Simpson Amik 301, Amik 300 Operating Manual

®
USA SINCE 1936
RELIABILITY BEYOND MEASURE
Operating Manual
Amik 300 / 301
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product. However, Company has no control over the field conditions which influence product installation. It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Company only obligations are those in Company standard Conditions of Sale for this product and in no case will Company be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products.
Cover Page 2
Three Phase (3W/4W)
Three Phase Touch Screen Digital Multi-fuction Meter
Installation & Operating Instructions
Section
1. Introduction
2. Measurement Reading Screens
3. Programming
Contents
3.1 Password Protection
3.1.1 Change Password
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 System type
3.2.1.2 Potential transformer Primary value
3.2.1.3 Potential transformer Secondary value
3.2.1.4 Current transformer Primary value
3.2.1.5 Current transformer Secondary valuealue
3.2.1.6 Demand integration time
3.2.1.7 Auto Scrolling
3.2.1.8 Low current noise cutoff
3.2.1.9 Energy On RS 485
3.2.1.10 Energy digit reset count
3.2.2 Communication Parameter selection screen
3.2.2 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection
1
3.2.3 Reset Parameter selection screen
3.2.3.1 Resetting Parameter
3.2.4 Output Option selection screen (menu)
3.2.4.3 Parameter setting for Analog Output-1
3.2.4.4 Parameter setting for Analog Output-2
3.2.5 Brightness & Contrast
4. Touch screen calibration.
5. Phase Rotation Error screen.
6. Run - Hour.
7.
8. Number of Interruption
9. Analog Output
On - Hour.
11.
RS 485 (Modbus) output
11.1
User Assignable modbus Registers
2
12.
Phaser Diagram
13. Installation
13.1
EMC installation Requirements
13.2
Case Dimensions and Panel Cut-out
13.3
Wiring
13.4 Auxilary Supply
13.5
Fusing Earth / Ground Connections
13.6
14.
15.
Connection Diagrams Specification
16.
Connection for Optional RS 485 / Analog Output
1. Introduction
This instrument is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the measurement of important electrical parameters like AC voltage, AC Current, Frequency, Power, Energy (Active / Reactive / Apparent). The instrument integrates accurate measurement of technology (All Voltage & Current measurement are True RMS up to 15th Harmonic) with 320x240 Pixels touch screen TFT LCD display.
This instrument can be configured and programmed at site for the following:
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
MAIN MENU
MAIN MENU
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
5 AMPERE
VOLTAGESYSTEM CURRENT
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2 VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VOLTAGESYSTEM CURRENT
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
POWER ENERGY SETUP
POWER ENERGY SETUP
OK
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
V
V
V
V
V
V
V
V
V
V
V
V
PT Primary, PT Secondary, CT Primary, CT Secondary (5A or 1A) and 3 phase 3W or 3 Phase 4W system.
The front panel has a 3.5” Touch Screen through which the user can move across the available measurement reading, reset the energy, Min/Max (System Voltage and System Current) and configure the product setting.
3
TABLE 1:
Measured Parameters
System Voltage System Current Voltage VL1-N(4wire only) Voltage VL2-N(4wire only) Voltage VL3-N(4wire only) Voltage VL1-L2 Voltage VL2-L3 Voltage VL3-L1 Current L1 Current L2 Current L3 Neutral Current ( 4 wire only ) Frequency Active Power (System / Phase (4 wire only) ) Reactive Power (System / Phase (4 wire only) ) Apparent Power (System / Phase (4 wire only) )
Power Factor (System / Phase (4 wire only) ) Phase Angle ( Phase (4 wire only) ) Active Import Energy (8 Digit resolution)
Units of
Measurement
Volts
Amps
Volts Volts Volts Volts Volts
Volts Amps Amps Amps Amps
Hz
Kwatts
KVAr
KVA
Degree
kWh Active Export Energy (8 Digit resolution) Reactive Import Energy (8 Digit resolution)
Reactive Export Energy (8 Digit resolution) Apparent Energy (8 Digit resolution)
Ampere Hour (8 Digit resolution)
4
kWh
kVArh kVArh
kVAh
KAh
Measured Parameters
Units of
Measurement
AmpsCurrent Demand
KVA Demand KVA KW Import Demand
KW Export Demand Max Current Demand
Max kVA Demand Max KW Import Demand
Max KW Export Demand Run Hour
On Hour Number of Interruptions
Phase Reversal Indication ( 4 wire only ) V1 THD*
V2 THD* V3 THD* I1 THD
I2 THD I3 THD
System Voltage THD System Current THD
Pictorial representation of Phaser Diagram (4 wire only) Pictorial representation of Voltage Waveform Pictorial representation of Current Waveform
Pictorial representation of VA Waveform per phase (4 wire only)
KW
KW
Amps
KVA
KW
KW
Hours
Hours
Counts
% % %
% %
% % %
*Note : THD Parameters are L-N in case of 3P 4W & L-L in case of 3P 3W .
5
2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens out of several screens. These screens form particular submenu may be scrolled through one at a time in incremental order by touching the “ key ” and in decremental order by touching “ key ” on that screen. Viewing of any individual parameter with large reading (eg. shown of Line to neutral Voltage L2 in sub meau 2 screen 13) is also possible by touching that particular parameter.
SUBMENU 1: SYSTEM
Screen 1: System Parameters
(System Voltage, System
Current, System Active Power)
SYSTEM PARAMETERS
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
239.6
VL2
VL2
VL2
5.001
3.592
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
V
KW
Angle
Max
A
KWh Ph B
Demand
Screen 4: Pictorial
Representation of Phaser
Diagram (For 4 wire only)
0
Capacitive
-P,+Q
0
180
-P,-Q
VL2
VL2
VL2
Inductive
270
MAIN
MAIN
MAIN
MAIN
90
Inductive
+P,+Q
+P,-Q
0.000
0.000
0.000
Capacitive
0
124.5
1.500 VL1 VL2 VL3
IL1
0
0
IL2
IL3 1 2 3
SYSTEM
VOLTAGE
VOLTAGE
VOLTAGE
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
V/Div A/Div
V V V A A A
Screen 2: System Max.
Values (System Voltage,
System Current)
SYSTEM Max. VALUE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
0.000
0.000
0.000
KVA
239.9
VL2
VL2
5.005
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
V
Min
Angle
Max
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
KVAh
Ph Y
%THD
V
V
V
A
KWh Ph B
Demand
Screen 5 :
System Run Hour
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM RUN HOUR
000001.19
VL2
VL2
VL2
0.000
0.000
0.000 hrs
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
Screen 3: System
Min. Values (System Voltage,
System Current)
V
x1000
SYSTEM Min. VALUES
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
0.000
0.000
0.000
239.2
4.998
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
V
KW
VBR
x1000
V
V
V
P.F.
A
Screen 6 :
System ON Hour
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM ON HOUR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
000005.18
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
hrs
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV V
V
V
6
Screen 7 : Screen 8 :
System Interruptions
System Frequency System Power Factor
Screen 9 :
SYSTEM INTERRUPTIONS
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
VL2
VL2
VL2
00000012
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV V
V
V
Screen 10 :
System % THD
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM % THD
VL2
VL2
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
VL2
VL2
VL2
A VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
SYSTEM
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV
% V
V
V
%
Phase Sequence Error
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM FREQUENCY
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
Screen 11 :
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV
Hz
V
V
V
Screen 12 : Phase Sequence
System Power
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM POWER
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2 VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
MAIN
MAIN
MAIN
MAIN
kVAr
kVA
kW
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV V
V
V
SUBMENU 2 : VOLTAGE
Screen 13 : Line-Neutral Voltage
(For 4 wire only)
(Displayed after touching any where
in the L2 row shown in screen 13)
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM POWER FACTOR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
1.000
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
( 4 wire only )
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
Correct
VVVV
VVVV
VVVV V
V
V
Phase Sequence
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
L1-L2-L3
VL2
VL2
VL2
0.000
0.000
0.000
CONNECTIONS ARE CORRECT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV V
V
V
Phase L2 Line-Neutral Voltage
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
ERROR
VL2
VL2
VL2
0.000
0.000
0.000
NOTE : WRONG PHASE SEQUENCE. PLEASE CHECK YOUR CONNECTIONS.
0.000
0.000
0.000
VL2
VL2
VL2
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
L1
239.5
VL2
L2
VL2
L3
MAIN
MAIN
0.000
239.6
0.000
239.3
0.000
VVVV
VVVV
VVVV V
V
V
VOLTAGE
VOLTAGE
VVVV
VVVV V
V
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
VOLTAGE
PHASE L2
239.6
V
BACK
7
Line-Line Voltage
Screen 15 : Phase Voltage THDScreen 14 :
Screen 15 : Line Voltage THD
(In case of 4 wire) (In case of 3 wire)
LINE-NEUTRAL VOLTAGE
LINE-LINE VOLTAGE
VL2
VL2
L12
0.000
415.1
VL2
L23
0.000
414.9
0.000
415.2
VL2
L31
MAIN
MAIN
Screen 16 : Pictorial representation
of Voltage Waveform (Only accessed
VOLTAGE
VOLTAGE
VVVV
VVVV
V
V
SUBMENU 3 : CURRENT
Screen 17 : Line Current
through voltage submenu list)
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
VOLTAGE WAVEFORM
116.5 Vrms
116.5 Vrms
116.5 Vrms
49.94
62.25
MAIN
V/Div
VOLTAGE
Screen 19:
Line Current %THD
Hz
2.500
ms/Div
Screen 20 : Pictorial representation
of Current Waveform
(Only accessed through
current submenu list)
PHASE VOLTAGE % THD
LINE-NEUTRAL VOLTAGE
VL2
VL2
L1
0.000
VL2
L2 VL2
L3
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VVVV
% V
% %
Screen 18 : Neutral Current
LINE-NEUTRAL VOLTAGE
LINE CURRENT
VL2
VL2
IL1
0.000
VL2
IL2 VL2
IL3
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
VOLTAGE
CURRENT
VVVV
A V
A A
LINE-NEUTRAL VOLTAGE
LINE VOLTAGE THD
VL2
VL2
L12 VL2
L23 VL2
L31
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
% %
%
(For 4 wire only)
NEUTRAL CURRENT
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
In
VL2
VL2
VL2 VL2
VL2
VL2
0.000
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
CURRENT
VVVV
VVVV
VVVV A
V
V
V
SUBMENU 4 : POWER
Screen 21 : L1 Phase Power
Reactive/Apparent/Active
(For 4 wire only)
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE CURRENT % THD
VL2
VL2
VL2
VL2
VL2
VL2
IL1
0.000
0.000
0.000
0.000
VL2
VL2
VL2
IL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
IL3
VOLTAGE
VOLTAGE
VOLTAGE
CURRENT
MAIN
MAIN
MAIN
MAIN
%
VVVV
VVVV
VVVV %
V
V
V %
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGECURRENT WAVEFORM
30.00
MAIN
A/Div
CURRENT
8
42.43 Arms
42.43 Arms
42.43 Arms
49.94 Hz
2.500
ms/Div
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
L1 PHASE POWER
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2 VL2
VL2
VL2
0.000
0.000
0.000
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
kVAr
kVA
POWER
VVVV
VVVV
VVVV V
V
V
kW
Screen 22 : L2 Phase Power Reactive/Apparent/Active
(For 4 wire only)
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
L2 PHASE POWER
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2 VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
MAIN
MAIN
MAIN
MAIN
kVAr
kVA
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV V
V
V
kW
Screen 23 : L3 Phase Power
Reactive/Apparent/Active
(For 4 wire only)
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
L3 PHASE POWER
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
VL2
VL2
VL2 VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
MAIN
MAIN
MAIN
MAIN
kVAr
kVA
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV V
V
V
kW
Screen 24 : Phase Angle
(Phase L1/L2/L3) (for 4W only)
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE ANGLE
VL2
VL2
VL2
VL2
VL2
VL2
L1
0.000
0.000
0.000
VL2
VL2
VL2
L2 VL2
VL2
VL2
L3
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
DEG DEG DEG
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV V
V
V
Screen 25 : Power Factor
(Phase L1/L2/L3) (for 4W only)
POWER FACTOR
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
L1
0.000
0.000
0.000
VL2
VL2
VL2
L2 VL2
VL2
VL2
L3
MAIN
MAIN
MAIN
MAIN
1.000
0.000
0.000
0.000
1.000
0.000
0.000
0.000
1.000
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV V
V
V
Screen 28 :
Import Active Demand
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
IMPORT ACTIVE DEMAND
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
Demand
VL2
VL2
VL2
Max
Demand
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV
kW
V
V
V
kW
Screen 26 :
Current Demand
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CURRENT DEMAND
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
Demand
VL2
VL2
VL2
Max
Demand
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV A
V
V
V A
Screen 29 :
Export Active Demand
EXPORT ACTIVE DEMAND
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
Demand
Max
Demand
MAIN
MAIN
MAIN
MAIN
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
POWER
kW kW
Screen 27 :
VA Demand
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VA DEMAND
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
Demand
VL2
VL2
VL2
Max
Demand
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
kVA kVA
VOLTAGE
VOLTAGE
VOLTAGE
POWER
VVVV
VVVV
VVVV V
V
V
Screen 30 : Pictorial representation
of L1 Phase Waveform (For 4 wire only)
(only accessed through power submenu list)
L1 PHASE WAVEFORM
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
210.4 DEG
49.94
Hz
116.5
V
42.43
62.25 V/Div
MAIN
POWER
A
2.500
ms/Div
9
Screen 31 : Pictorial representation L2 Phase Waveform (For 4 wire only)
(only accessed through power submenu list)
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
L2 PHASE WAVEFORM
62.25
MAIN
V/Div
POWER
210.4 DEG
49.94
Hz
116.5
V
42.43
A
2.500
ms/Div
Screen 32 : Pictorial representation L3 Phase Waveform (For 4 wire only)
(only accessed through power submenu list)
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
L3 PHASE WAVEFORM
62.25
MAIN
V/Div
POWER
210.4 DEG
49.94
Hz
116.5
V
42.43
A
2.500
ms/Div
SUBMENU 5 : ENERGY
Screen 33 :
Active Energy Import
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
ACTIVE ENERGY IMPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.0000000
VL2
VL2
VL2 VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
kWh
0.000
0.000
0.000
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV V
V
V
Screen 34 :
Screen 35 :
Active Energy Export Reactive Energy Import
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
ACTIVE ENERGY EXPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.0000000
VL2
VL2
VL2
0.000
0.000
0.000
kWh
0.000
0.000
0.000
VL2
VL2
VL2
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVV V
V
V
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
REACTIVE ENERGY IMPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.0000000
VL2
VL2
VL2
kVArh
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV V
V
V
Screen 37 : Screen 38 :
Apparent Energy
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
APPARENT ENERGY
0.000
0.000
0.000
0.0000000
0.000
0.000
0.000
kVAh
0.000
0.000
0.000
VL2
VL2
VL2
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
Ampere Hour
AMPERE HOUR
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.0000000
VL2
VL2
VL2
0.000
0.000
0.000
kAh
0.000
0.000
0.000
VL2
VL2
VL2
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVV V
V
V
Screen 36 :
Reactive Energy Export
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
REACTIVE ENERGY EXPORT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.0000000
VL2
VL2
VL2
kVArh
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
ENERGY
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV V
V
V
10
Parameter Screens
MAIN MENU
A
A
SYSTEM
COMMUNICATION
PARAMETERS
VOLT AGE
A
B
SYSTEM
SYSTEM TYPE
(Sec 3.2.1.1)
PARAMETERS
Max. V OLTAGE
PT PRIMARY
(Sec 3.2.1.2)
And CURRENT
Line to Neutral *
VOLTAGE
Line to Line
VOLTAGE
Min. VOLT AGE
PT SECONDARY
(Sec 3.2.1.3)
PHASER
CT PRIMARY
DIAGRAM *
And CURRENT
RUN HOUR
INTERRUPTIONS
FREQUENCY
(Sec 3.2.1.4)
CT SECONDARY
(Sec 3.2.1.5)
DEMAND
INTEGRATION
ON HOUR
TIME
No. OF
AUTO SCROLL
(Sec 3.2.1.7)
LOW CURR.
SYSTEM
NOISE CUTOFF
NOTE:SCREENS MARKED WITH * ARE AVAILABLE
VOLTAGE
(Sec 3.2.2.3)
% THD
VOLTAGE
(Sec 3.2.2.3)
WAVEFORM
CT SECONDARY
POWER FACTOR
(Sec 3.2.1.5)
DEMAND
THD.VOLT AGE
INTEGRATION
TIME
AND CURRENT
SYSTEM
AUTO SCROLL
(Sec 3.2.1.7)
POWER
LOW CURR.
PHASE
NOISE CUTOFF
SEQUENCE *
A
B
RESET
CURRENT
Line Current
Neutral Current *
LINE CURRENT
% THD
CURRENT
WA VEFORM
(Sec 3.2.2.3)
ONLY IN 4W SYSTEM (NOT IN 3 WIRE SYSTEM)
OPTIONS
POWER
(Sec 3.2.4)
WAVEFORM *
L1 PHASE
POWER *
L2 PHASE
POWER *
L3 PHASE
POWER *
PHASE
ANGLE *
PHASE
POWER FACTOR *
CURRENT
DEMAND
APP ARENT
DEMAND
IMPORT
ACTIVE DEMAND
EXPORT
ACTIVE DEMAND
L1 PHASE
CHANGE
PASSWOR D
ENERGY
(Sec 3.1)
ACTIVE ENERGY
ACTIVE ENERGY
REACTIVE ENERGY
REACTIVE ENERGY
APP ARENT
ENERGY
AMPERE
AA
IMPORT
EXPORT
IMPORT
EXPORT
HOUR
L2 PHASE
WAVEFORM *
L3 PHASE
WAVEFORM *
11
Setup Parameter Screens
PASSWORD
(Sec 3.1)
ENTER
SYSTEM
SYSTEM
PARAMETERS
PARAMETERS
(Sec 3.2.1)
(Sec 3.2.1)
SYSTEM TYPE
(Sec 3.2.1.1)
PT PRIMARY
(Sec 3.2.1.2)
PT SECONDARY
(Sec 3.2.1.3)
CT PRIMARY
(Sec 3.2.1.4)
CT SECONDARY
(Sec 3.2.1.5)
DEMAND
INTEGRATION
TIME
c 3.2.1.
(Se
6)
AUTO SCROLL
(Sec 3.2.1.7)
COMMUNICATION
PARAMETERS
PARAMETERS
(Sec 3.2.2)
Rs485 ADDRESS
(Sec 3.2.2.1)
RS485
RS485
BAUD RATE
BAUD RATE
(Sec 3.2.2.2)
(Sec 3.2.2.2)
RS485 PARITY
(Sec 3.2.2.3)
RESET
PARAMETERS
(Sec 3.2.3)
OUTPUT
OPTIONS
(Sec 3.2.4)
RESET ALL
RESET DEMAND PARAMETERS RESET ALL ENERGIES RESET MAX VOLTAGE & CURRENT
RESET MIN VOLTAGE & CURRENT RESET RUN-HOUR,ON-HOUR RESET AUX INTERRUPT COUNT
Select any option by touching on it.
CHANGE
PASSWORD
(Sec 3.1.1)
ANALOG OUTPUT 1
ANALOG OUTPUT 1
(Analog 1 parameter
selection)
(Acc. T o Table 2)
(Sec 3.2.4.3)
BRIGHTNESS
& CONTRAST
(Sec 3.2.5)
LOW CURR.
NOISE CUTOFF
(Sec 3.2.1.8)
ENERGY ON
RS485
(Sec 3.2.1.9)
ENERGY DIGIT
RESET COUNT
(Sec 3.2.1.10)
ANALOG OUTPUT 2
ANALOG OUTPUT 2
(Analog 2 parameter
selection)
cc.
(A
To Table 2)
(Sec 3.2.4.4)
12
3. Programming
The following sections comprise step by step procedures for configuring the instrument for individual user requirements.
To access the set-up screens touch on the “ SETUP ” icon in Main Menu. This will take the User into the Password Protection Stage(Section 3.1).
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up screens, by default
password is “0000”. Password protection is enable by selecting any four digit number.
After touching “ SETUP” icon Password protection screen is
SETUP
ENTER PASSWORD
12 4 789
0
3
5
6
BACK
DEL
ENTER
displayed. Screen consists of 0 to 9 digit input keypad for entering the password very similar to any calculator in touchscreen mobile. “Enter Password” is displayed on screen at start so that user can enter password using displayed keypad.
SETUP
1
12 4 789
0
3
5
6
BACK
DEL
ENTER
Touching “ key ” will display 1 in display area, similary user can
1
enter remaining 3 digits. For deleting any digit while entering password, user can touch
DEL
“ key”.
13
SETUP
1234
DEL
12 4 789
0
PASSWORD ACCEPTED
12 4 789
0
PASSWORD REJECTED.
12 4 7
0
3
5
6
BACK
SETUP
3
5
6
BACK
SETUP
3
5
6
89
BACK
ENTER
DEL
ENTER
DEL
ENTER
After entering the complete password user needs to confirm password by touching “ key”.
ENTER
Password confirmed.
If Entered password is correct then “Password Accepted” is displayed
on screen & user will enter into setup menu.
Password Incorrect.
If Entered password is wrong then Password Rejected” is displayed
on screen & user need to re-enter the password
PASSWORD
PRESS ENTER TO TRY AGAIN
DEL
12 4 789
0
3
5
6
ENTER
BACK
After wrong password is entered, user needs to touch “ key” for
ENTER
trying another password.
14
3.1.1 Change Password
Change Password Option is the second last option in list of “SETUP”
PASSWORD
ENTER CURRENT PASSWORD
DEL
12 4 789
0
ENTER NEW PASSWORD
12 4 789
0
PASSWORD CHANGED
12 4 789
0
3
5
6
PASSWORD
3
5
6
PASSWORD
3
5
6
ENTER
BACK
DEL
ENTER
BACK
DEL
ENTER
BACK
submenu, so can be accessed by a simple touch anywhere in “Change Password” row. In this screen user first need to enter the current password.
After input of correct password,“PASSWORD ACCEPTED”is displayed & now user can enter the new 4 digit password.
New Password confirmed.
After entering new password user needs to touch “ key” to confirm.
After confirming “PASSWORD CHANGED” is displayed on screen, which ensures successful changing of the password.
ENTER
3.2 Menu selection.
After entering in the SUBMENU 6 - SETUP, user will be asked to enter password & after input of correct password list of following parameters will be displayed on screen :-
3.2.1 SYSTEM PARAMETERS
3.2.2 COMMUNICATION PARAMETERS
15
3.2.3 RESET PARAMETERS
3.2.4 OUTPUT OPTIONS
3.2.5
BRIGHTNESS & CONTRAST
Touching on SYSTEM PARAMETER will open the system parameters list screen. Then these
screens from particular parameter may be scrolled through one at a time in incremental order by touching the “ key” and in decremental order by touching “ key” on given touch screen.
3.2.1 System Parameters Selection
After entering in the “SYSTEM PARAMETERS”, List of following parameters will be display :-
3.2.1.1 SYSTEM TYPE
3.2.1.2 PT PRIMARY(L-L)
3.2.1.3 PT SECONDARY(L-L)
3.2.1.4 CT PRIMARY
3.2.1.5 CT SECONDARY
3.2.1.6 DEMAND INTEGRATION TIME
3.2.1.7 AUTO SCROLL
3.2.1.8 LOW CURRENT NOISE CUTOFF
3.2.1.9 ENERGY ON RS485
3.2.1.10 ENERGY DIGIT RESET COUNT
3.2.1.1 System Type
This screen is used to set the system type.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM TYPE
3-PHASE 3 WIRE
VL2
VL2
VL2
VL2
VL2
VL2
FOR 3 PHASE DELTA CONNECTED LOAD
VL2
VL2
VL2
3-PHASE 4 WIRE FOR 3 PHASE STAR CONNECTED LOAD
0.000
0.000
0.000
VL2
VL2
VL2
OK BACK
MAINMAINMAINMAINMAINMAIN
Note : If system type is changed, relay parameter selection & analog output selection will be set to NONE.
Two types: 3 phase 3 wire & 3 phase 4 wire system are displayed on screen. Touching radio buttom in front of particular type will select that type.
OK
Touch on “ key” will confirm the system type. Touching the “ key” will keep the old selected setting and will
BACK
return to previous menu.
16
3.2.1.2 Potential Transformer Primary Value
The nominal full scale voltage will be displayed as Line to Line Voltages for all system types.
This screen can be accessed only from system parameters list menu.
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGEPT PRIMARY
ENTER PT PRIMARY VALUE(L-L)
DEL
5 8 9 0
3 6
ENTER
BACK
K
1 2 4 7
Here again 0 to 9 digit input keypad is provided to set value of PT Primary, & user can confirm this value with a simple touch “ key”. “ key” is used to multiply value by 1000.
K
ENTER
In case presently displayed Potenial Transformer Primary value together with the Current Transformer Primary value, previously set, would result in a maximum power of greater than 666.6 MVA per
phase, “Invalid value” will be displayed. Then the valid range will be displayed.
Valid range of PT primary setting value is from
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGEPT PRIMARY
INVALID VALUE
1 2 4 7 8 9
3
5
6
0
K
DEL
ENTER
BACK
100 VL-L to 692.8 KVL-L.
If value outside the range is entered, It will display “INVALID VALUE” followed by correct range of parameter
.
3.2.1.3 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained from the the Transformer when the potential transformer(PT)primary is supplied with the voltage defined in 3.2.1.2 potential transformer primary voltage. The ratio of full scale primary to full scale secondary is defined as the transformer ratio.
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGEPT SECONDARY
ENTER PT SECONDARY VALUE(L-L)
DEL
1 2 4 7 8 9
0
3
5
6
ENTER
BACK
This screen can be accessed only from system parameters list menu.
Here again 0 to 9 digit input keypad is provided to set value of PT Secondary, & user can confirm this value with a simple touch on
“ key”.
ENTER
17
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGEPT SECONDARY
INVALID VALUE
1 2 4 7 8 9
0
3
5
6
BACK
DEL
ENTER
Valid range of PT secondary setting value is from 241.0 to 480.0. for 415 VL-L. Please refer the table bellow for different ranges. If value outside the range is entered, It will display “INVALID VALUE” followed by correct range of parameter
.
Potential Transformer secondary ranges for various Input Voltages
110V L-L (63.5V L-N) 230V L-L (133.0V L-N) 415V L-L (239.6V L-N)
100 - 120V L-L (57.73V - 69.28V L-N) 121 - 240V L-L (69.86V - 138.56V L-N) 241 - 480V L-L (139.14V - 277.12V L-N)
3.2.1.4 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the user to display the Line currents inclusive of any transformer ratios, the values displayed represent the Current in Amps.
This screen can be accessed only from system parameters list menu.
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGECT PRIMARY
ENTER CT PRIMARY VALUE
DEL
1 2 4 7 8 9
3
5
6
ENTER
0
BACK
K
maximum power of greater than 666.6 MVA, “invalid value” will be displayed. Example:
If primary value of PT is set as 692.8kV L-L (max value) then primary value of Current is restricted to 1157A.
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120% of nominal voltage, i.e, 462.96 MVA nominal power per phase.
Here again 0 to 9 digit input keypad is provided to set value of CT Primary & user can confirm this value with a simple touch on “ key”. “ key” is used to multiply value by 1000.
K
ENTER
In case presently displayed Current Transformer Primary Value
together with the Potential Transformer Primary Value results in a
18
Valid range of CT primary setting value is from 1 to 9999. If value
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGECT PRIMARY
INVALID VALUE
5 8 9 0
3 6
K
1 2 4 7
DEL
ENTER
BACK
outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter
3.2.1.5 Current Transformer Secondary Value
.
This screen is used to set the secondary value for Cur
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
OK BACK
MAINMAINMAINMAINMAINMAIN
Two options: 1 AMPERE & 5 AMPERE are displayed on screen.
VVV
VVV
VVV
VVV
VVV
VVV V
V
V
V
V
V
Touching radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting. Touching the
BACK
“ key” will keep the old selected setting and will return
OK
to previous menu.
3.2.1.6 Demand Integration Time
This screen is used to set the period over which current and
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
DEMAND INTEGRATION TIME
CT SECONDARY
1 AMPERE
8 MINUTES
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
15 MINUTES
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
20 MINUTES
0.000
0.000
0.000
0.000
0.000
0.000
30 MINUTES
0.000
0.000
0.000
0.000
0.000
0.000
OK BACK
MAINMAINMAINMAINMAINMAIN
power
readings are to be integrated.
Four options: 8, 15, 20, 30 Minutes are displayed on screen. Touching
radio button in front of particular option will select that option. Touch on “ key” will confirm the setting.
Touching the “ key” will keep the old selected setting and will
OK
BACK
return to previous menu.
rent Transfor
mer.
19
3.2.1.7 Auto Scrolling
This screen allows user to enable screen scrolling. Seven options :
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
AUTO - SCROLL
1 AMPERE
ALL
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VOLTAGE POWER
VL2
VL2
VL2
VL2
VL2
VL2
Touching the “ key” will keep the old selected setting and will return to previous menu.
SYSTEM
0.000
0.000
0.000
0.000
0.000
0.000
CURRENT ENERGY
NONE
0.000
0.000
0.000
0.000
0.000
0.000
OK BACK
MAINMAINMAINMAINMAINMAIN
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
BACK
ALL, SYSTEM, VOLTAGE, CURRENT
POWER ENERGY & NONE are displayed on screen. Touching radio
button in front of particular option will select that option. Selecting
particular option means, only screen which are under that submenu will be scrolled automatically. Selecting NONE will disable Auto-Scroll.
Touch on “ key” will confirm the setting.
OK
While in Auto-scrolling mode, touch sense for entire screen will be disabled except for the top right most corner where “A” symbol would be displayed stating that meter is in Auto­scroll mode. Touching on “A” will show two options “ON” and “OFF”. Touching on “ON” will continue auto scrolling & touching on “OFF” will stop auto-scrolling & return to normal mode.
3.2.1.8 Low Current noise cutoff.
This screen allows the user to set Low noise current cutoff in mA.
Two options, 0 MILLI-AMPERE & 30 MILLI-AMPERE are displayed on
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
LOW CURRENT NOISE CUTOFF
1 AMPERE
0 MILLI-AMPERE
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
5 AMPERE
30 MILLI-AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
screen. Touching radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting.
OK
OK BACK
MAINMAINMAINMAINMAINMAIN
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
20
3.2.1.9 ENERGY ON RS485.
This screen enable user to set energy in terms of Wh / kWh / MWh on Rs485 Output depending as per the user’s requirement .This setting is applicable for all types of energy..
T hree options: WATT,KILO-WATT & MEGA-WATT are displayed on
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
ENERGY ON RS485
1 AMPERE
WATT (W)
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
5 AMPERE
KILO-WATT (KW)
VL2
VL2
VL2
VL2
VL2
VL2
MEGA-WATT (MW)
screen. Touching radio button in front of particular option will
select that option.
Touch on “ key” will confirm the setting.
OK
OK BACK
MAINMAINMAINMAINMAINMAIN
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
Note : Default value is set to ‘WATT’ i.e. Energy on Modbus will be in terms of Wh/VArh/VAh/Ah respectively.
3.2.1.10 ENERGY DIGIT RESET COUNT (ROLLOVER COUNT)
This screen
rollover to zero depending on the setting of Wh, kWh & Mwh in Energy on RS485 option.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
ENERGY DIGIT RESET COUNT
1 AMPERE
7 DIGITS
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
VL2VL2
9 DIGITS
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
11 DIGITS
13 DIGITS
Touching the “ key” will keep the old selected setting and will return to previous menu.
Note :
1) Default value of energy digit reset count is set to “14” i.e. if energy cross the 14 digit count it will rollover to zero.
2) If Energy on RS485 is set to kW & energy digit reset count is set to 12, Energy screen on display will show “-------” i.e. energy overflow when energy cross the 11 digit count.
3) If Energy on RS485 is set to MW & energy digit reset count is set to 9, Energy screen on display will show “-------” i.e. energy overflow when energy cross the 8 digit count.
enables the user for setting maximum energy count after which energy will
If Energy on RS485 is in WATT then rollover count can be from
CT SECONDARY
8 DIGITS 10 DIGITS 12 DIGITS 14 DIGITS
OK BACK
MAINMAINMAINMAINMAINMAIN
BACK
7 to 14 DIGITS.
If Energy on RS485 is in KILO-WATT then rollover count can be from
7 to 12 DIGITS.
If Energy on RS485 is in MEGA-WATT then rollover count can be from
7 to 9 DIGITS.
Touching radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting.
OK
21
3.2.2 Communication Parameter Selection :
After entering in the “COMMUNICATION PARAMETERS” list of following parameters will be displayed
3.2.2.1 RS485 ADDRESS
3.2.2.2 RS485 BAUD RATE
3.2.2.3 RS485 PARITY
3.2.2.1 RS485 Address Setting
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
RS485 ADDRESS
ENTER RS485 ADDRESS
DEL
12 4 789
0
3
5
6
ENTER
BACK
the user to set RS485 address parameter for the instrument. This screen can be accessed only from Communication
Parameters List menu. Here again 0 to 9 digit input keypad is provided to set RS485 address & user can confirm this value with a simple touch on
This screen applies to the RS 485 output only This screen allows
“ key”.
ENTER
LINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGELINE-NEUTRAL VOLTAGE
RS485 ADDRESS
INVALID VALUE
12
5
4 789
0
3 6
BACK
DEL
ENTER
The range of allowable address is 1 to 247. If value outside the range is entered, it will dispay “INVALID VALUE” followed by the correct range of parameter.
3.2.2.2 RS485 Baud Rate
This screen allows the user to set Baud Rate of RS 485 port. Four options: 2400, 4800, 9600, 19200 Bauds are displayed on
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
RS485 BAUD RATE
1 AMPERE
2400
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
4800
5 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2 VL2
VL2
VL2
VL2
VL2
VL2
9600
0.000
0.000
0.000
0.000
0.000
0.000
19200
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
OK BACK
MAINMAINMAINMAINMAINMAIN
V
V
V
V
V
V
screen. Touching radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting. Touching the “ key” will keep the old selected setting
and will Return to previous menu.
.
OK
BACK
22
3.2.2.3 RS485 Parity & Stop bit Selection
This screen allows the user to set Parity & number of stop bits.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RS485 PARITY & STOP BITS
1 AMPERE
ODD PARITY WITH ONE STOP BIT
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
NO PARITY WITH ONE STOP BIT
5 AMPERE
NO PARITY WITH TWO STOP BIT
VL2
VL2
VL2
VL2
VL2
VL2
EVEN PARITY WITH ONE STOP BIT
VL2
VL2
VL2
VL2
VL2
VL2
OK BACK
MAINMAINMAINMAINMAINMAIN
Four options: ODD PARITY WITH ONE STOP BIT, NO PARITY WITH ONE STOP BIT, NO PARITY WITH TWO STOP BITS, EVEN PARITY WITH ONE STOP BIT are displayed on screen. Touching radio button in front of particular option will select that option.
Touch on “ key” will confirm the setting.
OK
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
3.2.3 Reset Parameter Selection
3.2.3.1 Resetting Parameter
These screens allow the users to reset all the parameters
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RESET PARAMETERS
RESET ALL
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
RESET DEMAND PARAMETERS RESET ALL ENERGIES
VL2
VL2
VL2
0.000
0.000
0.000
RESET MAX VOLTAGE & CURRENT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RESET PARAMETERS
RESET MAX VOLTAGE & CURRENT
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
RESET MIN VOLTAGE & CURRENT
VL2
VL2
VL2
0.000
0.000
0.000
RESET RUN-HOUR, ON-HOUR
0.000
0.000
0.000
RESET AUX INTERRUPT COUNT
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SETUP
VOLTAGE
VOLTAGE
VOLTAGE
SETUP
VVVV
VVVV
VVVV V
V
V
VVVV
VVVV
VVVV V
V
V
eg;- Energy, Min, Max, Demand, Run hour, On hour, No. of Interrupts. Touching “ down” key scrolls list in upward direction.
This screen is displayed after repeatedly touching “ down.” key Touching “ Up” key scrolls list in downward direction. For resetting specific parameter user can touch on that parameter.
23
Touching on any parameter will display the confirmation dialog, now
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
RESET PARAMETERS
RESET ALL
RESET ALL ENERGIES
0.000
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
RESET DEMAND PARAMETERS
ARE YOU SURE YOU WANT TO RESET ALL THE STORED ENERGIES
VL2
VL2
VL2
0.000
0.000
0.000
YES NO
RESET MAX VOLTAGE & CURRENT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SETUP
VVVV
VVVV
VVVV V
V
V
a touch on “ key” will confirm the resetting of that particular
YES
Parameter. Touching on “ key” will move back to Reset parameters menu
NO
For example resetting All Energies will display a confirmation dialog as shown in the screen beside. User can reset other parameters in similar manner.
3.2.4. Output Option selection menu
After entering in the “OUTPUT OPTIONS”, List of following parameters will be displayed :-
3.2.4.3 ANALOG-1 ( Model 301 only)
3.2.4.4 ANALOG-2 ( Model 301 only)
3.2.4.3 Parameter setting for Analog Output 1 ( Only on Model 301 )
This option allows the user to set analog output 1 to corresponding measured parameter. A simple touch on “ANALOG-1” row will open screen having list of parameters.( Refer Table 2 “Parameter fo Analog output”) Touch on “ key” will confirm setting. Touching the “ key” will keep the old selected setting and will return to previous menu.
OK
BACK
3.2.4.4 Parameter setting for Analog Output 2 ( Only on Model 301 )
This option allows the user to set analog output 2 to corresponding measured parameter. A simple touch on “ANALOG-2” row will open screen having list of parameters.( Refer Table 2 “Parameter fo Analog output”) Touch on “ key” will confirm setting. Touching the “ key” will keep the old selected setting and will return to previous menu.
OK
BACK
24
Parameter
No.
Parameter
3P 4W 3P 3W
Range
Analog Output
51 52
53 54
101 102 103
113
VA DEMAND VA MAX DEMAND
CURRENT DEMAND
CURRENT MAX DEMAND
INPUT VOLTAGE L12 INPUT VOLTAGE L23 INPUT VOLTAGE L31
NEUTRAL CURRENT
99 99
99 99 9 9 9 9
8 8 8
8
0 - 120 % 0 - 120 %
0 - 100 % 0 - 100 % 0 - 100 % 0 - 100 % 0 - 100 % 0 - 100 %
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
(1) For Frequency 0% corresponds to 40 Hz & 100% corresponds to 70 Hz.
3.2.5 Brightness & Contrast
The brightness & contrast of the TFT LCD screen can be varied by
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
BRIGHTNESS & CONTRAST
VL2
VL2
VL2
VL2
0.000
VL2
VL2 VL2
VL2
DEFAULT
MAIN
MAIN
MAIN
0.000
BRIGHTNESS
0.000
0.000
DEFAULT
CONTRAST
OK
VOLTAGE
VOLTAGE
VOLTAGE
BACK
VVVV
VVVV V
V
the user by sliding the sliders. Touching the “ key” will confirm the current brightness contrast setting.
Touching the DEFAULT key will set brightness and contrast as per factory setting. Touching the BACK key will move back to the setup menu without making any changes.
OK
4 Touch screen calibration
This instrument is able to perform calibration to ensure the proper operation of the units touch screen functionalities. The calibration procedure will correct the problem of out of tolerance touch screen malfunction. Note that errors corrected by this calibration procedure are specific only to touch screen operation.
For starting touch screen calibration, touch the screen any where
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
IMPORTANT.
Performing touch
1 AMPERE
screen calibration.
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
Press & hold the center
5 AMPERE
of the filled circle
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
Touch screen to
continue.
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
for 1 sec at system reset. After that touch screen calibration will start & the message shown besides will be displayed. Touch the screen to continue.
25
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
1 AMPERE
Press
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
on the filled
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
Hold
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
5 AMPERE
5 AMPERE
the filled
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2 VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
0.000
Hold the filled circle
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
OK
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
V
V
V
V
V
V
LINE-NEUTRAL VOLTAGE
CT SECONDARY
CT SECONDARY
1 AMPERE
1 AMPERE
Release
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
Hold the filled
5 AMPERE
5 AMPERE
the filled
circle
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
OK
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
Follow the instructions displayed. Press & hold the center of the filled red circle for at least 2 seconds. Release when message for release is being displayed. For accurate results try to touch the center of the filled circle.
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
V
V
V
V
V
V
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
1 AMPERE
Press
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
5 AMPERE
on the filled
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
circle
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
1 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
Error in calibration
Touch screen to
5 AMPERE
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
re-calibrate.
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
Repeat the same procedure for the
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
remaining 3 corner circles.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
CT SECONDARY
Hold screen for 1 sec
after system reset to
1 AMPERE
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
REPEAT the calibration
5 AMPERE
procedure.
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VL2
VL2
VL2
VL2
VL2
VL2
Touch screen to
continue.
MAIN
MAIN
MAIN
MAIN
MAIN
MAIN
OK
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VOLTAGE
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
After successful calibration, the message shown besides would be displayed. Touch the screen to continue.
If the touch screen was not calibrated properly, “Error in calibration”message would be shown & the user will be asked to
VVVV
VVVV
VVVV
VVVV
VVVV
VVVV V
V
V
V
V
V
recalibrate the touch screen. In such case the meter will retain the previously stored touch - screen calibration values unless a successful calibration is being performed.
26
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
ERROR
VL2
VL2
VL2
0.000
0.000
0.000
NOTE : WRONG PHASE SEQUENCE. PLEASE CHECK YOUR CONNECTIONS.
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV V
V
V
5. Phase Rotation Error screen
Meter shows phase rotation error if the phase sequence
R-Y-B (L1-L2-L3) is not maintained This screen indicates that Phase sequence is incorrect. User must check this screen in order to get correct readings when meter is connected.
V
VRY
KVAr
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
Angle
KVAr
Angle
VYB
VRY
VYB
Sys
A
KVA
Min
KW
VBR
Max
V
Sys
A
KVA
Min
KW
VBR
Max
VVVV
VVVV
VVVV V
V
V
VVVV
VVVV
VVVV V
V
V
Demand
Demand
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
L1-L2-L3
VL2
VL2
VL2
0.000
0.000
0.000
CONNECTIONS ARE CORRECT
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PHASE SEQUENCE
VL2
VL2
VL2
VL2
VL2
VL2
INPUT ABSENT
VL2
VL2
VL2
0.000
0.000
0.000
PLEASE CHECK YOUR CONNECTIONS.
0.000
0.000
0.000
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
Correct Phase sequence
x1000
IN
KVArh
x1000
KVAh
%THD
x1000
x1000
KVArh
Ph R
x1000
KVAh
%THD
x1000
Ph R
Ph Y
Ph Y
KWh Ph B
This Screen indicates the phase sequence connected to
KAh
Hz
meter is correct. If phase sequence is wrong this screen is useful to get correct phase sequence by interchanging connection &
P.F.
KWh
verifying it with screen.
Ph B
This Screen indicates that either of the phases or all three
IN
KAh
phases (Voltages) are absent.
Hz
P.F.
6. Run Hour
This Screen shows the total no. of hours the load is connected
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM RUN HOUR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
000001.19
VL2
VL2
VL2
0.000
0.000
0.000 hrs
0.000
0.000
0.000
VL2
VL2
VL2
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
VVVV
VVVV
VVVV V
V
V
Even if the Auxiliary supply is interrupted count of Run hour will be
maintained in internal memory & displayed in the format
“hours. min”.
it indicates 1 hour & 19 minutes. After 999999.59 run hours display restart from zero. To reset run hour manually see section Resetting Parameter 3.2.3.1
For example if Displayed count is 000001.19 hrs
27
7. On Hour
This Screen shows the total no. of hours the Axillary Supply is ON.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM ON HOUR
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
0.000
000005.18
VL2
VL2
VL2
0.000
0.000
0.000 hrs
0.000
0.000
0.000
VL2
VL2
VL2
VOLTAGE
VOLTAGE
VOLTAGE
MAIN
MAIN
MAIN
MAIN
SYSTEM
VVVV
VVVV
VVVV V
V
V
Even if the Auxiliary supply is interrupted count of On hour will be
maintained in internal memory & displayed in format “hours. min.”
For example if Displayed count is 000005.18 hrs it indicates 15 hours & 18 minutes. After 999999.59 On hours display will restart from zero. To reset On hour manually see section Resetting Parameter 3.2.3.1
8. Number of Interruption
This Screen Displays the total no. of times the Axillary Supply was
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
SYSTEM INTERRUPTIONS
VL2
VL2
VL2
VL2
VL2
VL2
0.000
0.000
VL2
VL2
VL2
00000012
VL2
VL2
VL2
MAIN
MAIN
MAIN
MAIN
0.000
0.000
0.000
0.000
0.000
0.000
0.000
VOLTAGE
VOLTAGE
VOLTAGE
SYSTEM
VVVV
VVVV
VVVV V
V
V
Interrupted. Even if the Auxiliary supply is interrupted count will be maintained in internal memory To reset No of Interruption manually see section Resetting Parameter 3.2.3.1
9. Analog Output ( optional ) :
This module provides two d.c. isolated outputs .There are two output options
1) Two 4 - 20mA outputs , internally powered . On both modules the output signals are present on pins A1(Analog Output 1) &
A2 (Analog Output 2)
28
These outputs can be individually assigned to represent any one of the measured and displayed Parameters.
All settlings are user configurable via the user interface screen. See Analog o/p selection ( section 3.2.4.3 & section 3.2.4.4 ) for details .
* Note : Refer diagrams 1
Diagram 1 : ( 4 -20 mA )
0
0 (12 mA)
0
270 (8 mA)
0
181 (4 mA)
0
90 (16 mA)
0
180 (20 mA)
29
TABLE 2 : Parameter for Analog
Parameter
No.
0
1 2
2
3 4 INPUT CURRENT IL1
5 6 7
Parameter
None INPUT VOLTAGE L1 INPUT VOLTAGE L2
INPUT VOLTAGE L3
INPUT CURRENT IL2 INPUT CURRENT IL3 ACTIVE POWER L1
3P 4W 3P 3W
9 9 9
9 9 9
99 99
99 99 9
8
Range
Analog Output
– 0 - 100 % 0 - 100 % 0 - 100 %
0 - 100 % 0 - 100 %
0 - 100 % 0 - 120 %
30
Parameter
No.
Parameter
3P 4W 3P 3W
Range
Analog Output
8 ACTIVE POWER L2 9 ACTIVE POWER L3
10 APPARENT POWER L1
11 12 13 14 15 REACTIVE POWER L3
16 POWER FACTOR L1 17 18 POWER FACTOR L3
19 PHASE ANGLE L1 20
21 22
24 27
29 APPARENT POWER SUM
31 REACTIVE POWER SUM 32
34 PHASE ANGLE AVG 36 43 WATT DEMAND IMPORT
44 45 46
APPARENT POWER L2 APPARENT POWER L3 REACTIVE POWER L1 REACTIVE POWER L2
POWER FACTOR L2
PHASE ANGLE L2 PHASE ANGLE L3 VOLTAGE AVG
CURRENT AVG ACTIVE POWER SUM
POWER FACTOR AVG
FREQUENCY
WATT MAX DEMAND IMP. WATT DEMAND EXPORT
WATT MAX DEMAND EXP.
9 9
9 9 9 9 9 9
9 9 9 9
9 9
8 8
8 8 8 8 8 8
8 8 8 8
8 8
99 99
99 99
99 99
99 99 9
9
99 99 99
0 - 120 % 0 - 120 %
0 - 120 % 0 - 120 % 0 - 120 % 0 - 120 % 0 - 120 % 0 - 120 %
180 1800 / 0 / -180 1
800 / 0 / -180 1800 / 0 / -180 1800 / 0 / -180
1800 / 0 / -180 0 - 100 % 0 - 100 % 0 - 120 %
0 - 120 % 0 - 120 %
180 1800 / 0 / -180 45 to 66 Hz 0 - 120 % 0 - 120 %
0 - 120 % 0 - 120 %
0
/ 0 / -180
0
/ 0 / -180
0
0
0
0
0
0
0
0
31
Parameter
No.
Parameter
3P 4W 3P 3W
Range
Analog Output
51
52 53
54 101 102 103 113
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
VA DEMAND VA MAX DEMAND
CURRENT DEMAND
CURRENT MAX DEMAND
INPUT VOLTAGE L12 INPUT VOLTAGE L23 INPUT VOLTAGE L31
NEUTRAL CURRENT
99 99
99 99 9 9 9 9
8 8 8
8
0 - 120 % 0 - 120 %
0 - 100 % 0 - 100 % 0 - 100 % 0 - 100 % 0 - 100 % 0 - 100 %
32
11. RS 485 ( ModBus ) Output :
This instrument supports MODBUS (RS485) RTU protocol ( 2-wire ).
Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, an Earth connection should be made at one point on the network. Loop (ring) topology does not require any termination load. Line topology may or may not require terminating loads depending on the type and length of cable used. The impedance of the termination load should match the impedance of the cable and be at both ends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum lenght of 1.2km. Including the Master, a maximum of 32 instruments can be connected in RS 485 network. The permissible address range for the instrument is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.
The maximum latency time for the instrument is 200ms i.e. this is the amount of time that can pass before the first response character is output.
After sending any query through software ( of the Master) , it must allow 200ms of time to elapse before assuming that the instrument is not going to respond. If slave does not respond within 200 ms, Master can ignore the previous query and can issue fresh query to the slave.
33
The each byte in RTU mode has following format:
8-bit binary, hexadecimal 0-9, A-F 2 hexadecimal characters contained in each 8-bit field of the message
Format of Data Bytes
4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754 ) Most significant byte first (Alternative least significant first)
Error Checking Bytes
Byte format
Communication Baud Rate is user selectable from the front panel between 2400, 4800, 9600, 19200 bps.
2 byte Cyclical Redundancy Check (CRC) 1 start bit,
8 data bits, least significant bit sent first 1 bit for even/odd parity 1 stop bit if parity is used; 1 or 2 bits if no parity
Function code :
03 04 16
Read Holding Registers Read input Registers Presets Multiple Registers
Read content of read /write location ( 4X ) Read content of read only location ( 3X ) Set the content of read / write locations ( 4X )
Exception Cases : An exception code will be generated when the instrument receives
ModBus query with valid parity & error check but which contains some other error ( e.g. Attempt to set floating point variable to an invalid value ) The response generated will be “Function code” Ored with HEX (80H ). The exception codes are listed below
34
01
Illegal function
This function code is not supported by the instrument.
02
03
Accessing 3 X register for reading measured values:
Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses of 3X registers (Parameters measured by the instruments). Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Illegal Data Address
Illegal Data Value
Attempt to access an invalid address or an attempt to read or write part of a floating point value
Attempt to set a floating point variable to an invalid value
Example :
To read parameter , Volts 3 : Start address= 04 (Hex) Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding the 20 parameter limit will cause a ModBus exception code to be returned.
Query :
01 (Hex)
Device Address
Start Address High : Most significant 8 bits of starting address of the parameter requested. Start Address low : Least significant 8 bits of starting address of the parameter requested.
04 (Hex)
Function Code
00 (Hex)
Start Address High
04 (Hex) 00 (Hex)
Start Address Low
Number of Registers Hi
02 (Hex) 30 (Hex) 0A (Hex)
Number of Registers Lo
CRC Low
CRC High
35
Number of register Hi : Most significant 8 bits of Number of registers requested. Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.) Response: Volt3 (219.25V)
01 (Hex)
Device Address
Byte Count : Total number of data bytes received.
04 (Hex) Function
Code
04 (Hex)
Byte Count
43 (Hex) 5B (Hex)
Data Register 1
High Byte
Data Register 1
Low Byte
41 (Hex) 21 (Hex) 6F (Hex)
Data Register 2
High Byte
Data Register 2
Low Byte
CRC Low
9B (Hex)
CRC High
Data register 1 High Byte : Most significant 8 bit of Data register 1 of the parameter requested. Data register 1 Low Byte : Least significant 8 bit of Data register 1 of the parameter requested. Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent on parameter.)
Table 4 : 3 X register addresses (measured parameters)
P
Address
(Register)
30001
30003 30005 30007 30009 30011 6 Current 3 30013 7 W1
Parameter No.
1 2
3 4 5
P
Parameter
Volts 1
Volts 2
Volts 3 Current 1 Current 2
Modbus Start Address Hex
HHigh Byte
H
00
00
00
00 00 00 00
Low Byte
0 2 4 6
8 A C
3
3P 4W
9
3P 3W
3
9 99 99
99 99 99 9
8
36
Parameter
Address (Register)
30015 8 W2 30017 9 W3 30019 10 VA1
30021 11 VA2 30023 12 VA3 30025 13 VAR1 30027 14 VAR2
30029 15 VAR3 30031 16 PF1 30033 17 PF2 30035 18 PF3 30037 19 Phase Angle 1 30039 20 Phase Angle 2
30041 21 Phase Angle 3 30043 22 Volts Ave 30045 23 Volts Sum
30047 24 Current Ave 30049 25 Current Sum 30051 26 Watts Ave 30053 27 Watts Sum
30055 28 VA Ave
30057 29 VA Sum
30059 30 VAr Ave 30061 31 VAr Sum 30063 32 PF Ave
P
No.
Parameter
P
Modbus start
H
High Byte
H
00 E 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 32 00 00 00
00 00 00
Address Hex
A
Low Byte
10 12
14 16 18 1A
1C 1E 20 22 24 26
28 2A 2C
2E 30
34 36
38
3A 3C 3E
3P 4W
3
9 9 9 9 9 9 9 9 9 9
9 9 9 9
3P 3W
3
8
8
8
8
8
8
8
8
8
8
8
8
8
8
99 99 99 99 99 99
99 99 99
99 99
37
Address (Register)
30065 33 PF Sum
30067 34 Phase Angle Ave 30069 35 Phase Angle Sum 30071 36 Freq 30073 30075
30077 30079 30081 30083 30085
30087 30089
30091 30093 30095 30097 30099
30101 30103 30105 30107 30133
30135
30141 30143
30201
Parameter No.
37 Wh Import 38 Wh Export
39 40 41 42 43 44 45 46 47 48
49
50 51
52
53
54 67 68 71 72
101
Parameter
VARh Import VARh Export VAh Ah
W Demand (Import)
W Max Demand (Import)
W
W Max Demand (Export)
VA Demand
VA Max Demand A Demand A Max Demand Volts Ave Max
Volts Ave Min
Current Ave Max Current Ave Min VL1-2 (Calculated)
Demand (Export)
-
-
-
-
-
Modbus Start
High Byte
00
00 00 00 00 00
00 00 00 00
00 00 00 00
-
-
-
00 00 00
00 00 00 00 00 00 00
Address Hex
Low Byte
40 42 44 46 48 4A
4C 4E 50 52
54
56
58
5A
-
-
-
­64 66 68 6A
84 86 8C 8E C8
3P 4W
9
3P 3W
8
99 9
8
99 99
99 99 99 99 99 9 9 9 9
-
-
-
-
9 9
9 9
9 9 9 9
9
9 9 9 9
-
-
-
-
9 9
9 9
9 9 9 9
8
38
Address (Register)
30203 30205 30207 30209
30211 30213 30215 30217 30219
30221 30225 30227 30229
30231
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W.
Parameter No.
102 103 104 105 106 107
108 109 110 111 113 114 115 116
Parameter
VL 2 - 3 ( Calculated ) VL 3 - 1 ( Calculated )
V1 THD( % ) V2 THD( % ) V3 THD( % ) I1 THD( % ) I2 THD( % ) I3 THD( % )
System Voltage THD( % ) System Current THD( % )
I neutral Run Hour On Hour No. Of Interrupts
Modbus start
High Byte
00 00
00 00
00 00 00 00
00
00 00 00 00 00
Address Hex
Low Byte
CA
CC CE D0 D2 D4
D6
D8 DA DC E0 E2 E4 E6
3P 4W
9 9
9 9 9 9 9 9 9 9 9 9
9 9
3P 3W
8 8
9 9 9 9 9 9 9 9
8
9 9
9
Accessing 4 X register for Reading & Writing :
Each setting is held in the 4X registers. ModBus code 03 is used to read the current setting and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register addresses.
Example : Reading System type
System type : Start address= 0A (Hex) Number of registers = 02
Note : Number of registers = Number of Parameters x 2
39
Query :
Device Address Function Code
Start Address High Start Address Low
Number of Registers Hi Number of Registers Lo
CRC Low CRC High
Start Address High : Most significant 8 bits of starting address of the parameter requested. Start Address low : Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested. Number of register Lo : Least significant 8 bits of Number of registers requested.
01 (Hex) 03 (Hex)
00 (Hex) 0A (Hex)
00 (Hex)
02 (Hex) E4 (Hex)
09 (Hex)
(Note : Two consecutive 16 bit register represent one parameter.) Response : System Type ( 3 phase 4 wire = 3 )
Device Address Function Code
Byte Count Data Register1 High Byte
Data Register1 Low Byte
01 (Hex) 03 (Hex)
04 (Hex) 40 (Hex) 40 (Hex)
40
Data Register2 High Byte
00 (Hex)
Data Register2 Low Byte
CRC Low CRC High 27 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
00 (Hex) EE (Hex)
(Note : Two consecutive 16 bit register represent one parameter.)
Example : Writing System type
System type : Start address= 0A (Hex) Number of registers = 02
Query : ( Change System type to 3phase 3wire = 2 )
Device Address
01 (Hex)
Function Code Starting Address Hi
Number of Registers Hi Number of Registers Hi
10 (Hex) 00 (Hex)
0A (Hex)Starting Address Lo 00 (Hex)
02 (Hex)
41
Byte Count
04 (Hex)
Data Register-1 High Byte Data Register-1 Low Byte Data Register-2 High Byte
Data Register-2 Low Byte CRC Low CRC High
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
40 (Hex) 00 (Hex)
00 (Hex) 00 (Hex) 60 (Hex)
10 (Hex)
(Note : Two consecutive 16 bit register represent one parameter.)
Response:
Device Address Function Code
01 (Hex) 10 (Hex)
Start Address High Start Address Low
Number of Registers Hi Number of Registers Lo 02 (Hex)
CRC Low CRC High CA (Hex)
00 (Hex) 0A (Hex) 00 (Hex)
61 (Hex)
42
Start Address High : Most significant 8 bits of starting address of the parameter requested. Start Address low : Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested. Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Table 5 : 4 X register addresses
Address (Register)
40001 40003 Demand Period R/Wp 40005 R/Wp 40007 40009
Parameter No.
1 2
3 4 5 6
Parameter
Demand Reset
Read / Write
R/Wp
Energy on RS485
Sys Voltage
R Sys Current R Sys Type40011 R/Wp
Modbus Start Address Hex
High Byte
Low Byte
00 00 00 00 00 00
00 02 04 06 08
0A
40015 40017 40019
40021
40025 40027 40029 40031 40033 40035
10
11
13 14 15 16 17 18
8
Energy Reset
Run/On Hour & Interruption Reset
9
RS 485 Set-up Code Node Address.
Min Reset Max Reset Analog Out 1- Para Sel Analog Out 2- Para Sel PT Primary CT Primary
Wp
Wp
R/Wp
R/Wp
Wp
Wp
R/Wp R/Wp R/Wp R/Wp
00 00
00 00
00 00 00 00 00 00
0E 10 12 14
18 1A 1C 1E 20
22
43
Address (Register)
40037
40039 40041 40043 40045
Parameter No.
19 20
21 22 23
Parameter
System Power Energy digit reset count
CT Secondary PT Secondary
40071 36 Password 40079 40
30mA Noise Current Elimination
Read / Write
R R/Wp
R/Wp R/Wp R/Wp R/W
R/Wp
Modbus Start Address Hex
H
H
High Byte
00 00
00 00 00 00
00
Low Byte
24 26
28Register Order/Word Order 2A 2C 46 4E
44
Explanation for 4 X register :
Address Parameter Description
40001
40003
40005
Demand Reset
Demand Period
Energy display on Modbus
40007 System Voltage 40009 System Current
40011 System Type
Demand Reset is used to reset the Demand parameter. A value of zero must be Written to this register to reset the Demand period. Writing any other value will return an error.
Demand period represents demand time in minutes. The applicable value are 8,15,20 or 30. Writing any other value will return an error.
This address is used to set energy display on MODBUS in Wh, KWh & Mwh. Write one of the following value to this address.
1 = Energy in Wh. 3 = Energy in MWh.
2 = Energy in KWh.
This address is read only and displays System Voltage This address is read only and display System Current
This address is used to set the System type. Write one of the follow value to this address.
2 = 3 Phase 3 Wire 3 = 3 Phase 4 Wire.
Writing any other value will return error.
40015 Reset Energy
Counter
This address is used to reset the Energy Counter. Write zero value to this register to reset the energy counter. Writing any other value will return an error.
45
Address Parameter
Description
40017
40019
40021
40025
Run/On Hour & Interruption reset
Rs485 Set-up Code
Node Address
This address is used to reset the Run/ON hour & number of Interruption. Write zero value to this register to reset the Run/On hour & number of Interruption. Writing any other value will return an error.
This address is used to set the baud rate, Parity, Number of stop bits. Refer to Table 6 for details.
This register address is used to set Device address between 1 to 247.
Min - Reset This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters. Writing any other value will return an error.
40027
40029
Max - Reset This address is used reset the Max parameters value.
Write Zero value to this register to reset the Max parameters. Writing any other value will return an error.
Analog Out 1­Para Set
This address is used to set the parameter for Analog Output 1. Write one of the parameter no. As per the options given in Table 2 for Analog Output Parameters.
46
Address Parameter Description
40031
40033
40035
40037
40039
40041
Analog Out 2­Para Set
PT Primary This address allows the user to set PT Primary value.
CT Primary
Sys Power System Power (Read Only) is the Nominal system power base on
Energy digit Reset Count
Word Order Word Order controls the order in which the instrument receives
This address is used to set the parameter for Analog Output 2. Write one of the parameter no. AS per the option given in Table 2 for Analog Output Parameters.
The maximum settable value is 692.8kV L-L depends on the phase 666.6MVA Restriction of power combined with CT primary.
This address allows the user to set CT Primary Value. The maximum settable value is 9999 & also depends on the per phase 666.6MVA Restriction of power combined with PT primary.
the values of Nominal system volts and Nominal system current.
This address is used to set the rollover count for energy. If Energy on Rs485 is in Wh rollover count can be from 7 to 14. If it is in KWh then rollover count can be from 7 to 12 & for MWh rollover count can be from 7 to 9.
or sends floating - point numbers:- normal or reversed register order. In normal mode, the two registers that make up a floating point numbers are sent most significant bytes first. In reversed register mode, the two registers that make up a floating point numbers are sent least significant bytes first. To set mode, write the value ‘2141.0’ into this register­the instrument will detect the order used to send this value and set that order for all ModBus transaction invoving floating point numbers.
47
Address Parameter Description
40043
40045
40071
CT secondary
This address is used to read and write the CT secondary value write one of the following values this address. 1=1A CT secondary 5=5A CT secondary writing any other value will return an error.
PT secondary This address is used to read and write the PT secondary value.
Ref Table for the range of PT secondary settable value in Section 3.2.1.3
Password
This address is used to set & reset the password. Valid Range of Password can be set is 0000 - 9999.
1) If password lock is present & if this location is read it will return zero.
2) If Password lock is absent & if this location is read it will return One.
3) If password lock is present & to disable this lock first send valid password to this location then write “0000” to this location.
4) If password lock is present & to modify 4X parameter first send valid password to this location so that 4X parameter will be accessible for modification.
5) If for in any of the above case invalid password is sent then meter will return exceptional error 2.
40079 30mA Noise
current Elimination
This address is used to activate or de-activate the 30 mA noise current elimination write 0-Deactivate 30 (Decimal)-Activate Writing any other value will return an error.
48
Table 6 : RS 485 Set-up Code
Baud Rate
19200 19200 19200
Baud Rate
19200
9600
9600
9600 9600
4800 4800
4800 4800
2400 2400
2400
2400
Parity NONE
NONE EVEN
Parity
ODD NONE NONE
EVEN
ODD NONE NONE
EVEN
ODD
NONE NONE
EVEN
ODD
Stop Bit
01 02 01
Stop Bit
01 01 02
01 01
01 02 01 01
01 02 01
01
Decimal value
12
13
14
Decimal value
15 08 09 10 11 04 05 06 07 00 01 02
03
NOTE : Codes not listed in the table above may give rise to unpredictable results including loss of communication. Excise caution when attempting to change mode via direct Modbus writes.
49
This instrument contains the 20 user assignable registers in the address range of 0x200 (30513) to 0x226 (30551) (see Table 9). Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the instrument can be mapped to these 20 user assignable registers. Parameters (3X registers addresses ) that resides in different locations may be accessed by the single request by re-mapping them to adjacent address in the user assignable registers area. The actual address of the parameters ( 3X registers addresses) which are to be assessed via address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 10).
Table 9 : User Assignable 3X Data Registers
Address (Register)
30513 30515 258
30517 259
30519 30521 30523
Parameter Number.
Assignable Register
257
260 06 261 262
Assignable Reg 1 Assignable Reg 2 Assignable Reg 3 Assignable Reg 4 Assignable Reg 5 Assignable Reg 6
Modbus Start Address (Hex)
High Byte Low Byte
02 02 02 02 02 02
00 02
04
08 0A
50
Address (Register)
30525 30527 30529 30531 30533
30535 30537 30539 30541 30543
30545 30547 30549 30551
Parameter Number.
263 264 265 266 267 268 16 269 270 271
272 273 274 275 276
Assignable Register
Assignable Reg 7
Assignable Reg 8 Assignable Reg 9 Assignable Reg 10 Assignable Reg 11 Assignable Reg 12 Assignable Reg 13 Assignable Reg 14 Assignable Reg 15 Assignable Reg 16 Assignable Reg 17 Assignable Reg 18 Assignable Reg 19 Assignable Reg 20
Modbus Start Address (Hex)
High Byte Low Byte
02
02
02
02
02
02
02
02
02 02 02 02
02 02
Table 10 : User Assignable mapping register ( 4X registers)
0C 0E 10 12
14
18 1A
1C
1E 20 22
24 26
Parameter
(Register)
40513 40514 40515
40516
40517
40518 262
40519 263 40520 264
Number.
257 258 259
260 261
Mapping Register
Mapped Add for register #0x0200 Mapped Add for register #0x0202 Mapped Add for register #0x0204
Mapped Add for register #0x0206 Mapped Add for register #0x0208 Mapped Add for register #0x020A Mapped Add for register #0x020C
Mapped Add for register #0x020E
Modbus Start Address (Hex)Address
High Byte Low Byte
02 02 02
02 02 02 02
02
00 01 02 03
04 05 06
07
51
Address (Register)
40521 40522 40523
40524 40525 40526 40527
40528 40529
40530 40531 40532
Parameter Number.
265 266 267 268 269 270 271 272 273 274 275 276
Mapped Register
Mapped Add for register #0x0210 Mapped Add for register #0x0212
Mapped Add for register #0x0214
Mapped Add for register #0x0216 Mapped Add for register #0x0218 Mapped Add for register #0x021A
Mapped Add for register #0x021C Mapped Add for register #0x021E Mapped Add for register #0x0220 Mapped Add for register #0x0222 Mapped Add for register #0x0224
Mapped Add for register #0x0226
Modbus start Address (Hex)
High Byte Low Byte
02
02 02 02
02 02
02
02 02 02
02
02
08 09 0A 0B
0C 0D 0E 0F 10
11 12 13
Example : Assigning parameter to user assignable registers
To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E) through user assignable register assign these addresses to 4x register (Table 10 ) 0x0200 and 0x0201 respectively.
Assigning Query:
Device Address Function Code
01 (Hex) 10 (Hex)
02 (Hex)Starting Address Hi 00 (Hex)Starting Address Lo 00 (Hex)*Number of Register Hi
02 (Hex)*Number of Register Lo
52
Byte Count Data Register-1 High Byte
Data Register-1 Low Byte
04 (Hex) 00 (Hex) 02 (Hex)
Voltage 2 *
}
(3X Address 0x0002)
Data Register-2 High Byte
Data Register-2 Low Byte CRC Low CRC High
00 (Hex)
1E (Hex) CB (Hex)
07 (Hex)
Power Factor 1 *
}
(3X Address 0x001E)
Response :
Device Address Function Code
Start Address High Start Address Low Number of Register Hi
Number of Register Lo CRC Low CRC High
Reading Parameter data through User Assignable Registers:
In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x200 and 0x201(Table10) which will point to user assignable 3x registers 0x200 and 0x202 (Table 9). So to read Voltage2 and Power Factor1 data reading query should be as below.
01 (Hex) 10 (Hex) 02 (Hex) 00 (Hex) 00 (Hex) 02 (Hex) 40 (Hex) 70 (Hex)
53
Query:
Device Address Function Code Start Address High
Start Address Low Number of Registers Hi Number of Registers Lo
CRC Low CRC High
Start Address High : Most significant 8 bits of starting address of User assignable register. Start Address low : Least significant 8 bits of starting address of User assignable register. Number of register Hi : Most significant 8 bits of Number of registers requested. Number of register Lo : Least significant 8 bits of Number of registers requested.
**Note : Two consecutive 16 bit register represent one parameter. Since two parameters are requested four registers are required
Response : (Volt2 = 219.30 / Power Factor1 = 1.0)
Device Address Function Code
Byte count Data Register-1 High Byte Data Register-1 Low Byte
Data Register-2 High Byte Data Register-2 Low Byte
01 (Hex)
04 (Hex) 02 (Hex) 00 (Hex) 00 (Hex)
04 (Hex) ** F0 (Hex)
71 (Hex)
01 (Hex)
04 (Hex)
08 (Hex)
43 (Hex)
5B (Hex)
4E (Hex)
04 (Hex)
Voltage 2 Data
}
54
Data Register-3 High Byte Data Register-3 Low Byte Data Register-4 High Byte Data Register-4 Low Byte CRC Low CRC High
3F (Hex)
80 (Hex)
00 (Hex)
00 (Hex)
79 (Hex)
3F (Hex)
Power Factor 1Data
}
(Starting Address)
0x200
0x201
0x202 0x203
0x212 0x213
User Assignable mapping Registers
( 4X Registers Table 10 )
Voltage 2 (0x0002)
Power Factor 1 (0x001E)
Wh Import (0x0048)
Frequency (0x0046)
Current 1 (0x0006)
VAh (0x0050)
(Starting Address)
0x200
0x202
0x204 0x206
0x224 0x226
User Assignable Data Registers
( 3X Registers Table 9 )
0x200
(16 bit)
0x202
(16 bit)
0x204
(16 bit)
0x206
(16 bit)
0x224
(16 bit)
0x226
(16 bit)
0x201
(16 bit)
0x203
(16 bit)
0x205
(16 bit)
0x 207
(16 bit)
0x225
(16 bit)
0x227
(16 bit)
55
To get the data throught User assignable Register use following step:
1)
Assign starting addresses(Table3) of parameters of interest to a “User assignable mapping registers” in a sequence in which they are to be accessed (see section “Assigning parameter to user assignable registers”)
2) Once the parameters are mapped data can be acquired by using “User assignable data register “ Starting address . i.e to access data of Voltage2, Power factor1,Wh import, Frequency send query with starting address 0x200 with number of register 8 or individually parameters can be accessed for example if current1 to be accessed use starting address 0x212. (See section Reading Parameter data through User Assignable Registers)
12. Phaser Diagram :
Capacitive
2
-
+
180 degrees (-1.000)
Inductive
90 degrees (0.000)
270 degrees (0.000)
Inductive
0 degrees (+1.000)
Capacitive
+
-
4
56
Connections Quadrant
Sign of Active Power ( P )
Sign of Reactive Power ( Q )
Sign of Power Factor ( PF )
Inductive / Capacitive
Import Import Export Export
1 + P 4 2 3
+ P
- P
- P
+ Q
- Q + Q
- Q
+ +
-
-
L C C L
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
When the instrument displays Active power ( P )with “ + ” ( positive sign ) , the connection is “ Import ”.
When the instrument displays Active power ( P )with “ - ” ( negative sign ) , the connection is “Export”.
13. Installation
PANEL
SLIDE IN THIS DIRECTION AND LOCK
Mounting is by four side clamps, slide the side clamps through side slot till side clamp gets firmly locked in a groove (Refer fig.) Consideration should be given to the space required behind the
Meter
instrument to allow for bends in the connection cables.
57
As the front of the enclosure conforms to IP54 it is protected from water spray from all directions, additional protection to the panel may be obtained by the use of an optional panel gasket. The terminals at the rear of the product should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient temperature and where the operating temperature is within the range
-20 to 70ºC. Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight.
Caution
1. In the interest of safety and functionality this product must be installed by a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal connections of this unit. Ensure that all supplies are de-energised before attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must be used to ensure safety under fault conditions.
13.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed to a good code of practice for EMC in industrial environments, e,g,
1. Screened output and low signal input leads or have provision for fitting RF suppression components, such as ferrite absorbers, line filters ect., in the event that RF fields cause problems.
Note: it is good practice to install sensitive electronic instruments that are performing critical functions, in EMC enclosures that protect against electrical interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of interference.
58
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit has been designed to automatically recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via Current Transformers only, where one side is grounded.
4. ESD precautions must be taken at all times when handling this product.
13.2 Case Dimension and Panel Cut Out
3.78”
96mm
3.78”
96mm
FRONT DISPLAY
AREA
3.15”
80mm
3.62”
92mm
PANEL CUTOUT
MAX PANEL THICKNESS 0.18”, 5mm
13.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure. Numbering is clearly marked in the plastic moulding. Choice of cable should meet local regulations. Terminal for both Current and Voltage inputs will accept up to 3mm2 x 2 diameter cables.
Note : It is recommended to use wire with lug for connection with meter.
3.62”
92mm
59
13.4 Auxiliary Supply
The instrument should ideally be powered from a dedicated supply, however it may be powered
from the signal source, provided the source remains within the limits of the chosen auxiliary voltage.
13.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuses.
13.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with local regulations.
14. Connection Diagrams
3-PHASE 3-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
L1 L2 L3
N
5
8
2
3
6 7 9
4
L N
AUX
SUPPLY
S1
P1
S1
P1
15. Specification :
System
3 Phase 3 Wire / 4 Wire programmable at site
3-PHASE 4-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
5
8
2
L1
L
L2
O
A
L3
D
N
11 1
P1
3
6 7 9
4
S1
S1
P1
13
14
L N
AUX
SUPPLY
L
S1
P1
O A D
60
Inputs
Nominal input voltage (AC RMS) (Three wire and Four wire)
Max continuous input voltage Max short duration input voltage
Phase-Neutral 63.5 / 133 / 239.6 / 254 V
Line-Line 110 / 230 / 415 / 440 V 120% of Rated Value
2 x Rated Value (1s application repeated 10 times at 10s intervals)
Nominal input voltage burden
0.2VA approx. per phase Nominal input current 5A AC rms Max continuous input current 120% of Rated Value Nominal input current burden 0.6VA approx. per phase
Max short duration current input
20 x Rated Value (1s application repeated 5 times at 5 min. intervals)
System CT primary values
Std. Values from 1 to 9999A (1 or 5 Amp secondaries)
Auxiliary
Standard nominal Auxillary
supply voltages & Frequency
a.c. supply voltage tolerance +10 % / -10 % of Rated Value
d.c. supply voltage tolerance +10 % / -10 % of Rated Value
100 - 250VAC- DC (45-66Hz),
12 - 48V DC
L-N
L-L
a.c. supply frequency range 45 to 66 Hz a.c. supply burden 6.5 V A d.c. supply burden 3W
61
Operating Measuring Ranges
Voltage
Current 5 .. 120 % of Rated Value
Frequency
Power Factor
5 .. 120 % of Rated Value 40 .. 70 Hz
0.5 Lag ... 1 ... 0.8 Lead
Accuracy
Accuracy 1:
Voltage r 0.5 % of range Current Frequency
Active Power Re- Active Power
Apparent Power Active Energy Re -Active Energy Apparant Energy Power Factor Angle Analog Output Total Harmonic Distortion Neutral Current
r 0.5 % of range
0.15% of mid frequency
r 0.5 % of range r 0.5 % of range
r 0.5 % of range r 1.0 % of range r 1.0 % of range r 1.0 % of range r 1 % of Unity r 1 % of range r 1 % of Output end value
r 1 %
r 4 % of range.
Accuracy 0.5:
Voltage r 0.5 % of range Current
Frequency Active Power Re- Active Power
Apparent Power Active Energy
r 0.5 % of range
0.15% of mid frequency
r 0.5 % of range r 0.5 % of range r 0.5 % of range
r 0.5 % of range
62
Re -Active Energy Apparent Energy
Power Factor Angle
Analog Output
Total Harmonic Distortion
Neutral Current
Accuracy 0.2:
r 0.5 % of range r 0.5 % of range
r 1 % of Unity r 1 % of range
r 1 % of Output end value
r 1 %
r 4 % of range
Voltage Current
Frequency Active Power
Re- Active Power Apparent Power
Active Energy Re - Active Energy
Apparant Energy Power Factor
Angle Analog Output
Total Harmonic Distortion Neutral Current
Reference conditions for Accuracy :
Reference temperature Input frequency
Input waveform Auxiliary supply voltage Auxiliary supply frequency
Voltage Range
± 0.2 % of range
± 0.2 % of range
0.15 % of mid frequency
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 0.2 % of range
± 1 % of Unity
± 1 % of range
± 1 % of Output end value
± 1 %
± 4 % of range
23ºC ± 2ºC 50 or 60Hz ± 2% Sinusoidal (distortion factor 0.005) Rated Value ± 1%
Rated Value ± 1 %
50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
63
Current Range
Power
Power Factor / Phase Angle 40... 100% of Nominal Current &
10... 100% of Nominal Value.
20... 100% of Nominal Value for THD. cosØ / sinØ = 1
For Active / Reactive Power & Energy
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.
50... 100% of Nominal Voltage.
Nominal range of use of influence quantities for measurands
Voltage Current
Input frequency Temperature
Auxiliary supply voltage
Auxiliary supply frequency
Temperature Coefficient (For Rated value range of use
0... 50ºC ) Error change due to variation of an
influence quantity
Display
TFT LCD Update
Controls
User Interface
50 .. 120 % of Rated Value 10 .. 120 % of Rated Value Rated Value ± 10 %
-20 to 70º Rated Value ± 10 %
Rated Value ± 10 %
0.025% / ºC for Voltage (50..120% of Rated Value)
0.05% / ºC for Current (10..120% of Rated Value) 2 * Error allowed for the reference
condition applied in the test.
3.5” Graphical LCD, resolution 320x240 pixels Approx. 1 seconds
Resistive Touch screen
64
Standards
EMC Immunity
Safety IP for water & dust
Isolation
Dielectric voltage withstand test between circuits and accessible surfaces
Environmental
Operating temperature Storage temperature
Relative humidity Warm up time
Shock Vibration
IEC 61326 10V/m min-Level 3 industrial low level electromagnetic radiation environment IEC 61000-4-3. IEC 61010-1 , Year 2001 IEC 60529
2.2 kV RMS 50 Hz for 1 minute between all electrical circuits
-20 to 70 ºC
-30 to +80 ºC 0 .. 90 % RH 3 minute (minimum) 15g in 3 planes
10 .. 55 Hz, 0.15mm amplitude
Enclosure ( front only )
Enclosure
Style Material
Terminals
Depth
Weight
IP 54 as per IEC 60529
96mm x 96mm DIN Quadratic Polycarbonate Housing ,
Self extinguish & non dripping as per UL94 V-0
Screw-type terminals < 80 mm
0.620 kg Approx.
65
ModBus ( RS 485 ) Option :
Protocol
Baud Rate
Analog Output Option :
Linear
ModBus ( RS 485 ) 19200 , 9600 , 4800 or 2400
( Programmable ) Odd or Even, with 1 stop bit,Parity
Or None with 1 or 2 stop bits 4 ... 20mA dc into 0 - 500 ohm
Uni-directional, internally powered.
66
16. Connection for Optional RS 485 / Analog Output ( rear view of the instrument )
1. RS 485 + Two Analog Output
Gnd
A1 A2
4 -20 mA
Gnd
B A
RS 485
Gnd
67
WARRANTY
Dear Sir,
You are now the privileged owner of Multi Function Meter / accessories, a product that rank the first of its kind in the world. Company provides 36 months warranty from the original date of Purchase against defective material and workmanship. In the unlikely event of failure of this meter / accessories within the warranty period, Company undertakes to get the meter / accessories repaired free of charge, Please handover the meter / accessories to the dealer / stockist from whom you have purchased along with this card and relevant Cash memo / Invoice. This warranty entitles you to bring the meter / accessories at your cost to the nearest stockist / dealer collect it after repairs.
NO TRANSPORTATION CHARGE WILL BE REIMBURSED
The warranty is not valid in following cases:
1) Warranty card duly signed and stamped and original Cash memo/Invoice is not send along with meter / accessories.
2) Complete warranty card is not presented to authorized person at the time of repairs.
3) Meter / accessories is not used as per the instructions in the user manual.
4) Defect caused by misuse, negligence, accidents, tampering and Acts of God.
5) Improper repairing by any person not authorized by the company.
6) Any sort of Modification, Alteration is made in electrical circuitry.
7) Seal provided inside is broken.
68
In case of dispute to the validity of the warranty, the decision of services center will be final. If you bought this meter / accessories directly fro the company, and if you notice transit damage, then you must obtain the insurance surveyor report and forward it. Thank you.
(To be filled by authorised dealer)
Model No. Serial Number
Date of Purchase Cash Memo / Invoice No.
Dealers Signature Dealer Stamp
: :
: :
: :
Scope of supply
1) Side Clamp
2) Connecters
3) User Manual
4) Warranty Card *5) Test Certificate
*As per customer requirements
69
Caution, risk of electric shock.
Attention, risque de choc électrique.
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product. However, Company has no control over the field conditions which influence product installation. It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Company only obligations are those in Company standard Conditions of Sale for this product and in no case will Company be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products.
Simpson Electric Company 520 Simpson Avenue Lac Du Flambeau, WI 54538-0099 (USA) Web: www.simpsonelectric.com Contact: +1 715-588-3311
Manual Part No. 06-118318 Edition 2, 05/18
Loading...