SILENT KNIGHT 5895XL Installation And Operation Manual

Page 1
MODEL
5895XL
Intelligent Power Module
for the 5820XL System
Installation and Operations Manual
Document 151142-L8 Rev:
151142-L8:J 15-0644
J
Page 2
Page 3
Content
Section 1
Overview ......................................................................................................................................................1-1
1.1 5895XL Description ..................................................................................................................1-1
1.1.1 Maximum Number of SBUS Modules ................................................................................1-2
1.2 Agency Requirements ..............................................................................................................1-5
1.3 About This Manual ...................................................................................................................1-5
1.4 How to Contact Silent Knight ....................................................................................................1-5
Section 2
Before You Begin Installing ......................................................................................2-1
2.1 What’s in the Box? ...................................................................................................................2-1
2.2 Environmental Specifications ............. ... ... .... ... .......................................... ...............................2-1
2.3 Preventing Water Damage .......................................................................................................2-1
2.4 5895XL Board and Terminal Strip Description .........................................................................2-2
2.5 Earth Fault Resistance .............................................................................................................2-4
2.6 Calculating Current Draw and Standby Battery ........................................................................2-5
2.6.1 Worksheet Requirements ..................................................................................................2-5
Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2) ..................................2-5
2.6.1.1 Maximum Battery Standby Load .............................................................................. 2-5
2.6.2 Current Draw Worksheet ....................................... ... ... .... ... ... ... ... .... ... ...............................2-6
2.7 Wiring Specifications ................................................................................................................2-7
2.7.1 Length Limitations . .... ... ... ... ....................................... ... .... ... ... ... ... ......................................2-7
2.7.2 Calculating Wiring distance for SBUS modules .................. ............................................... 2-7
Wiring Distance calculation example: .............................................................................2-9
2.7.3 Wire Routing ....................................................................................................................2-10
Section 3
Hardware Installation .................................................................................................................. 3-1
3.1 AC Power ..................................................... ... ... ... ....................................... ... .... ... ... ...............3-1
3.2 Battery Connection ...................................................................................................................3-2
3.3 Connecting the 5895XL to the FACP .......................................................................................3-3
3.3.1 Setting the Device ID ......................... .... ... ... ....................................... ... ... .... .....................3-5
3.4 Connecting SBUS Modules to the 5895XL ..............................................................................3-6
3.5 Flexputs™ I/O Circuits .............................................................................................................3-7
3.5.1 Conventional Notification Appliance ..................................................................................3-7
3.5.2 Releasing Operations ......................................... ... ... ... .... ... ... ... ... .... ... ...............................3-7
3.5.2.1 Class B Notification Wiring .......................................................................................3-7
3.5.2.2 Class A Notification Wiring .......................................................................................3-8
3.5.3 Conventional Initiation Circuits ...........................................................................................3-9
3.5.3.1 ................................................................................................................................. 3-9
3.5.3.2 Class A Inputs ........................................... ... ... ... .... ... ... ... ... ......................................3-9
151142 i
Page 4
Model 5895XL Intelligent Power Module Installation and Operation Manual
3.5.4 Installing 2-Wire Smoke Detectors ............................ ....... ...... ...... ....... ...... ....... ...... ....... ...3-10
Class B Installation .......................................................................... ... ... .... ... ... ... ... .... ...3-10
2-Wire Class A Smoke Detector Installation .................................................................3-11
3.5.5 Installing 4-Wire Smoke Detectors ............................ ....... ...... ...... ....... ...... ....... ...... ....... ...3-12
Installing a Class B 4-Wire Smoke Detector .................................................................3-12
Installing 4-Wire Class A Smoke Detectors ..................................................................3-13
3.5.6 Auxiliary Power Configuration ..........................................................................................3-13
3.5.6.1 Door Holder Power .................................................................................................3-14
3.5.6.2 Constant Power ......................................................................................................3-14
3.5.6.3 Resettable Power ...................................................................................................3-14
3.6 Conventional Relay Installation ..............................................................................................3-14
Appendix A Compatible Devices
A.1 Notification Appliances ............................................................................................................ A-1
A.2 Door Holder Device ............................................................................................................... A-12
A.3 Two-Wire Smoke Detectors ............................................................ ... .... ... ... ... .... ... ... ... ... ...... A-12
A.4 Four-Wire Smoke Detectors ..................................................................................................A-15
..................................................................................................................... A-1
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability
ii 151142
Page 5
Section 1 Overview
1.1 5895XL Description
The Model 5895XL Intelligent Power Module provides additional power and circuits to the IntelliKnight 5820XL F A CPs. The 5895XL can power all IntelliKnight compatible modules, including SLC devices (via a Model 5815XL SLC Expander), remote annunciators (Model 5860); notification appliances, auxiliary power modules, and all other compatible modules.
Note: The 5808 does not use 5815XL SLC expanders.
The 5895XL has six Flexputs™ and two programmable relays. Outputs are rated 3.0 A (6.0 A total for each 5895XL). Relays are Form C rated at 2.5 A @ 24 VDC. Outputs and relays are fully programmable.
The 5895XL is optically isolated, providing ground loop isolation and transient protection. It functions as an SBUS repeater which conditions the RS-485 signal and allows the module to drive up to 6,000 feet of additional SBUS wiring.
The 5895XL is housed in a metal cabinet that is identical in size to the IntelliKnight 5820XL FACP cabinet. This cabinet is large enough to house two 17 AH batteries. Like the 5820XL cabinets, the 5895XL cabinet provides mounting studs for two Model 5815XL SLC Expander modules.
The 5895XL communicates to the main IntelliKnight FACP via the SBUS. Each 5895XL provides an additional 6,000 feet of SBUS wiring length to the main panel. As the drawings on the next pages illustrate, this allows you to distribute modules, SLC devices, and outputs throughout an extremely large facility.
As well as expanding the wiring length capabilities of IntelliKnight, the 5895XL also expands IntelliKnight’s power capabilities by an additional 6.0 A of current.
151142 1-1
Page 6
Model 5895XL Intelligent Power Module Installation and Operation Manual
1.1.1 Maximum Number of SBUS Modules
The chart below shows the maximum number of compatible modules that can be used in an IntelliKnight installation. Modules can be distributed among the main panel SBUS and each additional 5895XL SBUS in virtually any combination.
Module or Device Maximum Number
5895XL Intelligent Power Module 8 per IntelliKnight installation 5860 Remote Annunciator 8 per IntelliKnight installation 5815XL SLC Expander 2 per IntelliKnight installation 5824 Serial/Parallel Modules 8 per IntelliKnight installation Outputs 6 per 5820XL / 5895XL Conventional Relays 2 per 5820XL / 5895XL
1-2 151142
Page 7
Overview
Figure 1-1 Example 5895XL Installation Overview
151142 1-3
Page 8
Model 5895XL Intelligent Power Module Installation and Operation Manual
Figure 1-2 Example 5895XL Installation Overview (Details Added)
1-4 151142
Page 9
Overview
1.2 Agency Requirements
The 5895XL has the same requirements as the main control panel. These requirements are listed in the IntelliKnight 5820XL Installation Manual (P/N 151209).
1.3 About This Manual
This manual covers installation of 5895XL hardware. Software configuration information is contained in the IntelliKnight 5820XL Installation Manual (P/N 151209).
1.4 How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103 (or 203-484-7161).
151142 1-5
Page 10
Section 2 Before You Begin Installing
2.1 What’s in the Box?
The Model 5895XL ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Ten 4.7K ohm end-of-line resistors
Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used.
A battery cable for batteries wired in series
2.2 Environmental Specifications
It is important to protect the 5895XL control panel from water. To prevent water damage, the following precautions should be FOLLOWED when installing the units:
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, pro­duction machinery)
When selecting a location to mount the 5895XL, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
2.3 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
151142 2-1
Page 11
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.4 5895XL Board and Terminal Strip Description
Figure 2-1 shows the 5895XL circuit board including location of terminals, the DIP switch for setting module ID, and the LED.
2-2 151142
Figure 2-1 The 5895XL Board Layout
Page 12
Before You Begin Installing
Table 2-1: Terminal Strip Description and Electrical Ratings
Terminal # and Label
1 L AC input (hot) 2 G Earth ground N/A N/A 3 N AC input (neutral) 4X
5 O 100 mA Initiation Circuits 6 X 7 O 100 mA Initiation Circuits 8X
9O 10 X
11 O 100 mA Initiation Circuits 12 X 13 O 100 mA Initiation Circuits 14 X 15 O 100 mA Initiation Circuits 16 B 17 A 18 + 19 ­20 B 21 A 22 + 23 ­24 N.C.
26 N.O. 27 N.C.
29 N.O. 30 B
31 A 32 +
33 -
I/O 6* Flexput™ Circuit 24 VDC
I/O 5* Flexput™ Circuit 24 VDC
I/O 4* Flexput™ Circuit 24 VDC
I/O 3* Flexput™ Circuit 24 VDC
I/O 2* Flexput™ Circuit 24 VDC
I/O 1* Flexput™ Circuit 24 VDC
SBUS communication 5 VDC 100 mA
SBUS OUT
SBUS power 24 VDC 1.0 A
SBUS IN Used for Class A installations
RELAY 2 G eneral Purpose Relay 2 24 VDC 2.5 A25 C
RELAY 1 General Purpose Relay 1 24 VDC 2.5 A28 C
SBUS IN/ OUT
MAIN
5895XL communication with main panel or to controlling 5895XL if daisy-chained
5895XL SBUS power (from 5820XL)
Description
Voltage Current
120/240 VAC, 50/60 Hz
120/240 VAC, 50/60 Hz
5 VDC 100 mA
24 VDC 10 mA
Rating
2.7 A
1.4 A
2.7 A
1.4 A
3.0 A Notification Circuits
3.0 A Notification Circuits
3.0 A Notification Circuits 100 mA
Initiation Circuits
3.0 A Notification Circuits
3.0 A Notification Circuits
3.0 A Notification Circuits
* Regulated/special application when used for releasing.
151142 2-3
Page 13
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.5 Earth Fault Resistance
Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP .
Table 2-2: Earth Fault Resistance Values by Terminal
Terminal Label Low Biased High Biased
Function
Terminal
Number
(Values in kohms)
High
Trip
High
Restore
Low Trip
Low
Restore
Flexput™ Notification Circuits
SBUS Communication
SBUS Power
4X 5O 00-­6X 7O 00-­8X 9O 00-­10 X 11 O 0 0 - ­12 X 13 O 0 0 - ­14 X 15 O 0 0 - ­16 B 17 A - - 0 0 18 + 0 0 - ­19 - - - 0 0
I/O 6
I/O 5
I/O 4
I/O 3
I/O 2
I/O 1
SBUS OUT
--00
--00
--00
--00
--00
--00
--00
20 B
Used for Class A Installations
21 A - - 0 0 22 + 0 0 - ­23 - - - 0 0
2-4 151142
--00
SBUS IN
Page 14
Before You Begin Installing
2.6 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your installation.
2.6.1 Worksheet Requirements
The following steps must be taken when determining 5895XL current draw and standby battery requirements.
Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2)
1. For the 5895XL, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw require­ments for alarm and standby. Record this information in Table 2-4 at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed 6.0 A. This is the maximum alarm current allowable.
6. Complete the remaining instructions in Table 2-4 for determining battery size requirements.
2.6.1.1 Maximum Battery Standby Load
Table 2-3 shows the maximum battery standby load for the 5895XL based on 24 and 60 hours of standby. The standby load calculations of line G in the Current Draw Calculation Worksheet (Table 2-4) must be less than the number shown in Table 2-3 for the battery size used and standby hours required.
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
7 AH 270 mA 105 mA 12 AH 475 mA 190 mA 17 AH 685 mA 270 mA 33 AH 1370 mA 540 mA
* Required for NFP A 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box)
and Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Com­municator/Transmitter (DACT).
Max. Load for 24 hrs. Standby ,
5 mins. Alarm
*Max. Load for 60 hrs. Standby , 5
mins. Alarm
Note:33AH max battery size for FM (Factory Mutual) installations
151142 2-5
Page 15
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.6.2 Current Draw Worksheet
For *each 5895XL in the installation, use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.)
Table 2-4: Current Draw Calculations
Device
For each device use this formula: This column X This column = Current per number of devices.
5895XL Intelligent Power Module (Current draw from battery)
Additional 5895XL (Daisy-chained to this module)
Addressable Devices (381 max.)
5815XL SLC Expander (2 max.)
5860 Remote Fire Alarm Annunciator (8 max.)
5824 Serial / Parallel Module (2 max.) 5865-4 LED Annunciator
(with reset and silence switches) 5865-3 LED Annunciator
5880 Generic LED Driver Module
A Total System Current
**Auxiliary Devices Refer to devices manual for current rating.
B Auxiliary Devices Current
C Notification Appliances Current mA D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5 ) : H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J ***Add lines G and I. Total ampere hours required AH
Number of
Devices
1*
(7 max.)
(8 max.)
Current per Device
Standby: 40 mA
Alarm: 160 mA Standby: 10 mA
Alarm: 10 mA Standby: 0.55 mA Alarm: 0.55 mA Standby: 55 mA mA Alarm: 55 mA mA Standby: 20 mA mA Alarm: 25 mA mA Standby: 45 mA mA Alarm: 45 mA mA Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 200 mA mA
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
Alarm: mA Alarm: mA mA Alarm: mA Alarm: mA
Standby
Current
40 mA
Alarm Current
160 mA
mA
mA mA
AH
2-6 151142
Page 16
Before You Begin Installing
* Use a separate worksheet for each 5895XL.
** If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because
*** Use next size battery with capacity greater than required.
power is removed during that time. However, during normal operation, door holders draw current and must be included in the 6.0 A total current that can be drawn from the panel.
2.7 Wiring Specifications
2.7.1 Length Limitations
This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B).
2.7.2 Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of
accessory modules are required, and the worst case current draw will exceed the 1 amp limit, then the current draw must be distributed using 5895XL Powe r Expanders. Each 5895XL Power Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for each 5895XL, and separately for the panel itself.
Model Number Worst Case Current Draw
5860 Fire Annunciator .100 amps 5824 Parallel/Serial Interface .040 amps 5880 LED IO Expander .250 amps 5865 LED Fire Annunciator .200 amps 5895XL Intelligent Power Supply .010 amps 5496 Intelligent Power Module .010 amps
After calculating the total worst case current draw, Table 2-5 specifies the maximum distance the modules can be located from the panel on a single wire run. The table insures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
151142 2-7
Page 17
Model 5895XL Intelligent Power Module Installation and Operation Manual
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
Table 2-5: Wire Distances Per Wire Gauge
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
* 500
Table 2-6: Typical Wire Resistance Per 1000 ft.
Wire Gauge Ohms per 1000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
2-8 151142
Page 18
Before You Begin Installing
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps
5895XL Current Draw = 1 x .010 amps = .010 amps
5865 Current Draw = 1 x .200 amps = .200 amps
5824 Current Draw = 1 x .040 amps = .040 amps
Total Worst Case Current Draw = .450 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire
151142 2-9
Page 19
Model 5895XL Intelligent Power Module Installation and Operation Manual
5895XL Board
2.7.3 Wire Routing
You must follow power-limited wiring techniques, which includes maintaining one-quarter inch spacing between power-limited and nonpower-limited circuits and separating high and low voltage circuits.
Figure 2-2 Wire Routing Example
2-10 151142
Page 20
Section 3
To 120 VAC
Power Source
Green
White
Black
Hardware Installation
5895XL installation involves the following steps:
AC power (Section 3.1) and backup battery connection (Section 3.2).
Physical connection to the IntelliKnight 5820XL FA CP or to the controlling 5895XL (see Section 3.3).
Setting an ID for the 5895XL (Section 3.3.1).
Physical connection of SBUS modules t hat will be powered by this 5895XL (Section 3.4).
Physical connection of any outputs (conventional relays, notification appliances, auxiliary power modules, and so on) that will be powered by this 5895XL. See Section 3.5.1 for notification appliance wiring information. Refer to the IntelliKnight 5820XL Installation Manual (P/N 151209), for software configuration information and other information about installing outputs.
3.1 AC Power
At installation, connect the AC terminals to 120 VAC source as shown in Figure 3-1. It may be necessary for a professional electrician to make this connection.
The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.7 A.
Figure 3-1 AC Power Connection
151142 3-1
Page 21
Model 5895XL Intelligent Power Module Installation and Operation Manual
Red
To Panel
Black
UL Listed 12V Battery
UL Listed 12V Battery
Battery Jumper
(P/N 140694)
Shipped With 5895XL
Replace batteries every 5 years.
Gell Cell
Gell Cell
3.2 Battery Connection
The 5895XL battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section Table 2-4).
Note: When your backup batteries requirements use backup batteries that are to large to fit into the
5895XL cabinet. The AB-33 cabinet holds batteries up to the 33 AH size. (Refer to Installation Manual P/N 151209 for AB-33 installation instructions.
* 33AH max battery size for FM (Factory Mutual) installations
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
3-2 151142
Figure 3-2 Battery Connection
Page 22
Hardware Installation
(FACP SBUS)
5895XL Terminals 30-33 are used only for connection 5895XL to the FACP or to the controlling 5895XL. Use 5895XL Terminals 16-19 to connect other SBUS modules (5815XL, 5860,
5824) and to daisy-chain 5895XL’s
5895XL Board (5895XL-1)
5895XL Board (5895XL-2)
To next 5895XL
and other SBUS
modules.
3.3 Connecting the 5895XL to the FACP
1. Connect the 5895XL to the appropriate SBUS. The 5895XL can be connected directly to the IntelliKnight 5820XL FACP or can be daisy-chained to another 5895XL. Figure 3-3 and Figure 3-4 show both connections.
2. Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2-1 shows the location of the DIP switches on the 5895XL board.
3. Configure the 5895XL module by adding it to the system (through JumpStart or manually). You can also assign a name to the module. These procedures are described in the IntelliKnight 5820XL Installation Manuals (P/N 151209).
Figure 3-3 Class B 5895XL Connection to FACP
151142 3-3
Page 23
Model 5895XL Intelligent Power Module Installation and Operation Manual
See Figure 3-6 for SBUS Module Connections
See Figure 3-6 for
SBUS Module
Connections
Figure 3-4 Class A 5895XL Connection to FACP
3-4 151142
Page 24
Hardware Installation
3.3.1 Setting the Device ID
board to set the module ID#. Figure 2-1 shows the location of the DIP switch on the board.
151142 3-5
Figure 3-5 Possible Module Addresses
Page 25
Model 5895XL Intelligent Power Module Installation and Operation Manual
3.4 Connecting SBUS Modules to the 5895XL
1. Connect SBUS modules to the 5895XL as shown in Figure 3-6 or Figure 3-7.
2. All SBUS modules must have an ID. Use the DIP switches on the module board to assign an ID number (1-31) to the module. This number identifies the module to the 5895XL and must be unique.
3. Software configuration steps vary for each SBUS module. For more information, refer to the Installation Manual (P/N 151209) in the section that discusses the type of module you are installing.
Figure 3-6 SBUS Class A Connection to 5895XL
3-6 151142
Page 26
Hardware Installation
Figure 3-7 SBUS Class B Wiring to 5895XL
3.5 Flexputs
The six Flexput™ circuits are an innovative and versatile feature of the 5895XL panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder).
This section of the manual explains how to install conventional notification appliances and initiating devices to be used with the 5895XL.
I/O Circuits
3.5.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A (Style Z) and Class B (Style Y) configurations.
3.5.2 Releasing Operations
Approved releasing solenoids are list in Table 3-1. Do not mix cross alarming zones with smoke verification zones. There must be at least two automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the linear
151142 3-7
Page 27
Model 5895XL Intelligent Power Module Installation and Operation Manual
Alarm
Polarity
UL Listed EOL
Model 7628
4.7 k
Supervised Power Limited
Notification Wiring
Regulated
spacing in accordance with NFPA 72.
Table 3-1: Approved Releasing Solenoids
Manufacturer Part Number Rating Current Freq
Asco T8210A107 24 VDC 3A max 0 Hz
8210G207 24 VDC 3A max 0 Hz
3.5.2.1 Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A. To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 3-8.
2. Configure the circuit through programming.
Figure 3-8 Class B Notification Appliance Circuit Wiring
3-8 151142
Page 28
Hardware Installation
Regulated
3.5.2.2 Class A Notification Wiring
Y ou must use an appliance from the list of comp atible appliances in the Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 3-9.
2. Configure the circuit for Class A in programming (see Section 7.4 of the Installation Manual P/N 151209).
Figure 3-9 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-9 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
151142 3-9
Page 29
Model 5895XL Intelligent Power Module Installation and Operation Manual
UL Listed EOL
Model 7628
4.7 k
3.5.3 Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations.
3.5.3.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 3-10.
2. Configure the circuit through programming (see Section 7.4 of the Installation Manual P/N 151209).
Figure 3-10 Class B Input Switches
3.5.3.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 3-11.
3-10 151142
Page 30
Hardware Installation
Note: I/O circuit 5 and 6
used as an example. Any I/O point pairing could be used.
2. Configure the circuit through programming (see Section 7.4 of the Installation Manual
151209).
Figure 3-11 Class A initiating Switches
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-11 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
3.5.4 Installing 2-Wire Smoke Detectors
Any compatible U.L. listed two-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed 2-wire detector to the control panel.
151142 3-11
Page 31
Model 5895XL Intelligent Power Module Installation and Operation Manual
Note: I/O circuit 5
used as an example. Any I/O circuit could be used.
UL Listed EOL
Model 7628
4.7 k
Note: I/O circuit 5 and 6
used as an example. Any I/O point pairing could be used.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3-12.
Figure 3-12 Two-Wire Class B Smoke Detector
2-Wire Class A Smoke Detector Installation
To install a Class A two-wire smoke detector, wire as shown in Figure 3-13.
Figure 3-13 Two-Wire Class A Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-13 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
3-12 151142
Page 32
Hardware Installation
Air Products
PAM-2
Model 160150
Supervision
Module
UL Listed
EOL Resistor
Model 7628
ESL 449CT
Note: I/O circuit 5 and 6
used as an example. Any I/O point pairing could be used.
3.5.5 Installing 4-Wire Smoke Detectors
Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed four-wire detector to the control panel.
Installing a Class B 4-Wire Smoke Detector
Figure 3-14 illustrates how to install a 4-wire Class B smoke detector. Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at once.
2. Each Class B loop input is paired with a unique power source as shown in Figure 3-14.
3. Each loop gets smoke power from the even numbered I/O circuit and the contact input is connected to the odd numbered I/O circuit.
Figure 3-14 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-14 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
151142 3-13
Page 33
Model 5895XL Intelligent Power Module Installation and Operation Manual
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Installing 4-Wire Class A Smoke Detectors
Figure 3-15 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops:
1. Up to two Class A 4-wire loops can be connected to the control panel at once.
2. Smoke power is supplied to each Class A loop as shown in Figure 3-15.
Figure 3-15 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-15 uses I/O circuits 1, 2, 3 together and 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.
3.5.6 Auxiliary Power Configuration
Flexput circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are:
Door Holder (see Section 3.5.6.1 for description)
Constant (see Section 3.5.6.2 for description)
Resettable (see Section 3.5.6.3 for description)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 5A).
To configure a Flexput circuit as auxiliary power:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 3-16 for location or Flexput circuits.
3-14 151142
Page 34
Hardware Installation
2. Configure the auxiliary power output through programming fo r Door Holder, Constant or Resettable power.
Figure 3-16 Flexput Circuits Used as Auxiliary Power
3.5.6.1 Door Holder Power
Door holder is intended for fire door applications. When there are no alarms in the system and the panel has AC power , door holder circuits have 24-volt power present at their terminals. Any alarm will cause power to discontinue. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds the auxiliary door holder power will be discontinued to conserve the battery backup power. When AC power is restored, power is immediately restored to the door holder circuits.
3.5.6.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
3.5.6.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors, and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is removed from the terminals for 30 seconds, then re-applied.
3.6 Conventional Relay Installation
5895XL relay circuits are installed in exactly the same way as 5820XL main panel relay circuits. For ease of installation, the 5895XL output terminals use the same numbering scheme as 5820XL terminals. Refer to the Installation Manual P/N 151209 for information on installing conventional relays.
151142 3-15
Page 35
Appendix A Compatible Devices
A.1 Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the 5895XL must be polarized.
Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you
have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
A.1 below lists notification appliances compatible with the fire alarm control panel. Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and/or Visual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Horn/Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Horn/Strobe Horn/Strobe Horn/Strobe Chimes/Strobe Chimes/Strobe Chimes/Strobe Chimes/Strobe Horn Horn
AMSECO
SH24W-153075 SAD24-153075 SAD24-75110 SL24W-75110 SL24C-3075110 SLB24-75 RSD24-153075 RSD24-75110 SH24W-75110 SH24W-3075110 SHB24-75 SCM24W-153075 SCM24W-75110 SCM24C-3075110 SCM24C-177 H24W H24R
xx
x x x x x x
x xx xx xx x x x x x x
.
151142 A-1
Page 36
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
446 x Vibrating Bell 476 x Vibrating Bell 477 x Single Stroke Bell 2700 -M. -R, -T, -Y, -Z x Strobe 2701 Series x Strobe 2705 Series x Strobe 2820 x x Snyc Temporal Horn/Strobe 2821 x x Snyc Temporal Horn/Strobe 2824 x x Horn Strobe 5333 x Multi-Tone Horn) 5336 x x Multi-Tone Horn/Strobe
Faraday
5337 x x Multi-Tone Horn/Strobe 5338 x x Multi-Tone Horn/Strobe 5343 x x Single Tone Horn/Strobe 5346 x x Electronic Horn with Strobe 5347 x x Electronic Horn with Strobe 5348 x x Single Tone Horn/Strobe 5373 x x 8- Tone Horn/Strobe 6321 x x Sync Mini Horn/Strobe 6322 x x Mini Horn/Sync Strobe 6380 x 8-Tone Electronic Signal/Strobe 5376 x x 8- Tone Horn/Strobe 5377 x x 8- Tone Horn/Strobe
A-2 151142
Page 37
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
5378 x x 8- Tone Horn/Strobe 5383 x x 8-Tone Horn/Strobe with Sync Strobe 5386 x x 8-Tone Horn/Strobe with Sync Strobe 5387 x 8-Tone Horn/Strobe with Sync Strobe 5388 x 8-Tone Horn/Strobe with Sync Strobe 5508 x Single Gang Sync Strobe 5509 x Strobe 5510 x Strobe 5511 x Strobe 5512 x Strobe 5516 x Strobe 5517 x Strobe 5518 x Strobe 5519 x Strobe 5521 x 4” Square Sync Strobe 5522 x 4” Square Sync Strobe 6120 x Horn
Faraday (cont.)
FCI
6140 x Horn 6223 x Horn 6226 x x Horn/Strobe 6227 x x Horn/Strobe 6228 x x Horn/Strobe 6243 x Electron-Mechanical Horn 6244 x Electron-Mechanical Horn 6245 x Electron-Mechanical Horn 6246 x x Electron-Mechanical Horn/Strobe 6247 x x Electron-Mechanical Horn/Strobe 6248 x x Electron-Mechanical Horn/Strobe 6300 x Mini-Horn 6301 x Mini-Horn 6302 x Mini-Horn 6310 x
6311 x 6312 x 6314 Series -M, -R, -T, -Y, -Z x Strobe
6320 x x Sync Mini Horn/Strobe S2415-FC x Strobe S241575-FC x Strobe S2430-FC x Strobe 130-3117C
130-3147C BLV-6 BLV-10
x x x x
x
x
x
Mini-Horn/Strobe Mini-Horn/Strobe Mini-Horn/Strobe
Mini Horn Mini Horn Vibrating Bell Vibrating Bell
Compatible Devices
151142 A-3
Page 38
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Vibrating Chime Horn Horn Horn
Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe
MiniHorn Steady Tone MiniHorn Temporal Tone
FCI (cont.)
Federal Signal
Gentex
BLVCH H12/24-FC H12/24W-FC H12/24K-FC HC12/24-FC x Horn
HC12/24W-FC x Horn HC12/24K-FC x Horn P2415-FC x x Horn/Strobe P2415W-FC x x Horn/Strobe P2415K-FC x x Horn/Strobe P241575-FC x x Horn/Strobe P241575W-FC x x Horn/Strobe P241575F-FC x x Horn/Strobe P241575K-FC x x Horn/Strobe P2430-FC x x Horn/Strobe P2430W-FC x x Horn/Strobe P2430K-FC x x Horn/Strobe P2475-FC x x Horn/Strobe P2475W-FC x x Horn/Strobe P2475K-FC x x Horn/Strobe P24110-FC x x Horn/Strobe P24110W-FC x x Horn/Strobe P24110K-FC x x Horn/Strobe S2430W-FC x Strobe S2430K-FC x Strobe S2475-FC x Strobe S2475W-FC x Strobe S2475K-FC x Strobe S24110-FC x Strobe S24110W-FC x Strobe S24110K-FC x Strobe 450 x Horn VALS x x Horn/Strobe GEC-24-15 GEC-24-30 GEC-24-60 GEC-24-75 GEC-24-177 GEC-24-110 GEC-24-15/75 x x Horn/Strobe GX91 GX93
x x x x
xx xx xx xx xx xx
x x
A-4 151142
Page 39
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
HG124 x Horn
Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Multi Candella Horn/Strobe Ceiling Mount Multi Candella Horn/Strobe Ceiling Mount Multi Candella Strobe Ceiling Mount Multi Candella Strobe Ceiling Mount Multi Candella Horn/Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Multi Candella Strobe Multi Candella Strobe Horn Strobe Strobe Strobe Strobe Strobe Weatherproof Horn/Strobe Weatherproof Strobe
Gentex (cont.)
HS24-15 HS24-30 HS24-60 HS24-75 HS24-110 HS24-1575 GCC24 GCCR24 GCS24 GCSR24 GECR-24 GES24-15 GES24-30 GES24-60 GES24-75 GES24-110 GES24-15/75 GES24-177 GES3-24 GESR-24 GEH-24 ST24-30 ST24-60 ST24-75 ST24-110 ST24-1575 WGEC24-75W WGES24-75W WGMS-24-X x x Horn/Strobe
xx xx xx xx xx xx xx
x
x
x xx
x
x
x
x
x
x
x
x
x x
x
x
x
x
x xx
x
Compatible Devices
151142 A-5
Page 40
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Chime Chime 2-Wire Chime/Strobe 2-Wire Chime/Strobe Horn Horn Horn
Chime/Strobe Red Wall 4x4 Chime/Strobe WHT Wall 4x4 Chime/Strobe Red Ceil 4x4 Chime/Strobe WHT Ceil 4x4 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe High Candela
System Sensor
CHR CHW CHSR CHSW HR HW HRK HWL x Horn WHT Wall 4x4
HRL x Horn Red Wall 4x4 HGRL x Horn Red Wall 2x4 HGWL x Horn WHT Wall 2x4 CHWL x Chime WHT Wall 4x4 CHRL x Chime Red Wall 4x4 CHSRL CHSWL CHSCRL CHSCWL P2R P2R-P PC2R PC2R-P P2RH P2RH-P PC2RH PC2RH-P P2W P2W-P PC2W PC2W-P P2WH
x x xx xx xx
x
x
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
A-6 151142
Page 41
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
System Sensor (cont.)
P2WH-P PC2WH PC2WH-P P2RK PC2RK P2RHK PC2RHK P4R PC4R P4RH P4W PC4W P4WH PC4WH P4RK PC4RK P4RHK PC4RHK PC4RH P2RL, P2RL-P, P2RL-SP* x x Horn/Strobe 2W Red Wall 4x4 P2WL, P2WL-P, P2WL-SP* x x Horn/Strobe 2W WHT Wall 4x4
PC2RL x x Horn/Strobe 2W Red Ceil 4x4 PC2WL x x Horn/Strobe 2W WHT Ceil 4x4 P2GRL x x Horn/Strobe 2W Red Wall 2x4 P2GWL x x Horn/Strobe 2W WHT Wall 2x4 SR
SR-P SCR SCR-P SRH SRH-P SCRH SCRH-P SW SW-P SCW SCW-P SWH SWH-P SCWH
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe 4-Wire Horn/Strobe 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe 4-Wire Horn/Strobe 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe 4-Wire Horn/Strobe 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe High Candela
Strobe Strobe Strobe Strobe Strobe High Candela Strobe High Candela Strobe High Candela Strobe High Candela Strobe Strobe Strobe Strobe Strobe High Candela Strobe High Candela Strobe High Candela
Compatible Devices
151142 A-7
Page 42
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
System Sensor (cont.)
SCWH-P SRK SCRK SRHK SCRHK SRL, SRL-P, SRL-SP* SWL, SWL-P, SWL-ALERT
SWL-CLR-ALERT* SCRL
SCWL SCWL-CLR-ALERT SGRL SGWL P2RH-LF P2WH-LF HR-LF x Low Frequency Sounder HW-LF x Low Frequency Sounder
xx xx
x
x
x
x
x
x
x
x
x
x
x
x
Strobe High Candela Strobe Strobe Strobe High Candela Strobe High Candela Strobe Red Wall 4x4 Strobe White Wall 4x4
Strobe Red Ceil 4x4 Strobe White Ceil 4x4 Strobe WHT Ceil CLR Lens 4x4 Strobe Red Wall 2x4 Strobe White Wall 2x4 2-Wire Low Frequency Sounder Strobe 2-Wire Low Frequency Sounder Strobe
* P=Plain, ALERT=Pad Printing ALERT, SP=Fuego
Wheelock
AH-12 AH-24 AH-12WP AH-24WP AMT-241575W AMT-24MCW AMT-241575W-NYC AMT-12/24 AMT-12/24 NYC AS-121575W NH-12/24 AS-241575W AS-24MCC AS-24MCCH AS-24MCW AS-24MCWH ASWP-2475W ASWP-2475C
x x x x xx
x xx x x
x xx xx xx xx xx xx xx xx
Horn Horn Horn Weatherproof Horn Weatherproof Multi-Tone Horn Strobe Mutli-Tone Horn Strobe Multi-Tone Horn Strobe Multi-tone Horn Multi-tone Horn Horn/Strobe Horn Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Weatherproof Horn/Strobe Weatherproof
A-8 151142
Page 43
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Horn/Strobe Horn/Strobe Chime Chime Chime/Strobe Chime/Strobe Chime/Strobe Chime/Strobe Chime/Strobe Horn Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Mini Horn Strobe MultitoneHorn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Horn Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe
Wheelock (cont.)
ASWP-24MCWH ASWP-24MCCH CH-70 CH-90 CH70-241575W CH70-24MCW CH70-24MCWH CH90-24MCC CH90-24MCCH HS-24 HS4-241575W HS4-24MCW HS4-24MCWH HS4-24MCC MIZ-24S MT-121575W MT-241575W x MT-24MCW MTWP-2475W MTWP-2475C MTG-121575W MTR-121575W MTWPA-2475W MTWPB-2475W MTWPG-2475W MTWPR-2475W MTWPA-24MCCH ZNH NS-121575W NS-241575W NS-24MCW NS-24MCC NS-24MCCH ZNS-MCW ZNS-MCWH ZNS-24MCC
xx xx x x
x
x
x
x
x x xx xx xx xx xx
x
x
x
x
x xx xx xx xx xx xx xx x xx xx xx xx xx xx xx xx
Compatible Devices
151142 A-9
Page 44
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Horn/Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Multi-Cd Strobe Multi-Cd Strobe Multi-Cd Strobe Multi-Cd Strobe Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof
Wheelock (cont.)
ZNS-24MCCH RSS-121575W RSS-241575W RSS-24MCC RSS-24MCCR RSS-24MCCH RSS-24MCCHR RSS-24MCW RSS-24MCWH RSSP-121575W RSSP-241575W RSSR-2415W RSSR-2415C RSSR-2475W RSSR-2475C RSSR-24110C RSSA-24110W RSSB-24110W RSSG-24110W RSSR-24110W RSSA-24MCC RSSB-24MCC RSSG-24MCC RSSR-24MCC RSSWPA-2475W RSSWPA-24MCCH RSSWPG-24MCCH RSSWPR-24MCCH RSSWP-2475W RSSWP-2475C RSSWP-24MCWH
xx
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
A-10 151142
Page 45
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Strobe Strobe Strobe
Multitone Horn Multitone Horn Strobe Multitone Horn Strobe
Horn/Strobe Horn/Strobe Strobe Strobe Horn Horn
Wheelock (cont.)
ZRS-MCWH ZRS-24MCC ZRS-24MCCH MB-G6-24 x Motor Bell
MB-G10-24 x Motor Bell MB-G6-12 x Motor Bell MB-G10-12 x Motor Bell MIZ-24-R x Mini-Horn MT-12/24-R x MT4-12/2z x ZRS-MCW MTWPR-24MCCH x NH-12/24R x Horn HSR HSW STR STW HNR HNW
x
x
x
x
x
x
x
x
x
x
x
x
x
Compatible Devices
A.2 Two-Wire Smoke Detectors
Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used.
5895XL Identifier Operating Voltage Range
The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke detector . If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur. Do not mix detectors of different models unless the system is specifically intended to be installed in
that configuration. Control unit Smoke Reset Time must be pr ogrammed for a number greater than or equal to the
maximum reset time of the smoke detector. Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The table is
24H
18.5–27.4 VDC
151142 A-11
Page 46
Model 5895XL Intelligent Power Module Installation and Operation Manual
organized by manufacturer. The columns show the number of detectors per loop that can be used.
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
Apollo
Detection Systems
ESL
Model Name or Number
(Base model name or number in
parentheses.)
55000-350 (45681-200) 55000-350 45681-200 24 / loop 55000-250 (45681-200) 55000-250 45681-200 24 / loop DS200 (MB200-2W) A A 30 / loop DS200HD (MB200-2W) A A 30 / loop DS230 N/A N/A 30 / loop DS250 (MB2W or MB2WL) B A 30 / loop DS250HD (MB2W or MB2WL) B A 30 / loop DS250TH (MB2W or MB2WL) B A 30 / loop DS282 B N/A 30 / loop DS283 (MB2W or MB2WL) N/A N/A 30 / loop DS283TH (MB2W or MB2WL) N/A N/A 30 / loop 425 (S10) 30 / loop 425C (S11) 30 / loop 425CR (S11) 30 / loop 425CRT (S11) 30 / loop 425CT (S11) S10 N/A 30 / loop 429C (S10A) N/A S10A 30 / loop 429CRT (S11A) N/A S11A 30 / loop 429CST (S11A) N/A S11A 30 / loop 429CT (S10A) N/A S10A 30 / loop 521BXT N/A S11A 30 / loop 521B N/A S11A 30 / loop 609U01-11 S10 S00 40 / loop 609U02-11 S10 S00/S03 40 / loop 611U (601U or 602U) S10 S00/S03 40 / loop 611UD (601U or 602U) S10 S00/S03 40 / loop 611UT (601U or 602U) S10 S00/S03 40 / loop 612U (601U or 602U) S10 S00/S03 40 / loop 612UD (601U or 602U) S10 S00/S03 40 / loop 711U (701E or 701U) N/A S10A 25 / loop 712U (701E or 701U) N/A S10A 25 / loop 713-5U (702E or 701U) N/A S10A 25 / loop 713-6U (702E or 701U) N/A S10A 25 / loop 721-U (S10A) N/A S10A 30 / loop 721-UT (S10A) N/A S10A 30 / loop
Compatibility ID
# per Loop
Head Base
A-12 151142
Page 47
Table A-2: Compatible Two-Wire Smoke Detectors
Compatible Devices
Manufacturer
Kidde-Fenwall
Falcon
Faraday
Hochiki
Model Name or Number
(Base model name or number in
parentheses.)
PSD 7156 (FE01A) (P56FE1) P56FE1 FE01A 30 / loop PSD 7156 (FE51A) (P56FE1) P56FE1 FE51A 30 / loop PSD 7155 (FE01A) (P55FE1) P55FE1 FE1A 30 / loop PSD 7155 (FE51A) (P55FE1) P56FE1 FE1A 30 / loop CPD 7051 (FE01A) (I51FE1) CPD 7051 FE51A 30 / loop CPD 7051 (FE01A) CPD 7051 FE01A 30 / loop CPD 7051 (FE51A) CPD 7051 FE51A 30 / loop 525 FDT1 N/A 17 / loop 525T FDT1 N/A 17 / loop 9374 30 / loop 9375 30 / loop 9376 30 / loop SIH-24F (HS-224D OR HSD-224) HD-3 HB-5 30 / loop SLK-12 30 / loop SLK-24F (HS-224D) HD-3 HB-5 30 / loop SLK-24FH (HS-224D) HD-3 HB-5 30 / loop SLR-24 V 30 / loop SLR-835B-2 (HD-6) 30 / loop
Compatibility ID
# per Loop
Head Base
151142 A-13
Page 48
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
System Sensor
System Sensor (cont.)
Model Name or Number
(Base model name or number in
parentheses.)
Compatibility ID
# per Loop
Head Base
1100T A N/A 30 / loop 1100TB A N/A 30 / loop 1151 (110LP) A A 30 / loop 1400 A N/A 20 / loop 1451 (B401B) A A 20 / loop 1800 A N/A 30 / loop 1851B (B101B) A A 30 / loop 1851DH (DH1851DC) A A 30 / loop 2100 A N/A 30 / loop 2100D A N/A 30 / loop 2100S A N/A 30 / loop 2100T A N/A 30 / loop 2100TB A N/A 30 / loop 2100TS A N/A 30 / loop 2151 (B110LP) A N/A 30 / loop 2300T A N/A 30 / loop 2300 A N/A 30 / loop 2300TB A N/A 30 / loop 2400 A N/A 30 / loop 2400 (DH400) A N/A 30 / loop 2400AIT A N/A 30 / loop 2400AT A N/A 30 / loop 2400TH A N/A 30 / loop 2451 (B401B) A N/A 30 / loop 2451DH (DH 400) A N/A 30 / loop 2451TH (B401B) A N/A 30 / loop 2800 A N/A 30 / loop 2800TH A N/A 30 / loop 2851B (B101B) A A 30 / loop 2851BTH (B101B) A A 30 / loop 2851DH A A 30 / loop 2851TH (B101B) A A 30 / loop
3
2W-B
i
3
i
2WT-B
A N/A 30 / loop A N/A 30 / loop
A-14 151142
Page 49
A.3 Four-Wire Smoke Detectors
Table 3-2: Compatible Four-Wire Smoke Detectors
Manufacturer Model
Compatible Devices
Silent Knight Detection Systems
ESL
Gentex
Hochiki
System Sensor
SD-P24F with SD-B4 base
DS200/DS200HD MB200 Base
445 Series 449 Series
624 824 2040-24 Power Supervision Unit
SIH-24F HS-224D or SHB-224 Base SLK-24F HS-224D Base SLK-23FH HS-224D Base
1851B 2851/2851BTH DH200ADCD
A.3.1 Door Holder Device
The following UL listed door holder can be used with the 5895XL: ESL DHS-1224
151142 A-15
Page 50
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
All new fire products manufactured by Honeywell have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details.
This limited warranty does not apply to tho se produ cts that are damaged due to misuse, abuse, negligen ce, exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Repair and RMA Procedure
All products that are returned by Honeywell for credit or repair require a RMA (Return Authorization) number. Call Customer Service at 800-328-0103 or 203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday through Friday to obtain a return authorization number.
Honeywell Technical Support is available at 800-446-6444 between 8:00 A.M. and 5:00 P .M. CST, Monday through Friday.
All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit.
RMA number must be prominently displayed on the outside of the shipping box. See return address example under Advanced Replacement Policy.
Included with each return should be: a packing slip that has the RMA number, a content list, and a detailed description of the problem.
All products returned by Honeywell must be sent freight pre-paid. After product is processed by Honeywell will pay for shipping product back to customer via UPS ground.
Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an additional $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries to Honeywell has the authority to determine if a product is repairable. Products that are deemed un-repairable will be returned to the customer.
Product that is returned that has a board date code more than 36 months from date of manufacture will be repaired and the customer will be assessed the standard Honeywell repair charge for that model.
Advanced Replacement Policy
Honeywell offers an option of advance replacement for fire product printed circuit boards that fail during the first 6 months of the warranty period. These items must be returned with transportation charges prepaid and must be accompanied by a return authorization.
For advance replacement of a defective board, contact your local Honeywell distributor or call Honeywell at 800-328-0103 to obtain a RMA (Return Authorization) number and request advanced replacement.
A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Honeywell. All returned products must comply with the guidelines described under “General Terms and Conditions” and “Repair and RMA Procedure”.
The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit. No credit will be issued if the returned board was damaged due to misuse or abuse.
Page 51
Repairs and returns should be sent to: Honeywell Fire Systems Attn: Repair Department / RA Number_______________________ 12 Clintonville Road Northford, CT 06472 USA
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to extent possible, any warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, service repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY P AR TICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
Page 52
Page 53
Page 54
12 Clintonville Road
Northford, CT 06472-1610
Fax: 203-484-7118
www.silentknight.com
Silent Knight
203-484-7161
Loading...