To the best of our knowledge and at the time written, the information contained in this
document is technically correct and the procedures accurate and adequate to operate this
instrument in compliance with its original advertised specications.
Notes and Safety Information
This Operator’s Manual contains warning headings that alert the user to check for hazardous
conditions. These appear throughout this manual where applicable, and are dened below.
To ensure the safety of operating performance of this instrument, these instructions must be
adhered to.
Warning, refer to accompanying documents.
Attention, consulter les documents d’accompagnement.
Caution, risk of electric shock.
Attention, risque de choc électrique.
This instrument is designed to prevent accidental shock to the operator when properly
used. However, no engineering design can render safe an instrument which is used
carelessly. Therefore, this manual must be read carefully and completely before making any
measurements. Failure to follow directions can result in a serious or fatal accident.
Technical Assistance
SIMPSON ELECTRIC COMPANY offers assistance Monday through Friday 8:00 am to 4:30
pm Central Time by contacting Technical Support or Customer Service at (715) 588-3311.
Internet: http://www.simpsonelectric.com
Warranty and Returns
SIMPSON ELECTRIC COMPANY warrants each instrument and other articles manufactured
by it to be free from defects in material and workmanship under normal use and service, its
obligation under this warranty being limited to making good at its factory or other article of
equipment which shall within one (1) year after delivery of such instrument or other article
of equipment to the original purchaser be returned intact to it, or to one of its authorized
service centers, with transportation charges prepaid, and which its examination shall disclose
to its satisfaction to have been thus defective; this warranty being expressly in lieu of all
other warranties expressed or implied and of all other obligations or liabilities on its part,
and SIMPSON ELECTRIC COMPANY neither assumes nor authorizes any other persons to
assume for it any other liability in connection with the sales of its products.
This warranty shall not apply to any instrument or other article of equipment which shall
have been repaired or altered outside the SIMPSON ELECTRIC COMPANY factory or
authorized service centers, nor which has been subject to misuse, negligence or accident,
incorrect wiring by others, or installation or use not in accord with instructions furnished by the
manufacturer.
Page 3
Contents
1. INTRODUCTION4
1.1General Description4
1.2Specications4
2. DISPLAY AND KEYPAD CONTROLS5
3. INSTALLATION AND PANEL CUTOUT5
3.1Mounting Requirements5
3.2Engineering Label Placement6
4. REMOVING / INSTALLING OPTION MODULES6
5. OPERATING THE KEYS7
5.1In Run Mode7
5.2In Program Mode7
5.3In Edit Mode7
6. PROGRAMMING MENU8
6.1Relay Control8
6.2Display Control9
6.3Measurement Control9
6.4Output Control (If Present)10
6.5System Control10
6.6Password11
7. TEMPERATURE INPUT CARDS12
7.1Relay Cards12
7.2Frequently Asked Questions13
7.3Power Supply Card13
8. MENU FLOWCHART15
9. MENU DETAIL17
9.1Relay Control (Sp1 - Sp4)17
9.1.1 Response17
9.1.2 Delay17
9.1.3 Latch18
9.1.4 Alarm18
9.2Display Control18
9.3Output Control19
3
Page 4
1. Introduction
1.1 General Description
The Simpson Electric Hawk 3 Advanced Digital Panel Meter / Controller has 4-digit display. All LEDs are 7
segment and offer 5 brightness levels. The high quality instrument has user programmable parameters that
are all set from the front panel in easy to understand terminology. The display also shows activated set point
indicators (up to four). The keypad buttons have tactile feedback to prevent keystroke errors.
1.2 Specications
Display
Type7-segment, red LED, 4 digits
Height0.56” (14.2mm)
Decimal PointNone, Not Programmable
Brightness5 settings, user Programmable
Overrange IndicationDisplay ashes “EEEE” indicating Maximum Value Exceeded
Underrange IndicationDisplay ashes “-EEE” indicating Minimum Value Exceeded
Alarm Indicators4 LED indicators for up to 4 Independent Setpoints
Sensor BreakDisplay reads “EEEE”
(Burnout)
Power Requirements
AC Voltages85 to 250 VAC/120 VAC @ 10VA
DC Voltages9 to 36 DCV @ 10VA
AccuracyAll measurements are at 25° C and measured as percent of reading
Unit TypeAccuracyTemperature Range
RTD PT1000.2%. +/-2 Counts-200°C to + 200°C
J0.2%. +/-2 Counts-100°C to + 760°C
K0.2%. +/-2 Counts-200°C to +1250°C
E0.2%. +/-2 Counts-100°C to + 800°C
T0.2%. +/-2 Counts-200°C to + 400°C
Environmental
Operating Temperature0 to 50°C
Storage Temperature-10 to 60°C
Relative Humidity<80%
Ambient Temperature25°C
Temperature Drift±100 ppm/C°±0.05dgt/°C
Warmup Time10 minutes
Noise Rejection
NMRR60dB @ 50/60 Hz
CMRR100 dB @ 50/60 Hz
A to D Conversion
TechniqueSuccessive aproximation with oversampling
Sample Rate10 conversions per second
Display RateUser programmable from 1/minute - 8/seconds
4
Page 5
2.DISPLAY AND KEYPAD CONTROLS
1.Activated set point indicators (4)
2.4-button Keypad
3.Units Window
4.Numeric and message
Figure 2-1
3.INSTALLATION AND PANEL CUTOUT
3.59
90.7mm
3.93"
99.8mm
2.04"
51.8mm
0.52"
13.2mm
1.77"
45mm
3.62"
92mm
3.24"
82.3mm
1.76"
44.7mm
Figure 4-1. Installation and Panel Cutout
3.1Mounting Requirements
Engineering Label
The Hawk 3 Advanced Digital Controller 1/8 DIN counters require a panel
cutout of 1.77” (45mm) high be 3.62” (92mm) wide. To install the Hawk 3 into
the panel cutout, remove the clips from the side of the meter. Slide the meter
through the panel cutout, then slide the mounting clips back on the meter.
Press evenly to ensure a proper fit.
5
Page 6
3.2 Engineering Label Placement
If the engineering unit label needs replacing, place the tip of a ballpoint pen into the small hole
at the base of the engineering label in the bezel. Slide the label up until it pops out. Grasp and
remove. Slide the new label half the distance in, then use the ballpoint pen to slide it down into
place.
4. Removing / Installing Option Modules
Shut power off before removing or installing any option modules
Couper le courant avant de retirer ou d’installer des modules optionnels
1. Remove module from case by inserting a screwdriver into tab slot opening at top of input
module (see Figure 5-1). Apply pressure to release module from case. Repeat procedure
for tab located on underside of module and then slide module away from the case.
2. Refer to appropriate sections to congure switches or jumpers for proper operation.
3. Install module by carefully aligning module edges with slots in case and pressing forward
until tabs (on top and bottom) engage.
6
Page 7
5.OPERATING THE KEYS
5.1In Run Mode
W = Enters the Program Menu
S = Displays the Maximum Value (if enabled). Press S and hold while pressing
RESET
E to clear max. value.
ENTER
T= Displays Minimum Value, if enabled. PressTand hold while pressing to
clear min. value
RESET
RESET/E = Resets Latched Relays (If any)
ENTER
S and T = Sets Zero/ICE Value (if enabled). Also clears Minimum and Maximum Values
5.2In Program Mode
W = Enters the Edit Mode. Flashing cursor shows value to edit. (Numeric Values only)
S = Scrolls “UP” through menu choices
T = Scrolls “DOWN” through menu choices
RESET
RE = Selects a menu or submenu to edit.
ENTER
RESET
ENTER
5.3In Edit Mode
W = Moves Edit Cursor to the left. Flashing cursor shows value to edit (Numeric Values Only)
S = Increases Numeric Value or Scrolls “UP” through sub-menu choices.
T = Decreases Numeric Value or Scrolls “DOWN” through sub-menu choices.
RESET
RE = Confirms and Saves your new setting.
ENTER
IMPORTANT: After editing parameters, exit programming menu completely. If
this step is not followed, changes will not be saved.
7
Page 8
6. PROGRAMMING MENU
Depending on the operator’s password rights, some choices shown below be unavailable. Use
caution when changing values “on the y” because relay changes are immediate upon exiting menus.
While in local menu, RS-485 communications will halt to avoid command conict. While in local or
remote menu, relay and alarm operation are suspended. The local or remote menu will “time out” in
two minutes and resume normal operation.
6.1 Relay Control
SP1 Set Point #1 & Relay #1 (if present)
Val-1Value1000*
Rsp1 (Response 1)Hyst0° to 29.9%
Dlay*0° to 60.00 Seconds (0.10*)
LtchActive
Alr-1 (Alarm 1)Hi*
LO
OFF
St-1 (State when not in Alarm)ND*De-energized
NEEnergized
SP2 Set Point #2 & Relay #2 (if present)
Val-2Value0*
Rsp2 (Response 2)Hyst0° to 29.9%
Dlay*0° to 60.00 Seconds (0.10*)
LtchActive
Alr-2 (Alarm 2)HI
LO
OFF*
St-2 (State when not in Alarm)ND*
NE
SP3 Set Point #3 & Relay #3 (if present)
Val-3Value0*
Rsp3 (Response 3)Hyst0° to 29.9%
Dlay*0° to 60.00 Seconds (0.10*)
LtchActive
Alr-3 (Alarm 3)HI
LO
OFF*
St-3 (State when not in Alarm)ND*
NE
* Factory Reset Default Values
8
Page 9
SP4 Set Point #4 & Relay #4 (if present)
Val-4Value0*
Rsp4 (Response 4)Hyst0° to 29.9%
Alr-4 (Alarm 4)Hi*
St-4 (State when not in Alarm)ND*
* Factory Reset Default Values
6.2 Display Control
DctL
deg(rees)C (Celsius) F*(Fahrenheit) Fixed based on RTD
Frsh (RefreshValue - 1 to 480 updates per minute (240º *)
BandValue - 0* to 99 counts from current value
Brit (Brightness)▲ and ▼arrows move LED brightness through 5
* Factory Reset Default Values
Dlay*0° to 60.00 Seconds (0.10*)
LtchActive
LO
OFF*
NE
or TC
levels as indicated on display.
(5* full brightness)
6.3 Measurement Control
Meas
(Zero)
ICE (Point)
HILO (Minimum/Maximum)
Display Enable
Off *
On - Temporary TC Correction (Until power cycle)
Hold - Permanent TC Correction
Off *
On
9
Page 10
6.4 Output Control (If Present)
OctL
ALog out
LIMHI (electrical limit) (100 *)
FS (Fail Safe)
(Overrange or Underrange
6.5 System Control
( The process meter will have pre-loaded coordinates)
SctL
FACT / rSET (Factory Reset) Reset (Selectring this item will reset
NOTE: If you forget your password, turn power off in unit, press and hold the
key and the RE key. Turn power on and wait until the display reads “noPas”
T
then press the re key again to reset password to 000.
RESET
ENTER
RESET
ENTER
* Factory Reset default value
11
Page 12
7. Temperature Input Cards
Denotes position 1
RTD
PT 100
RTD PT100: The resistance input card has been congured
to track the characteristics of a PT100 sensor.
Lead length error can be cancelled out by bringing the sensor
to 0 C (ice point) and using the “ICE” command to zero the
IN HI
SENSE
meter. (Remember to move the ICE capture from the “On” to
“Hold” in order to retain the data.)
Lead length error can also be cancelled using the guard wire.
IN LO
TEMPERATURE
Denotes position 1
THERMO
COUPLE
J,K,E,T
IN+
IN-
TEMPERATURE
7.1 Relay Cards
Single Relay
N.C.
1
COM
N.O.
250V~
Never apply a voltage or current to these inputs as damage will occur.
Denotes position 5
5A
7.2 J, K, E, T Thermocouple: The thermocouple input card
contains all the response information needed to read a J
type or K type thermocouple.
Lead length error can be cancelled out by bringing the censor
to 0 C (ice point) and using the “ICE” command to zero
the meter. (Remember to move the ICE capture from “On” to
“Hold” to retain the data.
Dual Relay
N.C.
1
COM
N.O.
250V~
Denotes position 5
5A
Quad Relay
N.O.
1
COM
N.O.
2
COM
RELAY OUT
N.C.
2
COM
N.O.
RELAY OUT
12
N.O.
3
COM
4
N.O.
RELAY OUT
250V~
5A
Page 13
The relay cards are directly related to any alarms that occur on the Hawk 3.
The single relay is a “Form C” relay that activates in relationship to “SP1”.
The dual relay is a Form C” relay that activates in relationship to “SP1” & “SP2”.
The quad relay is a “Form A” relay that activates in relationship to “SP1” through “SP4”.
NOTE: “SP3” and “SP4” connections share a common.
All relay contacts are rated at 250VAC @ 5 amp maximum. The rating of the relay contact is intended for
resistive circuits only. Use a snubber circuit to protect the contacts from inductive loads.
Tous les contacts de relais sont évalués à 250VAC @ 5 ampères maximum. La note du contact de relais
est destiné uniquement aux circuits résistifs. Utiliser un circuit de protection pour protéger les contacts à
partir de charges inductives.
7.2 Frequently Asked Questions
What is a Form A or Form C relay?
The form A relay is a 1 contact switch that is either closed or open. The form C relay has 2 contacts, one of which
will be closed and one open. With the fac tory defaults used, N.O. on the relay means normally open when the
Hawk 3 is not in alarm. N.C. means normally closed when the Hawk 3 is not in alarm.
What does N.D. and N.E. do to the relay?
The effect of the relay can be reversed by setting the relay action to N.E. (nor mally energized) in the menu. When
the Hawk 3 is not in alarm, the N.C. contact will now be open and the N.O. contact will be closed. Setting the
alarm response back to N.D. (normally de-energized) will put the contacts back to their default state.
7.3 Power Supply Card
Universal AC Supply
IN ~
IN ~
85-250VAC
50/60 Hz
10VA
Hold
3-1/2 Digit 120 VAC Supply
Denotes modules position 4 at rear of meter
IN ~
IN ~
120V
Hold
DC to DC Supply
+
9 - 36 VDC
10W
Hold
The AC power cards are meant to operate from standard 50/60 Hz line power. The DC to DC power card is an
isolated supply that can operate between 9 and 32 volts DC.
NOTE: A fusible link is not provided on this module.
An external fuse is recommended for safe operation, for AC supply, Slow Blow fuse at .25A, Littlefuse Part
No. 313.250 or equal.
For DC supply Slow Blow fuse at 1.25A, Littlefuse Part No. 3131.25 or equal.
13
Page 14
The hold feature is used to freeze the display. When the contacts are shorted, the
display will “Hold” the last reading until the short is removed. It is recom mended that
a mechanical switch or relay be used to activate the hold circuit, solid state relays may
give unexpected results. The hold circuit cannot be ex ternally powered.
La fonction de maintien est utilisé pour geler l’afchage. Lorsque les contacts sont
court-circuitées, l’afchage “Hold” la dernière lecture jusqu’à ce que le court-circuit
est éliminé. Il est recommandé qu’un commutateur ou relais mécanique être utilisés
pour activer le circuit de maintien, relais statiques peuvent donner des résultats
inattendus. Le circuit de blocage ne peut pas être effectuée en externe.
No terminal can be above earth ground by more than 250Vrms.
Aucun terminal peut être supérieure à la terre de plus de 250Vrms.
Hazardous voltages may be present.
Disconnect power before making or re moving connections.
Des tensions dangereuses peuvent être présentes.
Coupez l’alimentation électrique avant d’effectuer ou de retirer les connexions.
14
Page 15
8. MENU FLOWCHART
Menu Mode
SP 1
SP 2
SP 3
VAL 1
RSP 1
ALR 1
ST 1
VAL 2
RSP 2
ALR 2
ST 2
VAL 3
RSP 3
ALR 3
ST 3
Value
HYST
DLAY
LTCH
HI
LO
OFF
ND
NE
Value
HYST
DLAY
LTCH
HI
LO
OFF
ND
NE
Value
HYST
DLAY
LTCH
HI
LO
OFF
ND
NE
Value
Value
Value
SP 4
DCTL
Page
2
VAL 4
RSP 4
ALR 4
ST 4
Deg
Frsh
Band
Brit
Value
HYST
DLAY
LTCH
HI
LO
OFF
ND
NE
C
F
Value
Value
Value
15
Value
Page 16
Page
2
Meas
OCTL
SCTL
ICE
ZERO
HILO
Anlg
Off
Off
On
On
Frd
Dir
SpAn
FS
Brd
LO
Full
rEAD
Off
HI
Value
Value
PASS
FACt
rSEt
Entr
Pwrd
Cng
Pwrd
rst
Pwrd
16
Page 17
9.MENU DETAIL
9.1Relay Control (Sp1-Sp4)
While in menu, all other operations are suspended.
The H340 has four setpoint parameters and up to four relays associated with
those four setpoints. The setpoint LEDs on the display will light even if no relay
is present for that setpoint.
To change the setpoint value, enter the menu by pressing W. If the password
allows relay control, it will be the first menu to appear. The display will show the
word “Sp1”. If this is the setpoint to be edited, press RE , otherwise press T
to move to the next choice. When editing Sp1, the display will alternate between Val-1 and a value. The “value” represents a threshold above or below
the setpoint being set to alarm.
NOTE: Before editing this value, be sure that the decimal point is in the proper
position. It is also recommended that any scaling or linearization be entered
before setpoints are determined.
Press RE to choose Val-1 as the setting to be edited. Notice that the far right
RESET
ENTER
digit has an alternating cursor. To change this digit, use S or T. To move to the
next digit, press W. When all changes to the value are complete, press
RESET
RE to confirm the change and save it to memory.
ENTER
NOTE: Any power loss before confirming a change will lose the edited value.
The menu will revert back to alternating between Val-1 and value. Press T to
move to the response setting.
RESET
ENTER
9.1.1Response
The display will now show “Rsp.” To edit response, press RE , otherwise
RESET
ENTER
press T to move to the next choice. When editing Rsp., the display will show
Hyst, Dlay, or Ltch Flashing. Use S or T to choose the required response.
Press RE to confirm the choice. When choosing Hyst, the display will
RESET
ENTER
alternate between Hyst and the current value.
To edit the value, press RE . Otherwise press T to move to the next choice.
RESET
ENTER
Hysteresis will be used above and below the setpoint in equal amounts. The
value represents a percentage of the setpoint. For example: If the setpoint is
set to 100.00 with a high alarm and therhysteresis is set for 8.5%, the alarm
will not turn on until the reading on the display reaches 108.50. Once tripped,
the alarm will not turn off until the display reaches 91.50.
9.1.2Delay
When choosing Dlay, the display will alternate between Dlay and current value.
To edit the value press RE . Otherwise press q to move to the next choice.
Dlay will be used above and below the setpoint in equal amounts. The value
represents the amount of delay in seconds. For example, if the setpoint is
again configured for high alarm and Dlay is set for 2.5 seconds the display
crosses the setpoint value and a timer begins to count off the 2.5 seconds
before the alarm trips. If, during those 2.5 seconds the value falls below the
setpoint, no action will be taken. When the unit successfully counts off 2.5
RESET
ENTER
17
Page 18
seconds the alarm will trip and remain in alarm until the display drops below
the setpoint for at least 2.5 seconds
9.1.3Latch
When choosing Ltch, the relay output will latch immediately after crossing the
setpoint. The unit can then only be unlatched with a front panel reset or a reset
command from the RS-485 port.
NOTE: If the display is still beyond the setpoint threshold, the reset will have
no effect and the unit will remain latched.
9.1.4Alarm
The Alr mode allows choice between High, Low, or Off. The High Alarm means
that the display value must be greater or equal to the setpoint to go into Alarm.
The Low Alarm means that the display value must be less than or equal to the
setpoint to into alarm The Off Alarm means that all features of this setpoint is
disabled. No action will occur when display crosses a setpoint and the relays
will revert to a normally de-energized state.
When selecting St (State) from the menu, the display will alternate between
Stand the current setting.
To edit the setting press RE . Otherwise press T to m
RESET
ENTER
If choosing ND (Normally De-energized) the relay will turn “on” the alar
dition. This is a typical configuration. The one and two-relay outputs will act as
abeled; the normally closed contact will be closed until an alarm condition
occurs, and the opposite is true for the normally open connection. The fourrelay output only has the choice of normally open.
If choosing NE (Normally Energized) the relay will turn on at power up and
remain on until in an alarm condition. This mode can be used to create a failsafe condition or reverse the action of the four-relay configuration. In the failsafe example, the relay output would be wired to protect some device during
an alarm condition. During a power failure, the relay would be in the same
position as though it were in alarm thus protecting a device that may be on a
separate and possible active circuit.
ove to the next choice.
m con-
9.2Display Control
The next item that will appear in the menu is Dctl (Display Control). If this is
the item to be edited press
to the next choice.
The display degrees, Deg, will allow you to select either °F or °C for the temperature indication. There is no need to change this value if you prefer the
default °C indication.
The display refresh, frsh, will slow the numbers of updates to the display. This
setting ranges from as fast as 480 updates per minute (8 updates per second)
to as slow as 1 update per minute.
RESET
Enter
, otherwise press the down arrow T to move
ENTER
18
Page 19
The display banding, band, works from a different approach. The value entered is the amount of digit movement allowed before the display should be
updated. With a band setting of 2, the value must move 2 counts up or down in
the rightmost position as compared to the current display to cause the display
to update.
NOTE: The two previous features can finely or coarsely stabilize the display
and remove the pops and jitters typically found when monitoring a power line.
The adjustment of this setting only filters what is displayed. The actual raw
signal is evaluated against the setpoint and will go into alarm even if the
display were set for maximum filtering and gave no indication of nearing the
setpoint. Use hysteresis on delay in SP menu to slow relay action.
The Brit( Brightness) of the display is adjustable to allow for dimming in low
light applications or for intensity matching with other equipment. The default is
set to the brightest setting (5).
ICE (Zero or Null) Using ICE allows the user to grab a running offset and zero
to it. A running offset can be useful for monitoring the tolerance to a value
instead of the value, cancelling lead error in measurement or removing some
signal difference in a measurement. Once ICE in enabled in the menu (ICE =
ON), the device will wait until the user presses S and T . At that point, the unit
will grab the current value and offset the display to zero. By choosing “hold” in
the ICE menu the ICE value can then be saved to a more permanent location.
No new ICE can be be taken, but the value will noy be lost if power fails.
NOTE: Be aware that introducing a ICE value will change the setpoint thresholds and erase any previous Hi Lo readings.
HILO (Min/Max) allows the user track the history of the readings on the display. By pressing S, the unit will momentarily display the highest value it has
reached after last being reset. By pressing T, the unit will momentarily display
the lowest value it has reached after last being reset.
9.3Output Control
An optional analog outputs is available.
The analog output is a current or voltage that represents an equivalent range
of signal on the input. Analog output can be purchased as 4-20mA DC out or
0-10V DC out. When installed, the Hawk 3 will sense the card and the menu
will open the choices available to it.
Setting the limits (LIM). The ends of the analog output range (4 & 20 or 0 & 10)
can be set or ‘pegged’ to and display value within the range of the meter.
Example: The Hawk 3 is purchased as a standard 200 volt meter. The analog
output is configured, by default, for HI=100.0 and LO=0.
When the display reaches 100 volts, the analog output would be 20mA. When
the display reaches 0 volts the analog output would be 4mA.
The Hawk3 is purchased as a process meter 4 – 20 mA input which will display 0-100 percent. The analog output is configured, by default, for HI=100.0
and LO=0. This means when the display reached 100 percent the analog output would be 20 mA. (Also, because this is a process meter the input should be
19
Page 20
20mA) When the display reaches 0 percent the analog output would be 4mA.
The limits can be moved or reversed (HI=0 and LO= 80.0), in this case when
the display reads 0, the analog output would be 20mA and when the display
reads 80, the analog output would be 4mA.
The Fail Safe option (FS) controls the action of the analog output when the
display goes into over-range (EEEE or –EEE).
In some cases, the low limit or high limit are reserved for error conditions.
With set to ‘HI’, the output will run to the 20mA value when over-range or
under-range occur. With failsafe set to ‘LO’, the output will run to 4mA at
over-range or under-range.
With failsafe ‘Off’, the output will go to the dened limit ends. (-EEE would be
4mA and
EEEE would be 20mA typically.)
20
Page 21
Ordering Information -
Hawk 3 Indicators can be congured by making an entry into each section. Example: H340-3-91-0-4-1
_____
IIIIII
Basic UnitPower
Supply
Basic UnitFunction/Range5A Relays
H340 4 Digit, Red LED91 J Thermocouple0None
Power Supply93 RTD, PT100 3-wire2Two
1120 ACV94 E Thermocouple4Four
39-36 DCV95 T Thermocouple
485-250 ACVExcitation
Function/
Range
Output5A RelaysExcitation
Select From Each One Below
92 K Thermocouple1One
Output0None
0None112 DCV - 100mA max current
14-20 DCmA224 DCV - 100mA max current
20-10 DCV
21
Page 22
NOTES:
22
Page 23
NOTES:
23
Page 24
Simpson Electric Company
520 Simpson Avenue, Lac du Flambeau, WI 54538
(715) 588-3311 FAX (715) 588-3326
www.simpsonelectric.com
Part No. 06-117489, Edition 7, 07/14
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.