Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
ii151142
Page 5
Section 1
Overview
1.15895XL Description
The Model 5895XL Intelligent Power Module provides additional power and circuits to
the IntelliKnight 5820XL F A CPs. The 5895XL can power all IntelliKnight compatible
modules, including SLC devices (via a Model 5815XL SLC Expander), remote
annunciators (Model 5860); notification appliances, auxiliary power modules, and all
other compatible modules.
Note: The 5808 does not use 5815XL SLC expanders.
The 5895XL has six Flexputs™ and two programmable relays. Outputs are rated 3.0
A (6.0 A total for each 5895XL). Relays are Form C rated at 2.5 A @ 24 VDC.
Outputs and relays are fully programmable.
The 5895XL is optically isolated, providing ground loop isolation and transient
protection. It functions as an SBUS repeater which conditions the RS-485 signal and
allows the module to drive up to 6,000 feet of additional SBUS wiring.
The 5895XL is housed in a metal cabinet that is identical in size to the IntelliKnight
5820XL FACP cabinet. This cabinet is large enough to house two 17 AH batteries.
Like the 5820XL cabinets, the 5895XL cabinet provides mounting studs for two Model
5815XL SLC Expander modules.
The 5895XL communicates to the main IntelliKnight FACP via the SBUS. Each
5895XL provides an additional 6,000 feet of SBUS wiring length to the main panel. As
the drawings on the next pages illustrate, this allows you to distribute modules, SLC
devices, and outputs throughout an extremely large facility.
As well as expanding the wiring length capabilities of IntelliKnight, the 5895XL also
expands IntelliKnight’s power capabilities by an additional 6.0 A of current.
1511421-1
Page 6
Model 5895XL Intelligent Power Module Installation and Operation Manual
1.1.1Maximum Number of SBUS Modules
The chart below shows the maximum number of compatible modules that can be
used in an IntelliKnight installation. Modules can be distributed among the main panel
SBUS and each additional 5895XL SBUS in virtually any combination.
Module or Device Maximum Number
5895XL Intelligent Power Module8 per IntelliKnight installation
5860 Remote Annunciator8 per IntelliKnight installation
5815XL SLC Expander2 per IntelliKnight installation
5824 Serial/Parallel Modules8 per IntelliKnight installation
Outputs 6 per 5820XL / 5895XL
Conventional Relays 2 per 5820XL / 5895XL
1-2151142
Page 7
Overview
Figure 1-1 Example 5895XL Installation Overview
1511421-3
Page 8
Model 5895XL Intelligent Power Module Installation and Operation Manual
Figure 1-2 Example 5895XL Installation Overview (Details Added)
1-4151142
Page 9
Overview
1.2Agency Requirements
The 5895XL has the same requirements as the main control panel. These
requirements are listed in the IntelliKnight 5820XL Installation Manual (P/N 151209).
1.3About This Manual
This manual covers installation of 5895XL hardware. Software configuration
information is contained in the IntelliKnight 5820XL Installation Manual (P/N 151209).
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact
Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103 (or 203-484-7161).
1511421-5
Page 10
Section 2
Before You Begin Installing
2.1What’s in the Box?
The Model 5895XL ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Ten 4.7K ohm end-of-line resistors
Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used.
•A battery cable for batteries wired in series
2.2Environmental Specifications
It is important to protect the 5895XL control panel from water. To prevent water
damage, the following precautions should be FOLLOWED when installing the units:
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the 5895XL, the unit should be mounted where it
will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
2.3Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet
through the conduits. Conduits that are installed to enter the top of the cabinet are
most likely to cause water problems. Installers should take reasonable precautions to
prevent water from entering the cabinet. Water damage is not covered under
warranty.
1511422-1
Page 11
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.45895XL Board and Terminal Strip Description
Figure 2-1 shows the 5895XL circuit board including location of terminals, the DIP
switch for setting module ID, and the LED.
2-2151142
Figure 2-1 The 5895XL Board Layout
Page 12
Before You Begin Installing
Table 2-1: Terminal Strip Description and Electrical Ratings
This section is for helping you determine the current draw and standby battery needs
for your installation.
2.6.1Worksheet Requirements
The following steps must be taken when determining 5895XL current draw and
standby battery requirements.
Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2)
1. For the 5895XL, the worst case current draw is listed for the panel, addressable
devices, and SLC expanders. Fill in the number of addressable devices and
expanders that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in Table 2-4 at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual,
refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the
panel itself, does not exceed 6.0 A. This is the maximum alarm current allowable.
6. Complete the remaining instructions in Table 2-4 for determining battery size
requirements.
2.6.1.1Maximum Battery Standby Load
Table 2-3 shows the maximum battery standby load for the 5895XL based on 24 and
60 hours of standby. The standby load calculations of line G in the Current Draw
Calculation Worksheet (Table 2-4) must be less than the number shown in Table 2-3
for the battery size used and standby hours required.
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
7 AH270 mA105 mA
12 AH475 mA190 mA
17 AH685 mA270 mA
33 AH1370 mA540 mA
* Required for NFP A 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box)
and Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Max. Load for 24 hrs. Standby ,
5 mins. Alarm
*Max. Load for 60 hrs. Standby , 5
mins. Alarm
Note:33AH max battery size for FM (Factory Mutual) installations
1511422-5
Page 15
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.6.2Current Draw Worksheet
For *each 5895XL in the installation, use this worksheet to determine current
requirements during alarm/battery standby operation. (Copy this page if additional
space is required.)
Table 2-4: Current Draw Calculations
Device
For each device use this formula: This columnX This column= Current per number of
devices.
5895XL Intelligent Power Module
(Current draw from battery)
Additional 5895XL
(Daisy-chained to this module)
Addressable Devices(381 max.)
5815XL SLC Expander(2 max.)
5860 Remote Fire Alarm Annunciator(8 max.)
5824 Serial / Parallel Module(2 max.)
5865-4 LED Annunciator
(with reset and silence switches)
5865-3 LED Annunciator
5880 Generic LED Driver Module
ATotal System Current
**Auxiliary DevicesRefer to devices manual for current rating.
BAuxiliary Devices Current
CNotification Appliances CurrentmA
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5 ) :H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
IMultiply lines E and H.Total alarm AH
J***Add lines G and I. Total ampere hours requiredAH
Number of
Devices
1*
(7 max.)
(8 max.)
Current per Device
Standby:40 mA
Alarm:160 mA
Standby:10 mA
Alarm:10 mA
Standby:0.55 mA
Alarm:0.55 mA
Standby:55 mAmA
Alarm:55 mAmA
Standby:20 mAmA
Alarm:25 mAmA
Standby:45 mAmA
Alarm:45 mAmA
Standby:35 mAmA
Alarm:145 mAmA
Standby:35 mAmA
Alarm:145 mAmA
Standby:35 mAmA
Alarm:200 mAmA
Alarm/Standby: mA mAmA
Alarm/Standby:mAmAmA
Alarm/Standby:mAmAmA
Alarm/Standby:mAmAmA
Alarm:mA
Alarm:mAmA
Alarm:mA
Alarm:mA
Standby
Current
40
mA
Alarm Current
160
mA
mA
mA
mA
AH
2-6151142
Page 16
Before You Begin Installing
*Use a separate worksheet for each 5895XL.
**If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because
***Use next size battery with capacity greater than required.
power is removed during that time. However, during normal operation, door holders draw current and must be
included in the 6.0 A total current that can be drawn from the panel.
2.7Wiring Specifications
2.7.1Length Limitations
This section contains information on calculating SBUS wire distances and the types
of wiring configurations (Class A and B).
2.7.2Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the
maximum wiring distance that can be used with SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the
panel, it is necessary to calculate the total worst case current draw for all modules on
a single 4-conductor bus. The total worst case current draw is calculated by adding
the individual worst case currents for each module. The individual worst case values
are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of
accessory modules are required, and the worst case current draw will exceed the 1 amp limit,
then the current draw must be distributed using 5895XL Powe r Expanders. Each 5895XL Power
Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring
distance calculations are done separately for each 5895XL, and separately for the panel itself.
Model NumberWorst Case Current Draw
5860 Fire Annunciator.100 amps
5824 Parallel/Serial Interface.040 amps
5880 LED IO Expander.250 amps
5865 LED Fire Annunciator.200 amps
5895XL Intelligent Power Supply.010 amps
5496 Intelligent Power Module.010 amps
After calculating the total worst case current draw, Table 2-5 specifies the maximum
distance the modules can be located from the panel on a single wire run. The table
insures 6.0 volts of line drop maximum. In general, the wire length is limited by
resistance, but for heavier wire gauges, capacitance is the limiting factor.
1511422-7
Page 17
Model 5895XL Intelligent Power Module Installation and Operation Manual
These cases are marked in the chart with an asterisk (*). Maximum length can never
be more than 6,000 feet, regardless of gauge used. (The formula used to generate
this chart is shown in the note below).
Table 2-5: Wire Distances Per Wire Gauge
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.1001852 ft.4688 ft.* 6000 ft.* 6000 ft.
0.200926 ft.2344 ft.3731 ft.5906 ft.
0.300617 ft.1563 ft.2488 ft.3937 ft.
0.400463 ft.1172 ft.1866 ft.2953 ft.
0.500370 ft.938 ft.1493 ft.2362 ft.
0.600309 ft.781 ft.1244 ft.1969 ft.
0.700265 ft.670 ft.1066 ft.1687 ft.
0.800231 ft.586 ft.933 ft.1476 ft.
0.900206 ft.521 ft.829 ft.1312 ft.
1.000 (Max)185 ft.469 ft.746 ft.1181 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
* 500
Table 2-6: Typical Wire Resistance Per 1000 ft.
Wire GaugeOhms per 1000 feet (Rpu)
2216.2
186.4
164.02
142.54
2-8151142
Page 18
Before You Begin Installing
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules:
2 - Module 5860 Fire Annunciator
1 - 5895XL Intelligent Power Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps
5895XL Current Draw = 1 x .010 amps= .010 amps
5865 Current Draw= 1 x .200 amps= .200 amps
5824 Current Draw= 1 x .040 amps= .040 amps
Total Worst Case Current Draw= .450 amps
Using this value, and referring to the Wiring Distance table, it can be found that the
available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
1511422-9
Page 19
Model 5895XL Intelligent Power Module Installation and Operation Manual
5895XL Board
2.7.3Wire Routing
You must follow power-limited wiring techniques, which includes maintaining
one-quarter inch spacing between power-limited and nonpower-limited circuits and
separating high and low voltage circuits.
Figure 2-2 Wire Routing Example
2-10151142
Page 20
Section 3
To 120 VAC
Power Source
Green
White
Black
Hardware Installation
5895XL installation involves the following steps:
•AC power (Section 3.1) and backup battery connection (Section 3.2).
•Physical connection to the IntelliKnight 5820XL FA CP or to the controlling 5895XL
(see Section 3.3).
•Setting an ID for the 5895XL (Section 3.3.1).
•Physical connection of SBUS modules t hat will be powered by this 5895XL
(Section 3.4).
•Physical connection of any outputs (conventional relays, notification appliances,
auxiliary power modules, and so on) that will be powered by this 5895XL. See
Section 3.5.1 for notification appliance wiring information. Refer to the IntelliKnight
5820XL Installation Manual (P/N 151209), for software configuration information
and other information about installing outputs.
3.1AC Power
At installation, connect the AC terminals to 120 VAC source as shown in Figure 3-1. It
may be necessary for a professional electrician to make this connection.
The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.7 A.
Figure 3-1 AC Power Connection
1511423-1
Page 21
Model 5895XL Intelligent Power Module Installation and Operation Manual
Red
To Panel
Black
UL Listed 12V Battery
UL Listed 12V Battery
Battery Jumper
(P/N 140694)
Shipped With 5895XL
Replace batteries every 5 years.
Gell Cell
Gell Cell
3.2Battery Connection
The 5895XL battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same
AH rating. Determine the correct AH rating as per your current load calculation (see
Section Table 2-4).
Note: When your backup batteries requirements use backup batteries that are to large to fit into the
5895XL cabinet. The AB-33 cabinet holds batteries up to the 33 AH size. (Refer to Installation
Manual P/N 151209 for AB-33 installation instructions.
* 33AH max battery size for FM (Factory Mutual) installations
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to
increase the AH rating.
3-2151142
Figure 3-2 Battery Connection
Page 22
Hardware Installation
(FACP SBUS)
5895XL Terminals 30-33 are used only for
connection 5895XL to the FACP or to the
controlling 5895XL. Use 5895XL Terminals 16-19
to connect other SBUS modules (5815XL, 5860,
5824) and to daisy-chain 5895XL’s
5895XL Board
(5895XL-1)
5895XL Board
(5895XL-2)
To next 5895XL
and other SBUS
modules.
3.3Connecting the 5895XL to the FACP
1. Connect the 5895XL to the appropriate SBUS. The 5895XL can be connected
directly to the IntelliKnight 5820XL FACP or can be daisy-chained to another
5895XL. Figure 3-3 and Figure 3-4 show both connections.
2. Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2-1 shows
the location of the DIP switches on the 5895XL board.
3. Configure the 5895XL module by adding it to the system (through JumpStart or
manually). You can also assign a name to the module. These procedures are
described in the IntelliKnight 5820XL Installation Manuals (P/N 151209).
Figure 3-3 Class B 5895XL Connection to FACP
1511423-3
Page 23
Model 5895XL Intelligent Power Module Installation and Operation Manual
See Figure 3-6 for SBUS Module Connections
See Figure 3-6 for
SBUS Module
Connections
Figure 3-4 Class A 5895XL Connection to FACP
3-4151142
Page 24
Hardware Installation
3.3.1Setting the Device ID
board to set the module ID#. Figure 2-1 shows the location of the DIP switch on the
board.
1511423-5
Figure 3-5 Possible Module Addresses
Page 25
Model 5895XL Intelligent Power Module Installation and Operation Manual
3.4Connecting SBUS Modules to the 5895XL
1. Connect SBUS modules to the 5895XL as shown in Figure 3-6 or Figure 3-7.
2. All SBUS modules must have an ID. Use the DIP switches on the module board to
assign an ID number (1-31) to the module. This number identifies the module to
the 5895XL and must be unique.
3. Software configuration steps vary for each SBUS module. For more information,
refer to the Installation Manual (P/N 151209) in the section that discusses the type
of module you are installing.
Figure 3-6 SBUS Class A Connection to 5895XL
3-6151142
Page 26
Hardware Installation
Figure 3-7 SBUS Class B Wiring to 5895XL
3.5Flexputs
The six Flexput™ circuits are an innovative and versatile feature of the 5895XL panel.
They can be used as: Class A or B notification circuits, Class A or B initiation circuits
(either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door
holder).
This section of the manual explains how to install conventional notification appliances
and initiating devices to be used with the 5895XL.
™
I/O Circuits
3.5.1Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification
appliances for Class A (Style Z) and Class B (Style Y) configurations.
3.5.2Releasing Operations
Approved releasing solenoids are list in Table 3-1. Do not mix cross alarming zones
with smoke verification zones. There must be at least two automatic detection
devices in each protected space. Spacing must be reduced to 0.7 times the linear
1511423-7
Page 27
Model 5895XL Intelligent Power Module Installation and Operation Manual
Alarm
Polarity
UL Listed EOL
Model 7628
4.7 k
Supervised
Power Limited
Notification Wiring
Regulated
spacing in accordance with NFPA 72.
Table 3-1: Approved Releasing Solenoids
ManufacturerPart NumberRatingCurrentFreq
AscoT8210A10724 VDC3A max0 Hz
8210G20724 VDC3A max0 Hz
3.5.2.1Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A.
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 3-8.
2. Configure the circuit through programming.
Figure 3-8 Class B Notification Appliance Circuit Wiring
3-8151142
Page 28
Hardware Installation
Regulated
3.5.2.2Class A Notification Wiring
Y ou must use an appliance from the list of comp atible appliances in the Appendix A at
the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 3-9.
2. Configure the circuit for Class A in programming (see Section 7.4 of the
Installation Manual P/N 151209).
Figure 3-9 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-9 uses both I/O circuit 5 and 6, so in programming it
would be referred to as point 5.
1511423-9
Page 29
Model 5895XL Intelligent Power Module Installation and Operation Manual
UL Listed EOL
Model 7628
4.7 k
3.5.3Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for
Class A (Style D) or Class B (Style B) configurations.
3.5.3.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull
stations, directly to the I/O circuits of the 5895XL panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 3-10.
2. Configure the circuit through programming (see Section 7.4 of the Installation Manual P/N 151209).
Figure 3-10 Class B Input Switches
3.5.3.2Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull
stations, directly to the I/O circuits of the 5895XL panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 3-11.
3-10151142
Page 30
Hardware Installation
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.
2. Configure the circuit through programming (see Section 7.4 of the Installation
Manual
151209).
Figure 3-11 Class A initiating Switches
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-11 uses both I/O circuit 5 and 6, so in programming
it would be referred to as point 5.
3.5.4Installing 2-Wire Smoke Detectors
Any compatible U.L. listed two-wire smoke detector can be used with the 5895XL
panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure
3-13 illustrate how to connect a UL listed 2-wire detector to the control panel.
1511423-11
Page 31
Model 5895XL Intelligent Power Module Installation and Operation Manual
Note:
I/O circuit 5
used as an example.
Any I/O circuit
could be used.
UL Listed EOL
Model 7628
4.7 k
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3-12.
Figure 3-12 Two-Wire Class B Smoke Detector
2-Wire Class A Smoke Detector Installation
To install a Class A two-wire smoke detector, wire as shown in Figure 3-13.
Figure 3-13 Two-Wire Class A Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-13 uses both I/O circuit 5 and 6, so in programming
it would be referred to as point 5.
3-12151142
Page 32
Hardware Installation
Air Products
PAM-2
Model 160150
Supervision
Module
UL Listed
EOL Resistor
Model 7628
ESL 449CT
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.
3.5.5Installing 4-Wire Smoke Detectors
Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL
panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure
3-13 illustrate how to connect a UL listed four-wire detector to the control panel.
Installing a Class B 4-Wire Smoke Detector
Figure 3-14 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control
panel at once.
2. Each Class B loop input is paired with a unique power source as shown in Figure
3-14.
3. Each loop gets smoke power from the even numbered I/O circuit and the contact
input is connected to the odd numbered I/O circuit.
Figure 3-14 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-14 uses both I/O circuit 5 and 6, so in programming
it would be referred to as point 5.
1511423-13
Page 33
Model 5895XL Intelligent Power Module Installation and Operation Manual
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Installing 4-Wire Class A Smoke Detectors
Figure 3-15 illustrates how to install 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loops:
1. Up to two Class A 4-wire loops can be connected to the control panel at once.
2. Smoke power is supplied to each Class A loop as shown in Figure 3-15.
Figure 3-15 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-15 uses I/O circuits 1, 2, 3 together and 4, 5, 6
together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred
to as point 4.
3.5.6Auxiliary Power Configuration
Flexput circuits 1-6 on the control panel can be used as auxiliary power circuits. The
three types of auxiliary power available are:
•Door Holder (see Section 3.5.6.1 for description)
•Constant (see Section 3.5.6.2 for description)
•Resettable (see Section 3.5.6.3 for description)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total
current for all Flexput circuits must not exceed 5A).
To configure a Flexput circuit as auxiliary power:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 3-16 for
location or Flexput circuits.
3-14151142
Page 34
Hardware Installation
2. Configure the auxiliary power output through programming fo r Door Holder,
Constant or Resettable power.
Figure 3-16 Flexput Circuits Used as Auxiliary Power
3.5.6.1Door Holder Power
Door holder is intended for fire door applications. When there are no alarms in the
system and the panel has AC power , door holder circuits have 24-volt power present
at their terminals. Any alarm will cause power to discontinue. Power will be re-applied
when the system is reset. If AC power is off for more than 15 seconds the auxiliary
door holder power will be discontinued to conserve the battery backup power. When
AC power is restored, power is immediately restored to the door holder circuits.
3.5.6.2Constant Power
Use constant power for applications that require a constant auxiliary power source.
Power is always present at Constant circuits.
3.5.6.3Resettable Power
Resettable power is typically used to power beam detectors, flame detectors, and
conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt
power is always present at the terminals unless a system reset occurs. If a system
reset occurs, power is removed from the terminals for 30 seconds, then re-applied.
3.6Conventional Relay Installation
5895XL relay circuits are installed in exactly the same way as 5820XL main panel
relay circuits. For ease of installation, the 5895XL output terminals use the same
numbering scheme as 5820XL terminals. Refer to the Installation Manual P/N
151209 for information on installing conventional relays.
1511423-15
Page 35
Appendix A
Compatible Devices
A.1Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on
each loop. All supervised notification appliances used with the 5895XL must be polarized.
Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you
have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
A.1 below lists notification appliances compatible with the fire alarm control panel. Appliances which
can be synchronized indicate the type of sync available in the columns marked Audio and/or Visual
Model 5895XL Intelligent Power Module Installation and Operation Manual
Table A-1: Compatible Notification Appliances
ManufacturerModelAudioVisualType
446xVibrating Bell
476xVibrating Bell
477xSingle Stroke Bell
2700 -M. -R, -T, -Y, -ZxStrobe
2701 SeriesxStrobe
2705 SeriesxStrobe
2820xxSnyc Temporal Horn/Strobe
2821xxSnyc Temporal Horn/Strobe
2824xxHorn Strobe
5333xMulti-Tone Horn)
5336xxMulti-Tone Horn/Strobe
Faraday
5337xxMulti-Tone Horn/Strobe
5338xxMulti-Tone Horn/Strobe
5343xxSingle Tone Horn/Strobe
5346xxElectronic Horn with Strobe
5347xxElectronic Horn with Strobe
5348xxSingle Tone Horn/Strobe
5373xx8- Tone Horn/Strobe
6321xxSync Mini Horn/Strobe
6322xxMini Horn/Sync Strobe
6380x8-Tone Electronic Signal/Strobe
5376xx8- Tone Horn/Strobe
5377xx8- Tone Horn/Strobe
A-2151142
Page 37
Table A-1: Compatible Notification Appliances
ManufacturerModelAudioVisualType
5378xx8- Tone Horn/Strobe
5383xx8-Tone Horn/Strobe with Sync Strobe
5386xx8-Tone Horn/Strobe with Sync Strobe
5387x8-Tone Horn/Strobe with Sync Strobe
5388x8-Tone Horn/Strobe with Sync Strobe
5508xSingle Gang Sync Strobe
5509xStrobe
5510xStrobe
5511xStrobe
5512xStrobe
5516xStrobe
5517xStrobe
5518xStrobe
5519xStrobe
5521x4” Square Sync Strobe
5522x4” Square Sync Strobe
6120xHorn
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Multi Candella Horn/Strobe Ceiling Mount
Multi Candella Horn/Strobe Ceiling Mount
Multi Candella Strobe Ceiling Mount
Multi Candella Strobe Ceiling Mount
Multi Candella Horn/Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Multi Candella Strobe
Multi Candella Strobe
Horn
Strobe
Strobe
Strobe
Strobe
Strobe
Weatherproof Horn/Strobe
Weatherproof Strobe
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe
2-Wire Horn/Strobe
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
Strobe
Strobe
Strobe
Strobe
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe
Strobe
Strobe
Strobe
Strobe High Candela
Strobe High Candela
Strobe High Candela
Compatible Devices
151142A-7
Page 42
Model 5895XL Intelligent Power Module Installation and Operation Manual
ZRS-MCWH
ZRS-24MCC
ZRS-24MCCH
MB-G6-24 xMotor Bell
MB-G10-24 xMotor Bell
MB-G6-12 xMotor Bell
MB-G10-12 xMotor Bell
MIZ-24-R xMini-Horn
MT-12/24-R x
MT4-12/2zx
ZRS-MCW
MTWPR-24MCCHx
NH-12/24RxHorn
HSR
HSW
STR
STW
HNR
HNW
x
x
x
x
x
x
x
x
x
x
x
x
x
Compatible Devices
A.2Two-Wire Smoke Detectors
Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is organized by
manufacturer. The columns show the number of detectors per loop that can be used.
5895XL
Identifier
Operating Voltage Range
The maximum number of smoke detectors per zone is determined by both the current draw and the
impedance of the smoke detector . If too many smoke detectors are used on any zone, false alarms
could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in
that configuration.
Control unit Smoke Reset Time must be pr ogrammed for a number greater than or equal to the
maximum reset time of the smoke detector.
Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The table is
24H
18.5–27.4 VDC
151142A-11
Page 46
Model 5895XL Intelligent Power Module Installation and Operation Manual
organized by manufacturer. The columns show the number of detectors per loop that can be used.
SIH-24FHS-224D or SHB-224 Base
SLK-24FHS-224D Base
SLK-23FHHS-224D Base
1851B
2851/2851BTH
DH200ADCD
A.3.1Door Holder Device
The following UL listed door holder can be used with the 5895XL: ESL DHS-1224
151142A-15
Page 50
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•All new fire products manufactured by Honeywell have a limited warranty period of 36 months from the
date of manufacture against defects in materials and workmanship. See limited warranty statement for
details.
•This limited warranty does not apply to tho se produ cts that are damaged due to misuse, abuse, negligen ce,
exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Repair and RMA Procedure
•All products that are returned by Honeywell for credit or repair require a RMA (Return Authorization)
number. Call Customer Service at 800-328-0103 or 203-484-7161 between 8:00 A.M. and 5:00 P.M. EST,
Monday through Friday to obtain a return authorization number.
• Honeywell Technical Support is available at 800-446-6444 between 8:00 A.M. and 5:00 P .M. CST, Monday
through Friday.
•All returns for credit are subject to inspection and testing at the factory before actual determination is made
to allow credit.
•RMA number must be prominently displayed on the outside of the shipping box. See return address example
under Advanced Replacement Policy.
•Included with each return should be: a packing slip that has the RMA number, a content list, and a detailed
description of the problem.
•All products returned by Honeywell must be sent freight pre-paid. After product is processed by Honeywell
will pay for shipping product back to customer via UPS ground.
•Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an
additional $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries to Honeywell has the authority to determine if a product is repairable. Products that are deemed
un-repairable will be returned to the customer.
•Product that is returned that has a board date code more than 36 months from date of manufacture will be
repaired and the customer will be assessed the standard Honeywell repair charge for that model.
Advanced Replacement Policy
• Honeywell offers an option of advance replacement for fire product printed circuit boards that fail during
the first 6 months of the warranty period. These items must be returned with transportation charges prepaid
and must be accompanied by a return authorization.
•For advance replacement of a defective board, contact your local Honeywell distributor or call Honeywell
at 800-328-0103 to obtain a RMA (Return Authorization) number and request advanced replacement.
•A new or refurbished board will be shipped to the customer. The customer will initially be billed for the
replacement board but a credit will be issued after the repairable board is received at Honeywell. All
returned products must comply with the guidelines described under “General Terms and Conditions” and
“Repair and RMA Procedure”.
•The defective board must be returned within 30 days of shipment of replacement board for customer to
receive credit. No credit will be issued if the returned board was damaged due to misuse or abuse.
Page 51
•Repairs and returns should be sent to:
Honeywell Fire Systems
Attn: Repair Department / RA Number_______________________
12 Clintonville Road
Northford, CT 06472 USA
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products
manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free,
under normal use and service, from defects in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by
Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not
manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to extent possible, any
warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, service
repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if
there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER
WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE
PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER
INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS
FOR ANY P AR TICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all
previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal,
of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any
loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its
authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have
been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock
and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY
IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
Page 52
Page 53
Page 54
12 Clintonville Road
Northford, CT 06472-1610
Fax: 203-484-7118
www.silentknight.com
Silent Knight
203-484-7161
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.