SILENT KNIGHT 4224 Installation Manual

Content
Section 1 Overview
1.1 SK-4224 Description ................................. ..... ...... ....................................................................................1-1
1.2 How to Contact Silent Knight ..................................................................................................................1-1
......................................................................................................................................................1-1
Section 2 Agency Requirements
2.1 FCC Warning ...........................................................................................................................................2-1
2.2 Underwriters Laboratories (UL) ..............................................................................................................2-1
2.2.1 Requirements for All Installations ....................................................................................................2-1
2.2.2 Requirements for Local Protected Fire Alarm Systems ...................................................................2-1
Section 3 Before You Begin Installing
3.1 What's in the Box? ...................................................................................................................................3-1
3.2 Optional Accessories ................................................................................................................................ 3-2
3.3 SK-4224 Board Layout ................. ...... ...... ...............................................................................................3-3
3.4 Electrical Specifications ...........................................................................................................................3-4
3.5 Environmental Specifications ..................................................................................................................3-4
3.6 Mounting the SK-4224 .............................................................................................................................3-5
3.7 Assembly ..................................................................................................................................................3-6
3.8 Wiring Specifications ...............................................................................................................................3-7
3.9 Calculating Current Draw and Standby Battery ......................................................................................3-8
3.9.1 Worksheet Requirements ......................................... .........................................................................3-8
Filling in the Current Draw Worksheet, Table 3-6 (Section 3.9.3) ............................................... 3-8
3.9.2 Maximum Battery Standby Load ......................................................................................................3-8
3.9.3 Current Draw Worksheet ..................................................................................................................3-9
...............................................................................................3-1
Section 4 Hardware Installation
4.1 AC Power ................................................................................................................................................. 4-1
4.2 Battery Connection ..................................................................................................................................4-2
4.3 Initiation Circuit Installation ....................................................................................................................4-3
4.3.1 Contact Wiring ..................................................................................................................................4-3
4.3.2 Two-Wire Smoke Detector Wiring ................................................................................................... 4-3
4.3.3 Class A Smoke Detector Installation ................................................................................................4-4
4.3.4 Four-Wire Smoke Detector ............................................................................................................... 4-5
4.3.5 Notification Circuit Installation ........................................................................................................ 4-6
4.3.6 Class A Notification Circuit Installation ..........................................................................................4-7
4.4 Alarm and Trouble Relays .......................................................................................................................4-7
4.5 Auxiliary Power Circuit ...........................................................................................................................4-7
151068 i
..................................................................................................................4-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.6 Door Release Wiring ................................................................................................................................4-8
4.7 Optional Accessories Installation .............................................................................................................4-9
4.7.1 Installing the Serial Driver Board (Model SK-2884) .......................................................................4-9
Wiring the SK-2884 to an Expansion Device .............................................................................4-10
4.7.2 SK-2865 LED Annunciator Installation .........................................................................................4-10
SK-2865 Electrical Specification ...................................................... ..... ...... ............................. ..4-10
Wiring the SK-2865 to the SK-2884 ...........................................................................................4-10
Setting the SK-2865’s address .................................................................................................... 4-12
Mounting the SK-2865 ................................................................................................................4-12
Section 5 Notification Expansion Mode
5.1 Class A Notification Expansion Wiring ...................................................................................................5-1
5.2 Class B Notification Expansion Wiring ...................................................................................................5-2
...........................................................................................5-1
Section 6 System Configuration
................................................................................................................6-1
Section 7 System Operation
7.1 Meaning of LEDs .....................................................................................................................................7-1
7.2 Operation Keys (Switches) ......................................................................................................................7-3
............................................................................................................................7-1
Appendix A Compatible Devices
A.1 Smoke Detectors ..................................................................................................................................... A -1
A.1.1 Enhanced Mode ............................................................................................................................ A-1
A.1.2 Two-Wire Smoke Detectors .........................................................................................................A-2
Four-Wire Smoke Detectors ......................................................................................................... A-3
A.2 Notification Appliances .......................................................................................................................... A-4
..................................................................................................................... A-1
ii 151068
Section 1 Overview
1.1 SK-4224 Description
The Model SK-4224 is a four zone, 24-volt fire control panel having the following features:
Zone inputs can be configured as: Four Class B zones Or Two Class A zones
2.5 amp power supply
Two notification circuits rated at 2.5 amp max.
Dedicated alarm and trouble relays
Auxiliary power output (.5 amp max.) for powering special applications, such as door holders.
Enhanced Verification Mode, a built-in feature that distinguishes two-wire smoke detec­tors from pull stations.
Housed in a 12.75"W x 15"H x 3.25"D metal cabinet
Cabinet supports two 7.0 AH backup batteries
1.2 How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-328-0103 (or 612-493-6455). To order parts, contact Silent Knight Sales at 800-446-6444 (or 612-493-6435).
151068 1-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
1-2 151068
Section 2 Agency Requirements
2.1 FCC Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the two following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
2.2 Underwriters Laboratories (UL)
The SK-4224 is UL listed as a control unit for use in NFPA 72 systems. If the SK-4224 and its accessories are to be used as part of a UL installation, carefully read the UL requirements in this section. For more information on NFPA 72 standards, refer to the NFPA National Fire Alarm Code, 1996 Edition.
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use UL listed smoke detectors and notification appliances compatible with the SK-4224 from those specified in the Appendix to this manual.
3. If you are using the smoke verification feature:
Do not use smoke detectors with built-in alarm verification.
Select "Enhanced Mode" if the installation includes pull stations or water flow
switches.
4. A full system checkout must be performed any time the panel is programmed.
5. UL installations using Class B wiring require the use of a Model 7628 EOL resistor assembly.
2.2.2 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
151068 2-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
2-2 151068
Section 3
g
Before You Begin Installin
3.1 What's in the Box?
The Model SK-4224 ships with the following hardware:
Table 3-1: Contents of Shipping Box
Containing
Main Part
Part Quantity/Item
1 Cabinet 122509
Panel Bag 1 Control Board 204224
1 Installation Manual 151068 2 #8 Screws 119152 2 #8 Nuts 119538
Hardware Bag
120 Vrms @ 60Hz 115061
1 Transformer
230 Vrms at 50Hz 115031
1 Viewing Bezel 122508
3 Self-tapping Scr e ws 119296 1 Earth Ground Wire 140668 1 Battery Wire Harness 130420 1 battery Jumper 140694
or a
Model
Number
6 End-of-line Resistors 111682
Note: See Section 3.7 for assembl y i nstructions.
151068 3-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
3.2 Optional Accessories
Table 3-2 is a list of optional accessories that can be used with the Model SK-4224 Fire Control Panel.
Table 3-2: Option Accessories for the SK-4224
Model
Number
SK-2884 Serial Driver Board Used to interface all SK-4224expansion device to the SK-
*SK-2880 Input/Output (I/O) Module Used to drive customized annunciators and interface devices. *SK-2865 LED Annunciator Remote LED annunciator with Silence and Reset keyswitch
*SK-2104 Diale r Used to communicate alarms, tr ouble and supervisories to
7628 UL listed End-of-line
(EOL) Resistor.
Name Description
4224 panel. Supports1 Dialer (Model 2104) and any combination of 4 LED Annunciators (Model 2865) or I/O Modules (Model 2880).
inputs.
central station. Offe rs 5 different reporting f ormats 3/1, 4/2, BFSK, SIA, and Contact ID.
EOL resistor required for UL installations.
* Require a SK-2884 to operate with the SK-4224 control panel.
3-2 151068
Before You Begin Installing
3.3 SK-4224 Board Layout
Figure 3-1 shows the SK-4224 circuit board including location of terminals, connectors, dip switches, and LEDs.
Programming DIP Switches
AC Power Connector
On-Board Piezo Sounder
Annunciator
SK-2884
Serial
Interface
Connector
Backup Battery Connector
Zone Inputs
4 Class B or
2 Class A Inputs
Figure 3-1 Model SK-4224 Layout
2 Notification
Appliance
Circuits
Notification
Expansion
Inputs
Trouble &
Alarm Relays
Auxiliary
Power
Output
151068 3-3
Model SK-4224 Fire Control Panel Installation/Operation Manual
3.4 Electrical Specifications
Table 3-3: Electrical Specifications
Circuit Rating
Primary AC *120 Vrms at 60 Hz, or 230 Vrms at 50 Hz
@ 1.5 Amps Total External DC Load 2.5A @ 24 VDC +24V Auxiliary Power 19.8 V to 28.0 V, 0.5 A max. Trouble & Alarm Relays 2.5 A @ 30 VDC resistive Notification Appliance Power 19.8 V to 28.0 V, 2.5 A max. Smoke Detector Power 19.8 V to 28.0 V, 1.0 A max. Battery Charging Voltage 27.0 - 27.6 V Maximum Battery Charging Current 750 mA Minimum Low Battery Detect 20.4 V Minimum Low AC Detect 100 Vrms at 60 Hz, full load
Note: * When ordering, specify your voltage requirements.
3.5 Environmental Specifications
Table 3-4: Environmental Specifications
Storage Temperature: -4° - 167° F (-20 - 75° C) Operating Temperature: 32° - 120° F (0° - 49° C) Humidity: 10 - 85% non-condensing
It is important to protect the SK-4224 control panel from water. To prevent water damage, the following conditions should be AVOIDED when mounting the units:
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
3-4 151068
Before You Begin Installing
3.6 Mounting the SK-4224
Read the environmental specifications in Section 3.5 before mounting the cabinet. The panel should be accessible to main drop wiring runs. It should be mounted as close to the
center of the building as possible and located within a secured area, but should be accessible for testing and service. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
Mount the cabinet so it is firmly secured to the wall surface. When mounting the cabinet on concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the concrete surface and then attach the cabinet to the plywood. Also mount any other modules to the plywood.
Follow these steps to mount the control panel cabinet:
1. Place the cabinet on the mounting surface, level the cabinet and mark the top two mounting holes.
2. Screw the top two mount screws about 3/4 of the way into the mounting surface.
3. Hang the control panel cabinet on the top mounting screws through the top mounting screw keyholes.
12-1/2”
11”
Top Mounting Screw Keyholes
15”
Bottom Mounting Holes
4. Insert the bottom two mounting screws into the cabinet’s bottom mounting holes.
5. Tighten all four mounting screws until the cabinet is properly secured.
6. Insert all cabinet components. See Section 3.7.
151068 3-5
Figure 3-2 Cabinet Mounting Holes
Model SK-4224 Fire Control Panel Installation/Operation Manual
3.7 Assembly
The components listed in Table 3-1 are all packed with in the cabinet and require some assembly. Follow these steps to assemble the cabinets inside the cabinet:
1. Remove keys from small manila envelope taped to the top of the cabinet.
2. Unlock the cabinet door.
3. Remove the packing material and the SK-4224 components.
4. Snap the bezel into the opening in the front of the cabinet. See Figure 3-3.
Side View of
Transformer Installation
Slotted Stand-Off
Bezel Insertion
CPU Mounting Screws
Figure 3-3 Assembly Diagram for the SK-4224
Note: The bezel will fit in only one way.
5. With the t wo #8 Screws and the two #8 nuts (with built in washers), mount the transformer in the holes in the upper left hand corner of the cabinet. See Figure 3-3.
6. With the three Self-trapping screws mount the control board on the cabinet stand-offs.
Note: See Section 4 for transformer connections and battery connections.
3-6 151068
Before You Begin Installing
3.8 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can cause false alarms or interfere with control panel operation in other ways.
To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi­conductor cable for the entire panel. Instead, separate the wiring as follows:
High current input/output: AC power and notification device wiring Low current input/output: Annunciator and zone loop wiring
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to circuit ground at the panel. You must route high and low voltages separately.
Route the wiring within the cabinet around the perimeter of the cabinet. It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-4 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
151068 3-7
Figure 3-4 Wire Routing Example
Model SK-4224 Fire Control Panel Installation/Operation Manual
3.9 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your installation.
3.9.1 Worksheet Requirements
The following steps must be taken when determining SK-4224 current draw and standby battery requirements.
Filling in the Current Draw Worksheet, Table 3-6 (Section 3.9.3)
1. For the SK-4224, the worst case current draw is listed for the panel and is recorded in the table at Line A.
2. Add up the current draw for all smoke detectors and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. Any additional devices should be recorded at Line D.
5. Make sure that the alarm current without the panel (Lines B-D) does not exceed 2.5 A. The total alarm current (including the panel, Lines A-D) should not exceed 2.75 A.
6. Complete the remaining instructions in Table 2 for determining battery size requirements.
3.9.2 Maximum Battery Standby Load
Table 3-5 shows the maximum battery standby load for the SK-4224 based on 24 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-6) must be less than the number shown in Table 3-5 for the battery size used and standby hours required.
Table 3-5: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH 270 mA
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
3-8 151068
Before You Begin Installing
3.9.3 Current Draw Worksheet
Use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.)
Table 3-6: Current Draw Calculations
Device
For each device, use this formula: This Column X This column = Current per number of devices SK-4224 Panel 1
A Current Subtotals:
Smoke Detectors
B Current Subtotals:
Notification Devices
C Current Subtotals:
Accesory Devices
SKC-2884
SKC-2865
D Current Subtotals:
*Additional Devices
E Current Subtotals:
Total current rating of all devices in system (add A throug h E): mA mA
F
Total current ratings converted to amperes (x .001): A A
Number of
Devices
Refer to device manual for current ratings. See Appendix to this manual for max. # per loop.
Refer to device manual for number of devices and current ratings.
Current per Device
Standby: 125 mA 125 mA Alarm: 250 mA 250 mA
Standby: mA mA Alarm: mA mA Standby: mA mA Alarm: mA mA Standby: mA mA Alarm: mA mA
Alarm: mA mA Alarm: mA mA Alarm: mA mA Alarm: mA mA
Standby: 10 mA mA Alarm: 10 mA mA Standby: 35 mA mA Alarm: 75 mA mA
Standby: mA mA Alarm: mA mA Standby: mA mA Alarm: mA mA
Standby
Current
125 mA 250 mA
mA mA
mA mA
mA mA
mA mA
Alarm
Current
*Note:If you are usin g do or ho lders, you do not need t o consider door holde r current for alarm/ba tt er y s ta ndb y,
because power is removed during that time. However, during normal operation, door ho lders draw current and must be included in the total current that can be drawn from the pane l.
151068 3-9
Model SK-4224 Fire Control Panel Installation/Operation Manual
3-10 151068
Section 4 Hardware Installation
4.1 AC Power
At installation, connect the transformer AC inputs to the AC power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection.
The AC inputs are rated as 120 VAC, 60 Hz (for transformer P/N 115061) or 230 VAC,50 Hz (for transformer P/N 115031). See Table 3-1 for more information.
To AC Power
White
Black
Green
Earth Ground
Transformer
Figure 4-1 AC Power Connection
Yellow
AC Power Connector
Control Panel
151068 4-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.2 Battery Connection
The SK-4224 battery charge capacity is 7.0 AH. Use two 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Table 3-6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
Note: The SK-4224 cabinet supports two 7.0 AH batteries.
Backup Battery Connector
Figure 4-2 Battery Connection
4-2 151068
Hardware Installation
4.3 Initiation Circuit Installation
4.3.1 Contact Wiring
Wire normally open contacts as shown in Figure 4-3. This is the type of wiring that would typically be used for water flow switches, heat detectors and other normally open devices.
Figure 4-3 N.O. Contact Wiring
4.3.2 Two-Wire Smoke Detector Wiring
Figure 4-4 shows how to connect two-wire smoke detectors to the SK-4224 loops. The figure uses Silent Knight's SLK-24F with HSB-224 base as an example. You can use any detector that has been UL listed for compatibility with the SK-4224. Refer to the Appendix for a list of compatible devices. Refer to Section 6 for configuration options.
Figure 4-4 Two-Wire Smoke Detector Wiring
151068 4-3
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.3.3 Class A Smoke Detector Installation
Figure 4-5 illustrates how to connect a UL listed smoke detector to the SK-4224 in a Class A configuration. Refer to the Appendix for a list of compatible devices. Information on selecting zone configuration options is in Section 6.
Figure 4-5 Class A Smoke Detector Wiring
4-4 151068
Hardware Installation
4.3.4 Four-Wire Smoke Detector
Figure 4-6 shows how to connect four-wire smoke detectors to the SK-4224 loops. The figure uses Silent Knight's SLK-24F with HSC-4R base as an example. You can use any UL listed device. Refer to the Appendix for a list of compatible devices. Information on selecting zone configuration options is in Section 6.
Figure 4-6 Four-Wire Smoke Detector Wiring
151068 4-5
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.3.5 Notification Circuit Installation
Notification appliances used with the SK-4224 must be UL listed for compatibility with the SK-4224. Refer to the list in the Appendix at the end of this manual for a list of compatible devices.
For proper operation, you must use polarized notification devices with a model 7628 4.7k ohm end-of-line (EOL) resistor on each loop. Select ANSI output pattern, if desired. Output is configured as steady (continuous sound) at the factory. See Section 6 for information on changing the pattern.
Figure 4-7 Notification Circuit Installation
4-6 151068
Hardware Installation
4.3.6 Class A Notification Circuit Installation
For proper operation, you must use polarized notification devices. Select ANSI output pattern, if desired. Output is configured as steady (continuous sound) at the factory. See Section 6 for information on changing the pattern.
Figure 4-8 Class A Notification Circuit
4.4 Alarm and Trouble Relays
The SK-4224 has built-in relays for alarm and trouble. The alarm relay is energized during any alarm condition. The trouble relay is energized during any trouble or supervisory trouble condition. Each relay has three terminals (N.O., Common, and N.C.). Refer to Figure 3-1 for location of these terminals.
4.5 Auxiliary Power Circuit
The SK-4224 has a power limited auxiliary power circuit which can source up to .5A. The terminal is labeled “AUX PWR”. Refer to Figure 3-1 for location of this terminal.
151068 4-7
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.6 Door Release Wiring
Figure 4-9 shows how to configure a door release using an ESL DH series door holder.
Figure 4-9 Door Release Wiring
4-8 151068
Hardware Installation
4.7 Optional Accessories Installation
This section describes how to install the optional accessories compatible with the SK-4224 control panel.
4.7.1 Installing the Serial Driver Board (Model SK-2884)
The SK-2884 is required if the installation uses any SK-4224 expansion devices such as Model SKC-2880 (I/O Module), Model SK-2865 (LED Annunciator), or Model 2104 (Dialer Board). The SK-2884 interfaces all the expansion devices to the SK-4224 control panel.
Follow these steps to install the SK-2884 Serial Driver Board:
1. Unplug the AC power connector from the SK-4224 control panel. See Figure 4-1.
2. Unplug the backup battery connector from the SK-4224 control panel. See Figure 4-2.
3. Plug the SK-2884 Serial board on SK-4224 control panel by aligning the 4-pin connector and the three stand-offs with their respective receptors. See Figure 4-10.
Figure 4-10 SK-2884 Connector and Stand-off alignment
4. Reconnect the AC power connector to the SK-4224 control panel. See Figure 4-1.
5. Reconnect the backup battery connector to the SK-4224 control panel. See Figure 4-2.
151068 4-9
Model SK-4224 Fire Control Panel Installation/Operation Manual
Wiring the SK-2884 to an Expansion Device
The SK-2884 uses a three wire connection to all of the SK-4224 compatible expansion devices (see Table 3-2).
Connect all the expansion devices to the SK-2884 as follows:
Table 4-1: SK-2884 Wiring Connections
SK-2884
Terminals
--
++
D (Data) D (Data)
SK-4224 Expansion
To
Device Terminal
4.7.2 SK-2865 LED Annunciator Installation
This section describes how to install the SK-2865 LED annunciator. The SK-2865 is used as a remote LED annunciator unit for the SK-4224.
SK-2865 Electrical Specification
Circuit Rating
Ω Ω Ω
Max Loop Re sistance:
Max. Current:
Data 50
-50 +50 Alarm: 75 mA Standby: 35 mA
Operating V oltage: 24 VDC
Wiring the SK-2865 to the SK-2884
Follow these steps to properly wire the SK-2865 to the SK-2884:
1. Unplug the AC power connector from the SK-4224 control panel. See Figure 4-1.
2. Unplug the backup battery connector from the SK-4224 control panel. See Figure 4-2.
4-10 151068
3. Terminate the wiring as shown in Figure 4-11. See also Table 4-2.
SK-2884
SK-2865
Supervised Power Limited
Hardware Installation
Figure 4-11 SK-2865 Connection to the SK-2884
Table 4-2: SK-2865 Wiring Connections
SK-2865
Terminals
D (Data) D (Data)
++
--
SK-2884 Terminals
151068 4-11
Model SK-4224 Fire Control Panel Installation/Operation Manual
Setting the SK-2865’s address
The range of valid addresses is 0-3. Each device requires a unique address. Set the dip switches as shown in Table 4-3. See also Figure 4-11.
Table 4-3: SK-2865 Addresses Per Dip Switch Setting
Dip Switch Position
Both Open (off) 0
One Closed (on) 1 Two Closed (on) 2
Both Closed (on) 3
Equivalent
Address
Mounting the SK-2865
The SK-2865 mounts into a standard 4” square electrical box. Follow these steps to mount the SK-2865:
1. Make sure that the SK-2865 is properly wired to the control panel. See Figure 4-11.
2. Slide the printed annunciator label into place on the SK-2865. The label fits in between the LEDs and the clear plastic plate.
3. Place the SK-2865 into the 4” square electrical box. See Figure 4-12.
Slide Printed Annunciator Label In
4” Square Electrical Box
Cover Plate Screw
SK-2865
Cover Plate
Figure 4-12 Mounting the SK-2865
4. Place the cover plate over the top of the SK-2865 and align the holes. See Figure 4-12.
5. Insert the four cover plate screws into the four screw holes on the 4” square electrical box.
6. Screw the four cover plate screws into the cover plate until the cover plate fits firmly against the SK-2865 and the electrical box. Do not over tighten.
4-12 151068
Hardware Installation
4.7.3 SK-2880 Installation
The SK-2880 is an Input/Output module. The SK-2880 has 33 pre-defined open collector outputs (see Table 4-6) that can be used to drive LEDs, interface with other controls or systems, or control one of the three built-in Form C relays. See Figure 4-13, Figure 4-15 and Figure 4-16.
The SK-2880 also has two supervised inputs used for Reset and Silence. See Figure 4-16.
Serial Communication
Terminals
Open Collector Outputs
Terminal Strip 2
Reset/Silence Switch Inputs
Figure 4-13 Components of the SK-2880 I/O Module
SK-2880 Specifications
Terminal
Strip 1
Form C Relay 1
Form C Relay 2
Table 4-4: Specifications
Status LED
Form C Relay 3
Max. Loop Resistance:
Max. Current:
Operating Voltage: 24 VDC Operating Temperature: 32° - 120° F (0° - 49° C) Form C Relays 2.5 A @ 30 VDC Resistive
151068 4-13
Circuit Rating
Data 25
-25
+25
Alarm: 35 mA
Standby: 35 mA
Open Collector: 175 mA
Ω Ω Ω
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.7.3.1 Connecting the SK-2880 to the SK-2884
The control panel communicates to the I/O module through the Serial Interface Board (see also Section 4.7.1). Figure 4-14 illustrates how to properly wire the I/O module to the Serial Interface Board.
Supervised Power Limited
SK-2884
SK-2880
Figure 4-14 I/O Module Wiring
4.7.3.2 Setting the SK-2880 Address
The range of valid addresses is 0-3. Each device requires a unique address. Set the dip switches as shown in Table 4-5. See Figure 4-14 for dip switch location.
Table 4-5: SK-2880 Addresses Per Dip Switch Setting
Dip Switch Position Address
Both Open (off) 0
One Closed (on) 1 Two Closed (on) 2
Both Closed (on) 3
4-14 151068
Hardware Installation
4.7.3.3 Open Collector Outputs (P1, P2, and P3)
Each pin on the Pin Connectors (P1, P2, and P3) have a predefined output. Table 4-6 lists the Pin Connectors and describes what each pin outputs.
Table 4-6: Pin-outs for Open Collector Outputs
Pin
Connector
P1
Pin 2
Pin Number Output Description
Pin 1 Zone 1 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 1. Pin 2 Zone 1 Trouble Outputs when a trouble condition exists on Zone 1.
Pin 3 Zone 1 Clean-Me Trouble
Pin 4 Zone 2 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 2. Pin 5 Zone 2 Trouble Outputs when a trouble condition exists on Zone 2.
Pin 6 Zone 2 Clean-Me Trouble
Pin 7 Zone 3 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 3. Pin 8 Zone 3 Trouble Outputs when a trouble condition exists on Zone 3.
Pin 9 Zone 3 Clean-Me Trouble
Pin 10 Zone 4 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 4. Pin 11 Zone 4 Trouble Outputs when a trouble condition exists on Zone 4.
Pin 12 Zone 4 Clean-Me Trouble
Pin 1 Zone 5 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 5. Pin 2 Zone 5 Trouble Outputs when a trouble condition exists on Zone 5.
Pin 3 Zone 5 Clean-Me Trouble
Pin 4 Zone 6 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 6. Pin 5 Zone 6 Trouble Outputs when a trouble condition exists on Zone 6.
Pin 6 Zone 6 Clean-Me Trouble
Pin 7 Zone 1 & 2 Pre-Alarm
Pin 8 Zone 3 & 4 Pre-Alarm
Pin 9 Zone 5 & 6 Pre-Alarm
Pin 10 Unused Not Used. Pin 11 +24 VDC Positive 24 DC voltage output. Pin 12 GND Circuit Ground
Outputs when a “Clean-Me” type detector indicates a Clean-me trouble on Zone 1.
Outputs when a “Clean-Me” type detector indicates a Clean-me trouble on Zone 2.
Outputs when a “Clean-Me” type detector indicates a Clean-me trouble on Zone 3.
Outputs when a “Clean-Me” type detector indicates a Clean-me trouble on Zone 4.
Outputs when a “Clean-Me” type detector indicates a Clean-me trouble on Zone 5.
Outputs when a “Clean-Me” type detector indicates a Clean-me trouble on Zone 6.
Outputs when zones 1 or 2 is in alarm (not both), and cross alarm for zones 1 and 2 is enabled.
Outputs when zones 3 or 4 is in alarm (not both), and cross alarm for zones 3 and 4 is enabled.
Outputs when zones 5 or 6 is in alarm (not both), and cross alarm for zones 5 and 6 is enabled.
151068 4-15
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table 4-6: Pin-outs for Open Collector Outputs
Pin
Connector
Pin 3
Pin Number Output Description
Pin 1 NAC 1 Trouble Outputs when a trouble condition exists on NAC 1. Pin 2 NAC 2 Trouble Outputs when a trouble condition exists on NAC 2. Pin 3 NAC 3 Trouble Outputs when a trouble condition exists on NAC 3.
Pin 4 Dialer Trouble
Pin 5 Expander Trouble
Pin 6 Alarm Silenced Outputs when an alarm has been silenced.
Pin 7 Low AC
Pin 8 Low Battery
Pin 9 Ground Fault
Pin 10 Walk Test Active Outputs when the control panel is in walk test mode.
Pin 11 Piezo Output
Pin 12 Local Trouble
Outputs when any type of trouble occurs with the dialer, such as, no line voltage or a communication failure.
Outputs when one of the Serial Devices connected to the control panel is in trouble .
Outputs if the control panel looses AC power or AC power drops below the cont r ol panels low AC threshold .
Outputs when the backup battery voltage drops below
20.4 VDC. Outputs when the control panel detects a ground fault
condition.
Outputs correspond to any trouble condition output from the control panel.
Outputs if the end-of-line resistor on the Reset or silence inputs not detected or if a seria l communication problem occurs between this device and the control panel.
Wiring SK-2880 Open Collector Outputs
Figure 4-15 illustrates examples of how to configure the open collector outputs on the I/O module for your uses.
LED
Dry Contact Relay
Figure 4-15 Output Configurations
Current Limiting Resistor 1 K
To P2, Pin 11 or C+ on Terminal Strip 2
4-16 151068
Hardware Installation
4.7.3.4 SK-2880 Input Switches and Relay Wiring
This section describes the components of terminal strip 2 (see Figure 4-13) on the SK-2880. T erminal strip 2 provides two input switches (Reset & Silence) and three Form C relay. Figure 4-16 illustrates how to configure the inputs switches and the Form C Relays.
Any Open Collector Output
4.7 K
UL
Listed
EOL
Model
7628
Use Either Configuration Supervised Power Limited
4.7 K
Normally
Open Contact
To
Input
or
Supervised Power Limited
To Normally Closed Contact Input
Figure 4-16 Wiring Examples for Input Switches and Form C Relays
151068 4-17
Model SK-4224 Fire Control Panel Installation/Operation Manual
4.7.3.5 Mounting the SK-2880
The I/O module must be mounted in a UL Listed enclosure. Follow these steps to mount the SK-2880:
1. Remove the SK-2880’s cover. A small screw driver can be used.
2. Remove the SK-2880 circuit board from the base by pushing outward on the base retain­ing tabs and lift the circuit board out. See Figure 4-17.
Circuit Board
Base Retaining Tabs
Base
Figure 4-17 Circuit Board and Plastic Base Components
3. Mount the plastic base in a UL listed enclosure using any of the mounting holes in the plastic base. See Figure 4-18 for locations of base mounting holes.
Mounting Holes
Mounting Holes
Mounting Holes
Verify the proper wire termination and then snap the I/O module cover in place.
4-18 151068
Figure 4-18 Base Mounting Holes
Section 5 Notification Expansion Mode
The SK-4224 can be used to expand the power capabilities of an existing system’s notification circuits. The SK-4224 does this buy connecting the notification circuits of an existing or host fire alarm control panel to the FACP input of the SK-4224, which can trigger the SK-4224 notification cicuits when the host panel goes into alarm.
Note: The SK-4224 does not go into the alarm state when the host control panel triggers the SK-4224’s
notification cicuits.
5.1 Class A Notification Expansion Wiring
Figure 5-1 shows Class supervised wiring from a host panel to the SK-4224 control board. Observe the proper polarity when making wire connections and follow these requirements:
When wiring to terminal B on the SK-4224, you must use two separate wires. Do not loop a single wire or twist two conductors together.
FACP input 20.4 VDC to 26.4 VDC.
Do not use notification appliances on Class A circuits connected to the SK-4224 FACP input. The SK-4224 will detect voltage across the input circuits, but is not designed to pass the added current load from the notification appliances.
Figure 5-1 Class A Supervised Notification Expansion Configuration
151068 5-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
5.2 Class B Notification Expansion Wiring
Figure 5-2 shows Class B supervised wiring from a host fire alarm control panel to the SK­4224 control panel. Use an EOL resistor as shown in to supervise the FACP input. The host fire alarm control panel may use an EOL with a value other than 4.7 KΩ, used by the SK-
4224. In this case, use an UL listed EOL for the host panel you are using.
Figure 5-2 Class B Supervised Notification Expansion Configuration
5-2 151068
Section 6 System Configuration
To configure the SK-4224 system set the dipswitch that controls the option you want to select. The following chart shows how to program the dipswitches that control system, zone, and notification appliance operation. Refer to Figure 3-1 for location of the dipswitches.
Important!
When you change a dipswitch, be sure to perform a system reset (press [RESET]) or power down the panel. Dipswitch changes will have no effect until after the system has been reset.
Table 6-1: System Configuration
To Enable
Enhanced mode (dipswitch ON). Use when both pull stations and detectors will be used in the same zone.
Normal mode (dipswitch OFF). Use when 4-wire smoke detectors and smoke verificat ion are used in the same zone.
Alarm verification
Note:
Do not use with smoke detectors that have veri­fication built-in.
Zone Type
Alarm delay options
Note:
Alarm delay options is to be used with water flow devices only. If the device has a built-in delay time the total delay time (de­vice delay + progr ammed delay) can not exceed 120 seconds.
To Enable For NAC 1 (DIP 3) For NAC 2 (DIP 3) DIP Position
Fire alarm SW 3 SW8 SW 3 SW8 OFF Supervisory SW 3 SW8 SW 3 SW8 ON No delay SW4
30 second delay SW4
60 second delay SW4
90 second delay SW4
Dip Switch 1 Dip Switch 2
For Zone 1 For Zone 2 For Zone 3 For Zone 4 DIP Position
SW1 SW6 SW1 SW6 ON = E nhanced
OFF = Normal
SW 2 SW 7 SW 2 SW 7 ON = Verification zone
OFF = No verification
SW5
SW5
SW5
SW5
SW9
SW10
SW9
SW10
SW9
SW10
SW9
SW10
SW4 SW5
SW4 SW5 SW4 SW5 SW4 SW5
SW9
SW10
SW9
SW10
SW9
SW10
SW9
SW10
OFF OFF
ON OFF OFF ON ON ON
Silencing
ANSI pattern
151068 6-1
SW 1 SW 3 ON = Can be silenced
OFF = No silence
SW 2 SW 4 ON = ANSI
Off = Steady
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table 6-1: System Configuration
To Enable For Entire Panel (DIP 3) DIP Position
SW5
Serial Accessory Devices
*SW6
AC loss report delay SW7
Input Output Circuits Class A / Class B Enable SW8
* Serial Dialer not available at this time.
ON = Serial Annunciator connected to the control panel. OFF = No Serial Annunciator connected to the control
panel. ON = Serial Dialer connected to the control panel OFF = No Serial Dialer connected to the control panel. ON = 6 hour delay on AC loss report.
OFF = No delay on AC.
Note: If there is not a serial dialer connected to the con-
trol panel this should be se t t o t he OFF po sitio n.
ON = Class A configuration for both the input and output circuits.
OFF = Class B configuration for both the input and output circuits.
6-2 151068
Section 7 System Operation
The annunciator on the SK-4224 board is used for all system operation. It contains the switches for enabling silencing, resetting, and so on. The LEDs that indicate system status are also located on the annunciator.
Figure 7-1 On-Board Annunciator
7.1 Meaning of LEDs
The chart below explains the meaning of LEDs on the system board.
Table 7-1: Meaning of LEDs
LED (Color) Function Comments
AC (green) ON = Good AC
OFF = Low AC trouble condition and it was acknowledged FLASHING = Unacknowledged AC Low trouble condition
GENERAL TROUBLE (yellow)
WALK TEST (yellow) ON = Walk test is in progress
ON = System trouble OFF = System OK FLASHING = At least one serial device is in trouble DOUBLE FLASHING = Two types of serial devices are in trouble.
OFF = Wa lk test is off. FLASHING = Walk test is on and at least one zone is not ready
If flashing press the ACK button to acknowledged the condition.
Allow approximately 47 seconds between detector tests.
In walk test when a detector is tripped it will cause an alarm for t wo sec ond s, th e n the control panel will drop power to the loop for seven seconds to reset the detector. Then an additional 38 seconds is needed to restore the detect or.
If verification is used the time between detector test will be about 2 minute and 30 seconds.
151068 7-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table 7-1: Meaning of LEDs
LED (Color) Function Comments
GND FAULT (yellow) ON = Ground fault condition exists and was acknowledged
OFF = No fault FLASHING = A ground f a ult condition det ected
LOW BATTERY (yellow) ON = Battery low condition that has been acknowledged
OFF = Good battery condition FLASHING = Battery low condition
ALARM (red) ON = Zone in alarm which has been acknowledged
OFF = No Alarm FLASHING = Zone in alarm has not yet been acknowledged
SUPERVISORY (yellow)
ZONE 1 and
ZONE 2
NAC 1 and
NAC 2
SYSTEM SILENCED (yellow)
TROUBLE (yellow)
ACTIVE (yellow) ON = NAC is active during an alarm
TROUBLE (yellow)
ON = Zone has a supervisory condition which has been acknowledged (self-restoring condition)
OFF = No supervisory condition exists FLASHING = Supervisor y trouble detected on that zone that has
not yet been acknowledged ON = Zone has a trouble condition which has been acknowledged OFF = No zone trouble FLASHING = Zone has a trouble condition not yet acknowledged
DOUBLE FLASHING = Zone was disabled CLEAN ME FLASHING = Indicates that the smoke detector needs
cleaning
OFF = NAC is not active during alarm ON = NAC has a trouble condition and was acknowledged OFF = No trouble condition
FLASHING = NAC is in trouble DOUBLE FLASHING = Circuit was disabled ON = System audible output has been silenced OFF = Nothing silenced FLASHING = Partially silenced
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
A “Clean Me Flash” is a flash with a long LED on Time and a short LED off time indicating that the smoke d etector needs cleaning. Applies only to smoke detectors with the CLEAN ME feature. The “Clean Me” flash starts after the tr ouble condition has been acknowledge.
If flashing press the ACK button to acknowledged the condition.
Audible trouble activations will clear automatically when the condition resets.
Audible alarm signals have to be manually reset.
Note:
general trouble condition.
Silencing an alarm will cause a
7-2 151068
System Operation
7.2 Operation Keys (Switches)
All system operation are performed from the on-board keys (switches) as described in the chart below.
Table 7-2: Operations and Instructions
Operation Keystrokes
Disable notification appliance circuit.
To re-enable the circuit, press [NAC DISABLE] again.
Disable a zone To re-enable the circuit, press
[ZONE DISABLE] again. Begin Walk Test Press [WALK TEST]. Walk Test LED turns on.
End Walk Test (The test ends automatically a fte r 1 0
minutes of no system activity.) Acknowledge condition (alarm,
supervisory, trouble) Silence Panel Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits
Perform system reset Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.
Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm condition.
Press the appropriate [ZONE DISABL E] key. The zone will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm or supervisory condition.
Note:
pervisory condition.
Press [WALK TEST]. NOTE: The Walk Test feature is not operational during an alarm, supervisory or
any system trouble condition. Press [ACK]. The corresponding LED will change from blinking to steady for the
duration of the condition. Except for CLEAN ME trouble indications.
that have been confi gured as "silenceable".
Walk test will not activate if th e c on trol pa nel h a s a t rou ble, a la rm , o r su-
151068 7-3
Model SK-4224 Fire Control Panel Installation/Operation Manual
7-4 151068
Appendix A Compatible Devices
This section of the manual lists devices (smoke detectors and notification appliances) that are compatible with the SK-4224. Contact Silent Knight if you have a question about whether a device not listed here is compatible.
A.1 Smoke Detectors
This section of the manual contains information about smoke detectors that are compatible with the SK-4224.
SK-4224 Identifier Voltage Range
Note: The maximum number of smoke det ect o rs pe r zone i s dete r min ed by bot h the curre nt draw and the imped-
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur. Do not mix different models of detectors on any zone; false alarms could occur.
24F
16.2-27.3 VDC
A.1.1 Enhanced Mode
Enhanced mode allows the installer to use pull stations on a loop that has been programmed for Enhanced Alarm Verification. If a single detector goes into alarm it will start the alarm verification cycle. If a pull station is activated any time during the alarm verification cycle and after the control panel re-applies loop power (power will drop for seven seconds to restore detector during verification), the panel will go into immediate alarm and discontinue the verification cycle.
Warning! Do not mix different models or manufacturers of smoke detectors on the input loops.
151068 A-1
Model SK-4224 Fire Control Panel Installation/Operation Manual
A.1.2 Two-Wire Smoke Detectors
The table below lists two-wire smoke detectors that are compatible with the SK-4224. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used.
Note: The check mark by manufacturers name indicates that this device can be used in enhanced mode.
Table A-1: Compatible Two-W ire Smoke Detectors
Manufacturer
Apollo
Detection Systems
ESL
Enhance
Mode
Compatible
Model Name or Number
(Base model name or number in
parentheses.)
55000-350 (45681-200) 55000-350 45681-200 24 / loop 55000-250 (45681-200) 55000-250 45681-200 24 / loop DS250 (MB2W or MB 2WL) B A 18 / loop DS250HD (MB2W or MB2WL) B A 18 / loop DS250TH (MB2W or MB2WL) B A 18 / loop 429C (S10A) N/A S10A 30 / loop 429CRT (S11A) N/A S11A 30 / loop 429CST (S11A) N/A S11A 30 / loop 429CT (S10A) N/A S10A 30 / loop 609U01-11 S10 S00 40 / loop 609U02-11 S10 S00/S03 40 / loop 611U (601U or 602U) S10 S00/S03 40 / loop 611UD (601U or 602U) S10 S00/S03 40 / loop 611UT (601U or 602U) S10 S00/S03 40 / loop 612U (601U or 602U) S10 S00/S03 40 / loop
Compatibility ID
# per Loop
Head Base
612UD (601U or 602U) S10 S00/S03 40 / loop 711U (701E or 701U) N/A S10A 25 / loop 712U (701E or 701U) N/A S10A 25 / loop 713-5U (702E or 70 1U) N/A S10A 25 / loop
ESL (Cont.)
Falcon
713-6U (702E or 70 1U) N/A S10A 25 / loop 721-U (S10A) N/A S10A 30 / loop 721-UT (S10A) N/A S10A 30 / loop 525 FDT1 N/A 17 / loop 525T FDT1 N/A 17 / loop
A-2 151068
Table A-1: Compatible Two-W ire Smoke Detectors
Compatible Devices
Enhance
Manufacturer
System Sensor
Mode
Compatible
Four-Wire Smoke Detectors
Table A-2: Compatible Four-Wire Smoke Detectors
Manufacturer Model
Silent Knight Detection Systems
Model Name or Number
(Base model name or number in
parentheses.)
1400 A N/A 20 / loop 1451 (B401B) A A 20 / loop 2300T A N/A 20 / loop 2300 A N/A 20 / loop 2300TB A N/A 20 / loop 2451 (B401B) A N/A 20 / loop 2451DH (DH 400) A N/A 20 / loop 2451TH (B401B) A N/A 20 / loop
SD-P24F with SD-B4@ base
DS200/DS200HD MB200
Compatibility ID
# per Loop
Head Base
ESL
Gentex
System Sensor
445 Series 449 Series
624 824 2040-24 Power Supervision Unit
1851B 2851/2851BTH DH200ADCD
151068 A-3
Model SK-4224 Fire Control Panel Installation/Operation Manual
A.2 Notification Appliances
The chart below lists notification appliances compatible with the SK-4224.
Note: Units that operate at 12 or 24 VDC must be selected for 24 VDC operation.
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Faraday 446X 12/24VDC Vibrating Bell Faraday 476X 12/24VDC Vibrating Bell Faraday 477X 12/24VDC Singl e Stroke Bell Faraday 5 303B-0-14-( )-DC Chime (flush) Faraday 5 304B-0-14-( )-DC Ch ime (surface) Faraday 5305B-0-4-( )-DC Chime (ceiling) Faraday 5306B-0-14-( )-24-DC Chime/Strobe (flush) Faraday 5307B-0-14-( )-24-DC Chime/Strobe (surface) Faraday 5308B-0-4-( )-24-DC Chime/Strobe (ceiling) Faraday 5333B-0-14-24-DC Multi-Tone Horn (flush) Faraday 5 334B-0-14-24-DC Multi-To ne Horn (surface) Faraday 5336B-( )-14-24-DC Multi-Tone Horn/Strobe (flush) Faraday 5337B-( )-14-24-DC Multi-Tone Horn/Strobe (surface) Faraday 5338B-( )-4-24-DC Multi-Tone Horn/Strobe (ceiling) Faraday 5343B-0-14-24-DC Single Tone Horn/Strobe (flush) Faraday 5344B-0-14-24-DC Single Tone Horn/Strobe (surface) Faraday 5345B-0-4-24-DC Single Tone Horn/Strobe (ceiling) Faraday 5348B-( )-4-24-DC Single Tone Horn/Strobe (ceiling) Faraday 5373B-0-14-24-DC 8-Tone Horn/Strobe (flush) Faraday 5374B-0-14-24-DC 8-Tone Horn/Strobe (surface) Faraday 5375B-0-4-24-DC 8-Tone Horn/Strobe (ceiling) Faraday 5376B-0-14-24-DC 8-Tone Horn/Strobe (flush) Faraday 5377B-0-14-24-DC 8-Tone Horn/Strobe (surface) Faraday 5378B-0-4-24-DC 8-Tone Horn/Strobe (ceiling) Faraday 5405B-0-14-24-DC S ync Control Unit Faraday 5508B-( )-14-24-DC Single Gang Sync Strobe (flush) Faraday 5521B-( )-14-24-DC 4” Square Sync Strobe (surface)
A-4 151068
Compatible Devices
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Faraday 5522B-( )-14-24-DC 4” Square Sync Strobe (flush) Faraday 6126B-U-14-24 VDC Horn/Strobe Faraday 6223B-0-14-24-DC Horn (flush) Faraday 6224B-0-14-24-DC Horn (surface ) Faraday 6225B-0-4-24-DC Horn (ceiling) Faraday 6226B-( )-14-24-DC Horn/Strobe (flush) Faraday 6227B-( )-14-24-DC Horn/Strobe (surface) Faraday 6228B-( )-4-24-DC Horn/Strobe (ceiling) Faraday 6243B-0-14-24-DC Electron -Mechanical Horn (flush) Faraday 6244B-0-14-24-DC Electron -Mechanical Horn (surface) Faraday 6245B-0-4-24-DC Electron-Mechanical Horn (ceiling) Faraday 6246B-( )-14-24-DC Electron-Mechanical Horn/Strobe (flush) Faraday 6247B-( )-14-24-DC Electron-Mechanical Horn/Strobe (surface) Faraday 6248B-( )-4-24-DC Electron-Mechanical Horn/Strobe (ceiling) Faraday 6300B-0-14-24-DC Mini-Horn (flush) Faraday 6301B-0-14-24-DC Mini-Horn (surface) Faraday 6302B-( )-4-24-DC Mini-Horn (ceiling) Faraday 6310B-0-14-24-DC Mini-Horn/Strobe/Strobe (flush) Faraday 6311B-0-14-24-DC Mini-Horn/Strobe/Strobe (surface) Faraday 6312B-( )-14-24-DC Mini-Horn/Strobe/Strobe (ceiling) Faraday 6320B-0-14-24-DC Sync Mi ni Horn/Strobe (1 gang) Faraday 6321B-0-14-24-DC Sync Mini Horn/Strobe (1,2 gang) Faraday 6322B-( )-14-24-DC Mini Horn/Sync Strobe (1,2 gang, 4SQ) Federal Signa l 450 Horn Federal Signa l VALS Horn/Strobe Gentex GX90-4 Horn Gentex GXS-4-15-1 Strobe Gentex GXS-4-1575 Strobe Gentex GX90S-4-15 Horn Gentex GX90S-4-1575 Horn Gentex HG124 Horn Gentex SHG24-1575 Horn/Strobe
151068 A-5
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Gentex SHG24-15 Horn/Strobe Gentex GMH-24-X Horn Gentex GMS-24-X Horn/Strobe Gentex GMS-24-X Horn/Strobe Gentex G0T24 Horn Gentex G0S24-X Horn Gentex WGMS-24-X Horn/Strobe System Sensor MASS241 Horn/Strobe System Sensor MASS24110ADA Horn/Strobe System Sensor MASS2415ADA Horn/Strobe System Sensor MASS2475ADA Horn/Strobe System Sensor SS4110ADA Strobe System Sensor SS2415ADA Strobe System Sensor SS2475ADA Strobe System Sensor PS2415ADA Mini-Horn/Strobe System Sensor PS241575ADA Mini-Horn/Strobe System Sensor PS24110ADA Mini-Horn/Strobe System Sensor PS2475ADA Mini-Horn/Strobe Wheelock 46T-G4-24-R Bell Wheelock 46T-G6-24-R Bell Wheelock 46T-G10-24-R Bell Wheelock 46T-G6-24-WS-24-HF-R Strobe/Bell Wheelock 46T-G10-24-WS-24-HF-R Strobe/Bell Wheelock 46T-G6-24-WH-24-HF-R Strobe/Bell Wheelock 46T-G10-24-WH-24-HF-R Strobe/Bell Wheelock 7001T-12\24-W-FR Strobe Horn Wheelock 7002T-12\24-W-FR Strobe Horn Wheelock AES-DL1-R Multitone Horn Wheelock AES-EL1-R Multitone Horn Wheelock AES-DL1-WS-24-VF-R Multitone Horn Wheelock AES-EL1-WS-24-VF-R Multitone Horn Wheelock AES-DL1-WH-24-VF-R Multitone Horn
A-6 151068
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Wheelock AES-EL1-WH-24-VF-R Multitone Horn Wheelock AES-DL1-WM-24-VF-R Multitone Horn Wheelock AES-EL1-WM-24-VF-R Multitone Horn Wheelock AH-24-R Horn Wheelock AH-24WP-R Horn Wheelock AMT-12\24-R Strobe Horn Wheelock AMT-24-LS-VFR Strobe Horn Wheelock AMT-24-LSM-VFR Strobe Horn Wheelock AMT-24-IS-VFR Strobe Horn Wheelock AS2415W-F R Audible Strobe Wheelock AS241575W-FR Audible Strobe Wheelock AS2430W-F R Audible Strobe
Compatible Devices
Wheelock AS2475W-F R Audible Strobe Wheelock AS24110W-FR Audible Strobe Wheelock AS2415C-FW Audible Strobe Wheelock AS2430C-FW Audible Strobe Wheelock AS2475C-FW Audible Strobe Wheelock AS24100C- FW Audible Strobe Wheelock AS-2415-VFR Strobe Horn Wheelock AS-241575-VFR Strobe Horn Wheelock AS-2430-VFR Strobe Horn Wheelock AS-2475-VFR Strobe Horn Wheelock AS-24110-HFR Strobe Horn Wheelock SM-12/24-R Strobe Horn Controller Wheelock DSM-12/24-R Strobe Horn Controller Wheelock CF-BF1 Chime Wheelock CF-BF1-R Chime Wheelock CH70-24-R Chime Wheelock CH90-24-W Chime Wheelock CH70-2415W-FR Chime Strobe Wheelock CH70-241575W-FR Chime Strobe Wheelock CH70-2430W-FR Chime Strobe
151068 A-7
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Wheelock CH70-2475W-FR Chime Strobe Wheelock CH70-24110W-FR Chime Strobe Wheelock CH-CF1 Chime Wheelock CH-CF1-R Chime Wheelock CH-CF1-W Chime Wheelock CH-DF1 Chime Wheelock CH-DF1-R Chime Wheelock CH-BF1-WS-24-HF-R Strobe Chime Wheelock CH-CF1-LS-24 Strobe Chime Wheelock CH-CF1-MS-24 Strobe Chime Wheelock CH-CF1-IS-24 Strobe Chime Wheelock CH-CF1-LS-24-CFW Strobe Chime Wheelock CH-CF1-MS-24-CFW Strobe Chime Wheelock CH-CF1-IS-24-CFW Strobe Chime Wheelock CH-CF1-WS-24-CF-W Strobe Chime Wheelock CH-DF1-LS-24 Strobe Chime Wheelock CH-DF1-MS-24 Strobe Chime Wheelock CH-DF1-IS-24 Strobe Chime Wheelock CH-DF1-LS-24-VFR Strobe Chime Wheelock CH-DF1-LSM-24-VFR Strobe Chime Wheelock CH-DF1-MS-24-VFR Strobe Chime Wheelock CH-DF1-IS-24-VFR Strobe Chime Wheelock CH-DF1-WM-24-VFR Strobe Chime Wheelock CH-DF1-WS-24-VF-R Strobe Chime Wheelock DSM-12/24 Sync Module Wheelock EH-DL1-R Electronic Horn Wheelock EH-EL1-R Electronic Horn Elect r onic Horn Wheelock EHS-DL1-W-VF-R Strobe Horn (single input) Wheelock EHS-EL1-W-VF-R Strobe Horn (single input) Wheelock E H-DL1-WS-24-VF-R Strobe Horn (dual input) Wheelock E H-EL1-WS-24-VF-R Strobe Horn (dual input) Wheelock E H-DL1-WH-24-VF-R Strobe Horn (dual input)
A-8 151068
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Wheelock E H-EL1-WH-24-VF-R Strobe Horn (dual input) Wheelock E H-DL1-WM-24-VF-R Strobe Horn (dual input) Wheelock E H-EL1-WM-24-VF-R Strobe Horn (dual input) Wheelock HSW-24-HFR Remote Strobe Wheelock HS2W-24 -HFR Remote Strobe Wheelock HSPW-24-HFR Remote Strobe Wheelock IS-24-VFR Remote Strobe Wheelock IS1-24-VFR Remote Strobe Wheelock IS3-24-VFR Remote Strobe Wheelock ISP-24-HFR Remote Strobe Wheelock LS-24-VFR Remote Strobe Wheelock LS1-24-VFR Remote Strobe
Compatible Devices
Wheelock LS3-24-VFR Remote Strobe Wheelock LSP-24-HFR Remote Strobe Wheelock LSM-24-VFR Remote Strobe Wheelock LS1M-24-VFR Remote Strobe Wheelock LS3M-24-VFR Remote Strobe Wheelock LSPM-24-VFR Remote Strobe Wheelock MS-24-VFR Remote Strobe Wheelock MS1-24-VFR Remote Strobe Wheelock MS3-24-VFR Remote Strobe Wheelock MSP-24-HFR Remo te Strobe Wheelock MB-G6-24-R Motor Bell Wheelock MB-G10-24-R Motor Bell Wheelock MBS-G6-24-W-HF-R Motor Bell with Strobe Wheelock MBS-G10-24-W-HF-R Motor Bell with Strobe Wheelock MIZ-24-R Mini-Horn Wheelock MIZ-24-W Mini-Horn Wheelock MIZ-24-LS-VFR Mini-Horn/Strobe Wheelock MIZ-24-LSM-VFR Mini-Horn/Strobe Wheelock MIZ-24-MS-VFR Mini-Horn/Strobe Wheelock MIZ-24-HSW-HFR Mini-Horn/Strobe
151068 A-9
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Wheelock MIZ-24-IS-VFR Mini-Horn/Strobe Wheelock MIZ-24-WS-VF-R Mini-Horn/Strobe Wheelock MIZ-24-WS-VF-W Mini-Horn/Strobe Wheelock MIZ-24-WH-VF-W Mini-Horn/Strobe Wheelock MIZ-24-WM-VF-W Mini-Horn/Strobe Wheelock MT-12/24-R Strobe Horn Wheelock MT4-12/24-R Multitone Appliance Wheelock MT4-115-R Multitone Appliance Wheelock MT-24-LS-VFR Strobe Horn Wheelock MT-24-LSM-VFR Strobe Horn Wheelock MT-24-MS-VFR Strobe Horn Wheelock MT-24-IS-VFR Strobe Horn Wheelock MT-24-SL-VFR Strobe Horn Wheelock MT-24-SLM-VFR Synch. Multitone Strobe Wheelock MT-24-WM Strobe Wheelock MT-24-WM-VF-R Horn Wheelock MT-24-WM-VFR Strobe Horn Wheelock NH-12/24-R Horn Wheelock NS-2415W-FR Strobe Horn Wheelock NS-241575W-FR Strobe Horn Wheelock NS-2430W-FR Strobe Horn Wheelock NS-2475W-FR Strobe Horn Wheelock NS-24110W-FR Strobe Horn Wheelock NS4-2415W-FR Strobe Horn Wheelock NS4-241575W-FR Strobe Horn Wheelock NS4-2430W-FR Strobe Horn Wheelock NS4-2475W-FR Strobe Horn Wheelock NS4-24110W-FR Strobe Horn Wheelock RS-2415W-FR Strobe Wheelock RS-2415W-FR Strobe Wheelock RS-241575W-FR Strobe Wheelock RS-2415-HFR Strobe
A-10 151068
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Wheelock RSP-2415-VFR Strobe Wheelock RS-241575-VFR Strobe Wheelock RSP-241575-VFR Strobe Wheelock RS-2430-VFR Strobe Wheelock RS-2430-HFR Strobe Wheelock RS-2475-VFR Strobe Wheelock RSP-2475-HFR Strobe Wheelock RS-24110-HFR Strobe Wheelock RSP-24110-HFR Strobe Wheelock RSS-2415W-FR Strobe Wheelock RSS-241575W-FR Strobe Wheelock RSS-2430W-FR Strobe
Compatible Devices
Wheelock RSS-2475W-FR Strobe Wheelock RSS-24110W-FR Strobe Wheelock RSS-2415C-FW Strobe Wheelock RSS-2430C-FW Strobe Wheelock RSS-2475C-FW Strobe Wheelock RSS-24100C-FW Strobe Wheelock RSSP-2415W-FR Strobe Wheelock RSSP-241575-FR Strobe Wheelock RSSP-2430W-FR Strobe Wheelock RSSP-2475W-FR Strobe Wheelock RSSP-24110W-FR Strobe Wheelock SL-24-VFR Synchronized Remote Strobe Wheelock SL1-24-VFR Synchronized Remote Strobe Wheelock SL3-24-VFR Synchronized Remote Strobe Wheelock SLP-24-VFR Synchronized Remote Strobe Wheelock SLM-24-VFR Synchronized Remote Strobe Wheelock SL1M-24-VFR Synchronized Remote Strobe Wheelock SL3M-24-VFR Synchronized Remote Strobe Wheelock SLPM-24-VFR Synchronized Remote Strobe Wheelock SHW-24-VFR Synchronized Remote Strobe
151068 A-11
Model SK-4224 Fire Control Panel Installation/Operation Manual
Table A-3: Compatible Notification Devices
Manufacturer Model Type
Wheelock SH2W-24-V FR Synchronized Remote Strobe Wheelock SHPW-24-VFR Synchronized Remote Strobe Wheelock SCM-24-R Controller for Synchronized Strobes Wheelock SM-12/24-R Sync Module Wheelock SR-2415-VFR Sync Strobe Wheelock SRP-2415-HFR Sync Strobe Wheelock SR-241575-VFR Sync Strobe Wheelock SRP-241575-VFR Sync Strobe Wheelock SR-2475-VFR Sync Strobe Wheelock SR-2475-HFR Sync Strobe Wheelock SR-24110-HFR Sync Strobe Wheelock SRP-24110-HFR Sync Strobe Wheelock V7001T-12\24-W-FR Strobe Horn Wheelock WM3T-24-FR Remote Strobe Wheelock WM3T-24-VFR Remote Strobe Wheelock WS1T-24-FR Strobe Wheelock WS3T-24-FR Strobe Wheelock WST-24-FR Strobe
A-12 151068
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
All new fire products manufactured by Silent Knight after September 1, 1997 have a limited warranty period of 18 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details.
This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, or have been modified in any manner whatsoever.
Repair and RA Procedure
All products that are returned to Silent Knight for credit or repair require a RA (Return Authorization) number. Call Silent Knight Cust omer Service at 800-446-6444 or 612-493­6435 between 8:00 A.M. and 5:00 P.M. CST, Monday through Friday to obtain a return authorization number. Silent Knight Technical Support is available at 800-328-0103 between 8:00 A.M. and 7:00 P.M. CST, Monday through Friday.
RA number must be prominently displayed on the outside of the shipping box. See return address example under Advanced Replacement Policy.
All products returned to Silent Knight must be sent freight pre-paid. After product is processed, Silent Knight will pay for shipping product back to customer.
Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an additional $20 to cover the extra shipping and handling costs over board only returns. Do not return batteries. Silent Knight has the authority to determine if a product is repairable. Products that are deemed un-repairable will be returned to the customer.
Product that is returned that has a board date code more than 18 months from date of manufacture will be repaired and the customer will be assessed the standard Silent Knight repair charge for that model.
A detailed description of the problem should be included with each return.
Advanced Replacement Policy
Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the 18 month warranty period.
For advance replacement of a defective board call Silent Knight at 800-446-6444 or 612-493-6435 to obtain a RA (Return Authorization) number and request advanced replacement.
Customers must use a MasterCard or Visa credit card to get an advance replacement.
151068
Model SK-4224 Fire Control Panel Installation/Operation Manual
A new or refurbished board will be shipped to the customer . The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Silent Knight.
The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit. No credit will be issue d if the returned bo ard was da maged due to misuse or abuse.
Repairs and returns should be sent to:
Silent Knight Attn: Repair Department 7550 Meridian Circle Maple Grove, MN 55369-4927
RA Number:___________________
Limited Warranty
Silent Knight warrants that the products of its manufacture shall be free from defects in materials or workmanship for 18 months from the manufacturing date code on the printed circuit board, if such goods have been properly installed, are subject to normal proper use, and have not been modified in any manner whatsoever. Upon return of the defective product to the nearest Silent Knight, Silent Knight will, at its sole discr etio n, eit her repai r or repla ce, at no cost, such go ods as may be o f defe ctive material or workmanship. Customers outside the United States are to return products to their distributor for repair.
SILENT KNIGHT SHALL NOT UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIA L DAMAGES ARISING FROM LOSS OF PROPERTY OR OTHER DAMAGE OR LOSSES OWING TO THE FAILURE OF SILENT KNIGHT SECURITY SYSTEMS PRODUCTS BEYOND THE COST OF REPAIR OR REPLACEMENT OF ANY DEFECTIVE PRODUCTS.
SILENT KNIGHT MAKES NO WARRANTY OF FITNESS OR MERCHANTABILITY AND NO OTHER WARRANTY, ORAL OR WRITTEN, EXPRESS OR IMPLIED, BEYOND THE 18 MONTH WARRANTY EXPRESSLY SPECIFIED HEREIN.
151068
SK-4224 BasicOperating Instructions P/N 151066
These instructions must be framed and displayed next to the SK-4224 panel in accordance with NFPA 72 fire code for Local Fire Alarm System.
LED (Color) Function Comments
AC (green) ON = Good AC
GENERAL TROUBLE (yellow) ON = System trouble
WALK TEST (yellow) ON = Walk test is in progress
GND FAULT (yellow) ON = Ground fault condition exists and was acknowledged
LOW BATTERY (yellow) ON = Battery low condition that has been acknowledged
ZONE 1 and ZONE 2
NAC 1 and NAC 2
Cut Along the Dotted Line
SYSTEM SILENCED (yellow) ON = System audio output has been silenced
ALARM (red) ON = Zone in alarm which has been acknowledged
SUPERVISORY (yellow)
TROUBLE (yellow) ON = Zone has a trouble condition which has been acknowledged
ACTIVE (yellow) ON = NAC is active during an alarm
TROUBLE (yellow) ON = NAC has a trouble condition and was acknowledged
OFF = Low AC trouble condition and it was acknowledged FLASHING = Unacknowledged AC Low trouble condition
OFF = System OK FLASHING = At least one serial device is in trouble DOUBLE FLASHING = Two types of serial devices are in trouble.
OFF = Walk tes t is off. FLASHING = Walk test is on and at least one zone is not ready
OFF = No fault FLASHING = A ground fault condition detected
OFF = Good battery condition FLASHING = Battery low condition
OFF = No Alarm FLASHING = Zone in alarm has not yet been acknowledged
ON = Zone has a supervisory condition which has been acknowledged (self­restoring condition) OFF = No supervisory condition exists FLASHING = Supervisory trouble detected on that zone that has not yet been acknowledged
OFF = No zone trouble FLASHING = Zone has a trouble condition not yet acknowledged DOUBLE FLASHING = Zone was disabled
CLEAN ME FLASHING = Indicates that the smoke detector needs cleaning A “Clean Me Flash” is a flash with a long LED on Time and a short
OFF = NAC is not active during alarm
OFF = No trouble condition FLASHING = NAC is in trouble DOUBLE FLASHING = Circuit was disabled
OFF = Nothing silenced FLASHING = Partially silenced
If flashing press the ACK button to acknowledged the condition.
Allow approximately 47 seconds between detector tests. In walk test when a detector is tripped it will cause an alarm for two seconds, then the control panel will drop power to the loop for seven seconds to reset the detector. Then an additional 38 seconds is needed to restore the detector. If verification is used the time between detector test will be about 2 minute and 30 seconds.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
If flashing press the ACK button to acknowledged the condition.
LED off time indicating that the smoke detector needs cleaning. Applies only to smoke detectors with the CLEAN ME feature. The “Clean Me” flash starts after the trouble condition has been acknowledge.
If flashing press the ACK button to acknowledged the condition.
When condition that caused audio activation clears, this condition will clear automatically.
Note: Silencing an alarm will cause a general trouble condition.
Operation Keystrokes
Disable notification appliance circuit. To re-enable the circuit, press [NAC DISABLE] again.
Disable a zone To re-enable the circuit, press [ZONE DISABLE] again.
Begin Walk Test Press [WALK TEST]. Walk Test LED turns on.
End Walk Test (The test ends automatically after 10 minutes of no system activity.)
Acknowledge condition (alarm, supervisory, trouble) Press [ACK]. The corresponding LED will change from blinking to steady for the duration of the condition.
Silence Panel Press [SILENCE]. This will silence the on-bo ar d PZT an d all active NAC cir cuits th at have bee n
Perform system reset Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.
For Service Contact:
Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm condition.
Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm or supervisory condition.
Note: Walk test will not activate if the control panel has a trouble, alarm, or supervisory condition.
Press [WALK TEST]. NOTE: The Walk Test feature is not operational during an alarm, supervisory or any system trouble condition.
Except for CLEAN ME trouble indications.
configured as "silenceable".
Cut Along the Dotted Line
Loading...