The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and
is intended to describe the correct method of installation for this product. However, Company has no control over the field conditions
which influence product installation.
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Company only
obligations are those in Company standard Conditions of Sale for this product and in no case will Company be liable for any other
incidental, indirect or consequential damages arising from the use or misuse of the products.
Cover Page 2
Three Phase (3W/4W)
Three Phase Touch Screen Digital Multi-fuction Meter
Installation & Operating Instructions
Section
1.Introduction
2.Measurement Reading Screens
3.Programming
Contents
3.1Password Protection
3.1.1 Change Password
3.2Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 System type
3.2.1.2 Potential transformer Primary value
3.2.1.3 Potential transformer Secondary value
3.2.1.4 Current transformer Primary value
3.2.1.5 Current transformer Secondary valuealue
3.2.1.6 Demand integration time
3.2.1.7 Auto Scrolling
3.2.1.8 Low current noise cutoff
3.2.1.9 Energy On RS 485
3.2.1.10 Energy digit reset count
3.2.2 Communication Parameter selection screen
3.2.2 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection
1
3.2.3 Reset Parameter selection screen
3.2.3.1 Resetting Parameter
3.2.4 Output Option selection screen (menu)
3.2.4.3 Parameter setting for Analog Output-1
3.2.4.4 Parameter setting for Analog Output-2
3.2.5Brightness & Contrast
4.Touch screen calibration.
5.Phase Rotation Error screen.
6.Run - Hour.
7.
8.Number of Interruption
9.Analog Output
On - Hour.
11.
RS 485 (Modbus) output
11.1
User Assignable modbus Registers
2
12.
Phaser Diagram
13.Installation
13.1
EMC installation Requirements
13.2
Case Dimensions and Panel Cut-out
13.3
Wiring
13.4 Auxilary Supply
13.5
Fusing
Earth / Ground Connections
13.6
14.
15.
Connection Diagrams
Specification
16.
Connection for Optional RS 485 / Analog Output
1. Introduction
This instrument is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the
measurement of important electrical parameters like AC voltage, AC Current, Frequency,
Power, Energy (Active / Reactive / Apparent). The instrument integrates accurate
measurement of technology (All Voltage & Current measurement are True RMS up to 15th
Harmonic) with 320x240 Pixels touch screen TFT LCD display.
This instrument can be configured and programmed at site for the following:
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
MAIN MENU
MAIN MENU
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
5 AMPERE
VOLTAGESYSTEMCURRENT
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VOLTAGESYSTEMCURRENT
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
POWERENERGYSETUP
POWERENERGYSETUP
OK
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
V
V
V
V
V
V
V
V
V
V
V
V
PT Primary, PT Secondary, CT Primary, CT Secondary (5A or 1A)
and 3 phase 3W or 3 Phase 4W system.
The front panel has a 3.5” Touch Screen through which the user can
move across the available measurement reading, reset the energy,
Min/Max (System Voltage and System Current) and configure the
product setting.
3
TABLE 1:
Measured Parameters
System Voltage
System Current
Voltage VL1-N(4wire only)
Voltage VL2-N(4wire only)
Voltage VL3-N(4wire only)
Voltage VL1-L2
Voltage VL2-L3
Voltage VL3-L1
Current L1
Current L2
Current L3
Neutral Current ( 4 wire only )
Frequency
Active Power (System / Phase (4 wire only) )
Reactive Power (System / Phase (4 wire only) )
Apparent Power (System / Phase (4 wire only) )
Power Factor (System / Phase (4 wire only) )
Phase Angle ( Phase (4 wire only) )
Active Import Energy (8 Digit resolution)
Units of
Measurement
Volts
Amps
Volts
Volts
Volts
Volts
Volts
Volts
Amps
Amps
Amps
Amps
Hz
Kwatts
KVAr
KVA
Degree
kWh
Active Export Energy (8 Digit resolution)
Reactive Import Energy (8 Digit resolution)
Reactive Export Energy (8 Digit resolution)
Apparent Energy (8 Digit resolution)
Ampere Hour (8 Digit resolution)
4
kWh
kVArh
kVArh
kVAh
KAh
Measured Parameters
Units of
Measurement
AmpsCurrent Demand
KVA DemandKVA
KW Import Demand
KW Export Demand
Max Current Demand
Max kVA Demand
Max KW Import Demand
Max KW Export Demand
Run Hour
On Hour
Number of Interruptions
Phase Reversal Indication ( 4 wire only )
V1 THD*
V2 THD*
V3 THD*
I1 THD
I2 THD
I3 THD
System Voltage THD
System Current THD
Pictorial representation of Phaser Diagram (4 wire only)
Pictorial representation of Voltage Waveform
Pictorial representation of Current Waveform
Pictorial representation of VA Waveform per phase (4 wire only)
KW
KW
Amps
KVA
KW
KW
Hours
Hours
Counts
%
%
%
%
%
%
%
%
*Note : THD Parameters are L-N in case of 3P 4W & L-L in case of 3P 3W .
5
2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens out of
several screens. These screens form particular submenu may be scrolled through one at a time
in incremental order by touching the “ key ” and in decremental order by touching “ key ”
on that screen. Viewing of any individual parameter with large reading (eg. shown
of Line to neutral Voltage L2 in sub meau 2 screen 13) is also possible by touching that
particular parameter.
SUBMENU 1: SYSTEM
Screen 1: System Parameters
(System Voltage, System
Current, System Active Power)
SYSTEM PARAMETERS
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
239.6
VL2
VL2
VL2
5.001
3.592
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
V
KW
Angle
Max
A
KWhPh B
Demand
Screen 4: Pictorial
Representation of Phaser
Diagram (For 4 wire only)
0
Capacitive
-P,+Q
0
180
-P,-Q
VL2
VL2
VL2
Inductive
270
MAIN
MAIN
MAIN
MAIN
90
Inductive
+P,+Q
+P,-Q
0.000
0.000
0.000
Capacitive
0
124.5
1.500
VL1
VL2
VL3
IL1
0
0
IL2
IL3
1
2
3
SYSTEM
VOLTAGE
VOLTAGE
VOLTAGE
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
V/Div
A/Div
V
V
V
A
A
A
Screen 2: System Max.
Values (System Voltage,
System Current)
SYSTEM Max. VALUE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
0.000
0.000
0.000
KVA
239.9
VL2
VL2
5.005
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
V
Min
Angle
Max
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
KVAh
Ph Y
%THD
V
V
V
A
KWhPh B
Demand
Screen 5 :
System Run Hour
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM RUN HOUR
000001.19
VL2
VL2
VL2
0.000
0.000
0.000
hrs
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
Screen 3: System
Min. Values (System Voltage,
System Current)
V
x1000
SYSTEM Min. VALUES
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
0.000
0.000
0.000
239.2
4.998
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
V
KW
VBR
x1000
V
V
V
P.F.
A
Screen 6 :
System ON Hour
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM ON HOUR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
000005.18
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
hrs
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVVV
V
V
6
Screen 7 : Screen 8 :
System Interruptions
System FrequencySystem Power Factor
Screen 9 :
SYSTEM INTERRUPTIONS
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
VL2
VL2
VL2
00000012
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVVV
V
V
Screen 10 :
System % THD
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM % THD
VL2
VL2
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
VL2
VL2
VL2
A
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
SYSTEM
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV
%
V
V
V
%
Phase Sequence Error
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM FREQUENCY
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
Screen 11 :
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV
Hz
V
V
V
Screen 12 : Phase Sequence
System Power
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM POWER
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
MAIN
MAIN
MAIN
MAIN
kVAr
kVA
kW
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVVV
V
V
SUBMENU 2 : VOLTAGE
Screen 13 : Line-Neutral Voltage
(For 4 wire only)
(Displayed after touching any where
in the L2 row shown in screen 13)
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM POWER FACTOR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
1.000
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
( 4 wire only )
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
Correct
VVVV
VVVV
VVVVV
V
V
Phase Sequence
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
L1-L2-L3
VL2
VL2
VL2
0.000
0.000
0.000
CONNECTIONS ARE CORRECT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVVV
V
V
Phase L2 Line-Neutral Voltage
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
ERROR
VL2
VL2
VL2
0.000
0.000
0.000
NOTE : WRONG PHASE SEQUENCE.
PLEASE CHECK YOUR CONNECTIONS.
0.000
0.000
0.000
VL2
VL2
VL2
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
L1
239.5
VL2
L2
VL2
L3
MAIN
MAIN
0.000
239.6
0.000
239.3
0.000
VVVV
VVVV
VVVVV
V
V
VOLTAGE
VOLTAGE
VVVV
VVVV
V
V
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
VOLTAGE
PHASE L2
239.6
V
BACK
7
Line-Line Voltage
Screen 15 : Phase Voltage THDScreen 14 :
Screen 15 : Line Voltage THD
(In case of 4 wire)(In case of 3 wire)
LINE-NEUTRAL VOLTAGE
LINE-LINE VOLTAGE
VL2
VL2
L12
0.000
415.1
VL2
L23
0.000
414.9
0.000
415.2
VL2
L31
MAIN
MAIN
Screen 16 : Pictorial representation
of Voltage Waveform (Only accessed
VOLTAGE
VOLTAGE
VVVV
VVVV
V
V
SUBMENU 3 : CURRENT
Screen 17 : Line Current
through voltage submenu list)
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
L3 PHASE WAVEFORM
62.25
MAIN
V/Div
POWER
210.4
DEG
49.94
Hz
116.5
V
42.43
A
2.500
ms/Div
SUBMENU 5 : ENERGY
Screen 33 :
Active Energy Import
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
ACTIVE ENERGY IMPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.0000000
VL2
VL2
VL2VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
kWh
0.000
0.000
0.000
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVVV
V
V
Screen 34 :
Screen 35 :
Active Energy Export Reactive Energy Import
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
ACTIVE ENERGY EXPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.0000000
VL2
VL2
VL2
0.000
0.000
0.000
kWh
0.000
0.000
0.000
VL2
VL2
VL2
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVVV
V
V
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
REACTIVE ENERGY IMPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.0000000
VL2
VL2
VL2
kVArh
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVVV
V
V
Screen 37 : Screen 38 :
Apparent Energy
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
APPARENT ENERGY
0.000
0.000
0.000
0.0000000
0.000
0.000
0.000
kVAh
0.000
0.000
0.000
VL2
VL2
VL2
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
Ampere Hour
AMPERE HOUR
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.0000000
VL2
VL2
VL2
0.000
0.000
0.000
kAh
0.000
0.000
0.000
VL2
VL2
VL2
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVVV
V
V
Screen 36 :
Reactive Energy Export
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
REACTIVE ENERGY EXPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.0000000
VL2
VL2
VL2
kVArh
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVVV
V
V
10
Parameter Screens
MAIN MENU
A
A
SYSTEM
COMMUNICATION
PARAMETERS
VOLT AGE
A
B
SYSTEM
SYSTEM TYPE
(Sec 3.2.1.1)
PARAMETERS
Max. V OLTAGE
PT PRIMARY
(Sec 3.2.1.2)
And CURRENT
Line to Neutral *
VOLTAGE
Line to Line
VOLTAGE
Min. VOLT AGE
PT SECONDARY
(Sec 3.2.1.3)
PHASER
CT PRIMARY
DIAGRAM *
And CURRENT
RUN HOUR
INTERRUPTIONS
FREQUENCY
(Sec 3.2.1.4)
CT SECONDARY
(Sec 3.2.1.5)
DEMAND
INTEGRATION
ON HOUR
TIME
No. OF
AUTO SCROLL
(Sec 3.2.1.7)
LOW CURR.
SYSTEM
NOISE CUTOFF
NOTE:SCREENS MARKED WITH * ARE AVAILABLE
VOLTAGE
(Sec 3.2.2.3)
% THD
VOLTAGE
(Sec 3.2.2.3)
WAVEFORM
CT SECONDARY
POWER FACTOR
(Sec 3.2.1.5)
DEMAND
THD.VOLT AGE
INTEGRATION
TIME
AND CURRENT
SYSTEM
AUTO SCROLL
(Sec 3.2.1.7)
POWER
LOW CURR.
PHASE
NOISE CUTOFF
SEQUENCE *
A
B
RESET
CURRENT
Line Current
Neutral Current *
LINE CURRENT
% THD
CURRENT
WA VEFORM
(Sec 3.2.2.3)
ONLY IN 4W SYSTEM (NOT IN 3 WIRE SYSTEM)
OPTIONS
POWER
(Sec 3.2.4)
WAVEFORM *
L1 PHASE
POWER *
L2 PHASE
POWER *
L3 PHASE
POWER *
PHASE
ANGLE *
PHASE
POWER FACTOR *
CURRENT
DEMAND
APP ARENT
DEMAND
IMPORT
ACTIVE DEMAND
EXPORT
ACTIVE DEMAND
L1 PHASE
CHANGE
PASSWORD
ENERGY
(Sec 3.1)
ACTIVE ENERGY
ACTIVE ENERGY
REACTIVE ENERGY
REACTIVE ENERGY
APP ARENT
ENERGY
AMPERE
AA
IMPORT
EXPORT
IMPORT
EXPORT
HOUR
L2 PHASE
WAVEFORM *
L3 PHASE
WAVEFORM *
11
Setup Parameter Screens
PASSWORD
(Sec 3.1)
ENTER
SYSTEM
SYSTEM
PARAMETERS
PARAMETERS
(Sec 3.2.1)
(Sec 3.2.1)
SYSTEM TYPE
(Sec 3.2.1.1)
PT PRIMARY
(Sec 3.2.1.2)
PT SECONDARY
(Sec 3.2.1.3)
CT PRIMARY
(Sec 3.2.1.4)
CT SECONDARY
(Sec 3.2.1.5)
DEMAND
INTEGRATION
TIME
c 3.2.1.
(Se
6)
AUTO SCROLL
(Sec 3.2.1.7)
COMMUNICATION
PARAMETERS
PARAMETERS
(Sec 3.2.2)
Rs485 ADDRESS
(Sec 3.2.2.1)
RS485
RS485
BAUD RATE
BAUD RATE
(Sec 3.2.2.2)
(Sec 3.2.2.2)
RS485 PARITY
(Sec 3.2.2.3)
RESET
PARAMETERS
(Sec 3.2.3)
OUTPUT
OPTIONS
(Sec 3.2.4)
RESET ALL
RESET DEMAND PARAMETERS
RESET ALL ENERGIES
RESET MAX VOLTAGE & CURRENT
RESET MIN VOLTAGE & CURRENT
RESET RUN-HOUR,ON-HOUR
RESET AUX INTERRUPT COUNT
Select any option by
touching on it.
CHANGE
PASSWORD
(Sec 3.1.1)
ANALOG OUTPUT 1
ANALOG OUTPUT 1
(Analog 1 parameter
selection)
(Acc. T o Table 2)
(Sec 3.2.4.3)
BRIGHTNESS
& CONTRAST
(Sec 3.2.5)
LOW CURR.
NOISE CUTOFF
(Sec 3.2.1.8)
ENERGY ON
RS485
(Sec 3.2.1.9)
ENERGY DIGIT
RESET COUNT
(Sec 3.2.1.10)
ANALOG OUTPUT 2
ANALOG OUTPUT 2
(Analog 2 parameter
selection)
cc.
(A
To Table 2)
(Sec 3.2.4.4)
12
3. Programming
The following sections comprise step by step procedures for configuring the instrument for
individual user requirements.
To access the set-up screens touch on the “ SETUP ” icon in Main Menu. This will take the
User into the Password Protection Stage(Section 3.1).
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up screens, by default
password is “0000”.
Password protection is enable by selecting any four digit number.
After touching “ SETUP” icon Password protection screen is
SETUP
ENTER PASSWORD
12
4
789
0
3
5
6
BACK
DEL
ENTER
displayed. Screen consists of 0 to 9 digit input keypad for entering
the password very similar to any calculator in touchscreen mobile.
“Enter Password” is displayed on screen at start so that user can
enter password using displayed keypad.
SETUP
1
12
4
789
0
3
5
6
BACK
DEL
ENTER
Touching “ key ” will display 1 in display area, similary user can
1
enter remaining 3 digits.
For deleting any digit while entering password, user can touch
DEL
“ key”.
13
SETUP
1234
DEL
12
4
789
0
PASSWORD ACCEPTED
12
4
789
0
PASSWORD REJECTED.
12
4
7
0
3
5
6
BACK
SETUP
3
5
6
BACK
SETUP
3
5
6
89
BACK
ENTER
DEL
ENTER
DEL
ENTER
After entering the complete password user needs to confirm password
by touching “ key”.
ENTER
Password confirmed.
If Entered password is correct then “Password Accepted” is displayed
on screen & user will enter into setup menu.
Password Incorrect.
If Entered password is wrong then Password “Rejected” is displayed
on screen & user need to re-enter the password
PASSWORD
PRESS ENTER TO TRY AGAIN
DEL
12
4
789
0
3
5
6
ENTER
BACK
After wrong password is entered, user needs to touch “ key” for
ENTER
trying another password.
14
3.1.1 Change Password
Change Password Option is the second last option in list of “SETUP”
PASSWORD
ENTER CURRENT PASSWORD
DEL
12
4
789
0
ENTER NEW PASSWORD
12
4
789
0
PASSWORD CHANGED
12
4
789
0
3
5
6
PASSWORD
3
5
6
PASSWORD
3
5
6
ENTER
BACK
DEL
ENTER
BACK
DEL
ENTER
BACK
submenu, so can be accessed by a simple touch anywhere in “Change
Password” row.
In this screen user first need to enter the current password.
After input of correct password,“PASSWORD ACCEPTED”is displayed
& now user can enter the new 4 digit password.
New Password confirmed.
After entering new password user needs to touch “
key” to confirm.
After confirming “PASSWORD CHANGED” is displayed on
screen, which ensures successful changing of the password.
ENTER
3.2 Menu selection.
After entering in the SUBMENU 6 - SETUP, user will be asked to enter password & after input of
correct password list of following parameters will be displayed on screen :-
3.2.1 SYSTEM PARAMETERS
3.2.2 COMMUNICATION PARAMETERS
15
3.2.3 RESET PARAMETERS
3.2.4 OUTPUT OPTIONS
3.2.5
BRIGHTNESS & CONTRAST
Touching on SYSTEM PARAMETER will open the system parameters list screen. Then these
screens from particular parameter may be scrolled through one at a time in incremental order by
touching the “ key” and in decremental order by touching “ key” on given touch screen.
3.2.1 System Parameters Selection
After entering in the “SYSTEM PARAMETERS”, List of following parameters will be display :-
3.2.1.1 SYSTEM TYPE
3.2.1.2 PT PRIMARY(L-L)
3.2.1.3 PT SECONDARY(L-L)
3.2.1.4 CT PRIMARY
3.2.1.5 CT SECONDARY
3.2.1.6 DEMAND INTEGRATION TIME
3.2.1.7 AUTO SCROLL
3.2.1.8 LOW CURRENT NOISE CUTOFF
3.2.1.9 ENERGY ON RS485
3.2.1.10 ENERGY DIGIT RESET COUNT
3.2.1.1 System Type
This screen is used to set the system type.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM TYPE
3-PHASE 3 WIRE
VL2
VL2
VL2
VL2
VL2
VL2
FOR 3 PHASE DELTA CONNECTED LOAD
VL2
VL2
VL2
3-PHASE 4 WIRE
FOR 3 PHASE STAR CONNECTED LOAD
0.000
0.000
0.000
VL2
VL2
VL2
OKBACK
MAINMAINMAINMAINMAINMAIN
Note : If system type is changed, relay parameter selection & analog output
selection will be set to NONE.
Two types: 3 phase 3 wire & 3 phase 4 wire system are displayed
on screen. Touching radio buttom in front of particular type will select
that type.
OK
Touch on “ key” will confirm the system type.
Touching the “ key” will keep the old selected setting and will
BACK
return to previous menu.
16
3.2.1.2 Potential Transformer Primary Value
The nominal full scale voltage will be displayed as Line to Line Voltages for all system types.
This screen can be accessed only from system parameters list menu.
Here again 0 to 9 digit input keypad is provided to set value of PT
Primary, & user can confirm this value with a simple touch “
key”. “ key” is used to multiply value by 1000.
K
ENTER
In case presently displayed Potenial Transformer Primary value
together with the Current Transformer Primary value, previously set,
would result in a maximum power of greater than 666.6 MVA per
phase, “Invalid value” will be displayed. Then the valid range will be displayed.
If value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter
.
3.2.1.3 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained from the
the Transformer when the potential transformer(PT)primary is supplied with the voltage defined
in 3.2.1.2 potential transformer primary voltage. The ratio of full scale primary to full scale
secondary is defined as the transformer ratio.
Valid range of PT secondary setting value is from 241.0 to 480.0.
for 415 VL-L. Please refer the table bellow for different ranges.
If value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter
.
Potential Transformer secondary ranges for various Input Voltages
The nominal Full Scale Current that will be displayed as the Line currents. This screen
enables the user to display the Line currents inclusive of any transformer ratios, the values
displayed represent the Current in Amps.
This screen can be accessed only from system parameters list menu.
maximum power of greater than 666.6 MVA, “invalid value” will be displayed. Example:
If primary value of PT is set as 692.8kV L-L (max value) then primary value of Current is
restricted to 1157A.
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and
120% of nominal voltage, i.e, 462.96 MVA nominal power per phase.
Here again 0 to 9 digit input keypad is provided to set value of CT
Primary & user can confirm this value with a simple touch on “
key”. “ key” is used to multiply value by 1000.
K
ENTER
In case presently displayed Current Transformer Primary Value
together with the Potential Transformer Primary Value results in a
18
Valid range of CT primary setting value is from 1 to 9999. If value
outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter
3.2.1.5 Current Transformer Secondary Value
.
This screen is used to set the secondary value for Cur
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
OKBACK
MAINMAINMAINMAINMAINMAIN
Two options: 1 AMPERE & 5 AMPERE are displayed on screen.
VVV
VVV
VVV
VVV
VVV
VVVV
V
V
V
V
V
Touching radio button in front of particular option will select that
option.
Touch on “ key” will confirm the setting. Touching the
BACK
“ key” will keep the old selected setting and will return
OK
to previous menu.
3.2.1.6 Demand Integration Time
This screen is used to set the period over which current and
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
DEMAND INTEGRATION TIME
CT SECONDARY
1 AMPERE
8 MINUTES
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
15 MINUTES
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
20 MINUTES
0.000
0.000
0.000
0.000
0.000
0.000
30 MINUTES
0.000
0.000
0.000
0.000
0.000
0.000
OKBACK
MAINMAINMAINMAINMAINMAIN
power
readings are to be integrated.
Four options: 8, 15, 20, 30 Minutes are displayed on screen. Touching
radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting.
Touching the “ key” will keep the old selected setting and will
OK
BACK
return to previous menu.
rent Transfor
mer.
19
3.2.1.7 Auto Scrolling
This screen allows user to enable screen scrolling. Seven options :
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
AUTO - SCROLL
1 AMPERE
ALL
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VOLTAGE
POWER
VL2
VL2
VL2
VL2
VL2
VL2
Touching the “ key” will keep the old selected setting and will return to previous menu.
SYSTEM
0.000
0.000
0.000
0.000
0.000
0.000
CURRENT
ENERGY
NONE
0.000
0.000
0.000
0.000
0.000
0.000
OKBACK
MAINMAINMAINMAINMAINMAIN
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
BACK
ALL, SYSTEM, VOLTAGE, CURRENT
POWER ENERGY & NONE are displayed on screen. Touching radio
button in front of particular option will select that option. Selecting
particular option means, only screen which are under that submenu
will be scrolled automatically. Selecting NONE will disable Auto-Scroll.
Touch on “ key” will confirm the setting.
OK
While in Auto-scrolling mode, touch sense for entire screen will be disabled except for the
top right most corner where “A” symbol would be displayed stating that meter is in Autoscroll mode.
Touching on “A” will show two options “ON” and “OFF”. Touching on “ON” will continue
auto scrolling & touching on “OFF” will stop auto-scrolling & return to normal mode.
3.2.1.8 Low Current noise cutoff.
This screen allows the user to set Low noise current cutoff in mA.
Two options, 0 MILLI-AMPERE & 30 MILLI-AMPERE are displayed on
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
LOW CURRENT NOISE CUTOFF
1 AMPERE
0 MILLI-AMPERE
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
5 AMPERE
30 MILLI-AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
screen. Touching radio button in front of particular option will
select that option.
Touch on “ key” will confirm the setting.
OK
OKBACK
MAINMAINMAINMAINMAINMAIN
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
20
3.2.1.9 ENERGY ON RS485.
This screen enable user to set energy in terms of Wh / kWh / MWh on Rs485 Output
depending as per the user’s requirement .This setting is applicable for all types of energy..
T hree options: WATT,KILO-WATT & MEGA-WATT are displayed on
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
ENERGY ON RS485
1 AMPERE
WATT (W)
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
5 AMPERE
KILO-WATT (KW)
VL2
VL2
VL2
VL2
VL2
VL2
MEGA-WATT (MW)
screen. Touching radio button in front of particular option will
select that option.
Touch on “ key” will confirm the setting.
OK
OKBACK
MAINMAINMAINMAINMAINMAIN
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
Note : Default value is set to ‘WATT’ i.e. Energy on Modbus will be in
terms of Wh/VArh/VAh/Ah respectively.
3.2.1.10 ENERGY DIGIT RESET COUNT (ROLLOVER COUNT)
This screen
rollover to zero depending on the setting of Wh, kWh & Mwh in Energy on RS485 option.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
ENERGY DIGIT RESET COUNT
1 AMPERE
7 DIGITS
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
9 DIGITS
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
11 DIGITS
13 DIGITS
Touching the “ key” will keep the old selected setting and will return to previous menu.
Note :
1) Default value of energy digit reset count is set to “14” i.e. if energy cross the
14 digit count it will rollover to zero.
2) If Energy on RS485 is set to kW & energy digit reset count is set to 12, Energy
screen on display will show “-------” i.e. energy overflow when energy cross the
11 digit count.
3) If Energy on RS485 is set to MW & energy digit reset count is set to 9, Energy
screen on display will show “-------” i.e. energy overflow when energy cross the
8 digit count.
enables the user for setting maximum energy count after which energy will
If Energy on RS485 is in WATT then rollover count can be from
CT SECONDARY
8 DIGITS
10 DIGITS
12 DIGITS
14 DIGITS
OKBACK
MAINMAINMAINMAINMAINMAIN
BACK
7 to 14 DIGITS.
If Energy on RS485 is in KILO-WATT then rollover count can be from
7 to 12 DIGITS.
If Energy on RS485 is in MEGA-WATT then rollover count can be from
7 to 9 DIGITS.
Touching radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting.
OK
21
3.2.2 Communication Parameter Selection :
After entering in the “COMMUNICATION PARAMETERS” list of following parameters
will be displayed
3.2.2.1 RS485 ADDRESS
3.2.2.2 RS485 BAUD RATE
3.2.2.3 RS485 PARITY
3.2.2.1 RS485 Address Setting
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
RS485 ADDRESS
ENTER RS485 ADDRESS
DEL
12
4
789
0
3
5
6
ENTER
BACK
the user to set RS485 address parameter for the instrument.
This screen can be accessed only from Communication
Parameters List menu.
Here again 0 to 9 digit input keypad is provided to set RS485
address & user can confirm this value with a simple touch on
This screen applies to the RS 485 output only This screen allows
“ key”.
ENTER
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
RS485 ADDRESS
INVALID VALUE
12
5
4
789
0
3
6
BACK
DEL
ENTER
The range of allowable address is 1 to 247.
If value outside the range is entered, it will dispay “INVALID VALUE”
followed by the correct range of parameter.
3.2.2.2 RS485 Baud Rate
This screen allows the user to set Baud Rate of RS 485 port.
Four options: 2400, 4800, 9600, 19200 Bauds are displayed on
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
RS485 BAUD RATE
1 AMPERE
2400
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
4800
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2VL2
VL2
VL2
VL2
VL2
VL2
9600
0.000
0.000
0.000
0.000
0.000
0.000
19200
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
OKBACK
MAINMAINMAINMAINMAINMAIN
V
V
V
V
V
V
screen. Touching radio button in front of particular option will
select that option.
Touch on “ key” will confirm the setting.
Touching the “ key” will keep the old selected setting
and will Return to previous menu.
.
OK
BACK
22
3.2.2.3 RS485 Parity & Stop bit Selection
This screen allows the user to set Parity & number of stop bits.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RS485 PARITY & STOP BITS
1 AMPERE
ODD PARITY WITH ONE STOP BIT
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
NO PARITY WITH ONE STOP BIT
5 AMPERE
NO PARITY WITH TWO STOP BIT
VL2
VL2
VL2
VL2
VL2
VL2
EVEN PARITY WITH ONE STOP BIT
VL2
VL2
VL2
VL2
VL2
VL2
OKBACK
MAINMAINMAINMAINMAINMAIN
Four options: ODD PARITY WITH ONE STOP BIT, NO PARITY
WITH ONE STOP BIT, NO PARITY WITH TWO STOP BITS,
EVEN PARITY WITH ONE STOP BIT are displayed on screen.
Touching radio button in front of particular option will select that
option.
Touch on “ key” will confirm the setting.
OK
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
3.2.3 Reset Parameter Selection
3.2.3.1 Resetting Parameter
These screens allow the users to reset all the parameters
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RESET PARAMETERS
RESET ALL
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
RESET DEMAND PARAMETERS
RESET ALL ENERGIES
VL2
VL2
VL2
0.000
0.000
0.000
RESET MAX VOLTAGE & CURRENT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RESET PARAMETERS
RESET MAX VOLTAGE & CURRENT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
RESET MIN VOLTAGE & CURRENT
VL2
VL2
VL2
0.000
0.000
0.000
RESET RUN-HOUR, ON-HOUR
0.000
0.000
0.000
RESET AUX INTERRUPT COUNT
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SETUP
VOLTAGE
VOLTAGE
VOLTAGE
SETUP
VVVV
VVVV
VVVVV
V
V
VVVV
VVVV
VVVVV
V
V
eg;- Energy, Min, Max, Demand, Run hour, On hour, No. of
Interrupts. Touching “ down” key scrolls list in upward
direction.
This screen is displayed after repeatedly touching “ down.” key
Touching “ Up” key scrolls list in downward direction.
For resetting specific parameter user can touch on that parameter.
23
Touching on any parameter will display the confirmation dialog, now
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RESET PARAMETERS
RESET ALL
RESET ALL ENERGIES
0.000
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
RESET DEMAND PARAMETERS
ARE YOU SURE YOU WANT TO RESET ALL
THE STORED ENERGIES
VL2
VL2
VL2
0.000
0.000
0.000
YESNO
RESET MAX VOLTAGE & CURRENT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SETUP
VVVV
VVVV
VVVVV
V
V
a touch on “ key” will confirm the resetting of that particular
YES
Parameter.
Touching on “ key” will move back to Reset parameters menu
NO
For example resetting All Energies will display a confirmation
dialog as shown in the screen beside.
User can reset other parameters in similar manner.
3.2.4. Output Option selection menu
After entering in the “OUTPUT OPTIONS”, List of following parameters will be displayed :-
3.2.4.3 ANALOG-1 ( Model 301 only)
3.2.4.4 ANALOG-2 ( Model 301 only)
3.2.4.3 Parameter setting for Analog Output 1 ( Only on Model 301 )
This option allows the user to set analog output 1 to corresponding measured parameter. A
simple touch on “ANALOG-1” row will open screen having list of parameters.( Refer Table 2
“Parameter fo Analog output”)
Touch on “ key” will confirm setting.
Touching the “ key” will keep the old selected setting and will return to previous menu.
OK
BACK
3.2.4.4 Parameter setting for Analog Output 2 ( Only on Model 301 )
This option allows the user to set analog output 2 to corresponding measured parameter. A
simple touch on “ANALOG-2” row will open screen having list of parameters.( Refer Table 2
“Parameter fo Analog output”)
Touch on “ key” will confirm setting.
Touching the “ key” will keep the old selected setting and will return to previous menu.
OK
BACK
24
Parameter
No.
Parameter
3P 4W3P 3W
Range
Analog Output
51
52
53
54
101
102
103
113
VA DEMAND
VA MAX DEMAND
CURRENT DEMAND
CURRENT MAX DEMAND
INPUT VOLTAGE L12
INPUT VOLTAGE L23
INPUT VOLTAGE L31
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
(1) For Frequency 0% corresponds to 40 Hz & 100% corresponds to 70 Hz.
3.2.5 Brightness & Contrast
The brightness & contrast of the TFT LCD screen can be varied by
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
BRIGHTNESS & CONTRAST
VL2
VL2
VL2
VL2
0.000
VL2
VL2VL2
VL2
DEFAULT
MAIN
MAIN
MAIN
0.000
BRIGHTNESS
0.000
0.000
DEFAULT
CONTRAST
OK
VOLTAGE
VOLTAGE
VOLTAGE
BACK
VVVV
VVVVV
V
the user by sliding the sliders. Touching the “ key” will
confirm the current brightness contrast setting.
Touching the DEFAULT key will set brightness and contrast as per
factory setting. Touching the BACK key will move back to the
setup menu without making any changes.
OK
4 Touch screen calibration
This instrument is able to perform calibration to ensure the proper operation of the units
touch screen functionalities. The calibration procedure will correct the problem of out of
tolerance touch screen malfunction. Note that errors corrected by this calibration
procedure are specific only to touch screen operation.
For starting touch screen calibration, touch the screen any where
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
IMPORTANT.
Performing touch
1 AMPERE
screen calibration.
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
Press & hold the center
5 AMPERE
of the filled circle
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
Touch screen to
continue.
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
for 1 sec at system reset. After that touch screen calibration will
start & the message shown besides will be displayed. Touch the
screen to continue.
25
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
1 AMPERE
Press
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
on the filled
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
Hold
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
5 AMPERE
5 AMPERE
the filled
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
0.000
Hold the filled circle
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
OK
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
V
V
V
V
V
V
LINE-NEUTRAL VOLTAGE
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
Release
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
Hold the filled
5 AMPERE
5 AMPERE
the filled
circle
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
OK
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
Follow the instructions displayed. Press & hold the center of the filled red circle for at least
2 seconds. Release when message for release is being displayed. For accurate results try
to touch the center of the filled circle.
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
V
V
V
V
V
V
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
1 AMPERE
Press
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
on the filled
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
1 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
Error in calibration
Touch screen to
5 AMPERE
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
re-calibrate.
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
Repeat the same
procedure for the
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
remaining 3
corner circles.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
Hold screen for 1 sec
after system reset to
1 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
REPEAT the calibration
5 AMPERE
procedure.
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
Touch screen to
continue.
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
After successful
calibration, the
message shown
besides would be
displayed. Touch the
screen to continue.
If the touch screen was not calibrated properly, “Error in
calibration”message would be shown & the user will be asked to
VVVV
VVVV
VVVV
VVVV
VVVV
VVVVV
V
V
V
V
V
recalibrate the touch screen. In such case the meter will retain the
previously stored touch - screen calibration values unless a
successful calibration is being performed.
26
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
ERROR
VL2
VL2
VL2
0.000
0.000
0.000
NOTE : WRONG PHASE SEQUENCE.
PLEASE CHECK YOUR CONNECTIONS.
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVVV
V
V
5. Phase Rotation Error screen
Meter shows phase rotation error if the phase sequence
R-Y-B (L1-L2-L3) is not maintained This screen indicates that
Phase sequence is incorrect. User must check this screen in order to
get correct readings when meter is connected.
V
VRY
KVAr
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
Angle
KVAr
Angle
VYB
VRY
VYB
Sys
A
KVA
Min
KW
VBR
Max
V
Sys
A
KVA
Min
KW
VBR
Max
VVVV
VVVV
VVVVV
V
V
VVVV
VVVV
VVVVV
V
V
Demand
Demand
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
L1-L2-L3
VL2
VL2
VL2
0.000
0.000
0.000
CONNECTIONS ARE CORRECT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
INPUT ABSENT
VL2
VL2
VL2
0.000
0.000
0.000
PLEASE CHECK YOUR CONNECTIONS.
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
Correct Phase sequence
x1000
IN
KVArh
x1000
KVAh
%THD
x1000
x1000
KVArh
Ph R
x1000
KVAh
%THD
x1000
Ph R
Ph Y
Ph Y
KWhPh B
This Screen indicates the phase sequence connected to
KAh
Hz
meter is correct. If phase sequence is wrong this screen is useful
to get correct phase sequence by interchanging connection &
P.F.
KWh
verifying it with screen.
Ph B
This Screen indicates that either of the phases or all three
IN
KAh
phases (Voltages) are absent.
Hz
P.F.
6. Run Hour
This Screen shows the total no. of hours the load is connected
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM RUN HOUR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
000001.19
VL2
VL2
VL2
0.000
0.000
0.000
hrs
0.000
0.000
0.000
VL2
VL2
VL2
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
VVVV
VVVV
VVVVV
V
V
Even if the Auxiliary supply is interrupted count of Run hour will be
maintained in internal memory & displayed in the format
“hours. min”.
it indicates 1 hour & 19 minutes.
After 999999.59 run hours display restart from zero.
To reset run hour manually see section Resetting Parameter 3.2.3.1
For example if Displayed count is 000001.19 hrs
27
7. On Hour
This Screen shows the total no. of hours the Axillary Supply is ON.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM ON HOUR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
000005.18
VL2
VL2
VL2
0.000
0.000
0.000
hrs
0.000
0.000
0.000
VL2
VL2
VL2
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
VVVV
VVVV
VVVVV
V
V
Even if the Auxiliary supply is interrupted count of On hour will be
maintained in internal memory & displayed in format “hours. min.”
For example if Displayed count is 000005.18 hrs it indicates
15 hours & 18 minutes.
After 999999.59 On hours display will restart from zero.
To reset On hour manually see section Resetting Parameter 3.2.3.1
8. Number of Interruption
This Screen Displays the total no. of times the Axillary Supply was
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM INTERRUPTIONS
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
VL2
VL2
VL2
00000012
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVVV
V
V
Interrupted. Even if the Auxiliary supply is interrupted count will be
maintained in internal memory
To reset No of Interruption manually see section Resetting
Parameter 3.2.3.1
9. Analog Output ( optional ) :
This module provides two d.c. isolated outputs .There are two output options
1) Two 4 - 20mA outputs , internally powered .
On both modules the output signals are present on pins A1(Analog Output 1) &
A2 (Analog Output 2)
28
These outputs can be individually assigned to represent any one of the measured and
displayed Parameters.
All settlings are user configurable via the user interface screen. See Analog o/p selection
( section 3.2.4.3 & section 3.2.4.4 ) for details .
* Note : Refer diagrams 1
Diagram 1 : ( 4 -20 mA )
0
0 (12 mA)
0
270 (8 mA)
0
181 (4 mA)
0
90 (16 mA)
0
180 (20 mA)
29
TABLE 2 : Parameter for Analog
Parameter
No.
0
1
2
2
3
4INPUT CURRENT IL1
5
6
7
Parameter
None
INPUT VOLTAGE L1
INPUT VOLTAGE L2
INPUT VOLTAGE L3
INPUT CURRENT IL2
INPUT CURRENT IL3
ACTIVE POWER L1
3P 4W 3P 3W
9
9
9
9
9
9
99
99
99
99
9
8
Range
Analog Output
–
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 120 %
30
Parameter
No.
Parameter
3P 4W3P 3W
Range
Analog Output
8ACTIVE POWER L2
9ACTIVE POWER L3
10APPARENT POWER L1
11
12
13
14
15REACTIVE POWER L3
16POWER FACTOR L1
17
18POWER FACTOR L3
19PHASE ANGLE L1
20
21
22
24
27
29APPARENT POWER SUM
31REACTIVE POWER SUM
32
34PHASE ANGLE AVG
36
43WATT DEMAND IMPORT
44
45
46
APPARENT POWER L2
APPARENT POWER L3
REACTIVE POWER L1
REACTIVE POWER L2
This instrument supports MODBUS (RS485) RTU protocol ( 2-wire ).
Connection should be made using twisted pair shielded cable. All "A" and "B" connections
are daisy chained together. The screens should also be connected to the “Gnd” terminal.
To avoid the possibility of loop currents, an Earth connection should be made at one point
on the network. Loop (ring) topology does not require any termination load. Line topology
may or may not require terminating loads depending on the type and length of cable used.
The impedance of the termination load should match the impedance of the cable and be at
both ends of the line. The cable should be terminated at each end with a 120 ohm
(1/4 Watt min.) resistor.
RS 485 network supports maximum lenght of 1.2km. Including the Master, a maximum of 32
instruments can be connected in RS 485 network. The permissible address range for the
instrument is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.
The maximum latency time for the instrument is 200ms i.e. this is the amount of time that
can pass before the first response character is output.
After sending any query through software ( of the Master) , it must allow 200ms of time to
elapse before assuming that the instrument is not going to respond. If slave does not
respond within 200 ms, Master can ignore the previous query and can issue fresh query
to the slave.
33
The each byte in RTU mode has following format:
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of
the message
Format of Data Bytes
4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754 )
Most significant byte first (Alternative least significant first)
Error Checking Bytes
Byte format
Communication Baud Rate is user selectable from the front panel between 2400, 4800,
9600, 19200 bps.
Read content of read /write location ( 4X )
Read content of read only location ( 3X )
Set the content of read / write locations ( 4X )
Exception Cases : An exception code will be generated when the instrument receives
ModBus query with valid parity & error check but which contains some other error
( e.g. Attempt to set floating point variable to an invalid value ) The response generated
will be “Function code” Ored with HEX (80H ). The exception codes are listed below
34
01
Illegal function
This function code is not supported by the instrument.
02
03
Accessing 3 X register for reading measured values:
Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses
of 3X registers (Parameters measured by the instruments).
Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Illegal Data
Address
Illegal Data
Value
Attempt to access an invalid address or an attempt to read
or write part of a floating point value
Attempt to set a floating point variable to an invalid value
Example :
To read parameter ,
Volts 3 : Start address= 04 (Hex) Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding
the 20 parameter limit will cause a ModBus exception code to be returned.
Query :
01 (Hex)
Device
Address
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low : Least significant 8 bits of starting address of the parameter requested.
04 (Hex)
Function
Code
00 (Hex)
Start Address
High
04 (Hex)00 (Hex)
Start Address
Low
Number of
Registers Hi
02 (Hex)30 (Hex) 0A (Hex)
Number of
Registers Lo
CRC
Low
CRC
High
35
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Response: Volt3 (219.25V)
01 (Hex)
Device
Address
Byte Count : Total number of data bytes received.
04 (Hex)
Function
Code
04 (Hex)
Byte
Count
43 (Hex)5B (Hex)
Data Register 1
High Byte
Data Register 1
Low Byte
41 (Hex)21 (Hex)6F (Hex)
Data Register 2
High Byte
Data Register 2
Low Byte
CRC
Low
9B (Hex)
CRC
High
Data register 1 High Byte : Most significant 8 bit of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bit of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent on parameter.)
Table 4 : 3 X register addresses (measured parameters)
Each setting is held in the 4X registers. ModBus code 03 is used to read the current setting
and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register addresses.
Example : Reading System type
System type : Start address= 0A (Hex) Number of registers = 02
Note : Number of registers = Number of Parameters x 2
39
Query :
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low : Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
01 (Hex)
03 (Hex)
00 (Hex)
0A (Hex)
00 (Hex)
02 (Hex)
E4 (Hex)
09 (Hex)
(Note : Two consecutive 16 bit register represent one parameter.)
Response : System Type ( 3 phase 4 wire = 3 )
Device Address
Function Code
Byte Count
Data Register1 High Byte
Data Register1 Low Byte
01 (Hex)
03 (Hex)
04 (Hex)
40 (Hex)
40 (Hex)
40
Data Register2 High Byte
00 (Hex)
Data Register2 Low Byte
CRC Low
CRC High27 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
00 (Hex)
EE (Hex)
(Note : Two consecutive 16 bit register represent one parameter.)
Example : Writing System type
System type : Start address= 0A (Hex) Number of registers = 02
Query : ( Change System type to 3phase 3wire = 2 )
Device Address
01 (Hex)
Function Code
Starting Address Hi
Number of Registers Hi
Number of Registers Hi
10 (Hex)
00 (Hex)
0A (Hex)Starting Address Lo
00 (Hex)
02 (Hex)
41
Byte Count
04 (Hex)
Data Register-1 High Byte
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-2 Low Byte
CRC Low
CRC High
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
40 (Hex)
00 (Hex)
00 (Hex)
00 (Hex)
60 (Hex)
10 (Hex)
(Note : Two consecutive 16 bit register represent one parameter.)
Response:
Device Address
Function Code
01 (Hex)
10 (Hex)
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo02 (Hex)
CRC Low
CRC HighCA (Hex)
00 (Hex)
0A (Hex)
00 (Hex)
61 (Hex)
42
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low : Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Min Reset
Max Reset
Analog Out 1- Para Sel
Analog Out 2- Para Sel
PT Primary
CT Primary
Wp
Wp
R/Wp
R/Wp
Wp
Wp
R/Wp
R/Wp
R/Wp
R/Wp
00
00
00
00
00
00
00
00
00
00
0E
10
12
14
18
1A
1C
1E
20
22
43
Address
(Register)
40037
40039
40041
40043
40045
Parameter
No.
19
20
21
22
23
Parameter
System Power
Energy digit reset count
CT Secondary
PT Secondary
4007136Password
4007940
30mA Noise Current Elimination
Read / Write
R
R/Wp
R/Wp
R/Wp
R/Wp
R/W
R/Wp
Modbus Start Address Hex
H
H
High Byte
00
00
00
00
00
00
00
Low Byte
24
26
28Register Order/Word Order
2A
2C
46
4E
44
Explanation for 4 X register :
AddressParameterDescription
40001
40003
40005
Demand Reset
Demand Period
Energy display
on Modbus
40007System Voltage
40009System Current
40011System Type
Demand Reset is used to reset the Demand parameter. A value
of zero must be Written to this register to reset the Demand
period. Writing any other value will return an error.
Demand period represents demand time in minutes. The
applicable value are 8,15,20 or 30. Writing any other value will
return an error.
This address is used to set energy display on MODBUS in Wh,
KWh & Mwh. Write one of the following value to this address.
1 = Energy in Wh.
3 = Energy in MWh.
2 = Energy in KWh.
This address is read only and displays System Voltage
This address is read only and display System Current
This address is used to set the System type.
Write one of the follow value to this address.
2 = 3 Phase 3 Wire
3 = 3 Phase 4 Wire.
Writing any other value will return error.
40015Reset Energy
Counter
This address is used to reset the Energy Counter.
Write zero value to this register to reset the energy counter.
Writing any other value will return an error.
45
AddressParameter
Description
40017
40019
40021
40025
Run/On Hour &
Interruption
reset
Rs485 Set-up
Code
Node
Address
This address is used to reset the Run/ON hour & number
of Interruption. Write zero value to this register to reset
the Run/On hour & number of Interruption.
Writing any other value will return an error.
This address is used to set the baud rate, Parity, Number of
stop bits. Refer to Table 6 for details.
This register address is used to set Device address
between 1 to 247.
Min - ResetThis address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters.
Writing any other value will return an error.
40027
40029
Max - ResetThis address is used reset the Max parameters value.
Write Zero value to this register to reset the Max parameters.
Writing any other value will return an error.
Analog Out 1Para Set
This address is used to set the parameter for Analog Output 1.
Write one of the parameter no. As per the options given in
Table 2 for Analog Output Parameters.
46
AddressParameterDescription
40031
40033
40035
40037
40039
40041
Analog Out 2Para Set
PT PrimaryThis address allows the user to set PT Primary value.
CT Primary
Sys PowerSystem Power (Read Only) is the Nominal system power base on
Energy digit
Reset Count
Word OrderWord Order controls the order in which the instrument receives
This address is used to set the parameter for Analog Output 2.
Write one of the parameter no. AS per the option given in
Table 2 for Analog Output Parameters.
The maximum settable value is 692.8kV L-L
depends on the phase 666.6MVA Restriction of power
combined with CT primary.
This address allows the user to set CT Primary Value.
The maximum settable value is 9999 & also depends on the per
phase 666.6MVA Restriction of power combined with PT primary.
the values of Nominal system volts and Nominal system current.
This address is used to set the rollover count for energy. If
Energy on Rs485 is in Wh rollover count can be from 7 to 14.
If it is in KWh then rollover count can be from 7 to 12 & for MWh
rollover count can be from 7 to 9.
or sends floating - point numbers:- normal or reversed register
order. In normal mode, the two registers that make up a floating
point numbers are sent most significant bytes first.
In reversed register mode, the two registers that make up
a floating point numbers are sent least significant bytes first.
To set mode, write the value ‘2141.0’ into this registerthe instrument will detect the order used to send this value and
set that order for all ModBus transaction invoving floating point
numbers.
47
AddressParameterDescription
40043
40045
40071
CT secondary
This address is used to read and write the CT secondary value
write one of the following values this address.
1=1A CT secondary
5=5A CT secondary
writing any other value will return an error.
PT secondaryThis address is used to read and write the PT secondary value.
Ref Table for the range of PT secondary settable value in
Section 3.2.1.3
Password
This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999.
1) If password lock is present & if this location is read it will
return zero.
2) If Password lock is absent & if this location is read it will
return One.
3) If password lock is present & to disable this lock
first send valid password to this location then write “0000”
to this location.
4) If password lock is present & to modify 4X parameter
first send valid password to this location so that 4X parameter
will be accessible for modification.
5) If for in any of the above case invalid password is sent then
meter will return exceptional error 2.
4007930mA Noise
current
Elimination
This address is used to activate or de-activate the 30 mA noise
current elimination write
0-Deactivate
30 (Decimal)-Activate
Writing any other value will return an error.
48
Table 6 : RS 485 Set-up Code
Baud Rate
19200
19200
19200
Baud Rate
19200
9600
9600
9600
9600
4800
4800
4800
4800
2400
2400
2400
2400
Parity
NONE
NONE
EVEN
Parity
ODD
NONE
NONE
EVEN
ODD
NONE
NONE
EVEN
ODD
NONE
NONE
EVEN
ODD
Stop Bit
01
02
01
Stop Bit
01
01
02
01
01
01
02
01
01
01
02
01
01
Decimal value
12
13
14
Decimal value
15
08
09
10
11
04
05
06
07
00
01
02
03
NOTE :
Codes not listed in the table above may give rise to unpredictable results including loss of
communication. Excise caution when attempting to change mode via direct Modbus writes.
49
This instrument contains the 20 user assignable registers in the address range of 0x200
(30513) to 0x226 (30551) (see Table 9).
Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the
instrument can be mapped to these 20 user assignable registers.
Parameters (3X registers addresses ) that resides in different locations may be accessed
by the single request by re-mapping them to adjacent address in the user assignable
registers area.
The actual address of the parameters ( 3X registers addresses) which are to be assessed
via address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 10).
Table 10 : User Assignable mapping register ( 4X registers)
0C
0E
10
12
14
18
1A
1C
1E
20
22
24
26
Parameter
(Register)
40513
40514
40515
40516
40517
40518262
40519263
40520264
Number.
257
258
259
260
261
Mapping Register
Mapped Add for register #0x0200
Mapped Add for register #0x0202
Mapped Add for register #0x0204
Mapped Add for register #0x0206
Mapped Add for register #0x0208
Mapped Add for register #0x020A
Mapped Add for register #0x020C
Mapped Add for register #0x020E
Modbus Start Address (Hex)Address
High ByteLow Byte
02
02
02
02
02
02
02
02
00
01
02
03
04
05
06
07
51
Address
(Register)
40521
40522
40523
40524
40525
40526
40527
40528
40529
40530
40531
40532
Parameter
Number.
265
266
267
268
269
270
271
272
273
274
275
276
Mapped Register
Mapped Add for register #0x0210
Mapped Add for register #0x0212
Mapped Add for register #0x0214
Mapped Add for register #0x0216
Mapped Add for register #0x0218
Mapped Add for register #0x021A
Mapped Add for register #0x021C
Mapped Add for register #0x021E
Mapped Add for register #0x0220
Mapped Add for register #0x0222
Mapped Add for register #0x0224
Mapped Add for register #0x0226
Modbus start Address (Hex)
High ByteLow Byte
02
02
02
02
02
02
02
02
02
02
02
02
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
Example :
Assigning parameter to user assignable registers
To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E)
through user assignable register assign these addresses to 4x register (Table 10 ) 0x0200
and 0x0201 respectively.
Assigning Query:
Device Address
Function Code
01 (Hex)
10 (Hex)
02 (Hex)Starting Address Hi
00 (Hex)Starting Address Lo
00 (Hex)*Number of Register Hi
02 (Hex)*Number of Register Lo
52
Byte Count
Data Register-1 High Byte
Data Register-1 Low Byte
04 (Hex)
00 (Hex)
02 (Hex)
Voltage 2 *
}
(3X Address 0x0002)
Data Register-2 High Byte
Data Register-2 Low Byte
CRC Low
CRC High
00 (Hex)
1E (Hex)
CB (Hex)
07 (Hex)
Power Factor 1 *
}
(3X Address 0x001E)
Response :
Device Address
Function Code
Start Address High
Start Address Low
Number of Register Hi
Number of Register Lo
CRC Low
CRC High
Reading Parameter data through User Assignable Registers:
In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x200 and
0x201(Table10) which will point to user assignable 3x registers 0x200 and 0x202 (Table 9).
So to read Voltage2 and Power Factor1 data reading query should be as below.
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
Start Address High : Most significant 8 bits of starting address of User assignable register.
Start Address low : Least significant 8 bits of starting address of User assignable register.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
**Note : Two consecutive 16 bit register represent one parameter.
Since two parameters are requested four registers are required
Response : (Volt2 = 219.30 / Power Factor1 = 1.0)
Device Address
Function Code
Byte count
Data Register-1 High Byte
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-2 Low Byte
01 (Hex)
04 (Hex)
02 (Hex)
00 (Hex)
00 (Hex)
04 (Hex) **
F0 (Hex)
71 (Hex)
01 (Hex)
04 (Hex)
08 (Hex)
43 (Hex)
5B (Hex)
4E (Hex)
04 (Hex)
Voltage 2 Data
}
54
Data Register-3 High Byte
Data Register-3 Low Byte
Data Register-4 High Byte
Data Register-4 Low Byte
CRC Low
CRC High
3F (Hex)
80 (Hex)
00 (Hex)
00 (Hex)
79 (Hex)
3F (Hex)
Power Factor 1Data
}
(Starting
Address)
0x200
0x201
0x202
0x203
0x212
0x213
User Assignable mapping Registers
( 4X Registers Table 10 )
Voltage 2 (0x0002)
Power Factor 1 (0x001E)
Wh Import (0x0048)
Frequency (0x0046)
Current 1 (0x0006)
VAh (0x0050)
(Starting
Address)
0x200
0x202
0x204
0x206
0x224
0x226
User Assignable Data Registers
( 3X Registers Table 9 )
0x200
(16 bit)
0x202
(16 bit)
0x204
(16 bit)
0x206
(16 bit)
0x224
(16 bit)
0x226
(16 bit)
0x201
(16 bit)
0x203
(16 bit)
0x205
(16 bit)
0x 207
(16 bit)
0x225
(16 bit)
0x227
(16 bit)
55
To get the data throught User assignable Register use following step:
1)
Assign starting addresses(Table3) of parameters of interest to a
“User assignable mapping registers” in a sequence in which they are to be accessed
(see section “Assigning parameter to user assignable registers”)
2) Once the parameters are mapped data can be acquired by using
“User assignable data register “ Starting address . i.e to access data of Voltage2,
Power factor1,Wh import, Frequency send query with starting address 0x200
with number of register 8 or individually parameters can be accessed
for example if current1 to be accessed use starting address 0x212.
(See section Reading Parameter data through User Assignable Registers)
12. Phaser Diagram :
Capacitive
2
-
+
180 degrees (-1.000)
Inductive
90 degrees (0.000)
270 degrees (0.000)
Inductive
0 degrees (+1.000)
Capacitive
+
-
4
56
Connections Quadrant
Sign of
Active
Power ( P )
Sign of
Reactive
Power ( Q )
Sign of
Power
Factor ( PF )
Inductive /
Capacitive
Import
Import
Export
Export
1+ P
4
2
3
+ P
- P
- P
+ Q
- Q
+ Q
- Q
+
+
-
-
L
C
C
L
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
When the instrument displays Active power ( P )with “ + ” ( positive sign ) ,
the connection is “ Import ”.
When the instrument displays Active power ( P )with “ - ” ( negative sign ) ,
the connection is “Export”.
13. Installation
PANEL
SLIDE IN THIS DIRECTION
AND LOCK
Mounting is by four side clamps, slide the side
clamps through side slot till side clamp gets firmly
locked in a groove (Refer fig.) Consideration should
be given to the space required behind the
Meter
instrument to allow for bends in the connection cables.
57
As the front of the enclosure conforms to IP54 it is protected from water spray from all directions,
additional protection to the panel may be obtained by the use of an optional panel gasket.
The terminals at the rear of the product should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range
-20 to 70ºC. Vibration should be kept to a minimum and the product should
not be mounted where it will be subjected to excessive direct sunlight.
Caution
1.In the interest of safety and functionality this product must be installed by
a qualified engineer, abiding by any local regulations.
2.Voltages dangerous to human life are present at some of the terminal
connections of this unit. Ensure that all supplies are de-energised before
attempting any connection or disconnection.
3.These products do not have internal fuses therefore external fuses must
be used to ensure safety under fault conditions.
13.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed to a
good code of practice for EMC in industrial environments, e,g,
1.Screened output and low signal input leads or have provision for fitting RF suppression
components, such as ferrite absorbers, line filters ect., in the event that RF fields cause
problems.
Note: it is good practice to install sensitive electronic instruments that are performing critical
functions, in EMC enclosures that protect against electrical interference which could cause a
disturbance in function.
2.Avoid routing leads alongside cables and products that are, or could be, a source of
interference.
58
3. To protect the product against permanent damage, surge transients must be limited to
2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source.
The unit has been designed to automatically recover in the event of a high level of
transients. In extreme circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via
Current Transformers only, where one side is grounded.
4. ESD precautions must be taken at all times when handling this product.
13.2 Case Dimension and Panel Cut Out
3.78”
96mm
3.78”
96mm
FRONT DISPLAY
AREA
3.15”
80mm
3.62”
92mm
PANEL CUTOUT
MAX PANEL THICKNESS 0.18”, 5mm
13.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure.
Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
regulations. Terminal for both Current and Voltage inputs will accept up to 3mm2 x 2
diameter cables.
Note : It is recommended to use wire with lug for
connection with meter.
3.62”
92mm
59
13.4 Auxiliary Supply
The instrument should ideally be powered from a dedicated supply, however it may be powered
from the signal source, provided the source remains within the limits of the chosen auxiliary voltage.
13.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuses.
13.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with local
regulations.
14. Connection Diagrams
3-PHASE 3-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
L1
L2
L3
N
5
8
2
3
6 7 9
4
L N
AUX
SUPPLY
S1
P1
S1
P1
15. Specification :
System
3 Phase 3 Wire / 4 Wire programmable at site
3-PHASE 4-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
5
8
2
L1
L
L2
O
A
L3
D
N
11 1
P1
3
6 7 9
4
S1
S1
P1
13
14
L N
AUX
SUPPLY
L
S1
P1
O
A
D
60
Inputs
Nominal input voltage (AC RMS)
(Three wire and Four wire)
Max continuous input voltage
Max short duration input voltage
Phase-Neutral 63.5 / 133 / 239.6 / 254 V
Line-Line 110 / 230 / 415 / 440 V
120% of Rated Value
2 x Rated Value
(1s application repeated 10 times
at 10s intervals)
Nominal input voltage burden
0.2VA approx. per phase
Nominal input current 5A AC rms
Max continuous input current 120% of Rated Value
Nominal input current burden 0.6VA approx. per phase
Max short duration current input
20 x Rated Value (1s application repeated
5 times at 5 min. intervals)
System CT primary values
Std. Values from 1 to 9999A
(1 or 5 Amp secondaries)
Auxiliary
Standard nominal Auxillary
supply voltages & Frequency
a.c. supply voltage tolerance +10 % / -10 % of Rated Value
d.c. supply voltage tolerance +10 % / -10 % of Rated Value
100 - 250VAC- DC (45-66Hz),
12 - 48V DC
L-N
L-L
a.c. supply frequency range 45 to 66 Hz
a.c. supply burden 6.5 V A
d.c. supply burden 3W
61
Operating Measuring Ranges
Voltage
Current5 .. 120 % of Rated Value
Frequency
Power Factor
5 .. 120 % of Rated Value
40 .. 70 Hz
0.5 Lag ... 1 ... 0.8 Lead
Accuracy
Accuracy 1:
Voltager 0.5 % of range
Current
Frequency
Active Power
Re- Active Power
Apparent Power
Active Energy
Re -Active Energy
Apparant Energy
Power Factor
Angle
Analog Output
Total Harmonic Distortion
Neutral Current
r 0.5 % of range
0.15% of mid frequency
r 0.5 % of range
r 0.5 % of range
r 0.5 % of range
r 1.0 % of range
r 1.0 % of range
r 1.0 % of range
r 1 % of Unity
r 1 % of range
r 1 % of Output end value
r 1 %
r 4 % of range.
Accuracy 0.5:
Voltager 0.5 % of range
Current
Frequency
Active Power
Re- Active Power
Apparent Power
Active Energy
r 0.5 % of range
0.15% of mid frequency
r 0.5 % of range
r 0.5 % of range
r 0.5 % of range
r 0.5 % of range
62
Re -Active Energy
Apparent Energy
Power Factor
Angle
Analog Output
Total Harmonic Distortion
Neutral Current
Accuracy 0.2:
r 0.5 % of range
r 0.5 % of range
r 1 % of Unity
r 1 % of range
r 1 % of Output end value
r 1 %
r 4 % of range
Voltage
Current
Frequency
Active Power
Re- Active Power
Apparent Power
Active Energy
Re - Active Energy
Apparant Energy
Power Factor
Angle
Analog Output
Total Harmonic Distortion
Neutral Current
Reference conditions for Accuracy :
Reference temperature
Input frequency
Input waveform
Auxiliary supply voltage
Auxiliary supply frequency
Voltage Range
± 0.2 % of range
± 0.2 % of range
0.15 % of mid frequency
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 1 % of Unity
± 1 % of range
± 1 % of Output end value
± 1 %
± 4 % of range
23ºC ± 2ºC
50 or 60Hz ± 2%
Sinusoidal (distortion factor 0.005)
Rated Value ± 1%
Rated Value ± 1 %
50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
63
Current Range
Power
Power Factor / Phase Angle40... 100% of Nominal Current &
10... 100% of Nominal Value.
20... 100% of Nominal Value for THD.
cosØ / sinØ = 1
For Active / Reactive Power & Energy
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.
50... 100% of Nominal Voltage.
Nominal range of use of influence quantities for measurands
Voltage
Current
Input frequency
Temperature
Auxiliary supply voltage
Auxiliary supply frequency
Temperature Coefficient
(For Rated value range of use
0... 50ºC )
Error change due to variation of an
influence quantity
Display
TFT LCD
Update
Controls
User Interface
50 .. 120 % of Rated Value
10 .. 120 % of Rated Value
Rated Value ± 10 %
-20 to 70º
Rated Value ± 10 %
Rated Value ± 10 %
0.025% / ºC for Voltage (50..120% of Rated Value)
0.05% / ºC for Current (10..120% of Rated Value)
2 * Error allowed for the reference
2.2 kV RMS 50 Hz for 1 minute
between all electrical circuits
-20 to 70 ºC
-30 to +80 ºC
0 .. 90 % RH
3 minute (minimum)
15g in 3 planes
10 .. 55 Hz, 0.15mm amplitude
Enclosure ( front only )
Enclosure
Style
Material
Terminals
Depth
Weight
IP 54 as per IEC 60529
96mm x 96mm DIN Quadratic
Polycarbonate Housing ,
Self extinguish & non dripping as per UL94 V-0
Screw-type terminals
< 80 mm
0.620 kg Approx.
65
ModBus ( RS 485 ) Option :
Protocol
Baud Rate
Analog Output Option :
Linear
ModBus ( RS 485 )
19200 , 9600 , 4800 or 2400
( Programmable )
Odd or Even, with 1 stop bit,Parity
Or None with 1 or 2 stop bits
4 ... 20mA dc into 0 - 500 ohm
Uni-directional, internally powered.
66
16. Connection for Optional RS 485 / Analog Output
( rear view of the instrument )
1. RS 485 + Two Analog Output
Gnd
A1 A2
4 -20 mA
Gnd
BA
RS 485
Gnd
67
WARRANTY
Dear Sir,
You are now the privileged owner of Multi Function Meter / accessories,
a product that rank the first of its kind in the world.
Company provides 36 months warranty from the original date of Purchase
against defective material and workmanship.
In the unlikely event of failure of this meter / accessories within the warranty
period, Company undertakes to get the meter / accessories repaired free of
charge, Please handover the meter / accessories to the dealer / stockist from
whom you have purchased along with this card and relevant Cash memo /
Invoice. This warranty entitles you to bring the meter / accessories at your
cost to the nearest stockist / dealer collect it after repairs.
NO TRANSPORTATION CHARGE WILL BE REIMBURSED
The warranty is not valid in following cases:
1) Warranty card duly signed and stamped and original Cash memo/Invoice is not
send along with meter / accessories.
2) Complete warranty card is not presented to authorized person at the time of
repairs.
3) Meter / accessories is not used as per the instructions in the user manual.
4) Defect caused by misuse, negligence, accidents, tampering and Acts of God.
5) Improper repairing by any person not authorized by the company.
6) Any sort of Modification, Alteration is made in electrical circuitry.
7) Seal provided inside is broken.
68
In case of dispute to the validity of the warranty, the decision of services center
will be final.
If you bought this meter / accessories directly fro the company, and if you notice
transit damage, then you must obtain the insurance surveyor report and forward it.
Thank you.
(To be filled by authorised dealer)
Model No.
Serial Number
Date of Purchase
Cash Memo / Invoice No.
Dealers Signature
Dealer Stamp
:
:
:
:
:
:
Scope of supply
1) Side Clamp
2) Connecters
3) User Manual
4) Warranty Card
*5) Test Certificate
*As per customer requirements
69
Caution, risk of electric shock.
Attention, risque de choc électrique.
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and
is intended to describe the correct method of installation for this product. However, Company has no control over the field conditions
which influence product installation.
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Company only
obligations are those in Company standard Conditions of Sale for this product and in no case will Company be liable for any other
incidental, indirect or consequential damages arising from the use or misuse of the products.
Simpson Electric Company
520 Simpson Avenue
Lac Du Flambeau, WI 54538-0099 (USA)
Web: www.simpsonelectric.com
Contact: +1 715-588-3311
Manual Part No. 06-118318
Edition 2, 05/18
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.