Simrad SD570 Installation Manual

Page 1
Simrad SD570 Fishery sonar
Installation manual
A L W A Y S A T T H E F O R E F R O N T O F T E C H N O L O G Y
www.simrad.com
Page 2
Page 3
Simrad SD570
Installation manual
851--160085 / Rev.B
Page 4
Note
Simrad AS makes every effort to ensure that the information contained within this document is correct. However, our equipment is continuously being improved and updated, so we cannot assume liability for any errors which may occur.
Warning
The equipment to which this manual applies must only be used for the purpose for which it was designed. Improper use or maintenance may cause damage to the equipment or injury to personnel. The user must be familiar with the contents of the appropriate manuals before attempting to operate or work on the equipment.
Simrad AS disclaims any responsibility for damage or injury caused by improper installation, use or maintenance of the equipment.
Copyright
E 2004 Simrad AS
ISBN 82-8066-018-6
The information contained within this document remains the sole property of Simrad AS. No part of this document may be copied or reproduced in any form or by any means, and the information contained within is not to be communicated to a third party, without the prior written consent of Simrad AS.
Support
For support on your Simrad equipment, consult your local dealer, visit www.simrad.com, or contact us directly at support.fish@simrad.com.
Simrad AS Strandpromenaden 50 Box 111 N-3191 Horten
Telephone: +47 33 03 40 00 Facsimile: +47 33 04 29 87
M A X I M I Z I N G Y O U R P E R F O R M A N C E A T S E A
Page 5
Installation manual
1
851-160085 /B
Sections
This book is the Installation manual for the SD570 fishery sonar. It describes how to install the various units used by the SD570 system.
1Introduction
This section gives a brief description of the SD 570/SE 570 sonars and the installation requirements.
2 Installation procedures
Thissectionprovidesthenecessaryinformationfortheinstallationandcabling of the complete sonar system according to Simrad’s requirements.
3 Start-up procedures
This sectioncontains the start-up procedures to be carried out after the installation of the sonar.
4 Trunk systems
This sectiondescribes the differenttrunk systemsthat can be used with the SD 570/SE570 Hull Unit. Also described are the adapter flanges which must be used if the Hull Unit is to be installed into alreadyinstalled SQ4, SQ, SB2 and SK3 trunks.
5Drawings 6 Appendices
Page 6
Simrad SD570
2
851-160085 / B
Remarks
References
Further information about the SD570 system may be found in the following manuals:
SD570 Operator manual
The reader
This Installation manual is intended for the design and installation engineers at the shipyard performing the installation. The information is supplied as the basis for the shipyard’s own installation drawings applicable to the vessel. On completion of the installation, this manual must be kept on the vessel for reference purposes during system maintenance.
Note
This manual includes sections that may be revised individually. In the event of a revision to any part of this manual, this “Cover and Contents” section will be replaced.
Page 7
Installation manual
3
851-160085 / B
Document revisions
Rev Written by
Checked by Approved by
Date Sign Date Sign Date Sign
A Unknown CL
B 02.02.04 RBr 02.02.04 EGj 02.02.04 ESB
Sect Title Revision File
0 Cover and contents B 851--160085
1 Introduction B 851--160115
2 Installation procedures B 851--160116
3
4
5
6
Start--up procedures
Trunk syst em
Drawings
Appendices
B
B
B
B
851--160117
851--160503
851--160118
851--160675
Rev.A First edition.
Rev.B Re--issued. All sections updated to Rev.B, but product specific informa-
tion has not been changed. ISBN number issued.
Page 8
Simrad SD570
4
851-160085 / B
Blank page
Page 9
Installation manual
I
851-160085 / B
High voltage safety warning
Precautionary measures
The voltages used to power this equipment are potentially lethal. Even 110 volts can kill. Whenever possible, the following precautionary measures must be taken before any work is carried out inside the equipment:
S Switch off all high-voltage power supplies. S Check the operation of any door interlocks
and any other safety devices.
S Completely discharge all high-voltage
capacitors.
It should be noted that interlocks and safety devices are normally located only at regular access points, and high voltages may be exposed during dismantling.
Never work alone on high-voltage equipment!
First aid in the event of electric shock
Normally, even a high voltage electric shock will not kill instantly. The victim can still be revived even when his breathing and heart-beat have ceased.
Could YOU save someone’s life? In the event of electric shock, the correct
actions, performed quickly may well save the victim’s life. Make sure you know what to do!
Immediate action
While shouting for help, remove the source of power from the victim. Switch off the supply if possible, or using a dry, non-conductive material (rubber gloves, broom handle etc.) to insulate yourself, separate the victim from the source. If the voltage exceeds 1000 volts, switch off the supply and be ready to catch the victim. Take care- do not become a victim yourself.
Commence first aid on the spot. Continue to shout for assistance till someone arrives.
1 Lay the victim flat on his back and loosen
any tight clothing (collar, tie, belt etc.).
2 Open his mouth and check for and remove
any false teeth, chewing gum etc.
3 Check if the victim is breathing. If not,
check if his heart is beating. The pulse is normally easily found in the main arteries of the neck, either side of the throat, up under the chin.
If his heart is beating but he is not breathing, commence artificial respiration. If the victim’s heart is not beating, commence external cardiac massage (ECM). Continue to shout for assistance till someone arrives.
External cardiac massage
1 Kneel beside the victim. Place the heel of
one hand in the centre of his chest, at a position half way between the notch between the collar-bones at the top of his chest, and the dip i n the breast-bone at the base of his rib cage. Place the other hand on top of the first.
2 Keeping the arms straight and using your
entire weight, press down rapidly so that the breast bone is depressed four- five cm, then release the pressure. Repeat rhythmically at a rate of one cycle per second. This will be hard work, but keep going. His life depends on YOU. Do not worry about breaking his ribs - these will heal if he survives.
Page 10
Simrad SD570
II
851-160085 / B
Artificial respiration
1 Kneel besides the victim’s head. Place one
hand under his neck and lift, allowing his head to fall back. This will lift his tongue and open the air passage in his throat.
2 Place the palm of the hand on his forehead
to maintain the ”chin-up” position.
3 Using the index finger and thumb of the
same hand, pinch the victim’s nostrils closed. Open his mouth.
4 Take a deep breath and cover his mouth
with yours. Blow steadily into his lungs to expand his chest. Remove your mouth from his to allow the air t o escape from his chest. You should be able to see his chest deflate.
5 Repeat the ”inflation-deflation” cycle at a
rate of about 12 cycles per minute till the victim begins to breath normally again.
Combining ECM and artificial respiration
If you are alone, perform one cycle of artificial respiration for every five cycles of ECM. This will be hard work, but keep going. His life depends on you!
If there are other people available to help, one should perform the ECM while one performs the artificial respiration for every five cycles of ECM. It will be much more efficient with two people.
Once the victim’s heart is beating and he is breathing, roll him onto his side and support him in that position. As consciousness returns he may vomit, and this will allow any liquid to drain out of his mouth.
Remove the victim to a hospital as soon as possible, but do not interrupt the artificial respiration and ECM cycles till his heart beat and breathing returns.
If started quickly and performed correctly, the resuscitation methods described will keep a sufficient volume of oxygenated blood flowing trough the victims body to allow full recovery.
Proficiency i n the resuscitation methods can only be achieved trough training. All personnel concerned should attend courses on a regular basis. Remember, someone’s life could depend on you.
Do you know what to do?
Page 11
Introduction
I
851--160115 / B
851- 160115 / AA000 / 3- 11
Introduction
This section gives a brief description of the SD 570 / SE 570 sonars and the installation requirements.
Page 12
Simrad SD570 / Base version
II
851--160115 / B
Document revisions
Rev Date Written by Checked by Approved by
A Unknown
B 03.01.01 RBr ESB RBr
C
D
(The original signatures are recorded in the company’s logistic database)
Page 13
Introduction
III
851--160115 / B
Table of contents
1 INSTALLATION DOCUMENT 1..................................
2 SUPPLY CONDITIONS 2.......................................
2.1 General 2.....................................................
2.2 Main units 2..................................................
2.3 Options 2.....................................................
2.4 Installation procedures 5.......................................
2.5 Equipment responsibility 5.....................................
2.6 Receipt, unpacking and storage 5................................
3 GENERAL REQUIREMENTS 7..................................
3.1 Responsibility and approbation 7................................
3.2 Compass deviation 7...........................................
3.3 Noise sources 7...............................................
3.4 Docking 7....................................................
3.5 Cabling 7.....................................................
3.6 Auxiliary equipment 8.........................................
3.7 Technical specifications 9.......................................
3.8 Weights and dimensions 10......................................
Page 14
Simrad SD570 / Base version
IV
851--160115 / B
Document history
(The information on this page is for internal use)
Rev.A Original issue for Base version.
Rev.B Document transferred to Interleaf. No changes made to text or illustra-
tions.
Page 15
Introduction
1
851--160115 / B
1 INSTALLATION DOCUMENT
This installation manual will act as an installation document for later updating and service on the sonar, and must therefore be stored on board the vessel into which the equipment is to be installed.
To ensure the best possible result of the installation, it is important that each procedure is carefully followed. Each listed procedure comprises squares for t icking off while proceeding in the procedure. In addition to be a sign that the procedure is followed, this will also be a good guidance for the installer.
Note that the installer becomes fully responsible for the equipment during the installation, and that the guarantee only is covered when the installation is made in full accordance with this installation manual.
Page 16
Simrad SD570 / Base version
2
851--160115 / B
2 SUPPLY CONDITIONS
2.1 General
This manual describes the installation for both the SD 570 and the SE 570 sonars. The only difference between these sonars is the angle to which the transducer can be tilted. The SD 570 transducer can be tilted to - 90_, while the SE 570 transducer is limited to - 45_. All units for the SD 570 and SE 570 have the same physical size.
The Hull Unit uses an installation trunk which is equal to the old Simrad SL and SX installation trunks. The Hull Unit can therefore easily be mounted in an old SL or SX trunk. As an option, an adapter flange can be delivered for mounting the Hull Unit in an old SK, SB or SQ trunk. Note that the trunk is not included in the standard delivery, but can be ordered as an option (see chapter 2.3
Options ).
2.2 Main units
The standard SD 570 Sonar system comprises the following main units:
Simrad SD 570 Sonar Control Unit SD5- 112629..............
Simrad SD 570 Transceiver Unit SD5- 112630................
Simrad SD 570 Hull Unit SD5- 112631.......................
The standard SE 570 Sonar system comprises the following main units:
Simrad SE 570 Sonar Control Unit SE5- 112898...............
Simrad SE 570 Transceiver Unit SE5- 112899.................
Simrad SE 570 Hull Unit SE5- 112900.......................
A diagram of the standard sonar system is shown in figure 1.
2.3 Options
The installation trunk can be made by the shipyard (refer to drawing in section “Trunksystems” ) or be ordered as an optional delivery:
Installation trunk with blind cover SD5- 112632..............
For installations in an existing SK, SB or SQ trunk, refer to the drawings in the section Trunk systems in this manual. The following adapters with blind covers can be ordered as options:
SQ4 Adapter flange SD5- 112641...........................
Page 17
Introduction
3
851--160115 / B
SQ & SB2 Adapter flange SD5- 112642......................
SK3 Adapter flange SD5- 112643...........................
The cable between the Sonar Control Unit in the wheelhouse and the Transceiver Unit in the sonar room (see figure 1) can be delivered with the following lengths:
50- meter interconnection cable 380- 112595..................
75- meter interconnection cable 380- 112596..................
100- meter interconnection cable 380- 112597.................
The interconnection cable has a preconnected connector at the Sonar Control Unit end.
A system for electronic stabilization of the transducer may be delivered as an option. If the stabilization system is ordered, the kit is included in the box for the Sonar Control Unit.
Stabilization system KIT- 113200...........................
Page 18
Simrad SD570 / Base version
4
851--160115 / B
Figure 1 - SD 570 / SE 570 sonar system
Page 19
Introduction
5
851--160115 / B
2.4 Installation procedures
The installation of the standard SD 570 / SE 570 Sonar systems includes the following stages:
The installation of the standard SP 270 Sonar system includes the following stages:
Mounting the Installation Trunk
Mounting the Hull Unit
Mounting the Transceiver Unit
Mounting the Sonar Control Unit
Cabling
Start- Up
Final Test
Refer to the cable plan, the main interconnection diagrams and the outline dimensions drawings of the units.
2.5 Equipment responsibility
Upon receipt of the equipment, the installation shipyard and/or the dealer automatically becomes fully responsible for the equipment unless otherwise is stated in the contract. This responsibility covers the storage period before the installation, the actual installation, commissioning, and the period between the commissioning and the acceptance of the equipment by the end user (normally the owner of the vessel into which the equipment is to be installed).
The guarantee period for the system (as specified in the contract) begins as soon as acceptance documents have been signed, unless other arrangements have been made in the contract.
2.6 Receipt, unpacking and storage
On receiving the equipment, the shipyard and/or the dealer should ensure that the delivery is complete and inspect each container for physical damage. If the inspection at receipt reveals indication of crushing, dropping, immersion in water or any other form of damage, the recipient should request a representative from the carrier to be present during unpacking.
During unpacking, the equipment should be inspected for physical damage, i.e. broken controls and indicators, dents, scratches etc.
If damage to the equipment is discovered, the recipient should notify the carrier and Simrad so that Simrad can arrange for replacement or repair of the damaged equipment.
Page 20
Simrad SD570 / Base version
6
851--160115 / B
The equipment, once unpacked, must be stored inside in a room with an atmosphere free from corrosive agents. In addition, the equipment must be covered to protect it from dust and other forms of contamination.
Page 21
Introduction
7
851--160115 / B
3 GENERAL REQUIREMENTS
3.1 Responsibility and approbation
The Hull Unit of the sonar is generally approved by The Norwegian Veritas (Organization for classification and registry of shipping). An approval of the installation must, however, be applied for in each case to the local maritime authority.
The ship owner and the shipyard are responsible for the application.
3.2 Compass deviation
When the installation is finished, the compass must be checked both with the sonar operative and inoperative. The ship owner and the skipper are responsible for such a check to be carried out.
3.3 Noise sources
Prior to installation, the vessel’s h ull should be thoroughly inspected in dock. Roughness on the shell plating surface, and protruding obstacles are examples of noise-causing elements. These must be smoothed or removed. Also ensure that the propeller is not chipped or corroded.
3.4 Docking
When dry docking the vessel, make sure that there is enough room underneath for installation of the sonar trunk and protection blister (refer to figures 4 and 5 in section Installation procedures .
3.5 Cabling
If the cable from the wheelhouse to the sonar room passes through hatches or places where it may be damaged, it should be run through a pipe. Note that the cable must not be installed together with high-power cables, antenna cables etc.
Page 22
Simrad SD570 / Base version
8
851--160115 / B
3.6 Auxiliary equipment
The SD 570/SE 570 sonars require connection of a speed log and a course gyro. An inaccurate log or gyro input will cause inaccurate indication of the vessel and target movements.
Speed
log:
Pulse log: 100, 200 or 400 pulses/nm.
Serial line, standard NMEA 0183; RS232, RS422 or Current
loop.
Course gyr
o:
3- phase synchro signal, 20-220V L- L, 50/60/400 Hz. Gear ratio 1:360, 1:180, 1:90, 1:36
3- phase stepper signal, 20- 220V L- L. Gear ratio 1:360, 1:180, 1:90, 1:36.
Serial line, standard NMEA 0183; RS232, RS422 or Current loop.
Echo
sounder:
In order to get a depth indication on the catch control page on the sonar, one of the following Simrad echo sounders can be connected:
EQ50, EQ55, EQ100, ES60, ES380 series, ES500 (RS232 serial line).
Traw l
system:
In order to get the trawl information on the sonar display, one of the following Simrad trawl systems can be connected:
FS 903 Trawl sonar system (RS232 serial line)
FS 3300 Trawl sonar (RS232 serial line or 20 mA current loop)
ITI Integrated trawl instrumentation (RS232 serial line)
Page 23
Introduction
9
851--160115 / B
3.7 Technical specifications
Table 1 comprises the specifications required for the installation. For further details, refer to the Operator Manual.
Sonar Control Unit
Transceiver Unit Hull Unit
Voltage, nominal 115/230VAC
Single phase*
115/230 VAC Single phase**
230/380/440 VAC 3--phase***
Voltage deviation ±15% of nominal ±15% of nominal 230V:±15%
380/440V: 340 -- 485V
Voltage transient ±20% of nominal
recovery time 3s
±20% of nominal recovery time 3s
±20% of nominal recovery time 3s
Power consump­tion
100 VA 500 VA 600 VA max.
Frequency 47 -- 63 Hz 47 -- 63 Hz 47 -- 63 Hz
Tem p .: S tor age
Operating
-- 4 0 t o + 7 0 °C 0to+40°C
-- 4 0 t o + 7 0 °C 0to+40°C
-- 2 0 t o + 7 0 °C 0to+40°C
Humidity 5--95% relative
non--condensing
5--95% relative non--condensing
5--96% relative non--condensing
Table 1 Technical specifications for the SD 570 / SE 570 sonars
Refer to the voltage, nominal line in table 1.
* Input voltage is automatically selected.
** Input voltage is selected with two switches.
*** Input voltage is selected on the motor connections
Page 24
Simrad SD570 / Base version
10
851--160115 / B
3.8 Weights and dimensions
Weight SD 570 Weight SE 570 Dimensions
Sonar Control Unit
28 kg 28 kg Seefigure2
Transceiver Unit 75 kg 70 kg Seefigure3
Hull Unit 275 kg 265 kg Seefigure4
Trunk (optional) 68 kg 68 kg Seefigure5
Table 2 Weights of the SD 570 and SE 570 sonars SP 270 sonar
The figures 2, 3, 4 and 5 show the outline dimensions of the SD 570 / SE 570 units.
Page 25
Introduction
11
851--160115 / B
Figure 2 - Outline dimensions of the Sonar Control Unit
Page 26
Simrad SD570 / Base version
12
851--160115 / B
Figure 3 - Outline dimensions of the Transceiver Unit
Page 27
Introduction
13
851--160115 / B
Figure 4 - Outline dimensions of the Hull Unit
Page 28
Simrad SD570 / Base version
14
851--160115 / B
Figure 5 - Outline dimensions of the optional trunk
Page 29
Introduction
I
851--160116 / B
851- 160116 / AA000 / 3 - 11
Installation procedures
This section provides the necessary information for the installation and cabling of the complete SD 570/ SE 570 sonar systems according to Simrad’s requirements.
Page 30
Simrad SD570 / Base version
II
851--160116 / B
Document revisions
Rev Date Written by Checked by Approved by
A Unknown
B 03.01.01 RBr ESB RBr
C
D
(The original signatures are recorded in the company’s logistic database)
Page 31
Introduction
III
851--160116 / B
Table of contents
1 INSTALLATION PLANNING 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Location of the Hull Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Sonar room requirements 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 INSTALLATION OF THE SONAR TRUNK 5. . . . . . . . . . . . . . . . . . . . . . .
2.1 Mounting of the trunk 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Protecting blister 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Corrosion protection 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Trunk installation measurements 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 INSTALLATION OF THE HULL UNIT 9. . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Unpacking the Hull Unit 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Mounting the Hull Unit 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Staying 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Alignment of the transducer 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Installation checklist 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 INSTALLATION OF THE TRANSCEIVER UNIT 13. . . . . . . . . . . . . . . . . .
5 INSTALLATION OF THE SONAR CONTROL UNIT 16. . . . . . . . . . . . . .
5.1 Location of the Sonar Control Unit 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Mounting of the Sonar Control Unit 17. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Desk top mounting 17. .. . . . .. . . .. . . . .. . . .. . . . .. . . .. . . . .. . .
Panel mounting 18. . .. . . .. . . . .. . . .. . . . .. . . .. . . . .. . . .. . . . ..
Bulkhead mounting 18. .. . . .. . . . .. . . .. . . . . . . . .. . . . . . . . .. . .
6 CABLING 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Cable plan 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 The Sonar Control Unit cabling 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 The Transceiver Unit cabling 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 The Hull Unit cabling 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 CONNECTING AUXILIARY EQUIPMENT 28. . . . . . . . . . . . . . . . . . . . . . .
7.1 General 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Connecting the course gyro 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting a course gyro with synchro output 29. .. . . .. . . . ..
Connecting a course gyro with stepper output 33. .. . . .. . . . .. .
Connecting a course gyro with serial line output 36. .. . . .. . . .
7.3 Connecting the speed log 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the pulse log 39. . . . . . .. . . . . . . . .. . . .. . . . .. . . .. . .
Page 32
Simrad SD570 / Base version
IV
851--160116 / B
Connecting a speed log with serial line output 40. . . .. . . . .. . .
7.4 Connecting other auxiliary equipment 42. . . . . . . . . . . . . . . . . . . . . . . . . .
7.5 Remounting the electronic drawer unit 42. . . . . . . . . . . . . . . . . . . . . . . . .
Page 33
Introduction
V
851--160116 / B
Document history
(The information on this page is for internal use)
Rev.A Original issue for Base version.
Rev.B Document transferred to Interleaf. No changes made to the text or
illustrations.
Page 34
Simrad SD570 / Base version
VI
851--160116 / B
Blank page
Page 35
Introduction
1
851--160116 / B
1 INSTALLATION PLANNING
Note ! For installation in an already installed trunk system, first read through
chapter 1.3 about the sonar room requirements. Then, for an already
installed SLor SX trunk system, continue to procedure 3 Installation
of the Hull Unit .
For installationin an already installed SK, SB or SQ trunk system, refer to section Trunk systems in this manual.
1.1 General
This chapter provides the necessary information for the ship
designer to plan and carry out the installation of the SD 570/SE 570 hull system according to Simrad’s requirements. Study this
chapter thoroughly to achieve the recommended knowledge of the procedures.
Note that individual installation drawings must be designed by the shipyard, and the construction must be approved by the classification authorities at the customer’s expense.
Simrad offers free advice for installation planning. The proposal for the arrangement may be sent to Simrad for comments, or may be worked out by Simrad. If such assistance is required, the following drawings should be submitted:
· General arrangement
· Body plan and drawings of bottom tanks and cofferdam
· Sheer drawing
1.2 Location of the Hull Unit
The Hull Unit should preferably be located within 1/10 to 1/3 of the ship’s length between perpendiculars (LBP), measured from the fore perpendicular (FP). Refer to figure 1. Larger deviations from this rule should not be made without consulting Simrad.
The Hull Unit may be located symmetrically on the centre line of the vessel, or alongside the keel. When determining the exact location, make sure that the transducer will have free view under the keel (refer to figure 1).
The Hull Unit trunk must be installed such that it will be vertical under normal operating conditions.
Water inlets and protruding details which create turbulence, should not be located in front of the transducer. For the same reason, check that the shell plating in front of the trunk is not damaged.
Page 36
Simrad SD570 / Base version
2
851--160116 / B
Figure 1 - Location of the Hull Unit
1.3 Sonar room requirements
The sonar room should be dimensioned to house the Hull Unit and the Transceiver Unit.This becausethe lengthof the flexi-hose protected cabling from the Hull Unit to the Transceiver Unit is
limited to approximately 3.5 meters.
By installing the units in a well designed sonar room, the risk of corrosion is reduced, the maintenance is simplified, and the reliability is increased.
A suggested arrangement of the sonar room is shownin figure 2. The free space should not be obstructed by girders or pipes etc., which might cause problems forthe installationand maintenance work.
Access hatches
The sonar room must be accessible under all conditions, and the doors or hatches should be so designed that the installed units can be removed without being disassembled. A tackle carrier designed for a load of a minimum of 2 tons should be mounted above the Hull Unit. The tackle may be used to facilitate the mounting of the trunk and Hull Unit, and is alsointended for use in future service of the Hull Unit.
Heating
The sonar room should be furnished with a heating element of 1000 W, mounted close to the floor.
Insulation
The bulkhead must be insulated and plateddown to thefloor.The insulation should equal a minimum of 50 mm of rock- wool.
Page 37
Introduction
3
851--160116 / B
Ventilation
The sonar room should preferably be connected to the ship’s ventilation system. If this is not possible, two 3-inch vent pipes must be laid from the sonar room to free air on deck. The air inlet should be close to the floor, while the outlet should be placed as high aspossible. Funnelsshould bemounted belowthe vent pipes to collect condensed water.
To ensure the best possible ventilation, the outlet pipe should run at least 4meters higher than the inletpipe. To keep rain and water splash out, the pipes should be fitted with goosenecks or cowls.
Cable pipes
If the cable between the wheelhouse and the sonar room passes through hatches or places where it can be damaged, it should be run through pipes (2” pipes are recommended).
Bilge pump
The sonar room should be connected to the ship’s main bilge pump system.If this is not possible, a separatebilge pump for the sonar room must be installed.
Lighting
To simplify the installation and future maintenance, the sonar room should be equipped with suitable lighting.
Docking
Make sure that there is ample space below the keel for mounting the hull system, when docking the vessel.
To facilitate future docking, mark the position of the trunk as indicated in figure 1
Flooring
When the installation is completed, the sonar room should be suitably floored.
Page 38
Figure 2 - Example of sonar room arrangement,
seen from the bow
Simrad SD570 / Base version
4
851--160116 / B
Page 39
Introduction
5
851--160116 / B
2 INSTALLATION OF THE SONAR TRUNK
2.1 Mounting of the trunk
The location of the sonar trunk has to be carefully selected, as described in chapter 1.2. Refer also to figures 4 and 5.
Note the orientation of the centre line of the trunk with regard to the mounting bolts, shown in figure 3.
Note ! Remove the gasket on the top flange during the welding.
Figure 3 - Orientation of the sonar
trunk
The height from the topof the trunk flange to the underside of the
protection blister must be minimum 920 mm (361/4”) as shown
in figures 4 and 5.
The top flange must be parallel tothe construction loadline in the fore- and- aft as well as the athwartships direction.
The installation trunk must be welded to an inserted plate which should be 1.5 timesas thick asthe originalshell plate.The sizemay be determined by the shipyard or the responsible maritime authorities. The trunk must be stiffened to the inserted plate by welding knee-plates on the trunk in both fore-and- aft and athwartships directions.
Page 40
Simrad SD570 / Base version
6
851--160116 / B
2.2 Protecting blister
As illustrated in figures 4 and 5, a steel blister must be fitted for protection. The blister shown in figure 4 is welded to the shell plating and then filled with oil to prevent corrosion. This method provides excellent protection and simplifies maintenance. The blister shown in figure 5 is of the open type, to be welded to the shell plating.
2.3 Corrosion protection
As soon as the trunk is mounted, and welding and grinding are finished, the trunk should be painted with a quality protective paint.
2.4 Trunk installation measurements
For future use, the measurements of the distance A, and the heights B and Cshown in figures4 and5 haveto becarried outand put into the table on the next page.
mm inches Distance A Height B Height C
In case of an other installation solution, make a scheme with dimensions below.
Page 41
Introduction
7
851--160116 / B
Figure 4 - Installation of trunk with extension
and oil- filled blister
Page 42
Simrad SD570 / Base version
8
851--160116 / B
Figure 5 - Installation of the trunk with open
protection blister. No trunk extension.
Page 43
Introduction
9
851--160116 / B
3 INSTALLATION OF THE HULL UNIT
3.1 Unpacking the Hull Unit
In order to prevent damage of the transducer and the transducer cables while handling the Hull Unit, these parts are especially protected. This means thatboth the transducer protection and the cable protection should still be mounted to the Hull Unit when it is being lowered down into the sonar room (see figure 6).
Figure 6 - Lifting the Hull Unit
Page 44
Simrad SD570 / Base version
10
851--160116 / B
j WhenunpackingtheHullUnit, first removethetopcover
fromthe woodenbox,then pulloutthe nailsmarkedwith Indianink. Fasten thelifting deviceto the twolifting eye bolts onthe top of the gallows andlift the Hull Unit with the protections carefully out from the transport box.
3.2 Mounting the Hull Unit
The Hull Unit should normally be oriented with the
hoisting/lowering motor pointing aft (see figure 7). If this
orientation makes the motor control unit onthe HullUnit difficult to access, the Hull Unit may be oriented in the most suitable position.
Note ! The motor control unit should never be dismounted from the Hull Unit
(see text above).
j Use a tackle to lower the Hull Unit with the protections
downintothe sonarroom(seefigure 6).Removethe blind cover from the trunk, and check that the gasket is not damaged. Store the blind cover in the sonar room for possible future use.
Figure 7 - Recommended orientation of the Hull Unit
j Removethetransportprotectionfromthetransducerand
lower the Hull Unit carefully down into the trunk. Tightenthe flange nuts witha torque ofapproximately 6 kpm.
Page 45
Introduction
11
851--160116 / B
j Remove the cable protection box. The transducer cables
andconnectorshave tobekeptdry andhandledwithcare to avoid mechanical damage.
3.3 Staying
The Hull Unit is constructed to be in the lower position with a maximum speed of 15 knots.Toprevent unwanted vibrations, the Hull Unit has to be stayed off against the bulkhead. Remove the lifting rings onthe top of the gallows on the Hull Unitand use the holes for fastening of the staying in the fore- and- aft direction. In case of serviceon the Hull Unit,it should be possibleto removethe staying.
3.4 Alignment of the transducer
Note that the transducer should not be mechanically aligned even if the Hull Unit is oriented differently from figure 7.
The transducer alignment will be carried out later by turning the echo picture in the computer.
Page 46
Simrad SD570 / Base version
12
851--160116 / B
3.5 Installation checklist
For the following check list, refer to the sonar room requirements in chapter 1.3.
INSTALLATION CHECKLIST YES NO Are the access hatches satisfactory? Is the heating satisfactory? Is the insulation satisfactory? Is the ventilation satisfactory? Are the access hatches satisfactory? Is a bilge pump installed? Is the lighting satisfactory? Is the sonar room suitably floored?
If the answer to any of the questions is NO, make a note in the installation certificate at the end of section Start-up procedures.
Page 47
Introduction
13
851--160116 / B
4 INSTALLATION OF THE TRANSCEIVER UNIT
Note ! The Transceiver Unit must be mounted as a complete unit, i.e. the door
should not be opened until the unit is securely fastened to the bulkhead.
Before starting the mounting of the Transceiver Unit, note that the distance between the HullUnit and the Transceiver Unitis limited because of the flexible transducer cables. Also remember to take into consideration the necessary slack for lowering of the transducer.
Do not fasten the transducer cables into the Transceiver Unit before mentioned later in the start- up procedure.
The Transceiver Unit cabinet requires a minimum free bulkhead space, which is shown in figure 8.
j Dismountthe twomounting bracketswhich arefastened
to theshock absorbers on theTransceiverUnit. An Allen key is located in the plastic bag which is fastened to the upper shock absorber.
j Weld the mounting brackets safely to the bulkhead as
shown in figure 8.
j Use a tackle carrier to lift the Transceiver Unit in
position, and bolt it to the mounting brackets with the boltsincluded inthe delivery. These8 boltsare locatedin the plastic bag that was fastened to the upper shock absorber. Remember to fasten the grounding cable from the Transceiver Unit to the mounting bracket as shown in figure 9.
Page 48
Simrad SD570 / Base version
14
851--160116 / B
Figure 8 - Mounting the brackets for the
Transceiver Unit
Page 49
Introduction
15
851--160116 / B
Figure 9 - Mounting the Transceiver Unit
Page 50
Simrad SD570 / Base version
16
851--160116 / B
5 INSTALLATION OF THE SONAR CONTROL
UNIT
5.1 Location of the Sonar Control Unit
The Sonar Control Unit may bemounted on a desk top, ina panel, or to the bulkhead. The necessary hardware for desk top and panel mounting of the unit is included inthe delivery.It shouldbe noted that the unit weighs approximately 28 kg, and this weight must be considered when deciding how to mount it.
In order to secure the best location according to the routines on board, the location of the Sonar Control Unit should be thoroughly discussed with the skipper. Make sure that proper operating and viewing height is provided.
Remember to include the ”Compass Safe Distance” when planning the location:
· Sonar Control Unit with internal display
Standard compass: 1.4 m Steering compass: 0.9 m
· Control Unit without display:
Standard compass: 1.1 m Steering compass: 0.6 m
When mounting the unit, ensure that it is located to allow easy access to the cable connection panel at the rear of the unit.
Ensure that the installation area is dry, and free from excessive dust and vibration.
Page 51
Introduction
17
851--160116 / B
5.2 Mounting of the Sonar Control Unit
Desk top mounting
Refer to figure 10 for minimum space for the desk top mounting of the cabinet.
j Dismount the mounting bracket from the Sonar Control
Unit by unscrewing the four bolts on the front. An Allen key is located in the spare parts box.
j Bolt the mounting bracket securely to the desk top with
the four 10x30mm bolts which are located in the spare parts box.
j Mountthe cabineton themounting bracketwith thefour
bolts.
Figure 10 - Desk top mounting
Page 52
Simrad SD570 / Base version
18
851--160116 / B
Panel mounting
j Dismount the mounting bracket from the Sonar Control
Unit by unscrewing the four bolts on the front. An Allen key is located in the spare parts box.
j Cut the panel opening to the following size:
Width: 345 mm
Height: 380 mm
j Place the cabinet into the opening to mark the four
fastening holes.
j Remove the cabinet and drill the four fastening holes in
the panel.
Metal panel: Drill 5mm holes for threading with M6 tap, or 7mm holes if through- bolts with nuts are preferred.
Wooden panel: Drill 9mm holes for the four thread inserts which are located in the spare parts box. Refer to figure 11 for information about mounting the thread inserts.
Figure 11 - Mounting the thread inserts
j Place the cabinet into the opening and fasten it with the
four bolts.
Bulkhead mounting
To obtain the best operation position of the cabinet, the cabinet should be mounted with a tilt angle of approximately 20 . An optional mounting bracket can be delivered from Simrad.
j Dismount the mounting bracket from the Sonar Control
Unit by unscrewing the four bolts on the front. An Allen key is located in the spare parts box.
Page 53
Introduction
19
851--160116 / B
j Bolt the bulkhead mounting bracket securely to the
bulkhead.
j Mountthe cabineton themounting bracketwith thefour
bolts.
Page 54
Simrad SD570 / Base version
20
851--160116 / B
6 CABLING
6.1 Cable plan
Figure 12 shows the cable plan for the SD 570 and SE 570 sonars. The cable numbers also refer to the interconnection diagram, drawing no. 824- 112979. This drawing is located in section
Drawings in thismanual. The cable specifications arelisted in the
table below.
Note that cable no. 4 is delivered with a standard length of 50 meters, and has a preconnected plug in the Sonar Control Unit (wheelhouse) end. Thiscable is includedin the Sonar ControlUnit package. As an option, cable no. 4 can be delivered in lengths of 75 or 100 meters.
Note that the length of the flexible transducer cables 7 and 8 is fixed to approximately 3.5 meters.
Cable no. Cable type Cable dia (mm) 1 Screened cable, 2x0.5 mm
2
6
2 RCOP 5x1 mm
2
12 3,5 Mains cable, length 2 m 7 4,6 Data cable 8x(2+1)x0.5 mm
2
14 7,8 Flexi--cable, 3.5 m fixed length. Mounted
to Hull Unit
62
9
RCCP/750V 4x2.5 mm@
17
Page 55
Introduction
21
851--160116 / B
Figure 12 - Cable plan for the SD 570 / SE 570 sonars
Page 56
Simrad SD570 / Base version
22
851--160116 / B
6.2 The Sonar Control Unit cabling
All the cables to the Sonar Control Unit are to be plug connected to the electronic drawer unit at the rear of the cabinet (see figure
13). The numbers on the figure refer to the cable numbers on the cable plan.
Note ! In order to make service onthe Sonar Control Unit,the cables must have
a slack so the electronic drawer unit can have all the cables connected while it is outside the cabinet. This couldbe either by pulling it out from the front, or by reconnecting the cables with the drawer at floor level.
Note that cable no. 4 (refer to figure 12) is delivered with a standard length of 50 meters, and has a preconnected plug in the Sonar Control Unit (wheelhouse) end.
j Pull cable no. 4 from the wheelhouse to the sonar room.
Note that the preconnected plug should be connected to the Sonar Control Unit in the wheelhouse. Remember to include the slack for service purpose.
j The mains power cable (3) may be connected to a normal
mains outlet in the wheelhouse. If the delivered cable does not fit, put on a suitable connector. Note that the mainspower totheSonar ControlUnit can be115VAC or 230 VAC, and that this unit will automatically sense the voltage.
The connection of the speed log (1) and the course gyro (2) will be described in chapter 7.
Page 57
Introduction
23
851--160116 / B
Figure 13 - Cable connections to the Sonar Control Unit
Page 58
Simrad SD570 / Base version
24
851--160116 / B
6.3 The Transceiver Unit cabling
The cable numbers on figure 14 and in the following procedures refer to the numbers on the cable plan and the interconnection diagram.
Figure 14 - The cable connection in the bottom of the Transceiver
Unit
j All cable connections to the TransceiverUnit must have
aslack to allowthe TransceiverUnit to move up to10 cm because of the flexible shock mounting.
j Start the termination with cable no. 6. This because this
cable is connected to the lowest row of the terminals on E201. Use the surplus of cable no. 4, or a similar type of cable. Use the cable gland on the left hand side (refer to figure 14) and terminate the main screen of the cable as shown in figure 15. For termination of each cable pair with screen, refer to the interconnection diagram. Use a part of the enclosed cable sleeve on the screen of each cable pair.
Page 59
Introduction
25
851--160116 / B
Figure 15 - Termination of the cable main screen
j Continue with cable no. 4 throughthe cable gland on the
righthand side (seefigure 14) andmake the termination of the main screen according to figure 15. Make the connections to terminal E201 according to the interconnection diagram.
Note that themains power connection to the Transceiver Unit can be 115 VAC or 230 VAC. Use the following procedure for the connection of the mains power:
j Pull out the mains input connector P201 on the power
supply in the Transceiver Unit. For location of the connector, refer to figure 16.
j Set the mains voltage selector switch S201 on the Power
Supply and S203 on the HV Power Unit to correspond to thecorrect mainsvoltage(115Vor230V), andreplace the switch lock to secure the switch in the correct position.
j Set the service switch S202 on the Power Supply to OFF
(middle) position.
Page 60
Simrad SD570 / Base version
26
851--160116 / B
Figure 16 - The Power Supply and the HV Power Unit
j The mains power cable (3) may be connected to a normal
mains outlet in the sonar room. If the delivered cable connector does not fit, put on a suitable connector.
j Do not mount the flexible transducer cables to the
T ransceiver Unit.
Page 61
Introduction
27
851--160116 / B
6.4 The Hull Unit cabling
Connection of cable no. 6 in the motor control unit:
j Usethe cableglandonthe right--handside,and makethe
termination of the main screen according to figure 15.
j Makea slackon thecableinside themotorcontrol unitas
shown on figure 17, and make the connections to the terminalE301 accordingtothe interconnectiondiagram.
Connection of cable no. 9 in the motor control unit:
j Use the cable gland on the left--hand side, and make the
termination of the cable screen in the cable gland.
j Make the connections of the three--phase mains power
directly to the motor overload switch S303 according to theinterconnection diagram. Thegrounding wireshould be connected to the ground terminal beside the overload switch.
Figure 17 - Connections to the Hull Unit
Page 62
Simrad SD570 / Base version
28
851--160116 / B
7 CONNECTING AUXILIARY EQUIPMENT
7.1 General
It is not necessary to make the connection of the auxiliary equipment before the start-up procedure is finished, and this equipment may therefore be connected later. Anyhow, do not connect the plugs for the auxiliary equipment to the Sonar Control Unit before mentioned in a later chapter.
The SD 570 / SE 570 sonars require connection of a speed log and a course gyro. An inaccurate log or gyro input will cause inaccurate indication of the vessel and target movements.
Speed log:
· Pulse log: 100, 200 or 400 pulses/nm.
· Serial line, standard NMEA 0183; RS232, RS422 or Current
loop.
Course gyro:
· 3- phase synchro signal, 20- 220V L- L, 50/60/400Hz.
· Gear ratio 1:360, 1:180, 1:90, 1:36.
· 3- phase stepper signal, 20-220V L- L.
Gear ratio 1:360, 1:180, 1:90, 1:36.
· Serial line, standard NMEA 0183; RS232, RS422 or Current
loop.
Echo sounder:
In order to get a depth indication on the catch control page on the sonar, one of the following Simrad echo sounders can be connected:
· EQ50, EQ55, EQ100, ES60, ES380 series, ES500 (RS232 serial
line).
Trawl system:
In order to get the trawl information on the sonar display, one of the following Simrad trawl systems can be connected:
· FS Trawl sonar (RS 232 serial line or 20mA current loop).
· ITI Integrated Trawl Instrumentation (RS232 serial line).
Page 63
Introduction
29
851--160116 / B
7.2 Connecting the course gyro
The Sonar Control Unit can be connected to a course gyro with one of the following outputs (tick off for the type which will be connected):
j 3--phase synchro signal See chapter 7.2.1 j 3--phase stepper signal See chapter 7.2.2 j Serial line (NMEA 0183) See chapter 7.2.3
Connecting a course gyro with synchro output
j First, get the specifications of the gyro to fill in the
following data: SYNCHRO DATA SPECIFICATIONS LEGAL VALUES OUTPUT VOLTAGE 20 to 220 VAC FREQUENCY 50/60/400 Hz GEAR RATIO 1:360/1:180/1:90/1:36
If it is difficult to find the specifications for the gyro, the output voltage and frequency can be measured in the following way:
j The output voltage can be measured by an AC voltmeter
or by an oscilloscope on the reference output R1 & R2.
Notethat ifanoscilloscopeisused,thereferenceprobe on
the oscilloscope must not be connected to the mains
ground, and the measured peak to peak value of the
output voltage must be divided by 2 Ö2 to get the RMS
voltage.
j Fill the output voltage value into the table above. j The frequencycan be measured by an oscilloscope onthe
reference output R1 & R2. Note that the referenceprobe
on the oscilloscope must not be connected to the mains
ground.Calculate thefrequency1/T(T isthe timefor one
sine wave) and fill the result into the table above.
j If the gear ratio of the gyro output also is unknown, this
has to be tried out later when testing the readout of the
gyroon theSonarControlUnit. Insuch case,set thegear
ratio to 1:360.
When connecting the gyro cable to the 15 pin D-connector, note that each of the three phases S1, S2, S3 and the reference R1 has three different connection pins, marked L (Low), M (Medium) and H (High). These pins are used for different gyro output voltage values as indicated for the connections below:
Page 64
Simrad SD570 / Base version
30
851--160116 / B
Signal phase 1: S1-L (20- 70V) pin 2
S1- M (80- 140V) pin 9
S1- H (150- 220V) pin 1
Signal phase 2: S2-L (20- 70V) pin 11
S2- M (80- 140V) pin 3
S2- H (150- 220V) pin 10
Signal phase 3: S3-L (20- 70V) pin 5
S3- M (80- 140V) pin 12
S3- H (150- 220V) pin 4
Reference 1: R1- L (20- 70V) pin 14
R1- M (80- 140V) pin 6
R1- H (150-220V) pin 13
Reference 2: R2 pin 8
j Locate the 15 pin D--connector, the connector housing
and the shrink tube in the spare parts box. Refer to the
output voltage in the table for the synchro data, and
make the connections to the 15 pin D--connector with
reference to the pin--connection list above. Also refer to
figure 18, which shows the pin location of the connector
seenfromthewiresolderingside.Thecable screenshould
be connected to the connector housing.
Figure 18 - Connections for a gyro with
synchro output
In order to read the data from the gyro, some DIL switches on the printed circuit board in the electronic drawer unit behind the operator panel must be selected. Use the following procedure to set the switches:
Page 65
Introduction
31
851--160116 / B
j Set the switch S101 at the rear panel on the Sonar
Control Unit to OFF position. For location of the switch,
refer to figure 13.
j Disconnect allconnections tothe rear panelon the Sonar
Control Unit.
j Usethe 3mmAllenkeywhichislocatedin the spareparts
boxto unscrewthe fourscrewsonthefrontoftheoperator
panel, and pull the electronic drawer carefully out. Note
thetwocablesto thedisplayonthetopof thedrawerunit.
j Disconnect the two display cable plugs on the drawer
unit, and dismount the top cover of the drawer.
j Locate the DIL switch S2 (referto figure 19), and setthe
switches according to table.
DIL SWITCH S2
GYR
O
1 2 3 4 5 6 7 8
50/60 Hz OFF OFF OFF OFF OFF OFF OFF ON
1:360
400 Hz OFF OFF OFF OFF OFF OFF OFF OFF 50/60 Hz OFF OFF OFF ON OFF OFF OFF ON
SYN-
1:180
400 Hz OFF OFF OFF ON OFF OFF OFF OFF
CHR
O
50/60 Hz OFF OFF OFF OFF ON OFF OFF ON
1:9
0
400 Hz OFF OFF OFF OFF ON OFF OFF OFF 50/60 Hz OFF OFF OFF ON ON OFF OFF ON
1:3
6
400 Hz OFF OFF OFF ON ON OFF OFF OFF
Do not insert the electronic drawer unit until mentioned in a later chapter.
Page 66
Simrad SD570 / Base version
32
851--160116 / B
Figure 19 - The electronic drawer unit
Page 67
Introduction
33
851--160116 / B
Connecting a course gyro with stepper output
j First, get the specification of the gyro to fill in the
following data: STEPPER DATA SPECIFICATIONS LEGAL VALUES
OUTPUT VOLTAGE 20 to 220 VAC REF. POLARITY + REF. or -- REF GEAR RATIO 1:360/1:180/1:90/1:36
If it is difficult to find the specifications for the gyro, the output voltage and the referencepolarity canbe measuredby avoltmeter in the following way:
j Connect the positive probe from the voltmeter to the
stepper reference output, and the negative probe to one
of the three signal phases which have a signal output.
Note that one or two signalphases always should have a
signal output voltage.
j Fill the highest measured output voltage value into the
table above.
j When readingthe signal outputvoltage, note thevoltage
polarity. If it is positive,the reference polarity is positive
(+ REF), and if it is negative, the reference polarity is
negative (-- REF). Fill the result into the table above.
j If the gyro output is specified to 6 step/degree, this is
equal to a gear ratioof 1:360. If the gear ratioof the gyro
output is unknown, this has to be tried out later when
testing the readout from the gyro on the Sonar Control
Unit. In such case, set the gear ratio to 1:360.
j Note that for somesteppertypegyros,the outputvoltage
is only half--wave rectified. This has to be checked by an
oscilloscope and ticked off below
j Full--wave rectified.
j Half--wave rectified.
Page 68
Simrad SD570 / Base version
34
851--160116 / B
When connecting the gyro cable to the 15 pin D-connector, note that each of the three phases S1, S2, S3 has three different connection pins, marked L (Low), M (Medium) and H (High). These pins are used for different gyro output voltage values as indicated for the connections below:
Signal phase 1: S1-L (20- 70V) pin 2
S1- M (80- 140V) pin 9
S1- H (150- 220V) pin 1
Signal phase 2: S2-L (20- 70V) pin 11
S2- M (80- 140V) pin 3
S2- H (150- 220V) pin 10
Signal phase 3: S3-L (20- 70V) pin 5
S3- M (80- 140V) pin 12
S3- H (150- 220V) pin 4
Reference : +/- REF pin 7
-/+ REF(see note) pin 15
Note ! If the output voltage is only half-wave rectified, the other reference from
the gyro which is not used for the three phases must be connected to pin
15.
j Locate the 15 pin D--connector, the connector housing
and the shrink tube in the spare parts box. Refer to the
output voltage which was written into the table for the
stepperdata specifications,and make the connections to
the 15--pin D--connector with reference to the
pin--connection list above. Also refer to figure 20 which
showsthepinlocationofthe connectorseenfromthewire
soldering side. The cable screen should be connected to
the connector housing.
Figure 20 - Connections for a gyro with stepper output
Page 69
Introduction
35
851--160116 / B
In order to read the data from the gyro, some DIL switches on the printed circuit board in the electronic drawer unit behind the operator panel must be selected. Use the following procedure to set the switches:
j Set the switch S101 at the rear panel on the Sonar
Control Unit to OFF position. For location of the switch,
refer to figure 13.
j Disconnect allconnections tothe rear panelon the Sonar
Control Unit.
j Use the3mm Allenkey to unscrewthe fourscrewson the
frontoftheoperator panel,andpullthe electronicdrawer
carefullyout.Notethetwo cablestothedisplayonthe top
of the drawer unit.
j Disconnect the two display cable plugs on the drawer
unit, and dismount the top cover of the drawer.
j Refer to figure 19, and set the links LK19, LK20 and
LK21 to position A.
j Locate the DIL switch S2 (referto figure 19), and setthe
switches according to the table below.
DIL SWITCH S2
GYR
O
1 2 3 4 5 6 7 8
+ REF ON OFF OFF OFF OFF OFF OFF OFF
1:360
-- REF ON ON OFF OFF OFF OFF OFF OFF + REF ON OFF OFF ON OFF OFF OFF OFF
STEP-
1:180
-- REF ON ON OFF ON OFF OFF OFF OFF
PER
+ REF ON OFF OFF OFF ON OFF OFF OFF
1:9
0
-- REF ON ON OFF OFF ON OFF OFF OFF + REF ON OFF OFF ON ON OFF OFF OFF
1:3
6
-- REF ON ON OFF ON ON OFF OFF OFF
Do not insert the Control Unit drawer until mentioned in a later chapter.
Page 70
Simrad SD570 / Base version
36
851--160116 / B
Connecting a course gyro with serial line output
The Sonar ControlUnit can read the course gyro data (and/or the speed log data) from a serial line with on ofthe followingoutputs (tick off for the type which will be connected):
j RS232 Serial line j RS422 Serial line j 20mA current loop
The format of the serial line data is standard NMEA 0183, and the telegram can contain both the course and speed data (refer to the telegram format in the end of this chapter).
When connecting the 9-pin D- connector, note that each of the three types of serial lines has different connection pins:
RS232: Serial line signal PORT B pin-2
Signal reference PORT B pin- 5
RS422: RS422+ PORT B pin- 1
RS422$ PORT B pin- 4
20mA current loop: CLI+ PORT B pin- 6
CLI- PORT B pin-9
j Use a 9--pin D--connector, male type, for connecting the
serial line to port B on the Sonar Control Unit (this
connector is not included in the delivery). To make the
connections, refer to the pin connection list above, and
figure 21 which shows the pin location of the connector
seenfromthewiresolderingside.Thecable screenshould
be connected to the connector housing.
j In order to read the data from the gyro, some DIL
switches and links on the printed circuit board in the
electronicdrawerunitbehind theoperatorpanel mustbe
selected.Use the followingprocedureto set the switches:
j Set the switch S101 at the rear panel on the Sonar
Control Unit to OFF position. For location of the switch,
refer to figure 13.
j Disconnect allconnections tothe rear panelon the Sonar
Control Unit.
j Use the3mm Allenkey to unscrewthe fourscrewson the
frontoftheoperator panel,andpullthe electronicdrawer
carefullyout.Notethetwo cablestothedisplayonthe top
of the drawer unit.
Page 71
Introduction
37
851--160116 / B
Figure 21 - Connections for a gyro with
serial line output
j Disconnect the two display cable plugs on the drawer
unit, and dismount the top cover of the drawer.
j Locate the DIL switch S2 (referto figure 19), and setthe
switches according to the table on next page.
DIL SWITCH S2
GYR
O
1 2 3 4 5 6 7 8
SERIAL LINE OUTPUT OFF OFF OFF OFF OFF ON OFF OFF
Locate the links LK2, LK3 and LK6 on the Control Unit Board,
(see figure 19) and set the links according to the table below.
GYRO LINK SETTING
LK2 LK3 LK6 RS232 OUT IN OUT RS422 OUT OUT IN 20 mA current loop IN OUT OUT
Do not insert the Control Unit drawer until mentioned in a later chapter.
Page 72
Simrad SD570 / Base version
38
851--160116 / B
The serial line telegram format for the course and speed data:
$xxHDT,ggg.g,T<cr><1f> Heading, Degrees True
$xxHDM,ggg.g,M<cr><1f> Heading, Degrees Magnetic
$xxVGT,ggg.g,T,ggg.g,M,nn.n,N,kk.k,K<cr><1f> Actual track and ground speed
$xxVHW,ggg.g,T,ggg.g,M,nn.n,N,kk.k,K<cr><1f> Heading and water speed
xx is indicator for transmitter, for instance:
’HE’ = gyro, earth seeking
’GP’ = Precision Global Positioning System
Heading data:
ggg.g is heading in degrees.
The gyro value can have variable amounts of digits in front of comma (max. 3), and after comma (min. 0). Comma can also be omitted. Leading zeroes and spaces are accepted.
In the twolast telegrams, the ”True” valueis used ifboth true and magnetic values are transmitted.
Speed data:
nn.n is speed in Nautical miles
kk.k is speed in Kilometer per hour
The speed value should have min. 1, max. 2 digits in front of comma, and 1 after. Leading zeroes and spaces are accepted.
Page 73
Introduction
39
851--160116 / B
7.3 Connecting the speed log
The Sonar Control Unit can be connected to a speed log with one of the following outputs (tick off for the type which will be connected):
j Pulse log (100, 200 or 400 pulses per nautical mile) j Serial line (RS232, RS422 or 20mA current loop)
The connection of these different speed log outputs is described in the following chapters.
Connecting the pulse log
The Sonar Control Unit can be connected to a pulse log with one of the following outputs (tick off for the type which will be connected):
j 100 pulses per nautical mile j 200 pulses per nautical mile j 400 pulses per nautical mile
For anytype of log output (relay, open collector, or opto-coupler), the output must be free from other connections.
Figure 22 shows the connection of a pulse log with relay output. For connection of open collector, or opto- coupler outputs, be aware of the polarization (see figure 23).
j Locatethe9--pinD --connector,theconnectorhousingand
the shrink tube in the spare parts box, and make the plug--connections. The cable screen should be connected to the connector housing.
Figure 22 - Connections for a pulse log with
relay output
j Locate the DIL switch S1 on the Control Unit Board
(refer to figure 19), and set the switches according to the table below.
Page 74
Simrad SD570 / Base version
40
851--160116 / B
DIL SWITCH S1
SPEED
1 2 3 4 5 6 7 8
100 pulses per nautical mile
OFF OFF ON OFF OFF OFF OFF OFF
200 pulses per nautical mile
OFF OFF OFF ON OFF OFF OFF OFF
400 pulses per nautical mile
OFF OFF ON ON OFF OFF OFF OFF
Do not insert the Control drawer unit before mentioned in a later chapter.
Figure 23 shows the pulse log interface circuit on the ControlUnit Board.
Figure 23 - Pulse log interface
When the system is started up, an oscilloscope can be connected to the test point TP5 to check if the pulse log signal is coming through the comparator U45 (TP4 is GND). If the signal is not coming through the comparator, try to adjust the 10- turn potmeter R45. In case of noise problems, R45 can be adjusted for noise limitation .
Connecting a speed log with serial line output
The Sonar Control Unit can read the speed log data (and/or the course gyro data) from a serial line with on of the following outputs (tick off for the type which will be connected):
j RS232 serial line j RS422 serial line j 20mA current loop
The format of the serial line data is standard NMEA 0183, and the telegram can contain both the course and speed data (refer to the telegram format in the end of chapter 7.2.3).
Page 75
Introduction
41
851--160116 / B
When connecting the 9-pin D- connector, note that each of the three types of serial lines has different connection pins:
RS232: Serial line signal PORT B pin-2
Signal reference PORT B pin- 5
RS422: RS422+ PORT B pin- 1
RS422- PORT B pin- 4
20mA current loop: CLI+ PORT B pin- 6
CLI- PORT B pin- 9
j Use a 9--pin D--connector, male type, for connecting the
serial line to port B on the Sonar Control Unit (this connector is not included in the delivery). To make the connections, refer to the pin connection list above, and figure 24 which shows the pin location of the connector seenfromthewiresolderingside.Thecable screenshould be connected to the connector housing.
Figure 24 - Connections for a speed log with
serial line output
j Locate the DIL switch S1 on the Control Unit Board
(refer to figure 19), and set the switches according to the table below.
DIL SWITCH S1
SPEED
1 2 3 4 5 6 7 8
SERIAL LINE OUTPUT OFF OFF OFF ON ON OFF OFF OFF
j Locate the links LK2, LK3 and LK6 on the Control Unit
Board, (see figure 19) and set the links according to the table below.
Page 76
Simrad SD570 / Base version
42
851--160116 / B
SPEED LINK SETTING
LK2 LK3 LK6 RS232 OUT IN OUT RS422 OUT OUT IN 20 mA current loop IN OUT OUT
Do not insert the Control drawer unit before mentioned in a later chapter.
7.4 Connecting other auxiliary equipment
If any other optional equipment is to be connected (echo sounderortrawlsystem),refertotheappendixesin thismanual.
7.5 Remounting the electronic drawer unit
When the DIL switches and link settings for all auxiliary equipment are correct, use the following procedure to remount the electronic drawer unit:
j Remount the top cover on the drawer unit. j Reconnect the two display cables.
j Lock the two display cables in the cable locker, and
arrange the cables as shown in figure 25. Enter the drawer unit carefully into the cabinet, and check the cables while entering the drawer. Note that the two guiding pins at the inside of the rear wall in the cabinet should enter the two guiding holes at the rear of the drawer unit.
j Fasten the electronic drawer unit with the four 3mm
Allen screws on the front of the operator panel.
Page 77
Introduction
43
851--160116 / B
Figure 25 - Mounting the electronic drawer
unit
Page 78
Simrad SD570 / Base version
44
851--160116 / B
Blank page
Page 79
Introduction
I
851--160117 / B
851- 160117 / AA000 / 3 - 11
Start- up procedures
This section contains the start- up procedures to be carried out after installation of the SD570/SE570 sonar.
Page 80
Simrad SD570 / Base version
II
851--160117 / B
Document revisions
Rev Date Written by Checked by Approved by
A Unknown
B 03.01.01 RBR ESB RBR
C
D
(The original signatures are recorded in the company’s logistic database)
Page 81
Introduction
III
851--160117 / B
Table of contents
1 PREPARING THE START--UP 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Before start- up check list 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Starting up the stand- by power supply 2. . . . . . . . . . . . . . . . . . . . . . . . .
2 THE HULL UNIT 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Starting up the Hull Unit 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Adjusting the middle position switch 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
3 THE SONAR CONTROL UNIT 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Starting up the sonar control unit 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Checking the control panel 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 CHECKING THE HOISTING/LOWERING SYSTEM 17. . . . . . . . . . . . . . .
4.1 Checking the bridge functions 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Checking the sonar room functions 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 THE TRANSCEIVER UNIT 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Starting up the Transceiver Unit 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Self- noise test 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Connecting the transducer 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 SYSTEM START--UP 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Air- bleeding of the sonar trunk 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Preparing the system start- up 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Starting up the transmitter 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions on the sonar control unit 27. .. . . .. . . . .. . . .. . . . . . . . .
Actions on the Transceiver Unit 29. . .. . . .. . . . .. . . .. . . . .. . . .
6.4 Alignment of the sonar picture 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 TESTING THE AUXILIARY EQUIPMENT 32. . . . . . . . . . . . . . . . . . . . . . .
7.1 General 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Checking the course gyro readout 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 Checking the speed log readout 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 Checking the echo sounder and trawl system readout 34. . . . . . . . . . . .
7.5 Remounting the electronic drawer unit 35. . . . . . . . . . . . . . . . . . . . . . . . .
8 FINAL TESTS AND MEASUREMENTS 37. . . . . . . . . . . . . . . . . . . . . . . . .
8.1 General 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 Source level (SL) measurements 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 Receiving voltage response (VR) 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.4 Noise/speed curve 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 INSTALLATION REMARKS AND SIGNATURE 48. . . . . . . . . . . . . . . . . .
Page 82
Simrad SD570 / Base version
IV
851--160117 / B
Document history
(The information on this page is for internal use)
Rev.A Original issue for Base version.
Rev.B Document transferred to Interleaf. No changes made to text or illustra-
tions.
Page 83
Introduction
1
851--160117 / B
1 PREPARING THE START--UP
1.1 Before start--up check list
Before beginning with the start- up procedure, check the following:
Sonar Control Unit:
j Check thatno connectionsare madetothe SonarControl
Unit.
Transceiver Unit:
j Checkthat theship’smainsfuses to theTransceiverUnit
are disconnected.
j Check thatthe mains inputconnector P201 on the power
supply in the Transceiver Unit is disconnected.
j Check thatthe transducer plugsare not connectedto the
front of the transceiver PCBs.
Hull Unit:
j Check that the ship’s mains fuses to the Hull Unit are
disconnected.
Page 84
Simrad SD570 / Base version
2
851--160117 / B
1.2 Starting up the stand--by power supply
In order to start up the sonar units, the 24 VDC stand-by power supply in the Transceiver Unit has to be started up first. Refer to figure 1 and use the following procedure to start up the stand-by power supply:
j Check that the mains input connector P201 on the front
of the power supply in the Transceiver Unit is disconnected.
j Check that the switch S202 on the front of the power
supply is set to OFF (middle) position.
j Insert the mains fuses to the Transceiver Unit on the
ship’s mains switchboard.
j Measure the mains voltage supplied to the Transceiver
Unit.
Write the measured voltage here:...................VAC.
j Check if the voltage selector switches S201 on the power
supply andS203 on the HV power unitcorrespond to the measured voltage (115V or 230V position).
j Reinsert the mains input connector P201 on the front of
the power supply.
j Check that the lamps L201 and L202 on the front of the
power supply illuminate.
j Check thatthe small LED(Light Emitting Diode)for the
+24Vstand --by powerontheTransceiverInterfaceBoard (TIB) illuminates (refer to indication on the front of the power supply).
Now the 24 VDCstand-by poweris suppliedboth tothe HullUnit and to the connector for the Sonar Control Unit.
Page 85
Introduction
3
851--160117 / B
Figure 1 - The transceiver power system
Page 86
Simrad SD570 / Base version
4
851--160117 / B
2 THE HULL UNIT
2.1 Starting up the Hull Unit
WARNING ! Before starting up the equipment on a launched ship,
make sure that there is sufficient depth for the transducer to be lowered. If starting up the equipment on board a docked ship, check both under the ship and inside the sonar room that neither persons nor things are in the way for the transducer or the lowering and hoisting machinery.
j Use a spanner to open the door on the motor control unit
which is mounted on the Hull Unit.
j Release the motor overload switch S301 in the motor
control unit by pressing the red button marked ”0” (see figure 2).
j Set the hoisting/lowering switch S302 in the motor
control unit to STOP position.
j Unscrew thetiming belt coveron the topof theHull Unit
(see figure 3). Locate the hand crank inside the motor control unit. Fasten the hand crank to the hoisting spindle and lower the transducer manually approximately 20 cm (8”).
j Remove the hand crank from the spindle, but do not
replace it in the motor control unit!
j Remountthetimingbelt coveronthetopofthe HullUnit.
j Setthehoisting/loweringswitch S302toHOISTposition,
and check that the hoisting contactor K301 is activated when pressing the hand crank safety switch S303.
j Set the hoisting/lowering switch S302 to LOWER
position, and check that the lowering contactor K302 is activated when pressing the hand crank safety switch S303.
j Set the hoisting/lowering switch S302 to STOP position. j Replace the hand crank to its storage position in the
motor control unit.
j Activate the hoisting contactor K301 by setting the
hoisting/lowering switch S302 to HOIST position, and check if the contactor is deactivated when pressing the upper limit switch S304 upwards (see figure 3).
Page 87
Introduction
5
851--160117 / B
Figure 2 - The motor control unit
j Activate the lowering contactor K302 by setting the
hoisting/lowering switch S302 to LOWER position, and check if the contactor is deactivated when pressing the lower limit switch S305 downwards.
j Set the hoisting/lowering switch S302 to STOP position. j Reinsert the three--phase mains fuses for the Hull Unit
on the ship’s mains switchboard.
j Measure thethree--phase voltageon the terminals of the
motor overload switch S301 in the motor control unit.
Page 88
Simrad SD570 / Base version
6
851--160117 / B
j Writemeasuredthree--phase voltagehere:.......................
j The hoist/lower motor is preconnected for 380V/440V
three--phase. If the measured three--phase voltage is 230V, the motor has to be reconnected.Remove the cover forthe mainsconnection on the motor,andrefer tofigure 4 to link the motor connections to correspond to the measured voltage.
j Adjust the release current of the motor overload switch
S301 according to the three-- phase voltage:
230V: 2.4 A
380/440V: 1.6 A
j Remove the hand crank from its storage position. j Set the motor overload switch to normal position by
pressing the black button marked ”1”.
j Set the hoisting/lowering switch S302 to LOWER. j Check the training direction of the hoisting/lowering
motor by briefly pressing the hand crank safety switch S303.
j If thetransducer shaft washoisted, disconnectthe ship’s
three--phase mains fuses and change two of the connectionstotheterminalsonthemotoroverloadswitch S301. Reinsert the three--phase mains fuses.
j Set the hoisting/lowering switch S302 to STOP. j Put thethe hand crankback to its storage position in the
motor control unit.
j Check ifthere is sufficientspace to lowerthe transducer. j Make surethat theflexible transducer cablesare insuch
a position that the transducer can be lowered without stretching or hard--bending the cables. Watch this carefully during the next steps in this procedure.
j Set the hoisting/loweringswitch S302 to LOWERfor full
lowering of the transducer. The lowering will automatically stop when the top of the transducer shaft hits the lower limit switch S305.
j Make a preliminary fastening of the flexible transducer
cables and watch the cables during the hoisting in the next step.
Page 89
Introduction
7
851--160117 / B
Figure 3 - The Hull Unit
Page 90
Simrad SD570 / Base version
8
851--160117 / B
j Set the hoisting/lowering switch to HOIST for full
hoisting of the transducer. The hoisting will stop automatically when the top of the transducer hits the upper limit switch S304.
j Repeat the hoisting/lowering to find the best position for
a permanent fastening of the flexible cables.
j Set the hoisting/lowering switch to STOP.
Page 91
Introduction
9
851--160117 / B
Figure 4 - Mains connection to the motor
Page 92
Simrad SD570 / Base version
10
851--160117 / B
2.2 Adjusting the middle position switch
Normally, when the transducer is selected to middle position on the Sonar Control Unit, only one half of the transducerface should be outside the sonar trunk (see figure 5). The middle position switch, which is a magnetic switch, must then be adjusted according to the trunk length:
j With the Hull Unit fully hoisted to upper position,
measure the distance x between the bottom of the transducerandthetrunkend.Seethelowerpartoffigure
5. X = mm
If it isimpossible to measure the distance x,it can be calculated by using the total trunk height C frompage 12in section“Installation procedures” .
Total trunk height C = mm
-- Distance flange/transducer bottom = 760 mm = Distance X mm
j Use the hoisting/lowering switch in the motor control
unit to position the transducer in the calculated correct position x + 240 mm (see figure 5).
j Loosen the bracket for the middle position switch and
aligntheswitchrelativetothemagnetasshownonfigure
5. If needed, spare cable is coiled up behind the bracket.
j Fasten the bracket and check that the distance between
the magnet and the switch is approximately 5--8 mm.
j Check the passingof the middle position switch by using
the hoisting/lowering switch.
j Usethe hoisting/loweringswitchtohoist theHullUnit to
its upper position.
j Release the motor overload switch S301 by pressing the
red button marked ”0”. This to prevent unwanted lowering of the transducer.
Page 93
Introduction
11
851--160117 / B
Figure 5 - Adjusting the middle position switch
Page 94
Simrad SD570 / Base version
12
851--160117 / B
3 THE SONAR CONTROL UNIT
3.1 Starting up the sonar control unit
Note that the Sonar Control Unit can be connected for either 115 or 230 VAC without any special action. Both the internal power supply and the display are specified for a voltage range of minimum 85 VAC to maximum 265 VAC.
j Set theswitch S101 atthe rear ofthe Sonar ControlUnit
to OFF position. For location of the switch, see figure 6.
j Connect the SONAR TRANSCEIVER (4) cable from the
transceiver unit to the rear of the drawer unit (refer to figure 6).
j Connect the 115/230 VAC mains power cable (3) to the
rear of the drawer unit.
j Set theswitch S101 atthe rear ofthe Sonar ControlUnit
to ON position.
j Press the ON/OFF--HOIST button on the operator panel
and hold it for approximately 2 seconds until the Sonar Control Unit starts up.
j After approximately 10 seconds, the menu will be
displayed on the screen. If not, check that the display brightness and contrast are correctly adjusted (refer to figure 7).
j Ifthe blinkingtextADJUST COURSEisdisplayed inthe
menu field, push the menu joystick to the right.
j Check that the ship symbol, tilt indicator etc. are
displayed on the screen.
Page 95
Introduction
13
851--160117 / B
Figure 6 - Connections to the rear of the Sonar Control Unit
j Use the menu joystick in the following way to get a
simulated echo on the screen:
- Move the menu cursor below the PP FILTER to the
CONSTANTS in the extra menu, and push enter (right).
- Move the cursor to SIMRAD TEST and push enter.
- Move the cursor to TEST2 and push enter.
- Move the cursor to SYNT. SHOAL and push enter.
j Check that after a few seconds a simulated echo will be
displayed on the screen.
j Check if the picture size and position on the display are
correct. If not, adjust the picture with the display adjustments (see figure 7).
Page 96
Simrad SD570 / Base version
14
851--160117 / B
Figure 7 - Adjustments on the display
3.2 Checking the control panel
The simulated trigger signalnow makesit possibleto operateand test most functions on the sonar control panel:
j Use the CURSOR JOYSTICK (1) to check if the yellow
cross on the screen can be moved in any direction, and that it stops when the joystick is released.
j Pressthe TARGETMARKERbutton(3, buttonno.1)and
check if a numbered triangle appears in the position of the yellow cross.
j Press the SHIP MARKER button (3, button no. 2) and
check if a numbered square appears across the ship’s symbol.
j Press theCIRCLE MARKERbutton (3,button no. 3)and
check if a circle appears, centered around the yellow cross. Also check that the button lights up. Press the button once more and check if the circle marker disappears, and that the button light extinguishes.
Page 97
Introduction
15
851--160117 / B
Figure 8 - The main control panel
j Press the GEAR button (3, button no. 4) and check if a
seine circle appears beside the ship symbol, and that the button lights up. A second press should give a yellow square at the ship symbol, and a third press should remove the seine circle and extinguish the button light.
j Select MODE True Motion in the menu, and press the
DISPLAY CENTRE button (3, button no. 5) to check if a new centre is formed.
j Press the GAIN +/-- buttons (4 lower) and check if the
readout inthe upper right--hand cornerof the screen can be changed from 0 to 50.
j PresstheRANGE+/-- buttons(5)andcheckif thereadout
in the upper right--hand corner of the screen can be changedtothe followingranges:125,250, 375,750,1000, 1500, 2000, 3000 and 4000 m.
j Pressthe TILTUP/DOWNbuttons (7)tocheckthe tilting
onthe tiltindicator.Also presstheAUTO buttontocheck if the button lights up, and that the tilt limits appear on the tiltindicator.Then press the MAN buttonto stop the automatic tilting.
j Press the PANEL ILLUMINATION +/-- buttons (8) to
check the adjustment of the backlight and signal light in the push buttons.
j Use the MANUAL TRAIN buttons (9 right) to check the
training of the white audio line on the screen. Try both directions.
j Press the AUTO SEARCH button (9) and check that the
sector limits are displayed.
Page 98
Simrad SD570 / Base version
16
851--160117 / B
j Use the SEARCH SECTOR +/-- buttons (9 left) to check
that the sector limits can be adjusted from 22° to 360°.
j Press the POSITION TRACK button (9) and check that
a circle appears at the yellow cross position.
j Press the TARGET TRACK button (9) and check that a
circle appears at the yellow cross position.
j Press the MAN (manual training) button (9) and check
that it lights up.
j Select STANDARD in the menu in order to put all the
menu settings back to normal.
j Set TX POWER (transmission power) in the menu to
OFF.
Page 99
Introduction
17
851--160117 / B
4 CHECKING THE HOISTING/LOWERING
SYSTEM
During the following procedure, there must be one person on the bridge, and one in the sonar room to control if the hoisting/lowering system works properly. If problems occur in the sonar room, press the button marked ”0” on the motor overload switch S301(see figure 2) to stopthe hoisting/lowering.
This procedure is made in duplicate, one for the person on the bridge (chapter 4.1), and one for the person in the sonar room (chapter 4.2). Thesechecking lists have to be used simultaneously in co-ordination. An asterisk (*) means thatthis testis made inthe ”other end”.
4.1 Checking the bridge functions
Note that this checklist has to be coordinated with chapter 4.2.
j Check that the depth is sufficient for lowering of the
transducer.
j Startup theSonar ControlUnitand checkthat thegreen
ON/OFF--HOISTbuttonlights,and thattheupperlinein the menu shows the text TRANSD. POS: UPPER.
* Set the motor overload switch S301 in the motor control
unit to normal position by pressing the black button marked 1”.
* Set the hoisting/lowering switch S302 in the motor
control unit to REMOTE position.
j Selectthe HullUnit toMIDDLEposition byashort press
ontheLOWERbutton,andcheckifthetextLOWERING: MIDDLE is shown in the menu. Check that both the HOIST and LOWER buttons light during the lowering, and that both extinguish when the transducer stops in the middle position. The menu should now show the text TRANSD. POS: MIDDLE.
j Press the LOWER button, and check if the text
LOWERING: LOWER is shown in the menu. Also check thatbothbuttonslightduringthe lowering,andthatonly the LOWER button lights when the transducer stops in the fully lowered position. The menu should now show the text TRANSD. POS: LOWER.
j Select the MIDDLE position by a short press on the
HOIST button, and check if the text HOISTING: MIDDLE is shown in the menu. Check that both the HOIST and LOWER buttons light during the hoisting, and that both extinguish when the transducer stops in the middle position. The menu should now show the text TRANSD. POS: MIDDLE.
Page 100
Simrad SD570 / Base version
18
851--160117 / B
j Press the HOIST button, and check if the text
HOISTING: UPPER is shown in the menu. Also check thatboth buttonslight duringthe hoisting,and thatonly theHOISTbuttonlightswhenthetransducerstopsinthe fully hoisted position. The menu should now show the text TRANSD. POS: UPPER.
j Press the LOWER button for approximately 2 seconds,
and check if the text LOWERING: LOWER is shown in the menu. Also check that both buttons light during the lowering, and that only the LOWER button lights when the transducer stops in the fully lowered position. The menushouldnowshowthetext TRANSD.POS:LOWER.
j PresstheHOISTbuttonforapproximately2seconds,and
check if the text HOISTING: UPPER is shown in the menu. Also check that both buttons light during the hoisting,andthatonly theHOISTbuttonlightswhenthe transducer stops in the fully hoisted position. The menu should now show the text TRANSD. POS: UPPER.
* Setthe switchinthe motor controlunitto STOPposition.
j Switch OFF the Sonar Control Unit by pressing the
ON/OFF--HOIST button for approximately 2 seconds.
Loading...