumption of distance
from the distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of power cable must be increased to a further grade.
The power supply must be of rated voltage of the unit and special electrical line for air-
conditioning.
All electrical installation shall be carried out by professional technicians in accordance with the
Minimum Sectional
Area of Power
Supply Wire
Page 28
local laws and regulations.
Air-to-water Heat Pump Monoblock
25
Ensure safe grounding and the grounding wire shall be connected with the special grounding
equipment of the building and must be installed by professional technicians.
The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, YJV XLPE insulated power cable) used at 40°C and resistible
to 90°C(see IEC 60364-5-52). If the working condition changes, they should be modied according to
the related national standard.
The specications of the breaker listed in the table above are applied to the breaker with the
working temperature at 40°C. If the working condition changes, they should be modied according to
the related national standard.
Page 29

18 Wring Diagram

Air-to-water Heat Pump Monoblock
26
18.1 Control Board
(1) Main Board (AP2): SMH-100IRA; SMH-140IRA
PWR1
DC-MOTOR0
AC-N AC-L 4V VA-1 HEAT
ENTH
FB FA
ENTH-PRESS
L-PRESS
H-PRESS
CN8
COM-ESPE2
CN7
HPP
T-SENSOR3
T-SENSOR2CN5DC-MOTOR1
Silk Screen Specication
AC_N Neutral wire input of power supply
AC_L Live wire input of power supply
4V 4-way valve
VA-1 E-heater of chassis HEAT Electric heating tape ENTH Solenoid valve
FB To EXV2,pipe electric expansion valve,1-4 pin: driving impulse output; 5 pin: +12V; FA To EXV1,pipe electric expansion valve,1-4 pin: driving impulse output; 5 pin: +12V;
ENTH-PRESS Signal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
L-PRESS Signal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
H-PRESS Signal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
CN8
To the wired controller, communication cable: 1 pin earthed, 2 pin B, 3 pin A, 4 pin+12power supply;
CN7 Communication between AP1 and AP2;communication cable 2 pin B, 3 pinA
COM-ESPE2 Pin for communication with the drive
HPP High pressure switch
T-SENSOR3 1 hole: +3.3V 2 hole: detection ; suction temperature sensor T-SENSOR2 1, 2 hole: pipe temperature; 3, 4 hole: environment; 5, 6 hole: exhaust
CN5 Supply 18V DC power to the drive.
DC-MOTOR1
DC-MOTOR0
DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V; 5 pin: control signal; 6pin:feedback signal; DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V; 5 pin: control signal; 6pin:feedback signal;
PWR1 Supply 310V DC power to the drive.
Page 30
(2)Main Board (AP1): SMH-100IRA; SMH-140IRA
Air-to-water Heat Pump Monoblock
27
CN31
CN33
TR-IN
CN18
TR-OUT2
TR-OUT1
AC-L NE RR RUNH EAT
HEAT1
HEAT2
BAN-HEAT
OTHER_HEAT_
220V
X5
X10X92V1_OFF
2V1_ON
2V2_OFF
2V2_ON
3V1_OFF 3V2_OFF
3V2_ON3V1_ON
OTHER_HEAT_DCOUT
OTHER_HEAT_DCIN
CN6
CN4
COM-OUT
INDOOR_PUMP
POOL_PUMP
SOLOR_PUMP
T-SEN13
T-SEN12
T-SEN11
T-SEN10
T-SEN9
T-SEN8
T-SEN7
T-SEN5
T-SEN1
T-SEN6
T-SEN2
T-SEN3
T-SEN4
Silk Screen Location Introduction
AC-L - Live wire of power supply
N - Neutral wire of power supply
ERR X19 Error indicator
RUN X15 Running indicator
WT_HEAT X16 E-heater of water tank
HEAT1 X17 E-heater 1
HEAT2 X18 E-heater 2
BAN_HEAT X3 Antifreeze heater for the heat exchanger
SW_INDOOR
SW_SOLAR
SW_POOL
DOOR_INOVC_WT_HEATOVC_HEAT2OVC_HEAT1
OTHER_HEAT_220V X6 Assistant heat by 220VAC
X5 X5 Reserved
X10 X10 Reserved
X9 X9 Reserved
2V1_OFF X8 Electric magnetic 2-way valve1 is normally closed.
Page 31
2V1_ON X7 Electric magnetic 2-way valve1 is normally open.
Air-to-water Heat Pump Monoblock
28
2V2_OFF X14 Electric magnetic 2-way valve2 is normally closed.
2V2_ON X13 Electric magnetic 2-way valve2 is normally open.
3V1_OFF X22 Electric magnetic 3-way valve1 is normally closed.
3V1_ON X21 Electric magnetic 3-way valve1 is normally open.
3V2_OFF X11 Electric magnetic 3-way valve2 is normally closed.
3V2_ON X12 Electric magnetic 3-way valve2 is normally open.
OTHER_HEAT_DCOUT X1 The dc output of assistant heat
OTHER_HEAT_DCIN X2 The dc input of assistant heat
COM-OUT CN5 Connect to AP2
CN6 CN6 Connect the wired controller
INDOR_PUMP CN4 Control and feedback of the water pump for the main unit
CN8 CN8 Feedback of the water pump for the main unit
POOL_PUMP CN9 Control and feedback of the water pump for the swimming pool
SOLAR_PUMP CN7 Control and feedback of the water pump for the solar system
SW_INDOOR CN25 Detection input of water ow switch for indoor
SW_SOLAR CN16 Detection input of water ow switch for solar
SW_POOL CN17 Detection input of water ow switch for pool
DOOR_IN CN23 Door detection input
OVC_WT_HEAT CN28 E-heater of water tank adhesion-proof protection detector
OVC-HEAT1 CN26 E-heater of indoor unit1 adhesion-proof protection detector
OVC-HEAT2 CN27 E-heater of indoor unit2 adhesion-proof protection detector
T-SEN4 CN20 Terminal of temperature sensor4
T-SEN3 CN22 Terminal of temperature sensor3
T-SEN2 CN21 Terminal of temperature sensor2
T-SEN1 CN11 Terminal of temperature sensor1
T-SEN6 CN12 Terminal of temperature sensor6
T-SEN5 CN10 Terminal of temperature sensor5
T-SEN7 CN29 Terminal of temperature sensor7
T-SEN8 CN32 Terminal of temperature sensor8
T-SEN9 CN30 Terminal of temperature sensor9
T-SEN10 CN24 Terminal of temperature sensor10
T-SEN11 CN15 Terminal of temperature sensor11
T-SEN12 CN13 Terminal of temperature sensor12
T-SEN13 CN14 Terminal of temperature sensor13
TR-OUT1 CN2 Transformer output 1 (12V)
TR-OUT2 CN3 Transformer output 2 (24V)
CN18 CN18 Power supply interface of the thermostat (220~240V)
TR-IN CN1 220V input of transformer
CN31 CN31 Power supply interface and control signal of the thermostat (24V))
CN33 CN33 Control signal of the thermostat
Page 32
(3) Drive Board (AP4): SMH-100IRA
Air-to-water Heat Pump Monoblock
29
U
V
W
G-OUT
P-OU
L1-2
L2-1 DC-BUS1
T
PWR
L1-1
L2-2
Silk Screen Introduction
AC-L Live line input of the drive board
N Neutral line input of the drive board
L1-1 To PFC inductor brown line
L1-2 To PFC inductor white line
L2-1 To PFC inductor white line
L2-2 To PFC inductor blue line
U To compressor phase U
V To compressor phase V
W To compressor phase W
DC-BUS1 Pin for electric discharge of the high-voltage bar during test.
P-OUT Reserved
G-OUT Reserved
COMM
COMM1
PWR Power input of the drive board [1-GND,2-18V,3-15V]
AC-L
N
Communication interface[1-3.3V,2-TX,3-RX,4-GND]
COMM1
COMM
Page 33
(4) Drive Board (AP4): SMH-140IRA
Air-to-water Heat Pump Monoblock
30
No Silk Screen Introduction
1 COMM Communication interface [1-3.3V, 2-TX, 3-RX, 4-GND]
2 PWR Switch power interface [1-310VDC, 3-GND]
3 X1 Connector to lter L1-F
4 X2 Connector to lter L2-F
5 X3 Connector to lter L3-F
6 X4 Connector to L1-1 OF PFC reactor 1
7 X5 Connector to L2-1 OF PFC reactor 2
8 X6 Connector to L3-1 OF PFC reactor 3
9 X9 Connector to L3-2 of PFC reactor 3
10 X8 Connector to L2-2 of PFC reactor 2
11 X7 Connector to L1-2 of PFC reactor 1
12 DC-BUS Pin for electric discharge of the high-voltage bar during test.
13 X501 Connector to the compressor phase-U
14 X502 Connector to the compressor phase-V
15 X503 Connector to the compressor phase-W
Page 34
(5) Filter Board (AP3): SMH-100IRA
Air-to-water Heat Pump Monoblock
31
N-OUT1
N-OUT
L
-OUT
Silk Screen Introduction
AC-N Neutral line of the power supply for the main unit
AC-L Live line of the power supply for the main unit
AC-N AC-L
E1
E2
N-OUT
Neutral line output of the lter board (to the drive board)
Neutral line output of the lter board (to the main board )
N-OUT1 Reserved
L-OUT Live line output of the lter board (to the drive and main boards)
E1 To the grounding line of the main unit
E2 Reserved
Page 35
(6) Filter Board (AP3): SMH-140IRA
Air-to-water Heat Pump Monoblock
32
1
2
3
4
1011
9
8
7
6
5
No Silk Screen Introduction
1 X1 Connector to power supply output line AC-L1
2 X2 Connector to power supply output line AC-L2
3 X3 Connector to power supply output line AC-L3
4 X4 Connector to power supply neutral line AC-N
5 X9 Connector to the grounding line E , reserved
6 X8 Connector to power supply neutral line N-F (mainboard AC-N)
7 X7 Connector to power supply output line L3-F (drive board L3-F)
8 X6 Connector to power supply output line L2-F (drive board L2-F)
9 X5 Connector to power supply output line L1-F (drive board L1-F and AC-L)
10 X11 Connector to power supply output line L1-F (drive board L1-F and AC-L)
11 X10 Connector to the grounding line E
Page 36
18.2 Electric Wiring
Air-to-water Heat Pump Monoblock
33
18.2.1 Wiring principle
Refer to Section 16.4.
18.2.2 Electric wiring design
Wiring diagram: monobloc unit.
SMH-100IRA
PE PE
XT1
Power
L
N
3
6
1
1
4
8
2
N
WatertankAuxiliary
electricheater
ConsumerConnection
PE PE
KM3
SpecificationX
1. The wires intheimaninalframes areconnectedbythe consumer.
2. power supply forThermostat: If it is 220V AC,PleaseconnectTerminal block(XT4) 21.22.23.24.25; If itis 24V AC, pleaseconnectTerminal block(XT4) 26.27.28.29.30.
3. If consumer needEH6 J Please connectTerminal block(XT2)19.2 0 withEH3 Together.
5
4
6
2
7 8
2
KM2
8
WH
PE PE
Electricalheater Earthing
9
4
KM1
6
RD
BK BU
EH2 EH1
Electricalbox Earthing
CODE NAME
AP MainBoardOnlyForRT6
AP1 Indoor unitMain Board
AP2 OutdoorunitMain Board
AP3 Filter Board
80
AP4 DriveBoard
COMP Compressor
EH1 Watersideelectricalheater1
PE
EH2 Watersideelectricalheater2
EH3 Plateheatexchangeranti-freezing
EH4 Compressorbandheater
EH5 Bottomband heater
EH6 expansiontankheater
EKV1 Electronicexpansionvalvecoil1
EKV2 Electronicexpansionvalvecoil2
HL1 Runningindicatinglamp
HL2 Errorindicatinglamp
HP Highpressure switch
HT1 Temperature limiter1
HT2 Temperature limiter2
KM1 Auxiliaryelectric heater1ACcontactor
KM2 Auxiliaryelectric heater2ACcontactor
KM3 WatertankAuxiliaryelectric heater ACcontactor
L Electrical Inductance
L1 Electrical Reactance1
L2 Electrical Inductance 2
L
L3L10
M1 DCmotor
M2 Indoorunit pump
RT1 Water-out tempsensor of thewhole unit
RT2 Water-intempsensorofthewholeunit
RT3 Auxiliary heaterleavingwatertemp sensor
RT4 Water-tanktempsensor1
RT5 Water-tanktempsensor2
RT6 Remote roomtemp sensor1
RT7 Remote roomtemp sensor2
RT8 Pool watertempsensor
RT9 Pool water-intemp sensor
RT10 Poolwater-outt temp sensor
RT11 Solarwater-outtemp sensor
RT12 Solarwater-intempsensor
RT13 SolarBoard temp sensor
RT14 Defrostingtemp sensor
RT15 Outdoortempsensor
RT16 Dischargedtempsensor
RT17 Suctiontempsensor
SP1 High pressuresensor
SP2 Lowpressure sensor
SP3 Enthalpy increasingpressure sensor
SW1 Solarwaterflowswitch
SW2 Swimming Pool waterflowswitch
SW3 Indoor unitswaterflow switch
TC Transformer
XT1 Terminal block(L,N,1,2)
1
XT2 Terminal block(1~20)
M K
XT3 Terminal block(1~6)
XT4 Terminal block(21~42)
KM2
YV1 Increase Enthalpysolenoid valve
KM3
YV4 4-wayvalve coil
XT3
XT1
Magnetic ring
L1
COM-ESPE2
DC-MOTOR1
L10
Display
AP4
L5
26
AC-L
AC-N
CN5
FA
FB
CN8
AC-L
AC-N
82
L2
81
X1 X2
L6
86 87 88
89 90 91 92
5
4
EKV1
3
2
1
5
4
EKV2
3
2
1
31456
M1
COMM
PWR
U V W
93 94 95
AP3
L-OUT N-OUT
83 85
L3
L4
L7
COMP
3
PE
96
PE
84
AC-L
AP4
L2-1L1-1L1-2 L2-2
YE BU
BN
E1
N
WH
PE
board
L2
AP2
AP3
TC
AP1
XT4
HT1
XT2
24
20K
15K
50K
20K
HP
p
YV1
YV4
EH4
EH5
Communication line
RT6
L9
YE/GN
PE
25
RT14
RT15
T-SENSOR2
RT16
RT17
T-SENSOR3
76 77
HPP
SP1
S
H-PRESS
P
SP2
S
L-PRESS
P
SP3
S
ENTH-PRESS
P
ENTH
4V
HEAT
VA-1
AP3
L-OUT N-OUT
AP2
CN7
48
34
Electric component positionmap
L
12
AC-L N
XT2
L1OFFG
32
10
L2F ONG
3-way
valve1
L1F OFFG L2F ONG
2
4
2-way
valve2
L1F OFFG L2F ONG
6
8
3-way
valve2
L1F OFFG L2F ONG
2-way
valve1
HT2
Other
thermal
RunningIndi­catinglamp
Errorindi­catinglamp
EH3
EH6
Gate­controller
SW1
SW2
220VAC
220VACGND
OFF
HEAT
Thermostat
COOL
HEAT COOL
24VACGND
24VAC
Thermostat
OFF
Pool-pump
controlsignal
Pool-pumpfault feedback signal
Solar-pump
controlsignal
Solar-pumpfault feedback signal
Pump Control
signal (OUT)
X22
1
33
X21
2
27
N
3
34
X14
4
35
X13
5
28
N
6
36
X12
7
37
X11
8
29
N
9
38
X8
10
39
X7
11
30
N
12
40
X6
13
31
N
14
41
HL1
X15
15
44
N
16
42
HL2
X19
17
45
N
18
43
X3
19
46
N
20
XT3
49
1
50
CN23
2
51
3
52
CN16
4
53
5
CN17
54
6
XT4
55 56
57 58 59
60 61 62 63 64
66 67 68 69
70 71 72 73
74 75
47
CN18
CN33
CN31
CN9
CN7
CN8
CN1 CN2 CN3
X23
1N
PE
AP1
2L
1L
2N
3L
3N
TC
21 22
23 24 25
26 27 28 29 30
31 32 33 34
35 36 37 38
39 40
20K
RT1
20K
CN10
CN13
CN11
CN12
CN14
CN20
CN21
CN22
CN24
CN29
CN30
X17
X18
CN26
CN27
CN28
X16
CN25
CN5
CN15
CN4
RT2
20K
RT3
50K
RT4
50K
78
RT5
79
15K
RT7
20K
RT8
20K
RT9
20K
RT10
20K
RT11
20K
RT12
50K
RT13
HT1
17
19
11 12
13 14
15 16
21
XT2
22 23
3
KM1
10
12
18
KM2
10
KM1-6
KM2-6
KM3-6
XT2
20
12
KM3
1
0
SW3
15K
2
CN1
AP
L8
BK/BN
M2
BU
L9
SMH-140IRA
XT1
Power
L1
L2
L3
N
PE PE
XT4
W16
1
W17
2
W18
3
WatertankAuxiliary
electricheater
PE PE
SpecificationX
1. Thewires in theimaninalframes areconnectedbythe consumer.
2. powersupply forThermostat: Ifit is 220VAC,Pleaseconnect Terminal block(XT3)21.22.23.24.25; If itis 24VAC, pleaseconnect Terminal block(XT3)26.27.28.29.30.
3. Ifconsumer needEH6 J Please connectTerminal block(XT2)19.20 withEH3 Together.
Front
Underlayer
KM3 2
4653
Top
AP2AP4
W5
1
W6
W7
XT3
XT2
KM3 KM2
L1 L2 L3
W8 W9 W10
3
1
KM1
2465
HT1 HT2
RD BK BU RD BK BU
3
1
EH1
4
2
PE PE
Electricalheater Earthing
AP3AP1
TC
XT1
XT5
XT4
KM1
W13
W12
W11
1
KM2
2465
1
EH2
6 5
2
HT3
3
3
4
Electricalbox Earthing
6 5
W14 W15
3-way valve1
2-way valve2
3-way valve2
2-way valve1
Other thermal
Running
indicatinglamp
Errorindicating
lamp
EH6
220VACGND
ThermostatThermostat
Pool-pump control
signal Pool-pump fault feedback signal
Solar-pump
controlsignal Solar-pump fault feedback signal
Pump Control
signal(OUT)
Gatecontroller
L1(OFF) L2(ON) N L1(OFF) L2(ON) N L1(OFF) L2(ON) N L1(OFF) L2(ON)
HL1
HL2
EH3
220VAC
OFF HEAT COOL
HEAT COOL
24VACGND
24VAC
SW1
SW2
L6
W1
W2
W3
W4
AC-L N
XT2
W45
W43
1
X22
W44
2
X21
3
W46
4
X14
W47
W50
5
X13
6
W48
7
X11
W51
W49
8
X12
9
W52
10
X8
W53
W54
11
N
N
OFF
X7
12
W55
13
X6
W59
14
W57
X15
15
W60
16
W58
X19
17
W61
18
W56
19
X3
W62
20
XT3
W63
21
W64
CN18
22
W70
23
W71
CN33
24
W72
25
W65
26
W66
27 28 29 30
31
32 33 34
35 36
37
38
39 40
XT4
5 6
7 8
9 10
AP1
W67 W68
CN31
W69
W73 W74 W75
CN9
W76
W77 W78 W79
CN7
W80
W81 W82
CN8
W102 W103
CN23
W106 W107
CN16
W104 W105
CN17
CN1
1N
1L
TC
RT1
CN10
RT2
RT3
CN13
RT4
CN11
W41 W42
CN12
RT7
CN14
RT8
CN20
RT9
CN21
RT10
CN22
RT11
CN24
RT12
CN29
RT13
CN30
W85 W86
CN26
W88
CN27
W87
X17
W90
X18
A1
W91 W92
CN28
W93
X16
CN25
CN5
2
CN15
L14
CN4
CN3
CN2
2N
2L
3N
3L
L5
X1(AC-L1)
X2(AC-L2)
AP3
X3(AC-L3)
X4(AC-N)
20K
20K
20K
RT14
RT15
50K
RT16
RT5
50K
RT17
15K
HP
20K
20K
20K
20K
20K
50K
KM1-2
KM2-2
EH5
W89
A2A1
KM1
EH4
W94
W95
A2
KM2
HT3
1
KM3-2
2
W96
XT5
W97
2
A2A1
KM3
SW3
RT6
15K
CN1
AP
M3
L15
BN
M
BU
YEGN
L15
PE
X9(E)
W112
PE
20K
15K
T-SENSOR2
50K
20K
T-SENSOR3
p
SP1
SP2
SP3
YV1
4YV
COM-ESPE2
W37 W38
HPP
H-PRESS
AP2
L-PRESS
ENT-PRESS
DC-MOTOR0
ENTH
4V
DC-MOTOR1
VA-1
HEAT
CN7
W98
2
XT5
W113
XT1-L1
1
W114
XT1-N
2
W19
X5(L1-F)
W20
X6(L2-F)
W21
X7(L3-F)
X11(L1)
RD
X8(N-F)
W22
L4
L1L2L3
BK
L13
X2(AC-N)
X1(AC-L)
PWR1 PWR
5
4
EKV1
FA
3
2
1
5
4
EKV2
FB
3
2
1
31456
CN8
M
M1
L16
4
Display
board
X1(L1-F)
X2(L2-F)
X3(L3-F)
L7
W25
X4(L1-1)
W26
X5(L2-1)
W27
X6(L3-1)
L8
W30
X9(L3-2)
W29
X8(L2-2)
W28
X7(L1-2)
L9
W31 W32
L10
W108 W109 W110 W111
L11
W33 W34 W35
L12
31456
M
M2
COMM
X501(U)
CODE NAME
4YV 4-wayvalvecoil
AP MainBoardOnlyFor RT6
AP1 IndoorunitMainBoard
AP2 OutdoorunitMainBoard
AP3 FilterBoard
AP4 DriveBoard
COMP Compressor
EH1,2 Auxiliaryelectricheater
EH3 Plateheat exchangerelectricheater
AP4
EH4 Compressorbandheater
EH5 Bottonband heater
EH6 Expandjarelectricheater
EKV1 Electric expansion valvecoil1
EKV2 Electric expansion valvecoil2
HL1 Running indicatinglamp
HL2 Errorindicatinglamp
HP Highpressure switch
HT1,2 Thermostat (WP95A-R)
HT3 Thermostat(WP75A-R)
L1~L3 Inductor
X502(V)
L4 Electrical Inductance
X503(W)
L5~L16 Magneticring
M1 DownDC Motor
M2 UPDC Motor
M3 Indoorunitpump
RT1 Water-outtemp sensor ofthewholeunit
RT2 Water-intemp sensor ofthewholeunit
RT3 Auxiliaryheaterwater-outtemp sensor
RT4 Water-tanktemp sensor 1
WVU
RT5 Water-tanktemp sensor 2
COMP 3
RT6 RemoteAirtempsensor1
W36
RT7 RemoteAirtempsensor2
PE
RT8 Poolwatertempsensor
RT9 poolwater-intempsensor
RT10 Pool water-outtemp sensor
RT11 Solarwater-out tempsensor
RT12 Solarwater-intempsensor
RT13 Solarboard tempsensor
RT14 Defrosting tempsensor
RT15 Outdoortempsensor
RT16 Dischargedtempsensor
RT17 Suctiontempsensor
SP1 Highpressure sensor
SP2 Low pressure sensor
SP3 Increaseenthalpypressuresensor
SW1 Solarwaterflow switch
SW2 Pool waterflowswitch
SW3 Indoor unitswaterflowswitch
TC Transformer
YV1 Increaseenthalpysolenoidvalve
Page 37
18.2.3 Terminal Board
Air-to-water Heat Pump Monoblock
34
SMH-100IRA
SMH-140IRA
Page 38

19 Commissioning

Air-to-water Heat Pump Monoblock
35
19.1 Check before startup
For safety of users and unit, the unit must be started up for check before debugging. The
procedures are as below:
The following items shall be performed by qualied repair persons.
Conrm together with the sales engineer, dealer, installing contractor and customers for the following items nished or to be nished.
No. Conrmation of Installation
If the contents of Application for Installation of this Unit by Installer are real. If not, debugging
1
will be refused. Is there written notice in which amendment items are shown in respect of unqualified
2
installation?
3 Are Application for Installation and Debugging list led together?
No. Pre-check
Is appearance of the unit and internal pipeline system ok during conveying, carrying or
1
installation?
2 Check the accessories attached with the unit for quantity, package and so on.
3 Make sure there is drawings in terms of electricity, control, design of pipeline and so on.
Check if installation of the unit is stable enough and there is enough space for operation and
4
repair.
5 Completely test refrigerant pressure of each unit and perform leakage detection of the unit.
6 Is the water tank installed stably and are supports secure when the water tank is full?
Are heat insulating measures for the water tank, outlet/inlet pipes and water replenishing pipe
7
proper? Are the nilometer of water tank, water temperature indicator, controller, manometer, pressure
8
relief valve and automatic discharge valve etc. installed and operated properly? Does power supply accord with the nameplate? Do power cords conform to applicable
9
requirements?
Is power supply and control wiring connected properly according to wiring diagram? Is
10
earthing safe? Is each terminal stable?
11 Are connection pipe, water pump, manometer, thermometer, valve etc. are installed properly?
12 Is each valve in the system open or closed according to requirements?
13 Conrm that the customers and inspection personnel of Part A are at site.
14 Is Installation Check-up Table completed and signed by the installation contractor?
Attention: If there is any item marked with ×, please notify the contractor. Items listed above are just for
reference.
General Evaluation: Debugging □ Amendment □
Conrmed Items after pre-checking
Judge the following items (if there is not any lling, qualication will be regarded.)
a: Power supply and electric control system b: Loading calculation
c: Heating problems of Unit d: Noise problem
e: Pipeline problem f: Others
Normal debugging work can’t be performed unless all installation items are qualied. If there is any problem, it must be solved rstly. The installer will be responsible for all costs for delay of debugging
and re-debugging incurred by any problem which is not solved immediately.
Submit schedule of amending reports to installer.
Is the written amending report which should be signed after communication provided to installer?
Yes ( ) No ( )
Page 39
19.2 Test run
Air-to-water Heat Pump Monoblock
36
Test run is testing whether the unit can run normally via preoperation. If the unit cannot run normally, find and solve problems until the test run is satisfactory. All inspections must meet the requirements before performing the test run. Test run should follow the content and steps of the table below:
The following procedure should be executed by experience and qualied maintenance men.
No. Start up the pretest procedure
Notice: before test, ensure that all power must be cut off, including the far- end power switch, otherwise, it may cause casualty.
1 Ensure that the compressor of the unit is preheated for 8h.
Caution: heat the lubricating oil at least 8h in advance to prevent refrigerant from mixing with the
lubricating oil, which may cause damage to the compressor when starting up the unit.
Check whether the oil temperature of the compressor is obviously higher than the outdoor ambient
2
temperature.
Caution: if the oil temperature of the compressor is obviously higher than the outdoor ambient
temperature, it means that the heating tape of compressor is damaged. In that case, the compressor will be damaged easily. Therefore, repair the heating tape before using the unit.
Check whether the phase sequence of the main power supply is correct. If not, correct the phase
3
sequence rstly.
Recheck the phase sequence before start-up to avoid reverse rotation of the compressor which may
damage the unit.
Apply the universal electric meter to measure the insulation resistance between each outdoor
4
phase and earth as well as between phases.
Caution: defective earthing may cause electric shock.
No. Ready to start
Cut off all temporary power supply, resume all the insurance and check the electricity for the last time.
1
Check the power supply and voltage of the control circuit; _____V must be ±10% within the range of rated operating power.
No. Start up the unit
1 Check all the conditions needed to start up the unit: oil temperature, mode, required load etc.
Start up the unit, and observe the operation of compressor, electric expanding valve, fan motor and water pump etc.
2
Note: the unit will be damaged under abnormal running state. Do not operate the unit in states of high pressure and high current.
Others:
Estimation or suggestion on the general running situation: good, modify
Identify the potential problem (nothing means the installation and debugging are in accordance with the requirements.)
a. problem of power supply and electric control system: b. problem of load calculation:
Items for acceptance after debugging
c. outdoor refrigerant system: d. noise problem:
e. problem of indoor and piping system: h. other problems:
During operation, it is needed to charge for the maintenance due to non-quality problems such as incorrect installation and maintenance.
Acceptance
Is the user trained as required? Please sign. Yes( ) No( )
Page 40

20 Daily Operation and Maintenance

Air-to-water Heat Pump Monoblock
37
In order to avoid damage of the unit, all protecting devices in the unit had been set before delivery, so please do not adjust or remove them.
For the rst startup of the unit or next startup of unit after long-period stop (above 1 day) by cutting
off the power, please electrify the unit in advance to preheat the unit for more than 8 hours.
Never put sundries on the unit and accessories. Keep dry, clean and ventilated around the unit.
Remove the dust accumulated on the condenser n timely to ensure performance of the unit and to
avoid stop of the unit for protection.
In order to avoid protection or damage of the unit caused by blockage of the water system, clean
the lter in water system periodically and frequently check water replenishing device.
In order to ensure anti-freezing protection, never cut off the power if ambient temperature is below zero in winter.
In order to avoid frost crack of the unit, water in the unit and pipeline system not used for a long period should be drained. In addition, open the end cap of the water tank for drainage.
Never frequently make the unit on/off and close the manual valve of the water system during operation of the unit by users.
Ensure frequent check to the working condition of each part to see if there is oil stain at pipeline joint and charge valve to avoid leakage of refrigerant.
If malfunction of the unit is out of control of users, please timely contact with authorized service center.
Notes:
The water pressure gage is installed in the returning water line in the unit. Please adjust the hydraulics system pressure according to next item:
If the pressure is less than 0.5 bar, please recharge the water immediately;
When recharging, the hydraulics system pressure should be not more than 2.5Bar.
Troubleshooting
Malfunctions Reasons Troubleshooting
Compressor does not start up
Heavy noise of fan
Heavy noise of compressor
Water pump does not run or runs abnormally
Compressor starts or stops frequently
The unit does not heat although compressor is running
Poor efciency of hot
water heating
Power supply has problem.
Connection wire is loose.
Malfunction of mainboard.
Malfunction of compressor.
Fixing bolt of fan is loose.
Fan blade touches shell or grill.
Operation of fan is unreliable.
Liquid slugging happens when liquid
refrigerant enters into compressor.
Internal parts in compressor are broken.
Malfunction of power supply or terminal.
Malfunction of relay.
There is air in water pipe.
Poor or excess refrigerant.
Poor circulation of water system.
Low load.
Leakage of refrigerant.
Malfunction of compressor.
Poor heat insulation of water system.
Poor heat exchange of evaporator.
Poor refrigerant of unit.
Blockage of heat exchanger at water side.
Phase sequence is reverse.
Check out and re-x.
Find out the reasons and repair.
Replace compressor.
Re-x xing bolt of fan.
Find out the reasons and adjust.
Replace fan.
Check if expansion valve is failure and
temp. sensor is loose .If that, repair it.
Replace compressor.
Find out the reasons and repair.
Replace relay.
Evacuate.
Discharge or add part of refrigerant.
Water system is blocked or there is air in
it.Check water pump, valve and pipeline.
Clean water lter or evacuate.
Adjust the load or add accumulating
devices.
Repair by leakage detection and add
refrigerant.
Replace compressor.
Enhance heat insulation efficiency of the
system.
Check if air in or out of unit is normal and
clean evaporator of the unit.
Check if refrigerant of unit leaks.
Clean or replace heat exchanger.
Page 41
Page 42
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The maintanance and the liquidation must be carried out by qualified personel. Type of refrigerant: R410A The composition of the cooling medium R410A: (50% HFC-32, 50% HFC-125) The quantity of the refrigerant: please see the unit label. The value GWP: 2088 GWP = Global Warming Potential
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com This product was manufactured in China (Made in China).
REPRESENTATIVE, TECHNICAL SUPPORT
NEPA spol. s r.o. Purkyňova 45 612 00 Brno Czech republic
Tel.: +420 541 590 140 Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...