Sierra Monitor Corporation 5000 User Manual

MODEL 5000
S E N T R Y
GAS MONITORING SYSTEM
Sensors Service
APPLICABILITY & EFFECTIVITY
Effective for all Sentry systems manufactured after September 1, 1995.
Instruction Manual Part Number T12001-A1
Sierra Monitor Corporation
1991 Tarob Court, Milpitas, CA 95035
(408) 262-6611
Applicability & Effectivity
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.5 COMBUSTIBLE GAS SENSOR MODULE
(5100-02)
7.5.1 DESCRIPTION
The Combustible Gas Module includes the sensor and electronic assembly installed in an explosion proof housing. The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling to the controller connects to a three pin spring loaded terminal strip.
7.5.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages:
CHK BRIDGE VOLT
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Warning: : During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the
CHANGE MODULE mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful information
can be displayed or printed. See diagnostic codes 0004
and 0008 in Appendix C.
7.5.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-6 to locate test points during the following procedures:
Caution: The area must be free of flammable vapors or gases during any adjustments or maintenance procedures.
7.5.3.1 BRIDGE VOLTAGE ADJUSTMENT
Confirm that no combustible gas is present and remove sensor module cover.
Figure 7-6
Cover Plate - Combustible Gas Module
Comparing to the "GND" (ground) test point measure "BRIDGE VOL" (bridge voltage) and adjust to 2.00 VDC using "BRIDGE ADJ" potentiometer. Turn counter­clockwise to increase.
7.5.3.2 ZERO ADJUSTMENT
Comparing to ground measure SIGNAL OUT and adjust to
0.18 VDC by turning
ZERO ADJ potentiometer. Turn
counter clock-wise to increase.
7.5.3.3 SPAN ADJUSTMENT
1. Determine the concentration of the calibration
gas (CG) in % LEL.
2. Use the following formula to determine the
response to the calibration gas at
SIGNAL OUT.
Voltage (Signal Out) = (CG+12)/60 For Example: If CG = 50% L.E.L Signal Out = (50+12)/60
= 1.03 volts
SERVICE
Page: 69
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
3. Using a Sierra Monitor Model 1200-26 Gas
Calibrator with a Sierra Monitor Model 5358­00 calibration adapter, or Model 5360 Gas Delivery Fitting. Apply the calibration gas at a flow rate of 100 cc/min. until the signal out voltage stops changing (approx. 2 minutes). Then adjust span adj. potentiometer to the calculated value.
4. Remove the calibration gas and wait for the
voltage to drop. If the voltage is below 0.30 VDC the procedure is complete. If the voltage is above 0.30 VDC repeat the zero and span adjustments.
5. Calibrate the sensor using the instruction
manual procedure.
LOW SENSITIVITY message during
A
calibration indicates one of the two conditions for a combustible sensor:
The zero gas voltage must be less than
.3 volts.
The new span change (span voltage less
zero voltage) must exceed 30% of the calculated span change.
For Example:
Zero gas voltage = .20 VDC Span voltage = .43 VDC Span change is .43-.2 = .23 VDC As the calculated span value (from
step 5 above) is 1.03, the calculated span change is: 1.03-.2 = .87
By calculation: 30% of .87 = .26 The new span change (.23) is less than
30% of the calculated span change so a
LOW SENSITIVITY message will be
displayed.
LOW SENSITIVITY calculation is made to insure that
The the calibration does not adjust the electronics so that the "gain" is large enough to cause false alarms due to minor drift or due to minimal electronic noise.
PIN FUNCTION WIRE COLOR
1 DETECTOR WHITE 2 COMPENSATOR BROWN 3 CALIB. SW. RED 4 DETECTOR BLACK 5 DRAIN BARE 6 CALIB. SW. GREEN
Table 7-5
Combustible Gas Sensor
Wiring Pin Out
1. Detector element resistance should be between 1.5 to
2 ohms.
2. Compensator element resistance should be between
1.5 to 2 ohms.
3. Calibration switch should be open in normal
operation and should close when the calibration magnet is applied.
If the sensor fails any of these tests it should be replaced. If the sensor passes these tests the electronics are suspect and BOTH the sensor and electronics should be replaced. (The electronics and sensor which are removed should be returned to the factory for evaluation).
When a new sensor is installed th e follo wing action s must be taken:
Make the bridge voltage adjustment
immediately to avoid over-voltage damage to the sensor.
Use diagnostic code 0020 to establish nominal
value calibration.
Allow 24 hours for full stabilization of the
sensor, recheck the zero and span adjustments and calibrate the sensor module.
7.5.4 SENSOR REPLACEMENT
If any of the above adjustments cannot be completed successfully the sensor and/or electronics will require replacement. To check the sensor unplug it from the electronics and remove from the housing so that continuity and resistance tests can be made. Table 7-4 provides the pin out for the sensor assembly.
SERVICE
Page: 70
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.5.5 COMBUSTIBLE GAS SCALING FACTORS
For combustible gas monitoring, a calibration standard of Methane or Propane my be used in conjunction with scaling factors to cause Sentry concentration display and alarm function in %LEL scale of another gas as follows:
GAS METHANE PROPANE
FACTOR FACTOR
Acetaldehyde 60 109 Acetic Acid 54 98 Acetic Anhydride 46 83 Acetone 52 94 Acetylene 57 103 Alkyl Alcohol 51 92 Ammonia 126 229 n-Amyl Alcohol 33 59 Aniline 39 71 Benzene 41 74 Biphenyl 25 45 1,3-Butadiene 56 101 n-Butane 58 106 iso-Butane 52 94 Butene-1 45 82 cis-Butene-2 48 88 trans-Butene-2 51 92 n-Butyl Alcohol 34 62 iso-Butyl Alcohol 53 96 tert-Butyl-Alcohol 74 134 n-Butyl Benzene 31 57 iso-Butyl Benzene 32 58 n-Butyric Acid 38 69 Carbon Disulfide 18 32 Carbon Monoxide 75 137 Carbon Oxysulphide 93 169 Chlorobenzene 34 62 Cyanogen 89 162 Cyclohexane 41 74 Cyclopropane 62 113 n-Decane 33 59 Diethylamine 49 88 Dimethylamine 58 105 2,3-Dimethylpentane 40 72 2,3-Dimethylpropane 40 72 Dimethylsulphide 43 79 1,4-Dioxane 45 81 Epichlorohydrin 45 82 Ethane 68 123 Ethyl Acetate 51 93 Ethyl Alcohol 73 132 Ethylamine 53 95 Ethyl Benzene 36 65 Ethyl Bromide 91 165 Ethyl Chloride 57 103 Ethylcyclopentane 40 72 Ethylene 71 128 Ethylenedichloride 66 120 Ethyleneoxide 52 94
NOTES:
Diethyl Ether 46 84 Dimethoxyethane 42 75 Dimethyl Ether 63 113 Dimethylformamide 46 83 Ethyl Formate 44 80 Ethylmercaptan 56 102 n-Heptane 39 70 n-Hexane 37 67 Hydrazine 45 82 Hydrogencyanide 48 86 Hydrogen 77 139 Hydrogen Sulfide 41 74 Methane 100 181 Methyl Actetate 50 90 Methyl Alcohol 86 156 Methylamine 77 140 Methyl Bromide 90 162 Methyl Chloride 102 186 Methylcyclohexane 44 80 Methylenedichloride 93 168 Methylethylether 44 80 Methylethylketone 41 75 Methyl Formate 67 121 Methylmercaptan 61 110 Methylpropionate 51 93 Methyl n-propylketone 40 73 Napthalene 34 62 Nitromethane 34 62 n-Nonane 31 57 n-Octane 37 68 n-Pentane 46 83 i-Pentane 46 84 Propane 55 100 n-Propyl Alcohol 47 85 n-Propylamine 48 88 n-Propylchloride 50 90 Propylene 52 93 Propyleneoxide 46 83 iso-Propylether 44 79 Propyne 42 75 Toluene 40 73 Triethylamine 40 72 Trimethylamine 48 88 Vinylethylether 42 76 o-Xylene 36 65 m-Xylene 39 71 p-Xylene 39 71 JP-4 (Jet Fuel) 41 73
GAS METHANE PROPANE
FACTOR FACTOR
1. Scaling factors are not FMRC approved.
2. Base data source: EEV sensor specification catalog. (EEV claims some data is the result of specific tests, other
data is empirically derived.)
SERVICE
Page: 71
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.6 OXYGEN MODULE (5100-03)
7.6.1 DESCRIPTION
The Oxygen Module includes the electronic assembly installed in an explosion proof housing and the electrochemical sensor connected to one hub of the enclosure. Cabling from the controller connects to a three pin spring loaded terminal strip.
7.6.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages:
CHANGE SENSOR
SENSOR FAILURE
REPLACE SENSOR
False readings or alarms are received due to
sensor inaccuracy.
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful information
can be displayed on the controller or printed. See
diagnostic codes 0004 and 0008 in Appendix C.
7.6.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-7 to locate test points during the following procedures.
7.6.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SENSITIVITY ADJ potentiometer to set the voltage equal to
1/10 of the actual oxygen concentration. In clean air the concentration is 20.9% so the voltage should be set at
2.09 VDC.
Figure 7-7
Cover Plate - Oxygen Module
7.6.4 SENSOR REPLACEMENT
The oxygen sensor should be replaced when it can no longer be calibrated correctly or when the signal output drops to zero. Generally this is every twelve to eighteen months. The Sentry clock keeps track of the age of the sensor if it is correctly initialized in the "change module" mode.
When a new sensor is installed use the
CHANGE MODULE
menu selection to answer yes to the "new sensor?" question. After nine months the
CHANGE SENSOR
message will be displayed to warn that a new sensor should be installed.
SENSOR FAILURE message for Oxygen sensors does
The not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
When sensor replacement is required, open the cover of the sensor module, remove the transmitter and disconnect the sensor wiring harness from the back of the transmitter.
SERVICE
Page: 72
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Unscrew the old sensor from the conduit hub, screw in the new sensor and connect the wiring harness to the transmitter electronics. Replace the transmitter into the enclosure, make signal adjustments as described above, and replace the enclosure cover.
After the sensor is installed:
Update "new sensor" status in the change
module mode.
Allow one hour of stabilization of the new
sensor.
Make the electrical sensitivity adjustment as
described above.
Calibrate the sensor module.
SERVICE
Page: 73
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.7 CARBON MONOXIDE MODULE (5100-04)
7.7.1 DESCRIPTION
The Carbon Monoxide Module includes the sensor and electronic assembly installed in an explosion proof housing.
The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling from the controller connects to a three pin spring loaded terminal strip.
7.7.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
Note
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful information
can be displayed on the controller or printed. See
diagnostic codes 0004 and 0008 in Appendix C.
7.7.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-8 to locate test points during the following procedures.
Cover Plate - Carbon Monoxide Module
1 ppm CO = 0.004 VDC.
100 ppm CO = 0.40 VDC.
250 ppm CO = 1.00 VDC.
7.7.3.2 SENSOR REPLACEMENT
The carbon monoxide sensor should be replaced when it can no longer be calibrated correctly. Generally this is every twenty four to thirty months.
The "SENSOR FAILURE" message for Carbon Monoxide sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
Figure 7-8
7.7.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SENSITIVITY ADJ potentiometer to adjust the voltage
based on the following:
SERVICE
Page: 74
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
If sensor replacement is necessary remove the electronics from the housing and unplug the old sensor from the bottom board, remove it from the enclosure hub and reverse the procedure to install the new sensor.
After the sensor is installed:
Allow one hour of stabilization of the new
sensor.
Make the electrical sensitivity adjustment as
described above.
Calibrate the sensor using the instruction
manual procedure.
SERVICE
Page: 75
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.8 HYDROGEN SULFIDE MODULE (5100-05)
7.8.1 DESCRIPTION
Model 5100-05 Hydrogen Sulfide Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
The sensor assembly includes a reuseable housing and disposable electrochemical sensor. The assembly screws into one hub of the sensor module enclosure and plugs into the bottom electronics card via a six pin connector.
Cabling from the controller connects to a three pin spring loaded terminal strip on the electronics assembly.
7.8.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Cover Plate - Hydrogen Sulfide Module
Figure 7-9
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful information
can be displayed on the controller or printed. See
diagnostic codes 0004 and 0008 in Appendix C.
7.8.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-9 to locate test points during the following procedures.
7.8.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SPAN ADJ
potentiometer to adjust the voltage based on the following:
1 ppm H
100 ppm H
7.8.3.2 SENSOR REPLACEMENT
S = 0.02 VDC.
2
S = 2.00 VDC.
2
The Hydrogen Sulfide sensor should be replaced when it can no longer be calibrated correctly. Generally this is every twenty four to thirty months.
SENSOR FAILURE message for Hydrogen Sulfide
The sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of the housing. To replace the sensor:
SERVICE
Page: 76
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
1. Confirm that system power has been
removed.
2. Remove the transmitter electronics board
from the main housing and unplug the sensor harness from the transmitter electronics.
3. Unscrew the sensor housing from the
bottom of the enclosure
4. Hold the sensor assembly so that the
harness faces down and the sensor faces up. Unscrew and remove the round section of the housing from the hex section. Be careful not to lose the spacer washer which will be sitting on top of th e exposed sensor.
5. Carefully pull the old sensor straight up
from the socket.
6. Orient the new sensor so that the sensor
pin labeled “
“C” which is on the far side of the board
from the vertical reed switch. The reed switch will slide into a hole on the side of the new sensor. Press the new sensor’s pins into the three sockets.
7. Carefully replace the cover on the sensor
assembly including the spacer washer.
8. Install the sensor assembly into the enclosure and
tighten firmly.
9. Reconnect the sensor harness to the transmitter,
install the transmitter into the housing and restore power.
10. Allow one hour for the sensor to stabilize prior to
recalibration.
11. Recalibrate the sensor module.
7.8.3.3 SENSOR OUTPUT ADJUSTMENT
The following procedure is to be used when, during normal calibration of a new sensor, the span voltage cannot be adjusted to a high enough level.
1. Adjust the span potentiometer so that it is
approximately mid range. (Twenty turns clockwise and tens turns counter-clockwise).
2. Remove system power and remove both the
transmitter and the sensor assembly from the enclosure. Remove the sensor assembly cover so that the sensor is visible.
3. Plug the sensor harness into the transmitter
assembly and check that no components are touching the enclosure. Restore power and allow a minimum of 30 minutes for stabilization before adjustment.
C” faces the socket labeled
Figure 7-10
Hydrogen Sulfide Transmitter Component Locator
4. Connect a DVM across TP10 and GT1 on the
transmitter assembly. Figure 7-10
5. Locate the gain potentiometer which is on the
sensor electronics directly behind one of the holes in the sensor body. The potentiometer is accessible by inserting a jewelers screwdriver through the hole in the sensor.
6. Determine the correct value to be read at TP10
based on the following formula:
= 2 (C/R) , where C = concentration of span gas,
V
TP10
and R = range of detection (100 PPM).
7. Apply span gas. Adjust the gain potentiometer
until TP10 = correct value as described above. To increase voltage at TP10 turn the gain potentiometer counter clockwise.
8. Remove system power and re-install the sensor
and transmitter in the enclosure. Restore power and calibrate.
SERVICE
Page: 77
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.9 TOXIC GAS SENSOR MODULE
7.9.1 DESCRIPTION
Toxic Gas Sensor Modules include the following models and default ranges:
5100-06 Chlorine -10 PPM 5100-07 Hydrogen - 2000 PPM 5100-12 Nitrogen Dioxide - 20 PPM 5100-13 Carbon Monoxide, High Range -
1,000 PPM 5100-10 Sulfur Dioxide - 100 PPM 5100-16 Carbon Monoxide, H2 Tolerant -
2,000 PPM 5100-19 Nitric Oxide - 20 PPM 5100-21 Hydrogen Chloride - 20 PPM 5100-22 Hydrogen Cyanide - 20 PPM 5100-27 Ethylene Oxide - 20 PPM
The Toxic Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
The sensor assembly includes a reuseable housing and disposable electrochemical sensor. The assembly screws into one hub of the sensor module enclosure and plugs into the bottom electronics card via a six pin connector.
Cabling from the controller connects to a three pin spring loaded terminal strip on the electronics assembly.
7.9.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received due to
sensor inaccuracy.
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful information
can be displayed on the controller or printed. See
diagnostic codes 0004 and 0008 in Appendix C.
Cover Plate - Toxic Gas Module
7.9.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-11 to locate test points during the following procedures.
7.9.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SPAN ADJ
potentiometer to adjust the voltage based on the following:
1% of full scale = 0.02 VDC.
100% of full scale = 2.00 VDC.
7.9.3.2 SENSOR REPLACEMENT
The toxic gas sensor should be replaced when it can no longer be calibrated correctly. Generally this is every twenty four to thirty months.
Figure 7-11
SERVICE
Page: 78
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
The
SENSOR FAILURE message for toxic gas
sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of the housing. To replace the sensor:
1. Confirm that system power has been
removed.
2. Remove the transmitter electronics board
from the main housing and unplug the sensor harness from the transmitter electronics.
3. Unscrew the sensor housing from the
bottom of the enclosure
4. Hold the sensor assembly so that the
harness faces down and the sensor faces up. Unscrew and remove the round section of the housing from the hex section. Be careful not to lose the spacer washer which will be sitting on top of th e exposed sensor.
5. Carefully pull the old sensor straight up from the
socket.
6. Orient the new sensor so that the sensor pin
labeled “
C” faces the socket labeled “C” which is
on the far side of the board from the vertical reed switch. The reed switch will slide into a hole on the side of the new sensor. Press the new sensor’s pins into the three sockets.
7. Carefully replace the cover on the sensor
assembly including the spacer washer.
8. Install the sensor assembly into the enclosure and
tighten firmly.
9. Reconnect the sensor harness to the transmitter,
install the transmitter into the housing and restore power.
10. Allow one hour for the sensor to stabilize prior to
recalibration.
11. Recalibrate the sensor module.
7.9.3.3 SENSOR OUTPUT ADJUSTMENT
The following procedure is to be used when, during normal calibration of a new sensor, the span voltage cannot be adjusted to a high enough level.
Toxic Gas Transmitter Component Locator
1. Adjust the span potentiometer so that it is
approximately mid range. (Twenty turns clockwise and tens turns counter-clockwise).
2. Remove system power and remove both the
transmitter and the sensor assembly from the enclosure. Remove the sensor assembly cover so that the sensor is visible.
3. Plug the sensor harness into the transmitter
assembly and check that no components are touching the enclosure. Restore power and allow a minimum of 30 minutes for stabilization before adjustment.
4. Connect a DVM across TP10 and GT1 on the
transmitter assembly. Figure 7-12
5. Locate the gain potentiometer which is on the
sensor electronics directly behind one of the holes in the sensor body. The potentiometer is accessible by inserting a jewelers screwdriver through the hole in the sensor.
6. Determine the correct value to be read at TP10
based on the following formula:
= 2 (C/R) , where C = concentration of span gas,
V
TP10
and R = range of detection (100 PPM). The value is negative for all models except 5100-06, and 5100-19.
Figure 7-12
SERVICE
Page: 79
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7. Apply span gas. Adjust the gain potentiometer
until TP10 = correct value as described above. To increase voltage at TP10 turn the gain potentiometer counter clockwise.
8. Remove system power and re-install the sensor
and transmitter in the enclosure. Restore power and calibrate.
SERVICE
Page: 80
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.10 AMMONIA SENSOR MODULE (5100-25)
7.10.1 DESCRIPTION
The Ammonia Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
The sensor assembly includes a rechargeable electrochemical sensor. The assembly screws into one hub of the sensor module enclosure and plugs into the bottom electronics card via a six pin connector.
Cabling from the controller connects to a three pin spring loaded terminal strip on the electronics assembly.
7.10.2 TROUBLE ANALYSIS
Electrical adjustment, recharge, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Cover Plate - Ammonia Module
Figure 7-13
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful information
can be displayed on the controller or printed. See
diagnostic codes 0004 and 0008 in Appendix C.
7.10.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-13 to locate test points during the following procedures.
7.10.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SPAN ADJ
potentiometer to adjust the voltage based on the following:
1% of full scale = 0.02 VDC.
100% of full scale = 2.00 VDC.
7.10.3.2 SENSOR RECHARGE
The Ammonia sensor can be recharged by removing it from service, draining electrolyte, cleaning electrodes and replacing the electrolyte and membrane.
Step by step instructions for sensor recharge are supplied with the recharge kit.
7.10.3.3 SENSOR REPLACEMENT
The Ammonia sensor assembly should be replaced when it can no longer be recharged and calibrated correctly.
SERVICE
Page: 81
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
The
SENSOR FAILURE message for ammonia sensors does
not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
To replace the sensor assembly:
1. Confirm that system power has been removed.
2. Remove the transmitter electronics board from
the main housing and unplug the sensor harness from the transmitter electronics.
3. Unscrew the sensor housing from the bottom of
the enclosure
4. Install the new sensor assembly into the enclosure
and tighten firmly.
5. Reconnect the sensor harness to the transmitter,
install the transmitter into the housing and restore power.
6. Allow one hour for the sensor to stabilize prior to
recalibration.
7. Recalibrate the sensor module.
SERVICE
Page: 82
Loading...