Sierra Monitor Corporation 4011, 4001 User Manual

Model 4001 and 4011 Single Channel Controllers interface with industry standard two- or three-wire 4-20 mA sensor transmitters and provide the user with concentration display and two independent adjustable alarm levels.
The Model 4001 and Model 401 1 Single Channel Control­lers are single channel gas detection controllers that also can be used with most industry standard 4-20 mA or other standard voltage/current sensor transmitters. Both con­trollers provide the user with two independent adjustable alarm levels. In addition, the output can be continuously sent to a chart recorder .
The alarm relays can be programmed to be either latching or non-latching and to activate either as a rising or falling alarm. When the controller is used with 4-20 mA sensors, a third alarm provides a fault indication when the controller detects loop current less than 3 mA. The alarms are ac­knowledged via either an external reset switch or a reset push-button on the Model 401 1
Single Channel Controllers
Model 4001
Model 4011
Model 4001
Model 4011
The 3 1/2 digit LCD display can read the concentration or alarm setpoints. LEDs on the front panel provide indication of all three alarms or low battery power.
Model 4011
Each alarm relay is fused to prevent damage from alarm and control circuits. The relays are SPDT Form C type rated at 5 Amps to provide direct alarm action, reducing the need for interposing relays.
Model 4001
The Model 4001 is housed in a NEMA 4X wall mount en­closure or the optional NEMA 7 explosion proof enclosure. AC or DC powered versions are available. Both versions include as standard an integral battery charger that can provide a trickle charge to an optional battery to provide reliable continuous service.
Features Benefits
Two adjustable alarm setpoints with latching or
non-latching relays 4-20 mA or standard voltage/current input Battery backup option Chart recorder output signal
The Model 4011 is in a 1/8 DIN panel mount enclosure. This controller is DC powered. Optional power supply/ battery chargers can power to a single unit or up to 4 con­trollers.
The front panel includes a 3 1/2 digit LCD display, LEDs indicating the three alarms, reset push-button, four dis­play selection LEDs and a Select Pushbutton. The RE­SET button is used to reset the relays when the user has selected Latching or Acknowledge mode. The SELECT button steps the display through each of the four possible selections that will be indicated by the appropriate illumi­nated LED.
Flexibility to fit your application needs
Interfaces with industry standard sensor transmitters Insure continuous operation Continuous logging of concentration data
Single Channel Controllers
SPECIFICATIONS
INPUT SIGNAL: Standard: 4-20mA
Factory Options: 0-5V, 0-10 V, 0-20mA
INPUT The input loop resistance for the 4-20mA RESIST ANCE: loop is 100 ohms
INPUT POWER:
Model 4001 18-24 VDC, Nominal 350 mA, Max. 500 mA.
Battery charger feature accepts 120V AC
Model 401 1 14-30 VDC, Nominal 100 mA @24VDC
without sensor module, 180 mA @20VDC with sensor module at 20 mA loop current
ALARM LEVELS: Two alarms, user adjustable, alarm levels
HiHi, HiLo, or LoLo
ALARM Jumper selectable for Latching/Non­ CONFIGURA TION: Latching. Jumper selectable for Alarming
on GREATER or LESS than Alarm Level.
TROUBLE RELA Y: Relay de-energizes when loop current is
less than 3 mA or when power is removed.
RELAY RA TING: SPDT Form C, 28VDC @ 5 Amp (fused),
120 VAC @ 4 Amp
ALARM ACKNOWLEDGE:
Model 4001 External alarm reset available - resets
latched relays. Alarm relays reset but alarm status LEDs will track actual condition.
Model 4011 Front panel push-button or external alarm
reset will reset alarm relays programmed for Latching. Alarm relays reset but alarm status LEDs will track actual condition.
DISPLA Y: 3 1/2 digit liquid crystal RECORDER 0-2 VDC with RL=1000 ohms minimum.
OUTPUT: Output proportional to display. Power available
is 12VDC @ 5OmA
CHARGER OUTPUT 12 VDC Trickle Charge for battery back-up (Model 4001):
ENCLOSURE:
Model 4001 NEMA 4X (NEMA 7 optional)
11.5"H x 8.0"W x 6.9"D (29.2 x 20.3 x 17.5 cm)
11.2 lbs (5.1 Kg)
Model 4011 1/8 DIN
1.9"H x 3.8"W x 7.3"D (4.8 x 9.6 x 18.5 cm)
1.2 lbs (0.5 Kg)
ORDERING INFORMA TION
4001-01 Model 4001 Controller , DC, NEMA 4X 4001-1 1 Model 4001 Controller , AC, NEMA 4X 4001-12 Model 4001 Controller, AC, NEMA 7 401 1-00 Model 401 1 Controller, DC, DIN
(Adding SPM69155 Power Supply converts AC
power to DC input to the 401 1-00) 4346-01 Power Supply/Battery Back-up for 401 1 SPM69155 Power Supply AC/DC for 401 1 (plugs in
wall socket)(1 unit)
Model 4001
Model 4011
Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-661 1 800-727-4377 F AX: (408) 262-9042
Visit our web site: www.sierramonitor.com E-Mail: sierra@sierramonitor.com
@ l997 by Sierra Monitor Corporation Printed in USA
Loading...