Manufacturer Warranties and Limitation of Liability
ii151253
Introduction
Section 1
Introduction
The 5499 is a notification appliance circuit and auxiliary power expander that provides up to 9 amps of filtered,
24 volt power for powering notification appliances and auxiliary devices. The 5499 provides its own AC power
connection, battery charging circuit, and battery connections. Used with security and fire alarm control panels,
the 5499 enables you to connect and distribute power to many more devices than your panel may normally allow.
•Input Configurations
The 5499 has two optically isolated signaling inputs that provide the signal connection from the main
control panel to the 5499 (see Section 3.2 for more details).
•Output Configurations
The 5499 has four power-limited notification appliance circuits that can be configured in various
combinations of Class A and Class B circuits (see Section 3.3 for details).
•Auxiliary Power Configurations
The 5499 has a dedicated, power-limited, auxiliary output that can be configured in two different ways. The
auxiliary output can either be non-resettable (always on), or configured to switch off during the AC power
failure to conserve the battery standby power. When the auxiliary power is configured to switch off, there is
a 30 second delay before the auxiliary power is turned off after the AC power fails (see Section 4.8.4 for
details).
•Form C Trouble Relay
The 5499 includes a general trouble relay that will de-energize for any trouble situation. (see Section 4.4.1
for details).
•Earth Fault Detection
The 5499 monitors for earth faults to the system power or system ground. When detected, the system
DE-energizes the trouble relay and the input supervision relays (see Section 5.2 for details).
•ANSI Temporal Code
The 5499 provides two configuration options that will drive outputs with the ANSI temporal code if the
inputs are on constantly (see Section 4.8.1 for details).
•Supports Synchronized appliances
The 5499 provides configuration options that will eliminate the need for synchronized modules when using
AMSECO, Faraday, Gentex, System Sensor, or Wheelock synchronization appliances.
Section 2
UL Requirements
When installed in accordance with NFPA 70 and NFPA 72 standards, the 5499 can be connected to UL Listed
devices.
The 5499 is also listed to meet UL 864, UL 2572 and power limiting requirements.
The 5499 is compatible with any UL listed control unit utilizing reverse polarity supervised notification
appliance circuits, using 24 VDC regulated outputs.
1-1
151253
Section 3
System Overview
CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut down
(power limit). The circuit will automatically reset once you remove the overload condition.
3.1Terminal Descriptions and Electrical Ratings
Terminal #DescriptionRatings
TB1
1AC (black–“hot”)120 VAC 60 Hz, 3A
2Earth Ground
3AC (white–“neutral”)
TB2
1Auxiliary Power (-)27.4 VDC 3.0 amps
2Auxiliary Power (+)
3Notification 4 Output (-)27.4 VDC 3.0 amps
4Notification 4 Output (+)Although each output
5Notification 3 Output (-)27.4 VDC 3.0 ampsis rated for 3 amps, the
6Notification 3 Output (+)total current draw from
7Notification 2 Output (-)27.4 VDC 3.0 ampsthe 4 outputs and the
Terminals 14 through 19 are polarized signal input terminals. They provide the signaling connection from the
3-2
5499 Distributed Power Module Installation Manual
main panel to the 5499. See Figure 4-2 for more details.
The main panel supervises its notification appliance circuits used for communicating with the 5499 the same way
it supervises ordinary notification appliance circuits. The signal inputs on the 5499 monitor the polarity of the
voltage coming from the main panel’s notification appliance circuits to determine when to operate the
notification appliance circuits on the 5499. The 5499 emulates the trouble behavior of a normal notification
appliance circuit by interrupting the EOL supervision current for internal or output trouble conditions on the
5499.
Note that the 5499 will accurately sense the polarity of the main panel’s notification appliance circuits to drive
the outputs whether or not the supervision connection is intact. The following situations will disconnect the EOL
supervision at the signal inputs and indicate a trouble condition:
•Low AC power
•Low Battery condition
•Earth ground fault to the system power or system ground
•Auxiliary output power-limited condition
•EOL supervision trouble or power-limited condition at an output
Trouble conditions will not necessarily occur for both inputs when the trouble is specific to a particular output.
Only the signal input controlling the output circuit that is in trouble will indicate a trouble condition. Below are
examples where both inputs do NOT indicate trouble for a trouble occurring at only one output circuit.
Example 1:If input 1 controls all four outputs, a fault on any output will cause input 1 to
indicate trouble. The fault does not affect input 2.
Example 2:If input 1 controls outputs 1 and 2, and input 2 controls outputs 3 and 4, a fault
condition on output 3 or 4 will cause input 2 to indicate trouble. The fault does not
affect input 1.
Note:
Once the inputs are driven with forward polarity to activate the outputs, the main control panel will not be able to sense
trouble conditions through its notification appliance circuit connected to the 5499 input circuits. Use the 5499 trouble
relay when it is necessary to monitor trouble conditions and active alarm conditions at the same time.
Section 6 explains the significance of each trouble condition in more detail.
3.3Notification Appliance Circuit Terminals
Terminals 3 through 10 are the notification appliance circuit output terminals. Each of the four circuits are rated
at 3 amps, although you can only draw a total of 9 amps from the 5499. The 5499 outputs are short-circuit
protected (power limited) according to UL 864 standards. Overcurrent indicators are yellow LEDs. The output
voltage can vary depending on the load and input voltage.
The four power-limited NAC outputs can be configured as follows:
•Four Class B circuits•Faraday synchronized outputs
•Two Class A circuits•Gentex synchronized outputs
•One Class A and two Class B circuits•System Sensor synchronized outputs
One or both 5499 signal inputs control the NAC outputs, depending on the specific configuration setup. Possible
configurations for the 5499 are:
For Option:These Inputs:Control These Outputs:As:
1Input 1All outputsClass B circuits
3-3
151253
For Option:These Inputs:Control These Outputs:As:
2Input 1 orOutputs 1, 2, 3, and 4Class B ANSI temporal-
Input 2coded circuits
3Input 1Outputs 1 and 2Class B circuits
Input 2Outputs 3 and 4Class B circuits
4Input 1Output 1Class B circuits
Input 2Outputs 2, 3, and 4Class B circuits
5Input 1Outputs 1-2 and 3-4Class A circuit pairs
6Input 1Outputs 1 and 2Class B ANSI temporal-coded circuits
Input 2Outputs 3 and 4Class B circuits
7Input 1Outputs 1-2Class A circuit pair
Input 2Outputs 3-4Class A circuit pair
8Input 1Outputs 1-2Class A circuit pair
Input 2Outputs 3 and 4Class B circuits
9Input 1 (Strobe Control) All outputsClass A or Class B
Input 2 (Audio Control)Faraday Sync. Output
10Input 1 (Strobe Control) All outputsClass A or Class B
Input 2 (Audio Control)Gentex Sync. Output
11Input 1 (Strobe Control) All outputsClass A or Class B
Input 2 (Audio Control)System Sensor Sync. Output
12Input 1 (Strobe Control) All outputsClass A or Class B
Input 2 (Audio Control)Wheelock Sync. Output
13Input 1 (Strobe Control) All outputsClass A or Class B
Input 2 (Audio Control)Amseco Sync. Output
You can select which input controls which output, and which inputs are Class A and Class B using the 7-position
DIP switch on the printed circuit board. Section 4.8 for DIP switch settings.
3-4
5499 Distributed Power Module Installation Manual
Section 4
Installation
Before installing the 5499, the AC input must first be wired into the building’s main electrical power through the
TB1 terminals (see Figure 4-2). Shut off the electrical power to the 5499, and then complete the general
installation of the 5499 using the information in this section.
4.1Mounting
Mount the 5499 in locations that meet the following temperature and humidity requirements. Do not expose the
panel to conditions outside these ranges. For use in indoor, dry environments.
Temperature
Humidity
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete,
especially when moisture is expected, first attach a piece of 3/4-inch plywood to the concrete surface. Attach the
5499 to the plywood.
o
C-49o C (32o F-120o F)
0
o
10%-93% at 30
C (86o F) noncondensing
4.1.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.2Wire Routing
To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from
high current output and power-limited wiring. Induced noise can interfere with telephone communication or even
cause false alarms. Avoid pulling a single multiconductor cable for the entire system. Instead, separate high
current input/output from low current. Separate power-limited from non-power-limited wiring.
Non-power-limited wiring must be enclosed in conduit.
Wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed
circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from
4-5
151253
Note: The use of this knock out will reduce the number and/or size
of batteries this cabinet can contain. Evaluation of space is
important before using.
the switching power supply circuit.
Figure 4-1 Sample Wire Routing
Ground fault and wire to wire short impedance to any terminal is 0
4.3Current Requirements (Standby and Alarm)
4.3.1Current Drawn From Host Panel
Table 4-1 shows the 5499 current draw requirements from the main control panel when the panel’s notification
appliance circuit is in alarm. The current draw from the main panel when it is supervising the 5499 is the same
current draw that would be present when the main panel supervises an ordinary notification appliance circuit.
Table 4-1: Alarm Current Drawn From Main Control Panel
Panel VoltageCurrent
Alarm Current (for typical voltages) drawn
from main panel’s notification appliance
circuits.
4.3.2Current Drawn from Battery
Batteries used with the 5499 must not exceed 35AH. (33AH max. for FM (Factory Mutual) Installations).
Batteries larger than 7 AH will not fit into the 5499 cabinet and must be housed in the RBB Remote Battery Box.
See Section 4.7 for battery installation.
12 VDC6.5 mA
24 VDCOne input circuit: 15 mA
Both input circuits: 30 mA
4-6
5499 Distributed Power Module Installation Manual
The following is the maximum current draw from the auxiliary power terminals for standby calculations. These
currents assume 24 or 60 hours of standby time, followed by 5 minutes of maximum alarm current.
•195 mA for 24 Hour Standby Current
•39 mA for 60 Hours of Auxiliary Standby Current
The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated capacity.
The total current of the 5499, plus all items powered from it, must not exceed 9 A when the panel is in alarm. Use
Table 4-2 to ensure that the current does not exceed 9 A and, that the desired amount of standby is possible for
the battery intended for use with the 5499.
4-7
151253
Table 4-2: Battery Calculation Worksheet
Device
For each device use this formula:This column X This column=Current per number of devices.
5499 Distributed Power Module
(Current draw from battery)
5499 Current75 mA205 mA
A
Auxiliary DevicesRefer to device manual for current ratings.
Auxiliary Device CurrentmAmA
B
Notification appliancesRefer to device manual for current ratings.
Notification Appliance Current 0 mAmA
C
Total current ratings of all devices in system (line A + line B + line C)mAmA
D
Total current ratings converted to amperes (line D x .001): AA
E
Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). 24 Hrs. for NBC,
F
section 3.2.7.8
Multiply lines E and F. Total standby AHAH
G
Alarm sounding period in hours. In accordance with NBC and ULC.
H
(For example, 5 minutes = .0833 hours.)H
Multiply lines E and H.Total alarm AHAH
I
Add lines G and I.Total standby and alarm AHAH
J
Multiply line J by 1.20.
K
(20% extra insurance to meet desired performance) Total ampere-hours requiredAH
Number of
Devices
1Standby:75 mA75 mA
Current per Device
Alarm:205 mA205 mA
Alarm/StandbymAmAmA
Alarm/StandbymAmAmA
Alarm/StandbymAmAmA
Alarm/StandbymAmAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Standby
Current
Alarm
Current
H
4-8
5499 Distributed Power Module Installation Manual
4.4Connecting the 5499 to a Control Panel
Figure 4-2 shows the general layout of the 5499 PC board. This section also provides specific wiring details for
accessories.
Figure 4-2 The Model 5499 PC Board Layout
Consult the installation manual for specific wiring information for the control panel being used.
4.4.1Common Trouble Relay
The 5499 has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a
normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any trouble
condition.
4-9
151253
Must be connected to
a power limited source
A typical application of the trouble relay is to connect the 5499 normally closed (N.C.) contacts in series with the
EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control panel when the
5499 opens its trouble contacts.
Note:
The N.C. contact is the contact that is closed when the 5499 has power and there are no trouble conditions.
Figure 4-3 Trouble Relay Connection Example
4.5Notification Appliance Wiring
Note: Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device you have chosen will work
with this feature.
Important!
For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2
must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles,
input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be
inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1
remains active. If input 1 is not active, then input 2 is ignored.
4.5.1Class A Supervised Wiring
Figure 4-4 shows how to wire for Class A input and output supervision. Use in/out wiring methods for proper
supervision. (Refer to Appendix A for notification appliances compatible with the 5499.)
Class A Output Notification Circuits
The configuration shown in Figure 4-4 shows two, 3 A devices wired as Class A. When using the outputs as
Class A circuits, loop the wiring back to the corresponding circuit pair. For Class A wiring, no external EOL is
necessary since it is built into the 5499 board.
Class A Supervised Input Circuits
The configuration shown in Figure 4-4 shows Class A supervised wiring from a fire alarm control panel to the
5499 board. Pay close attention to the polarities when wiring a panel to the 5499 and follow these requirements:
•When wiring to Terminal 18 on the 5499, you must use two separate wires. Do not loop a single wire or twist
4-10
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.