Sigma 1433-000-E, 1434-000-E, 1456 User Manual

SERVICE MANUAL
(INTERNATIONAL)
IMPINGER CONVEYOR OVENS
MODEL 1433-000-E, 1434-000-E,
WITH PUSH BUTTON CONTROLS
Lincoln Foodservice Products, LLC
1111 North Hadley Road
Fort Wayne, Indiana 46804
United States of America
Phone : (800) 374-3004
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1450digexport REV 1/5/07
SEQUENCE OF OPERATION
IMPINGER ADVANTAGE
SERIAL NUMBER N28654 AND ABOVE
(OVENS WITH PUSH BUTTON CONTROLS)
MODEL 1433-000-E 230VAC 50 HZ. NAT. GAS MODEL 1434-000-E 230VAC 50 HZ. LP GAS MODEL 1456 220/240VAC 50 HZ. NAT. GAS MODEL 1457 220/240VAC 50 HZ. LP GAS
POWER SUPPLY Electrical power is to be supplied to the oven by a three conductor
service. Brown conductor is hot. Blue conductor is neutral.
Green conductor is ground. CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied, through the 10 Amp oven
BURNER CIRCUIT Closing the oven power switch supplies line voltage through the main
TEMPERATURE CONTROL Closing the oven fan switch supplies line voltage to the primary of the
CONVEYOR DRIVE Closing the oven power switch supplies line voltage to the conveyor
2
When the temperature in the control box reaches 120°F ± 3°F (48.9°C
± 1.7°C), the cooling fan thermostat will switch power to the control
box cooling fan. The thermostat will interrupt power to the cooling fan
when the control box temperature falls to 100°F ± 3°F (37°C ± 1.7°C).
fuse, to a normally open contact of the oven power switch. Power is
also supplied to the control box cooling fan. Closing the oven power
switch supplies line voltage to the main fan motor. Closing the oven
power switch also supplies line voltage to the heat circuit and to the
primary of the oven control transformer.
fan air pressure switch, through the normally closed oven cavity hi-limit
thermostat. Through the gas pressure proving switch (gas pressure
switch removed at S/N N31348) to the ignition control. The combustion
motor is now energized, the normally open combustion air switch
closes upon sensing air. After a pre-purge period between 30 and 60
seconds, the spark generator and the main gas valve are energized.
Ignition should now occur
control transformer and through the ignition control, to the oven
control. Secondary voltage, 24VAC, is supplied to the oven control.
The oven control is set to desired temperature. The thermocouple will
provide varying millivolts to the oven control. The oven control supplies
line voltage to the temperature regulation valve at intermittent intervals
to maintain desired temperature. The display on the oven control will
indicate when the temperature regulation valve is energized.
NOTE: The display also indicates oven temperature.
motor and to the primary of the control transformer. Secondary
voltage, 24VAC, is supplied to the oven control. Setting the oven
control to the desired time outputs voltage, through a reversing switch,
to the conveyor motor.
NOTE: The conveyor system uses a hall effect sensor and magnet to
prove operation of the conveyor motor. If the motor is not running,
“BELT JAM” is indicated on the display.
Impinger I – Adv Digital – Gas Service Manual – International
SCHEMATIC DIAGRAM
MODEL 1433-000-E, 1434-000-E
SERIAL NUMBER N28654 TO N31348
Impinger I – Adv Digital – Gas Service Manual – International
3
SCHEMATIC DIAGRAM
MODEL 1456, 1457
SERIAL NUMBER N28654 TO N31348
4
Impinger I – Adv Digital – Gas Service Manual – International
SCHEMATIC DIAGRAM
MODEL 1433-000-E, 1434-000-E, 1456, 1457
SERIAL NUMBER N31349 AND ABOVE
Impinger I – Adv Digital – Gas Service Manual – International
5
TROUBLESHOOTING GUIDE
IMPINGER ADVANTAGE GAS OVENS
SERIAL NUMBER N28654 AND ABOVE
(OVENS WITH PUSH BUTTON CONTROLS)
SYMPTOM POSSIBLE CAUSE EVALUATION Oven fan will not run Incoming power supply Check circuit breaker, reset if required. Check power
plug to be sure it is firmly in receptacle. Measure
incoming power, call power co. if required. Fuse, 10 Amp Check, replace if necessary. Fuse holder Check, replace if necessary. Switch, oven power Check for line voltage supplied to switch. If no voltage is
present, trace wiring back to fuse holder. Check
continuity between switch terminals. Replace switch as
needed. Motor, main fan Check for line voltage supplied to motor. If no voltage is
present, trace wiring back to oven power switch. Check
motor for opens, shorts or grounds.
WITH POWER OFF: Turn fan blade to check for locked
rotor. No control box cooling Incoming power supply Check circuit breaker, reset if required. Check power
plug to be sure it is firmly in receptacle. Measure
incoming power, call power co. if required. Fuse, 10 Amp Check, replace if necessary. Fuse holder Check, replace if necessary. Switch, oven power Check for line voltage supplied to switch. If no voltage
is present, trace wiring back to fuse holder. Check
continuity between switch terminals. Replace switch as
needed. Cooling fan Check for supply voltage to the cooling fan. If no
voltage is present, trace wiring back to the fuse holder.
If voltage is present and motor does not run, check
motor for opens shorts or grounds.
WITH POWER OFF: Check for locked rotor. No automatic control box cooling
Incoming power supply Check circuit breaker, reset if required. Check power
plug to be sure it is firmly in receptacle. Measure
incoming power, call power co. if required. Cooling fan thermostat Check cooling fan thermostat (thermostat closes at
120°F and opens at 100°F). With cooling fan thermostat
pre-heated, check for continuity Control box cooling fan continues to run
Cooling fan thermostat See “Cooling fan thermostat” (NOTE: Thermostat will
remain closed if control box temperature remains above
120°F. Oven will not heat Main fan If not operating, refer to “Oven fan will not run” S/N N31348 and Below
Gas supply Check for adequate gas supply and be sure that the
manual gas shut off valve is open. Also check flexible
gas line connection. Air pressure switch Check air switch terminals for supply voltage to
terminals NO2 and COM. If voltage is present on one
side only, check for air tube blockage or misalignment. If
these are okay, adjust air pressure switch or replace
switch as needed. Oven cavity hi-limit
thermostat
Terminals are normally closed, opens at 350°C (660°F).
If open, reset and test oven for proper operation. If
thermostat will not hold for maximum temperature, and
oven is not exceeding control setting, check for proper
location of the capillary bulb in its spring holder. If above
checks are okay, replace hi-limit thermostat. Gas pressure switch This switch is located inside the gas valve and should
close when gas pressure is present.
6
Impinger I – Adv Digital – Gas Service Manual – International
WITH POWER OFF: Remove 3 prong plug (on gas
valve) and measure continuity between terminals 2 and
3. If no continuity, check the following: Proper gas
pressure supply to gas valve as marked on the oven
specification plate. Check for proper adjustment of the
gas pressure switch, 10 for Nat. gas, 27 for LP gas or
4.5 for town gas. Check the filter in the gas valve for
blockage or damage. If above checks are okay, but
pressure switch is still not closed, replace gas valve. Ignition control Check for supply voltage to ignition control at terminal
#1 and neutral. If no voltage is present, trace wiring back
to gas pressure switch. If voltage is present, check for
supply voltage to burner blower motor at terminal #6 and
neutral. If no voltage is present, wait 30 seconds, reset
ignition control, and re- try. If the above fails, replace
ignition control. Burner reset switch Switch is normally open. Check to see that the switch
closes when reset button is pushed. Replace as needed. Burner blower motor Check for supply voltage to burner blower motor. If no
voltage is present, trace wiring back to the ignition
control.
WITH POWER OFF: Turn blower wheel to check for
locked rotor.
If supply voltage is present and motor does not run,
replace burner blower motor. Burner blower motor air
pressure switch
Check for supply voltage switching to terminal NO as the
air pressure switch closes. Check for air tube blockage
or misalignment, adjust air pressure switch. If the above
fails, replace air pressure switch. Spark generator After a pre-purge time of 30 to 60 seconds after burner
blower motor starts, check for supply voltage to spark
generator. If voltage is not present, check burner reset
switch. If voltage is still not present, replace ignition
control. If voltage is present, visually check for spark at
igniter. Igniter/sensor assembly Check for visible damage to the igniter/sensor assembly.
If there is no visible damage to the components, and no
spark, replace the spark generator. If there is visible
damage to the igniter/sensor assembly, replace. Also
check for frayed or damaged wires in burner tube. Gas valve Check for supply voltage to gas valve. If no voltage is
present, check reset button. Check all connections for
tightness. If there is still no voltage at the gas valve,
replace ignition control. If there is voltage present, check
for gas pressure at gas pressure tap located in gas
piping. If there is no gas pressure, replace gas valve. Flame will not stay on Flame sensor Check for flame sensor operation, connect a digital
multimeter (capable of measuring DC microamps)
between the flame sensor wire and terminal #1 on the
ignition control. Sensor current is to be 3 microamps,
minimum. If these readings are not achieved, replace
igniter/sensor assembly. Also check for any type of
damage to flame sensor wire and connections.
NOTE: The DC microamp test must be conducted with
the oven in low flame (bypass) operation. Power supply Set the temperature to the lowest temperature setting. If
there is sufficient microamp current, but the flame will
not stay on, check for proper polarity of the power
supply. Ignition control If there is sufficient microamp current, and there is
proper polarity of the power supply, but the burner will
Impinger I – Adv Digital – Gas Service Manual – International
7
not stay on, check the reset button for the ignition
Check for visible damage to the igniter/sensor assembly.
control. If the above check okay, replace ignition control. Oven will not heat
Main fan If not operating, refer to “Oven fan will not run” S/N N31349 and Above Gas supply Check for adequate gas supply and be sure that the
manual gas shut off valve is open. Also check flexible gas line connection..
Air pressure switch Check air switch terminals for supply voltage to
terminals COM and NO. If voltage is present on one side only, check for air tube blockage or misalignment. If these are okay, adjust air pressure switch or replace switch as needed.
Oven cavity hi-limit
thermostat
Terminals are normally closed, opens at 350°C (660°F). If open, reset and test oven for proper operation. If thermostat will not hold for maximum temperature, and oven is not exceeding control setting, check for proper location of the capillary bulb in its spring holder. If above checks are okay, replace hi-limit thermostat.
Ignition control Check for supply voltage to ignition control at terminal
#1 and neutral. If no voltage is present, trace wiring back to hi-limit thermostat. If voltage is present, check for supply voltage to burner blower motor at terminal #8 and neutral. If no voltage is present, wait 30 seconds, reset ignition control, and re- try. If the above fails, replace ignition control.
Burner reset switch Switch is normally open. Check to see that the switch
closes when reset button is pushed. Replace as needed.
Burner blower motor Check for supply voltage to burner blower motor. If no
voltage is present, trace wiring back to the ignition control. WITH POWER OFF: Turn blower wheel to check for locked rotor. If supply voltage is present and motor does not run, replace burner blower motor.
Burner blower motor air
pressure switch
Check for air pressure switch to be switching from “NC” to “NO”. Check for air tube blockage or misalignment. Adjust air pressure switch. If the above fails, replace air pressure switch.
Ignition control A pre-purge time of 30 to 60 seconds occurs after
burner blower motor starts. Check for high voltage spark output from the ignition control. If there is no high voltage spark output, check reset button for the ignition control. If there is still no high voltage output, replace the ignition control.
Igniter/sensor assembly
If there is visible damage to the igniter/sensor assembly, replace. If there is no visible damage to the components, and no spark, replace the igniter/sensor assy. Also check for frayed or damaged wires in burner tube. Replace components as needed.
Ignition control Gas valve should open as the ignition control generates
the high voltage spark. Check for supply voltage to pilot valve at terminal #5 and neutral. If no voltage is present, check reset button for the ignition control. If there is still no voltage to the pilot valve, replace ignition control.
Gas valve Check for supply voltage to pilot valve terminal #5 to
neutral, if there is no voltage, trace wiring back to ignition control. If there is supply voltage, connect a manometer to the pressure tap fitting on the gas valve. If
8
Impinger I – Adv Digital – Gas Service Manual – International
there is voltage to the pilot valve, but there is no gas pressure, replace gas valve.
Pilot tube Check for gas pressure at pilot tube. Disconnect pilot
tube at burner and connect manometer. If there is no gas pressure, check for blockage in pilot tube. Repair or replace as needed.
Pilot orifice If there is gas pressure at the pilot tube, check the pilot
orifice for damage or obstructions. Replace pilot orifice as needed.
Flame will not stay on Flame sensor To check flame sensor operation, connect a digital
multimeter (capable of measuring D.C. microamps) between the flame sensor wire and the flame sensor connection on the ignition control (terminal #13). Flame sensor current is to be 0.7 microamps, minimum. If these readings are not achieved, replace igniter/sensor assembly. Also check for any type of damage to flame sensor wire and connections. NOTE: The D.C. microamp test must be conducted with the oven in low flame (bypass) operation.
Power supply Set the temperature to the lowest temperature setting. If
there is sufficient microamp current, but the flame will not stay lit, check for proper polarity of the power supply.
Ignition control If there is sufficient microamp current, and there is
proper polarity of the power supply, but the burner will not stay lit, check the reset button for the ignition control. If the above test is okay, replace the ignition control.
NOTE: Flame should be on at
this time Low flame is on, but no main flame
Control transformer Check for supply voltage to primary of control
transformer. If no voltage is present, trace wiring back to oven power switch. If voltage is present, check for 24VAC at transformer secondary. If there is primary voltage, but no secondary voltage, replace control transformer.
Oven control Check for 24VAC supply to oven control. If no voltage is
present, trace wiring back to control transformer. Check for supply voltage to oven control. If no voltage is present, trace wiring back to ignition control. If voltage is present, check for a read-out on the display. If there is no read-out on the display, replace oven control. If there is a read-out on the display, set the oven control to maximum temperature (see installation operations manual for temperature adjustment). With the oven control at maximum temperature, check for supply voltage to the temperature regulation valve. If there is voltage at the temperature regulation valve, proceed to “Temperature regulation valve “. If there is no voltage at the temperature regulation valve, trace wiring back to the oven control. If there is no voltage output at the oven control, check the read-out on the oven control. If the oven control reads “PROBE FAIL” this indicates that the thermocouple has failed or become disconnected from the oven control
Thermocouple Check to see that the thermocouple is securely
connected to the oven control. If the thermocouple is connected to the oven control, and the display indicates “PROBE FAIL”, disconnect the thermocouple from the oven control and measure the resistance of the thermocouple. The thermocouple should read approx. 11. If these readings are not achieved, replace the thermocouple. If these readings are correct, proceed.
Impinger I – Adv Digital – Gas Service Manual – International
9
Loading...
+ 19 hidden pages