Sinclair DRY CONTACT GATEWAY SDG-01 User Manual

Page 1
USER'S MANUAL
EN
DRY CONTACT GATEWAY
SDG-01
Page 2
“Originalinstructions”
IMPO
RTANT N
Read this manual ca or operating your new air conditioning
unit. Make sure to save this manual for futu
re r
efe
ence.
r
r
efully befo
r
e installing
Page 3
To Users
Thank you for
manual
carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as below:
(1) This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsibility for their safety. Children should be supervised to ensure that they do not play with the appliance.
(2) This instruction manual is a universal manual; some functions are only
applicable to particular product. All the illustrations and information in the instruction manual are only for reference, and control interface should be subject to actual operation.
(3) In order to make the product better, we will continuously conduct
improvement and innovation. We have the right to make necessary revision to the product from time to time due to the reason of sales or production, and reserve the right to revise the contents without further notice.
(4) For personal injury or property loss and damage caused by improper
selecting Sinclair’s
product. Please read this instruction
I
Page 4
operation such as improper installation and debugging, unnecessary maintenance, violation of related national laws and rules and industrial standard, and violation of this instruction manual, etc., we will bear no liability.
(5) The final right to interpret for this instruction manual belongs to
SINCLAIR CORPORATION Ltd..
II
Page 5
III
Contents
1 Safety Notices (Please be sure to abide) .................................. 1
2 Appearance ..................................................................................... 2
3 DIP switch instruction .................................................................... 4
4 Functions ......................................................................................... 5
4.1 Shield general terminals ................................................................... 5
4.2 Input function ...................................................................................... 5
4.2.1 Level input ............................................................................... 5
4.2.2 Impulse input ........................................................................... 6
4.3 Output function ................................................................................... 7
4.4 Indicator instruction ........................................................................... 8
5 Product Installation ........................................................................ 9
5.1 Dimension ........................................................................................... 9
5.2 Installation requirement ................................................................... 10
5.3 Wire specification ............................................................................. 10
5.4 Wiring instruction ............................................................................. 11
5.4.1 Communication and power cord connection .................... 11
5.4.2 Connection of input dry contact .......................................... 11
5.4.3 Connection of output dry contact........................................ 11
5.4.4 Installation procedure ........................................................... 12
Page 6
1 Safety Notices (Please be sure to abide)
Warning: If not abide strictly, it may cause severe damage to the unit or the people. Note: If not abide strictly, it may cause slight or medium damage to the unit or the people. This sign indicates that the operation must be prohibited. Improper operation may cause severe damage or death to people. This sign indicates that the items must be observed. Improper operation may cause damage to people or property.
WARNING!
This product can’t be installed at corrosive, inflammable or explosive environment or the place with special requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of the unit, or even cause fire hazard or serious injury. As for above special places, please adopt special air conditioner which is with anti-corrosive or anti-explosion function.
1
Page 7
2 Appearance
Fig. 2.1 Appearance of dry contact gateway
2
Page 8
Fig. 2.2 Main board of dry contact gateway
Table 2.1 Instruction of main board
No. Components No. Components
4-core needle stand (common
1
2 3 4 5 Reserved terminal block 11 6 DIP switch S2 12
use for communication and
power supply)
Force OFF dry contact input
terminal block
ON/OFF dry contact input
terminal block
Mode dry contact input terminal
block
7 DIP switch S1
ON/OFF dry contact output
8 9
10
Ventilation dry contact output
3
terminal block
Error indicator dry contact
output terminal block
Mode dry contact output
terminal block
Cold plasma dry contact
output terminal block
terminal block
Page 9
3 DIP switch instruction
Two DIP switches S1 and S2 are installed on the dry contact gateway. Before energization, please set to proper position according to requirement. Once energization is finished, please do not dial any DIP switch. As for the function definition for DIP switch S1 and S2, please refer to table 3.1 and table 3.2.
Table 3.1 Function for DIP switch S1
Dip switch bit 1 2 3 4 5 6 7
Description
ON position Enable Level /
Digital position Disable Impulse /
Dip switch bit 1 2 3 4 5 6 7
Input name Force OFF ON/OFF Mode Reserved ON position Enable Enable Enable /
Digital position Disable Disable Disable /
General terminals
control enable
Table 3.2 Function for DIP switch S2
Input
type
Reserved
4
Page 10
4 Functions
4.1 Shield general terminals
Once the first bit of DIP switch S1 is set to Digital position (General terminals control disable), the unit will shield the general terminals (wired controller, remote controller, APP and light board), and high-end terminals (central controller, long-distance monitor, keycard control) and dry contact gateway can still control the unit. When the first bit of DIP switch S1 is set to ON position (General terminals control enable), all the terminals can control the unit.
4.2 Input function
Dry contact gateway is compatible with level input method and impulse input method, which can be selected by the second bit of DIP switch S1. Each input function can be set as enable or disable through the corresponding bit of DIP switch S2. When it is set as disable, the unit wont execute corresponding input command. The following descriptions of input functions are supposed as the input functions are enabled.
4.2.1 Level input
Under level input method, the input command is decided by the Connected/Disconnected of the dry contact. Each time when the status of dry contact is changed, input commands of all the dry contacts will be re-executed. The
5
Page 11
relationship between dry contact status and the input command are shown as the table 4.1.
Table 4.1 Level input
Input name Status of dry contact Command
Force OFF
ON/OFF
Mode
Connected Cancel Force OFF
Disconnected Force OFF
Connected
Disconnected
Connected
Disconnected
Turn unit on Turn unit off
Heating Cooling
4.2.2 Impulse input
Under impulse input method, for each detection of dry contact from disconnected to connected (connected time should be more than 500ms), it is deemed as valid impulse input. When valid impulse input is detected, dry contact gateway updates corresponding input commands. The detail commands are shown as Table 4.2. For each detection of valid impulse input, commands of all the dry contacts will be re-executed. When dry contact gateway is energized, it needs about 6 seconds to acquire operating status of unit, during such period, all the inputs are invalid.
6
Page 12
Table 4.2 Impulse input
Input name Machine state Machine type Command
With Force OFF
Force OFF
ON/OFF
Mode
Note: when it conducts Force OFF, all the terminals including dry contact gateway cannot turn on the unit.
Without Force OFF
(default when
energized) Machine on Turn off the unit Machine off Turn on the unit
Heating Cooling
/
Cooling only
Not heating
Cooling and
Heating
Cancel Force OFF
Force OFF
Cooling
Heating
4.3 Output function
The dry contact gateway will output corresponding function and status by controlling the connected/disconnected of the dry contact. User can connect power cord with load to the output terminal to turn corresponding load ON/OFF via dry contact gateway. Definition of output contacts are shown in Table 4.3.
Table 4.3 Function definition of output contact
Output dry contact Contact connected Contact disconnected
ON/OFF Unit on Unit off
Error indicator Unit Faulty Normal
Operating mode Heating Cool/Dry/Fan
Cold plasma Turn cold plasma on Turn cold plasma off
Ventilation Turn ventilation on Turn ventilation off
7
Page 13
4.4 Indicator instruction
The normal display of the indicator indicates the normal operation of the dry contact gateway.
Table 4.4 Indicator instruction
No. Indicator Function introduction
1 Power indicator (red) It’s on after energization
Communication indicator
2
(green)
Flashing during
communication
8
Page 14
5 Product Installation
5.1 Dimension
Fig. 5.1 Dimension of dry contact gatewayunitmm
9
Page 15
5.2 Installation requirement
(1) Do not install the product at wet place or the place where there’s splashing
water.
(2) Do not install the product at the place where is closing to the
high-temperature object or the position with direct sunshine.
(3) This product is suggested to be installed at indoors. The suggested
working temperature range for installation is 050.
(4) Before installation, please cut off the power for the strong wire embedded
in the installation hole on the wall. Ho-line work is not allowed during the complete installation process.
(5) Please pay attention to below notices for wiring to avoid abnormal
phenomenon due to electromagnetic interference. 1 Make sure the communication wire connects to the correct interface.
Otherwise, there will be communication error.
2 The communication wire of dry contact gateway (4-core wire) should
be separated from other power cord and the minimum distance should be more than 20cm. Otherwise, there will be communication error.
5.3 Wire specification
It is recommended to use the connecting wire with cross sectional area of
10
Page 16
0.75mm² for input and output of dry contact gateway.
5.4 Wiring instruction
5.4.1 Communication and power cord connection
Connect one end of wiring (4-core wire) to the COM1 needle stand of dry contact gateway and then connect the other end to the 4-core COM1 or COM2 needle stand of the indoor unit.
5.4.2 Connection of input dry contact
Connect two terminals of each group of input dry contact to the both ends of switch respectively. Single control switch is suggested for the level input method, and touch switch is recommended for impulse input method.
5.4.3 Connection of output dry contact
Connect the two terminals of each group output to the load respectively. The
requirement for the allowable connected load:
(1) Weak current12~24VDC(100mA500mA).
(2) Strong current200~240VAC(100mA3A).
11
Page 17
Fig. 5.2 Sketp map for input/output wiring
5.4.4 Installation procedure
(1) Remove the screws used for fixing the front cover; Open the front cover of
dry contact gateway.
(2) Check whether the screws used for fixing the main board is loose. If yes,
please tighten the screws to fix the main board.
(3) Attach the bottom case of dry contact gateway at the installation position
(such as the wall) and then use screws to fix the base case and the installation hole on the wall together.
12
Page 18
(4) Set the DIP switch S1 and S2 to the corresponding position.
(5) Put the wire through the rubber ring and make sure the basic insulation
layer and the protective jacket of the wire can put through the rubber ring and wire clamp.
(6) Connect the wire to corresponding terminals, and screw up the screw in
the contact to make sure that it will not loose.
(7) Use wire clamp to press the wire, and screw up to fix the screws of wire
clamp. If the wires for connecting are less than 3 sets, please use white wire clamp, otherwise use black wire clamp.
(8) Close the front cover of dry contact gateway and then tighten the screws of
the front cover.
13
Page 19
Fig. 5.3 Sketch map for wire-pressing
14
Page 20
ZPĚTNÝ ODBĚR ELEKTROODPADU
Uvedený symbol na výrobku nebo v průvodní dokumentaci znamená, že použité elektrické nebo elektronické výrobky nesmí být likvidovány společně s komunálním odpadem. Za účelem správné likvidace výrobku jej odevzdejte na určených sběrných místech, kde budou přijata zdarma. Správnou likvidací tohoto produktu pomůžete zachovat cenné přírodní zdroje a napomáháte prevenci potenciálních negativních dopadů na životní prostředí a lidské zdraví, což by mohly být důsledky nesprávné likvidace odpadů. Další podrobnosti si vyžádejte od místního úřadu nebo nejbližšího sběrného místa.
V případě problémů s kvalitou nebo jiných kontaktujte prosím místního prodejce nebo autorizované servisní středisko.
Tísňové volání - telefonní číslo: 112
VÝROBCE
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain www.sinclair-world.com Zařízení bylo vyrobeno v Číně (Made in China).
ZÁSTUPCE
SINCLAIR Global Group s.r.o. Purkyňova 45 612 00 Brno Česká republika
SERVISNÍ PODPORA
SINCLAIR Global Group s.r.o. Purkyňova 45 612 00 Brno Česká republika
Bezplatná infolinka: +420 800 100 285
www.sinclair-solutions.com
Obchod: info@sinclair-solutions.com, tel.: +420 541 590 140, fax: +420 541 590 124 Servis: servis@sinclair.cz, tel.: +420 541 590 150, fax: +420 541 590 153 Objednávky: brno-fakturace@sinclair.cz