Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
ii151142
Section 1
Overview
1.15895XL Description
The Model 5895XL Intelligent Power Module provides additional power and circuits to
the IntelliKnight 5820XL F A CPs. The 5895XL can power all IntelliKnight compatible
modules, including SLC devices (via a Model 5815XL SLC Expander), remote
annunciators (Model 5860); notification appliances, auxiliary power modules, and all
other compatible modules.
Note: The 5808 does not use 5815XL SLC expanders.
The 5895XL has six Flexputs™ and two programmable relays. Outputs are rated 3.0
A (6.0 A total for each 5895XL). Relays are Form C rated at 2.5 A @ 24 VDC.
Outputs and relays are fully programmable.
The 5895XL is optically isolated, providing ground loop isolation and transient
protection. It functions as an SBUS repeater which conditions the RS-485 signal and
allows the module to drive up to 6,000 feet of additional SBUS wiring.
The 5895XL is housed in a metal cabinet that is identical in size to the IntelliKnight
5820XL FACP cabinet. This cabinet is large enough to house two 17 AH batteries.
Like the 5820XL cabinets, the 5895XL cabinet provides mounting studs for two Model
5815XL SLC Expander modules.
The 5895XL communicates to the main IntelliKnight FACP via the SBUS. Each
5895XL provides an additional 6,000 feet of SBUS wiring length to the main panel. As
the drawings on the next pages illustrate, this allows you to distribute modules, SLC
devices, and outputs throughout an extremely large facility.
As well as expanding the wiring length capabilities of IntelliKnight, the 5895XL also
expands IntelliKnight’s power capabilities by an additional 6.0 A of current.
1511421-1
Model 5895XL Intelligent Power Module Installation and Operation Manual
1.1.1Maximum Number of SBUS Modules
The chart below shows the maximum number of compatible modules that can be
used in an IntelliKnight installation. Modules can be distributed among the main panel
SBUS and each additional 5895XL SBUS in virtually any combination.
Module or Device Maximum Number
5895XL Intelligent Power Module8 per IntelliKnight installation
5860 Remote Annunciator8 per IntelliKnight installation
5815XL SLC Expander2 per IntelliKnight installation
5824 Serial/Parallel Modules8 per IntelliKnight installation
Outputs 6 per 5820XL / 5895XL
Conventional Relays 2 per 5820XL / 5895XL
1-2151142
Overview
Figure 1-1 Example 5895XL Installation Overview
1511421-3
Model 5895XL Intelligent Power Module Installation and Operation Manual
Figure 1-2 Example 5895XL Installation Overview (Details Added)
1-4151142
Overview
1.2Agency Requirements
The 5895XL has the same requirements as the main control panel. These
requirements are listed in the IntelliKnight 5820XL Installation Manual (P/N 151209).
1.3About This Manual
This manual covers installation of 5895XL hardware. Software configuration
information is contained in the IntelliKnight 5820XL Installation Manual (P/N 151209).
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact
Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103 (or 203-484-7161).
1511421-5
Section 2
Before You Begin Installing
2.1What’s in the Box?
The Model 5895XL ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Ten 4.7K ohm end-of-line resistors
Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used.
•A battery cable for batteries wired in series
2.2Environmental Specifications
It is important to protect the 5895XL control panel from water. To prevent water
damage, the following precautions should be FOLLOWED when installing the units:
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the 5895XL, the unit should be mounted where it
will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
2.3Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet
through the conduits. Conduits that are installed to enter the top of the cabinet are
most likely to cause water problems. Installers should take reasonable precautions to
prevent water from entering the cabinet. Water damage is not covered under
warranty.
1511422-1
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.45895XL Board and Terminal Strip Description
Figure 2-1 shows the 5895XL circuit board including location of terminals, the DIP
switch for setting module ID, and the LED.
2-2151142
Figure 2-1 The 5895XL Board Layout
Before You Begin Installing
Table 2-1: Terminal Strip Description and Electrical Ratings
This section is for helping you determine the current draw and standby battery needs
for your installation.
2.6.1Worksheet Requirements
The following steps must be taken when determining 5895XL current draw and
standby battery requirements.
Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2)
1. For the 5895XL, the worst case current draw is listed for the panel, addressable
devices, and SLC expanders. Fill in the number of addressable devices and
expanders that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in Table 2-4 at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual,
refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the
panel itself, does not exceed 6.0 A. This is the maximum alarm current allowable.
6. Complete the remaining instructions in Table 2-4 for determining battery size
requirements.
2.6.1.1Maximum Battery Standby Load
Table 2-3 shows the maximum battery standby load for the 5895XL based on 24 and
60 hours of standby. The standby load calculations of line G in the Current Draw
Calculation Worksheet (Table 2-4) must be less than the number shown in Table 2-3
for the battery size used and standby hours required.
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
7 AH270 mA105 mA
12 AH475 mA190 mA
17 AH685 mA270 mA
33 AH1370 mA540 mA
* Required for NFP A 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box)
and Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Max. Load for 24 hrs. Standby ,
5 mins. Alarm
*Max. Load for 60 hrs. Standby , 5
mins. Alarm
Note:33AH max battery size for FM (Factory Mutual) installations
1511422-5
Model 5895XL Intelligent Power Module Installation and Operation Manual
2.6.2Current Draw Worksheet
For *each 5895XL in the installation, use this worksheet to determine current
requirements during alarm/battery standby operation. (Copy this page if additional
space is required.)
Table 2-4: Current Draw Calculations
Device
For each device use this formula: This columnX This column= Current per number of
devices.
5895XL Intelligent Power Module
(Current draw from battery)
Additional 5895XL
(Daisy-chained to this module)
Addressable Devices(381 max.)
5815XL SLC Expander(2 max.)
5860 Remote Fire Alarm Annunciator(8 max.)
5824 Serial / Parallel Module(2 max.)
5865-4 LED Annunciator
(with reset and silence switches)
5865-3 LED Annunciator
5880 Generic LED Driver Module
ATotal System Current
**Auxiliary DevicesRefer to devices manual for current rating.
BAuxiliary Devices Current
CNotification Appliances CurrentmA
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5 ) :H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
IMultiply lines E and H.Total alarm AH
J***Add lines G and I. Total ampere hours requiredAH
Number of
Devices
1*
(7 max.)
(8 max.)
Current per Device
Standby:40 mA
Alarm:160 mA
Standby:10 mA
Alarm:10 mA
Standby:0.55 mA
Alarm:0.55 mA
Standby:55 mAmA
Alarm:55 mAmA
Standby:20 mAmA
Alarm:25 mAmA
Standby:45 mAmA
Alarm:45 mAmA
Standby:35 mAmA
Alarm:145 mAmA
Standby:35 mAmA
Alarm:145 mAmA
Standby:35 mAmA
Alarm:200 mAmA
Alarm/Standby: mA mAmA
Alarm/Standby:mAmAmA
Alarm/Standby:mAmAmA
Alarm/Standby:mAmAmA
Alarm:mA
Alarm:mAmA
Alarm:mA
Alarm:mA
Standby
Current
40
mA
Alarm Current
160
mA
mA
mA
mA
AH
2-6151142
Before You Begin Installing
*Use a separate worksheet for each 5895XL.
**If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because
***Use next size battery with capacity greater than required.
power is removed during that time. However, during normal operation, door holders draw current and must be
included in the 6.0 A total current that can be drawn from the panel.
2.7Wiring Specifications
2.7.1Length Limitations
This section contains information on calculating SBUS wire distances and the types
of wiring configurations (Class A and B).
2.7.2Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the
maximum wiring distance that can be used with SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the
panel, it is necessary to calculate the total worst case current draw for all modules on
a single 4-conductor bus. The total worst case current draw is calculated by adding
the individual worst case currents for each module. The individual worst case values
are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of
accessory modules are required, and the worst case current draw will exceed the 1 amp limit,
then the current draw must be distributed using 5895XL Powe r Expanders. Each 5895XL Power
Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring
distance calculations are done separately for each 5895XL, and separately for the panel itself.
Model NumberWorst Case Current Draw
5860 Fire Annunciator.100 amps
5824 Parallel/Serial Interface.040 amps
5880 LED IO Expander.250 amps
5865 LED Fire Annunciator.200 amps
5895XL Intelligent Power Supply.010 amps
5496 Intelligent Power Module.010 amps
After calculating the total worst case current draw, Table 2-5 specifies the maximum
distance the modules can be located from the panel on a single wire run. The table
insures 6.0 volts of line drop maximum. In general, the wire length is limited by
resistance, but for heavier wire gauges, capacitance is the limiting factor.
1511422-7
Model 5895XL Intelligent Power Module Installation and Operation Manual
These cases are marked in the chart with an asterisk (*). Maximum length can never
be more than 6,000 feet, regardless of gauge used. (The formula used to generate
this chart is shown in the note below).
Table 2-5: Wire Distances Per Wire Gauge
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.1001852 ft.4688 ft.* 6000 ft.* 6000 ft.
0.200926 ft.2344 ft.3731 ft.5906 ft.
0.300617 ft.1563 ft.2488 ft.3937 ft.
0.400463 ft.1172 ft.1866 ft.2953 ft.
0.500370 ft.938 ft.1493 ft.2362 ft.
0.600309 ft.781 ft.1244 ft.1969 ft.
0.700265 ft.670 ft.1066 ft.1687 ft.
0.800231 ft.586 ft.933 ft.1476 ft.
0.900206 ft.521 ft.829 ft.1312 ft.
1.000 (Max)185 ft.469 ft.746 ft.1181 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
* 500
Table 2-6: Typical Wire Resistance Per 1000 ft.
Wire GaugeOhms per 1000 feet (Rpu)
2216.2
186.4
164.02
142.54
2-8151142
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.